Documentos de Académico
Documentos de Profesional
Documentos de Cultura
Diseno Hidraulico Agua
Diseno Hidraulico Agua
TRAMO J-I I-H H-G G-F F-E E-D D-C C-B B-A
UNIDADES HUNTER 9.00 17.25 17.25 28.50 64.75 77.50 81.25 85.00 97.75
Q (Lt/seg) 0.320 0.485 0.485 0.720 1.307 1.430 1.463 1.500 1.648
(cm.) 1.843 2.268 2.268 2.764 3.724 3.895 3.939 3.989 4.181
DIÁMETRO
(pulg.) 3/4 1 1 1 1 1/2 1 1/2 1 1/2 1 1/2 2
LONGITUD (m) 7.00 3.65 8.00 20.70 21.35 1.95 13.50 2.55 7.95
Cantidad 2 5 0 0 0 0 0 5 4
90º
Long. Equiv. 1.08 1.42 1.42 1.42 2.16 2.16 2.16 2.16 2.84
CODO
Long. Equiv. 0.36 0.48 0.48 0.48 0.72 0.72 0.72 0.72 0.95
Sub total 0 0 0 0 0 0 0 0 0
Cantidad 0 0 1 0 1 0 0 1 0
90º
Long. Equiv. 1.55 2.04 2.04 2.04 3.11 3.11 3.11 3.11 4.09
Sub total 0 0 2.04 0 3.11 0 0 3.11 0
TEE
Cantidad 2 1 0 1 0 1 1 0 1
RECTO
Long. Equiv. 0.52 0.68 0.68 0.68 1.04 1.04 1.04 1.04 1.36
Sub total 1.04 0.68 0 0.68 0 1.04 1.04 0 1.36
Cantidad 1 0 0 0 0 0 0 1 1
COMP.
Long. Equiv. 0.16 0.22 0.22 0.22 0.33 0.33 0.33 0.33 0.43
VÁLVULA
Long. Equiv. 8.64 11.36 11.36 11.36 17.27 17.27 17.27 17.27 22.73
Sub total 0 0 0 0 0 0 0 0 0
LONGITUD ADICIONAL 3.36 7.78 2.04 0.68 3.11 1.04 1.04 14.24 13.15
LONGITUD TOTAL 10.36 11.43 10.04 21.38 24.46 2.99 14.54 16.79 21.10
Sf (m/m) 0.067 0.055 0.055 0.045 0.033 0.032 0.032 0.031 0.030
PERDIDA DE CARGA 0.699 0.627 0.550 0.962 0.817 0.095 0.459 0.523 0.628
ALT. DEL APAR. MAS DESFAV. 0.25 0 0 0 0 0 0 0 0
PRESIÓN DE SALIDA 2 0 0 0 0 0 0 0 0
PERDIDA CARGA EN MEDIDOR 0 0 0 0 0 0 0 1.3 1.3
PRESIÓN NECESARIA 2.949 3.576 4.126 5.088 5.905 6.000 6.459 8.283 10.210
Por lo tanto el primer piso que corresponde al RESTAURANTE, será un sistema directo ya que
contamos con presión necesaria de 15 mca. Y tan solo necesitamos 10.21mca.
SEGUNDO NIVEL: DEPARTAMENTOS
Vmedia = 1.2 m/s
Long. Equiv. 0.74 0.74 1.08 1.08 1.42 2.16 2.16 2.16
CODO
Long. Equiv. 0.25 0.25 0.36 0.36 0.48 0.72 0.72 0.72
Sub total 0 0 0 0 0 0 0 0
Cantidad 0 0 1 1 0 0 1 0
TEE
90º
Long. Equiv. 1.06 1.06 1.55 1.55 2.04 3.11 3.11 3.11
Sub total 0 0 1.55 1.55 0 0 3.11 0
Cantidad 1 1 0 0 1 1 0 0
RECTO
Long. Equiv. 0.35 0.35 0.52 0.52 0.68 1.04 1.04 1.04
Sub total 0.35 0.35 0 0 0.68 1.04 0 0
Cantidad 1 0 0 1 0 0 0 1
VÁLVULA
COMP.
