AMPACITY TABLE - AMP vs TEMP – SAN JUAN (ARGENTINA) 16/12/2013

GENERAL CABLE CORP - ECN ENGINEERING OFFICE

CONDUCTOR : CODE WORD - DOVE EQ ALUM STRAND DIA - .4237 CM


SIZE - 282.0 SQ MM CORE STRAND DIA - .2890 CM
STRANDING - 20 / 7 OUTSIDE DIAMETER - 2.160 CM
TYPE - ACSS/TW ALUM CONDUCTIVITY - 63.0% IACS
EMISSIVITY- .60 CORE CONDUCTIVITY - 8.0% IACS

OPERATING CONDITIONS : AMBIENT TEMPERATURE - 45. DEG C


CROSSWIND VELOCITY - .60 M /SEC

OPERATING R-DC R-AC AMPACITY WITHOUT SUN AMPACITY WITH SUN


TEMP (OHMS/ (OHMS/ WITHOUT WITH WITHOUT WITH
C-DEG-F 1000 M ) 1000 M ) WIND WIND WIND WIND

20. 68. .097218 .097618 0. 0. 0. 0.


25. 77. .099241 .099632 0. 0. 0. 0.
30. 86. .101263 .101646 0. 0. 0. 0.
35. 95. .103285 .103661 0. 0. 0. 0.
40. 104. .105307 .105676 0. 0. 0. 0.
45. 113. .107329 .107691 0. 0. 0. 0.
50. 122. .109351 .109706 169. 261. 0. 0.
55. 131. .111373 .111722 249. 366. 0. 194.
60. 140. .113396 .113738 312. 446. 51. 322.
65. 149. .115418 .115754 366. 511. 202. 410.
70. 158. .117440 .117771 414. 568. 283. 481.
75. 167. .119462 .119787 458. 619. 345. 541.
80. 176. .121484 .121804 498. 665. 399. 594.
85. 185. .123506 .123821 535. 706. 446. 641.
90. 194. .125528 .125838 570. 745. 489. 685.
95. 203. .127551 .127855 603. 782. 528. 725.
100. 212. .129573 .129873 634. 815. 564. 763.
105. 221. .131595 .131890 664. 847. 599. 798.
110. 230. .133617 .133908 692. 878. 631. 831.
115. 239. .135639 .135926 719. 907. 662. 862.
120. 248. .137661 .137944 745. 934. 691. 891.
125. 257. .139683 .139962 771. 961. 719. 920.
130. 266. .141706 .141980 795. 986. 746. 947.
135. 275. .143728 .143998 819. 1011. 772. 973.
140. 284. .145750 .146017 842. 1034. 796. 998.
145. 293. .147772 .148035 864. 1058. 821. 1022.
150. 302. .149794 .150054 886. 1079. 844. 1045.
155. 311. .151816 .152072 907. 1101. 867. 1068.
160. 320. .153838 .154091 927. 1122. 889. 1090.
165. 329. .155861 .156110 948. 1143. 910. 1112.
170. 338. .157883 .158129 968. 1162. 932. 1133.
175. 347. .159905 .160148 987. 1182. 952. 1153.
180. 356. .161927 .162167 1006. 1201. 972. 1173.
185. 365. .163949 .164186 1024. 1219. 992. 1192.
190. 374. .165971 .166206 1043. 1238. 1011. 1212.
195. 383. .167993 .168225 1061. 1256. 1030. 1230.
200. 392. .170016 .170244 1079. 1274. 1049. 1249.

SUN CONDITIONS : AZIMUTH OF LINE - 270. DEG ALTITUDE OF SUN - 63. DEG
AZIMUTH OF SUN - 180. DEG SOLAR ABSORPTION - .5
TOTAL SOLAR AND SKY RADIATED HEAT -1000.1 WATTS/SQ M
ALTITUDE : 700. M ABOVE SEA LEVEL
FREQUENCY OF OPERATION = 50.0 HERTZ

Calculations according to IEEE 738