ETAP Página: 1
Ubicación: 12.6.0H Fecha: 19-10-2015
Contrato: SN:
Ingeniero: Revisión: Base
Caso de Estudio: LF
Nombre de Archivo: PtoVentanas Config.: Normal
* Bus1 12.000 100.000 0.0 4.272 2.150 0 0 Bus9 4.272 2.150 230.1 89.3
Bus2 4.000 96.824 -2.5 0 0 0 0 Bus9 -1.466 -0.710 242.9 90.0
Bus4 0.333 0.161 55.2 90.0
Bus7 0.267 0.129 44.2 90.0
Bus6 0.333 0.161 55.2 90.0
Bus8 0.267 0.129 44.2 90.0
Bus18 0.267 0.129 44.2 90.0
Bus4 4.000 96.824 -2.5 0 0 0.333 0.161 Bus2 -0.333 -0.161 55.2 90.0
Bus6 4.000 96.824 -2.5 0 0 0.333 0.161 Bus2 -0.333 -0.161 55.2 90.0
Bus7 4.000 96.824 -2.5 0 0 0.267 0.129 Bus2 -0.267 -0.129 44.2 90.0
Bus8 4.000 96.824 -2.5 0 0 0.267 0.129 Bus2 -0.267 -0.129 44.2 90.0
Bus9 12.000 99.955 0.0 0 0 0 0 Bus1 -4.270 -2.149 230.1 89.3
Bus2 1.481 0.798 81.0 88.0
Bus15 0.720 0.349 38.5 90.0
Bus14 0.337 0.163 18.0 90.0
Bus13 0.337 0.163 18.0 90.0
Bus11 0.945 0.458 50.5 90.0
Bus10 0.450 0.218 24.1 90.0
Bus10 12.000 99.955 0.0 0 0 0.450 0.218 Bus9 -0.450 -0.218 24.1 90.0
Bus11 12.000 99.955 0.0 0 0 0.945 0.458 Bus9 -0.945 -0.458 50.5 90.0
Bus13 12.000 99.955 0.0 0 0 0.337 0.163 Bus9 -0.337 -0.163 18.0 90.0
Bus14 12.000 99.955 0.0 0 0 0.337 0.163 Bus9 -0.337 -0.163 18.0 90.0
Bus15 12.000 99.955 0.0 0 0 0.720 0.349 Bus9 -0.720 -0.349 38.5 90.0
Bus18 4.000 96.824 -2.5 0 0 0.267 0.129 Bus2 -0.267 -0.129 44.2 90.0
* Indica una barra con tensión regulada (con máquinas de tensión controlada o máquinas de referencia conectadas)
# Indica una barra con tiene un error de convergencia de carga mayor a 0.1 MVA