Long. Equiv. 0.11 0.11 0.16 0.16 0.22 0.33 0.33 0.33
Sub total 0.11 0 0 0.16 0 0 0 0.33
Cantidad 0 0 0 0 0 0 0 0
GLOBO
Long. Equiv. 5.91 5.91 8.64 8.64 11.36 17.27 17.27 17.27
Sub total 0 0 0 0 0 0 0 0
LONGITUD ADICIONAL 4.9 0.35 1.55 6.03 0.68 1.04 5.27 8.97
LONGITUD TOTAL 12.70 2.60 2.80 10.23 16.68 17.04 28.22 10.02
Sf (m/m) 0.095 0.076 0.056 0.050 0.040 0.035 0.030 0.026
PERDIDA DE CARGA 1.212 0.199 0.158 0.513 0.668 0.589 0.854 0.257
ALT. DEL APAR. MAS DESFAV. 1.1 0 0 0 0 0 0 0
PRESIÓN DE SALIDA 2 0 0 0 0 0 0 0
PERDIDA CARGA EN MEDIDOR 0 0 0 0.95 0 0 0 1.64
PRESIÓN NECESARIA 4.312 4.511 4.668 6.131 6.799 7.388 8.242 10.139
TERCER NIVEL: DEPARTAMENTOS
Vmedia = 1.2 m/s
Long. Equiv. 0.74 0.74 1.08 1.08 1.42 2.16 2.16 2.16
CODO
Long. Equiv. 0.25 0.25 0.36 0.36 0.48 0.72 0.72 0.72
Sub total 0 0 0 0 0 0 0 0
Cantidad 0 0 1 1 0 0 1 0
TEE
90º
Long. Equiv. 1.06 1.06 1.55 1.55 2.04 3.11 3.11 3.11
Sub total 0 0 1.55 1.55 0 0 3.11 0
Cantidad 1 1 0 0 1 1 0 0
RECTO
Long. Equiv. 0.35 0.35 0.52 0.52 0.68 1.04 1.04 1.04
Sub total 0.35 0.35 0 0 0.68 1.04 0 0
Cantidad 1 0 0 1 0 0 0 1
VÁLVULA
COMP.
Long. Equiv. 0.11 0.11 0.16 0.16 0.22 0.33 0.33 0.33
Sub total 0.11 0 0 0.16 0 0 0 0.33
Cantidad 0 0 0 0 0 0 0 0
GLOBO
Long. Equiv. 5.91 5.91 8.64 8.64 11.36 17.27 17.27 17.27
Sub total 0 0 0 0 0 0 0 0
LONGITUD ADICIONAL 4.9 0.35 1.55 6.03 0.68 1.04 5.27 8.97
LONGITUD TOTAL 12.70 2.60 2.80 10.23 16.68 17.04 28.22 10.02
Sf (m/m) 0.095 0.076 0.056 0.050 0.040 0.035 0.030 0.026
PERDIDA DE CARGA 1.212 0.199 0.158 0.513 0.668 0.589 0.854 0.257
ALT. DEL APAR. MAS DESFAV. 1.1 0 0 0 0 0 0 0
PRESIÓN DE SALIDA 2 0 0 0 0 0 0 0
PERDIDA CARGA EN MEDIDOR 0 0 0 0.95 0 0 0 1.64
PRESIÓN NECESARIA 4.312 4.511 4.668 6.131 6.799 7.388 8.242 10.139
CUARTO NIVEL: DEPARTAMENTOS
Vmedia = 1.2 m/s
Long. Equiv. 0.74 0.74 1.08 1.08 1.42 2.16 2.16 2.16
CODO
Long. Equiv. 0.25 0.25 0.36 0.36 0.48 0.72 0.72 0.72
Sub total 0 0 0 0 0 0 0 0
Cantidad 0 0 1 1 0 0 1 0
TEE
90º
Long. Equiv. 1.06 1.06 1.55 1.55 2.04 3.11 3.11 3.11
Sub total 0 0 1.55 1.55 0 0 3.11 0
Cantidad 1 1 0 0 1 1 0 0
RECTO
Long. Equiv. 0.35 0.35 0.52 0.52 0.68 1.04 1.04 1.04
Sub total 0.35 0.35 0 0 0.68 1.04 0 0
Cantidad 1 0 0 1 0 0 0 1
VÁLVULA
COMP.
