ANEXO 6

DIgSILENT
3*I0
I =2063,023
=2063,040pri.A
=2063,050 pri.A
100

I =1191,082 pri.A

I =2063,026 pri.A
51N_TRF
Normal Inverse
Ipset: 3,09 sec.A
Tpset: 0,50 51BT_TRF
Tripping Time: 2,415 s Extremely Inverse
Ipset: 5,96 sec.A
Tpset: 0,50
Tripping Time: 9999,999 s
[s]

51AT_TRF
Extremely Inverse
Ipset: 5,44 sec.A
Tpset: 0,50
Tripping Time: 9999,999 s

10

51-ALD
Very Inverse 2.415 s
Ipset: 3,25 sec.A
Tpset: 0,40
Tripping Time: 1,259 s

1.259 s

1
0.828 s

51N-ALD
Very Inverse 67N_ARJ-LAG
Ipset: 1,30 sec.A Normal Inverse
Tpset: 0,75 Ipset: 1,30 sec.A
Tripping Time: 0,828 s Tpset: 0,30
Tripping Time: 9999,999 s

0,1
10,50 kV 100 1000 10000 [pri.A] 100000

69,00 kV 100 1000 10000


LAG025\Cub_1\51BT_TRF LAG025\Cub_1\51N_TRF
LAG069\Cub_3\51AT_TRF ALIM_D\Cub_2\51-ALD
ALIM_D\Cub_2\51N-ALD ARJ069\Cub_4\67N_ARJ-LAG

ESTUDIO DE COORDINA CION DE PROTECCIONES ALIM A Date: 5/29/2018


SUBESTACION LAGUNA 10.5 kV CORTOCIRCUITO TRIFASICO AL 99% ALIMENTADOR L-D Annex: 17

Se muestran la curvas de coordinación de protecciones, en las que con los ajustes


declarados ante CNDC del relé de protección de la línea ARJLAG069 no debería llegar a
operar durante la falla originada en la red de distribución de CESSA