ATEX
motor control device 0080 II (2) GD - Zones 1 - 2, 21 - 22
Thermal overload relay EC type examination certificate:
LRD 01...35 INERIS 06ATEX0036X
Description
LRD01 to LRD35 3-pole thermal overload relays are designed to protect a.c. circuits
and motors against overloads, phase failure, long starting times and prolonged
810465
5 Trip indicator.
6 Setting locked by sealing the cover.
7 Selector for manual or automatic reset. Relays LRD 01 to 35 are supplied with the
selector in the manual position, protected by a cover. Deliberate action is required
to move it to the automatic position.
Environment
Conforming to standards IEC 60947-1, IEC 60947-4-1, NF C 63-650
VDE 0660, BS 4941
Product certifications CSA, UL, Sichere Trennung, ATEX except LAD 4: UL, CSA.
Degree of protection Conforming to VDE 0106 Protection against direct finger contact IP 2X
Protective treatment Conforming to IEC 60068 “TH”
Ambient air temperature Storage °C - 60…+ 70
around the device Normal operation, °C - 20…+ 60
without derating
(IEC 60947-4-1)
Minimum and maximum °C - 40…+ 70
operating temperatures
(with derating)
Operating positions In relation to normal Any position
without derating vertical mounting plane
Shock resistance Permissible acceleration 15 gn - 11 ms
conforming to IEC 60068-2-7
Vibration resistance Permissible acceleration 6 gn
conforming to IEC 60068-2-6
Dielectric strength at 50 Hz Conforming to IEC 60255-5 kV 6
Surge withstand Conforming to IEC 60801-5 kV 6
W9 1672545 02 11 A01
09-2006
1/4
e
ATEX
motor control device 0080 II (2) GD - Zones 1 - 2, 21 - 22
Thermal overload relay EC type examination certificate:
LRD 01...35 INERIS 06ATEX0036X
Operating characteristics
Relay type LRD 01…16, LRD 21…35,
LR3 D01…D16 LR3 D21…D35
Temperature compensation °C - 20…+ 60 - 30…+ 60
Tripping threshold Conforming to IEC 60947-4-1 A 1,14 ± 0,06 In
Sensitivity to phase failure Conforming to IEC 60947-4-1 Tripping current 30 % of In on one phase, the others at In
Tripping curves
Average operating times related to multiples of the setting current
1 Balanced operation, 3-phase, from cold state.
DB110938
Relay Fuses to be used with selected relay For use Reference Weight
setting range (A) aM (A) gG (A) BS88 (A) with contactor LC1 kg
Dimensions
Direct mounting beneath contactors with screw clamp Independent mounting on 50 mm centres or on rail AM1 DP200 or DE200
connections
DB110939
DB110940
add-on blocks)
DANGER
HAZARDOUS VOLTAGE
Connection
Connection accessories With LC1 D contactor On LAD 7B106
DB110942
DB110943
DB110944
Connection
Power circuit
DB110945
DB110947
TEST
LRD
08
2.5
3.5
Manual position
Maintenance
In accordance with the maintenance rules for all electrical installations, check the
following once a year:
b The correct tightening of the cables, by re-tightening all the connections
b The mechanical operation of the product, by manually operating the test button.