Long. Equiv. 0.11 0.11 0.16 0.16 0.22 0.33 0.33 0.33
Sub total 0.11 0 0 0.16 0 0 0 0.33
Cantidad 0 0 0 0 0 0 0 0
GLOBO
Long. Equiv. 5.91 5.91 8.64 8.64 11.36 17.27 17.27 17.27
Sub total 0 0 0 0 0 0 0 0
LONGITUD ADICIONAL 4.9 0.35 1.55 6.03 0.68 1.04 5.27 8.97
LONGITUD TOTAL 12.70 2.60 2.80 10.23 16.68 17.04 28.22 10.02
Sf (m/m) 0.095 0.076 0.056 0.050 0.040 0.035 0.030 0.026
PERDIDA DE CARGA 1.212 0.199 0.158 0.513 0.668 0.589 0.854 0.257
ALT. DEL APAR. MAS DESFAV. 1.1 0 0 0 0 0 0 0
PRESIÓN DE SALIDA 2 0 0 0 0 0 0 0
PERDIDA CARGA EN MEDIDOR 0 0 0 0.95 0 0 0 1.64
PRESIÓN NECESARIA 4.312 4.511 4.668 6.131 6.799 7.388 8.242 10.139
DISEÑO: TANQUES DE ALMACENAMIENTO
- CAPACIDAD: V = (DOTACIÓN)
V = 1 x 53.62 = 53.62 m3
Adoptamos: V = 53.68 m3
Donde: (he) : Distancia vertical, entre el techo del tanque; y el eje del tubo de entrada = 0.2 m
(hre) : Distancia vertical, entre el eje de la tubería de rebose; y del eje del tubo de entrada de agua.
Es igual al doble del diámetro (tubería de rebose); y en ningún caso menor de 0.15 m.
(h) = 3.9 m
DIMENCIONAMIENTO: TANQUE HIDRONEOMATICO
HT=2.60*3+0.25*3+2
HT= 10.3 m
HF= 10.11 m
a-4) considerando que el gasto de Bombeo es la dotacion de los tres pisos superiores:
Gasto de bombeo= 29000 l/d
Factor de multiplicacion según RNE Para 25 psi: 7.5
b) Volumen tanque hidroneumatico(VH):
1
4⋅Q
DIÁMETRO DE TUBERÍA: φ=
π⋅v ( ) 2
1
4⋅Q
DIÁMETRO DE TUBERÍA: φ=
π⋅v ( ) 2
Pm : Presión en la matriz : 15 m
Ps : Presión de salida (mínima) : 2 m
Ht :Altura estática del edificio : 0.5 m
Hf : Perdidas de carga
(Referido al nivel de RED PUBLICA)
Hf = 15 - 0.5 - 2
Hf = 12.5 mca
DIAMETRO Hfm
3/4 12 Para Q=100 Lt/min
1 4.7
1 1/2 1.3
Por lo tanto el medidor tendra un dianetro de = 3/2 ''
POTENCIA DE LA BOMBA:
Q2 Donde:
Sf = β
φ5 β = 14 Tub. PVC rigido
Sf = 0.02545 (m/m)
PERDIDAS DE CARGA LOCALES (Perdida de carga por accesorios)
POTENCIA DE LA BOMBA:
P = 2.48 x 20.09 = 0.949 HP
75 x 0.7
GASTO: Q = 4 Lt/s
TUBERÍA ALIMENTADORA:
1
4⋅Q
DIÁMETRO DE TUBERÍA: φ=
π⋅v ( ) 2
2
PERDIDA DE CARAGA. (al punto de conexión (G.C.I.) mas desfaborable:
2
Q
Sf = β Donde:
φ5 β = 14 Tub. PVC rigido
Sf = 0.00872
33.4
4.85
DISEÑO: SISTEMA DE ABASTECIMIENTO DE AGUA CALIENTE
Primer Nivel:
Nota: El tercer y cuarto nivel son iguales por lo tanto tienen las mismas
caracteristicas en agua caliente.
1
4⋅Q
DIÁMETRO DE TUBERÍA: φ =
( π⋅v ) 2
Carga disponible:
H= 15-(2+1)= 12 mca
Tabla:
Q Diámetro Pc
1" 11.5
167.58 1 1/2" 1.9
2" 1.2