Está en la página 1de 1

BMyE en una torre de enfriamiento de agua corrida 1

Datos proporcionados y calculados

Cpav ≔ 1.888 TA ≔ 31.5 YA ≔ 0.046 A ≔ 69.4147

CpaL ≔ 4.191 TB ≔ 40.15 YB ≔ 0.081 B ≔ 69.4147

Cpaire ≔ 1.005 TC ≔ 42 C ≔ 238.8

λ0 ≔ 2501.7 TD ≔ 32 D ≔ 230.004

T0 ≔ 0

Agua por arrastre


solve , Bagua
Bagua ≔ C + A ⋅ YA = D + B ⋅ YB + Bagua ―――― → 6.3664855

Agua evaporada

Wev ≔ A ⋅ ⎛⎝YB − YA⎞⎠

Wev = 2.43

Balance de energia

ΔH1 ≔ 0 ΔH1 = 0

ΔH2 ≔ 0 ΔH2 = 0

ΔH3 ≔ A ⋅ Cpaire ⋅ ⎛⎝TB − TA⎞⎠ ΔH3 = 603.4393

ΔH4 ≔ A ⋅ YA ⋅ Cpav ⋅ ⎛⎝TB − TA⎞⎠ ΔH4 = 52.1468

ΔH5 ≔ A ⋅ ⎛⎝YB − YA⎞⎠ ⎛⎝CpaL ⋅ ⎛⎝T0 − TC⎞⎠ + λ0 + Cpav ⋅ ⎛⎝TB − T0⎞⎠⎞⎠ ΔH5 = 5834.4334

ΔH6 ≔ 0 ΔH6 = 0

ΔH7 ≔ Bagua ⋅ CpaL ⋅ ⎛⎝TB − TC⎞⎠ ΔH7 = −49.3616

ΔH8 ≔ D ⋅ CpaL ⋅ ⎛⎝TD − TC⎞⎠ ΔH8 = −9639.4676

ΔHtotal ≔ ΔH1 + ΔH2 + ΔH3 + ΔH4 + ΔH5 + ΔH6 + ΔH7 + ΔH8 ΔHtotal = −3198.8097

También podría gustarte