Manual de instrucciones OI/FCB300/FCH300-ES Rev.

CoriolisMaster FCB330, FCB350, FCH330, FCH350


Caudalmetro Msico Coriolis

Measurement made easy


CoriolisMaster FCB330, FCB350, FCH330, FCH350
Caudalmetro Msico Coriolis

Manual de instrucciones
OI/FCB300/FCH300-ES

Rev. F
Fecha de edicin: 05.2014

Traduccin de las instrucciones originales

Fabricante
ABB Automation Products GmbH
Process Automation
Dransfelder Str. 2
37079 Gttingen
Germany
Tel: +49 551 905-0
Fax: +49 551 905-777

Customer Center Service


Phone.: +49 180 5 222 580
Fax: +49 621 381 931-29031
automation.service@de.abb.com

2 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


Change from one to tw o c olumns

Contenido 4.6.2 Montaje en vertical, en una tubera descendente 20


4.6.3 Montaje en horizontal para la medicin de lquidos
1 Seguridad ........................................................................ 6 .......................................................................... 20
1.1 Informaciones generales e indicaciones para la 4.6.4 Montaje en horizontal para la medicin de gases 20
lectura ................................................................. 6 4.6.5 Puntos de montaje problemticos para la medida
1.2 Uso conforme al fin previsto ................................. 6 de lquidos ......................................................... 21
1.3 Uso contrario al fin previsto .................................. 6 4.6.6 Puntos de montaje problemticos para la medida
1.4 Grupos destinatarios y cualificaciones .................. 6 de gases ............................................................ 21
1.5 Suministro de garanta ......................................... 6 4.6.7 Ajuste del cero ................................................... 21
1.6 Etiquetas y smbolos ............................................ 7 4.6.8 Instalacin en funcin de la temperatura del fluido
1.6.1 Smbolos de seguridad / peligro, smbolos de .......................................................................... 22
informacin .......................................................... 7 4.6.9 Instalacin en caso de uso de la opcin TE1
1.6.2 Placa de caractersticas ....................................... 7 "Longitud ampliada de la torre" .......................... 22
1.7 Instrucciones de seguridad para el transporte ...... 8 4.6.10 Notas sobre la conformidad EHEDG .................. 22
1.8 Instrucciones de seguridad para el montaje ......... 8
1.9 Instrucciones de seguridad para la instalacin 5 Conexiones elctricas ................................................... 23
elctrica ............................................................... 8 5.1 Instrucciones para conectar la alimentacin
1.10 Instrucciones de seguridad relativas al elctrica ............................................................. 23
funcionamiento .................................................... 8 5.2 Indicaciones para el cableado ............................ 23
1.11 Valores tcnicos lmite.......................................... 9 5.3 Diseo compacto............................................... 24
1.12 Fluidos permitidos................................................ 9 5.4 Diseo remoto ................................................... 25
1.13 Instrucciones de seguridad para trabajos de 5.4.1 Especificacin del cable ..................................... 25
inspeccin y mantenimiento ................................. 9 5.4.2 Colocacin del cable de seal ............................ 25
1.14 Devolucin de aparatos ....................................... 9 5.4.3 Conexin del cable de seal .............................. 25
1.15 Sistema de gestin integrado ............................. 10 5.5 Comunicacin digital .......................................... 26
1.16 Eliminacin de residuos ..................................... 10 5.5.1 Protocolo HART ................................................. 26
1.16.1 Informacin sobre la directiva WEEE 2002/96/CE 5.6 Esquemas de conexin ...................................... 27
(residuos de aparatos elctricos y electrnicos) 5.6.1 Conexin de modelos de transductor a equipos
(Waste Electrical and Electronic Equipment) ....... 10 perifricos .......................................................... 27
1.16.2 Directiva ROHS 2002/95/CE .............................. 10 5.6.2 Ejemplos de conexin con perifricos ................ 28
5.6.3 Conexin del transductor al sensor de caudal .... 29
2 Diseo y funcin............................................................ 11 5.6.4 Conexin del transductor al sensor de caudal en
2.1 Generalidades.................................................... 11 Zona 1 / Div. 1 ................................................... 30
2.2 Principio de medicin......................................... 11
2.3 Versiones del aparato ........................................ 12 6 Puesta en marcha ......................................................... 31
2.3.1 Cuadro sinptico del aparato ATEX, IECEx, NEPSI 6.1 Controles antes de la puesta en funcionamiento 31
.......................................................................... 14 6.2 Conectar la alimentacin de corriente................. 31
2.3.2 Cuadro sinptico del aparato cFMus.................. 15 6.2.1 Medidas de control despus de conectar la
alimentacin de corriente ................................... 31
3 Transporte ..................................................................... 16 6.3 Ajustes bsicos .................................................. 31
3.1 Controles ........................................................... 16 6.4 Configuracin de la salida de impulsos ............... 32
3.2 Generalidades.................................................... 16 6.5 Interruptor de proteccin contra modificaciones no
autorizadas ........................................................ 32
4 Montaje .......................................................................... 16 6.6 Instrucciones para el funcionamiento seguro en
4.1 Generalidades.................................................... 16 zonas potencialmente explosivas (ATEX) ............ 33
4.2 Sensor de caudal ............................................... 16 6.6.1 Controles ........................................................... 33
4.3 Transmisor......................................................... 17 6.6.2 Circuitos elctricos de salida .............................. 33
4.3.1 Transmisor de diseo remoto (opcin F1 o F2)... 17 6.6.3 Contacto NAMUR .............................................. 34
4.3.2 Transmisor de diseo remoto (opcin R1 o R2).. 17 6.6.4 Entradas de cables ............................................ 34
4.4 Orientacin de la caja del transmisor y del indicador 6.6.5 Aislamiento del sensor de caudal ....................... 34
LCD ................................................................... 18 6.6.6 Uso en la zona 2, con la clase de proteccin "a
4.4.1 Caja del transmisor ............................................ 18 prueba de vapor" (nR) ........................................ 34
4.4.2 Indicador LCD ................................................... 18 6.6.7 Cambio de tipo de proteccin ............................ 35
4.5 Instrucciones para el montaje............................. 19 6.7 Instrucciones para el funcionamiento seguro en
4.5.1 Requisitos de montaje / instrucciones de zonas potencialmente explosivas (cFMus) .......... 36
planificacin ....................................................... 19 6.7.1 Controles ........................................................... 36
4.5.2 Tramos de entrada ............................................ 19 6.7.2 Entradas de cables ............................................ 36
4.5.3 Modelos de diseo remoto ................................ 19 6.7.3 Conexin elctrica ............................................. 36
4.5.4 Prdida de presin............................................. 19 6.7.4 Process sealing.................................................. 37
4.6 Posiciones de montaje ....................................... 19 6.7.5 Cambio del tipo de proteccin ........................... 37
4.6.1 Montaje en vertical, en una tubera ascendente .. 19

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 3


7 Configuracin, parametracin ...................................... 38 10.3.2 Desviacin del valor medido ............................... 68
7.1 Manejo .............................................................. 38 10.3.3 Estabilidad del cero............................................ 69
7.1.1 Navegacin por mens ...................................... 38 10.3.4 Influencia de la temperatura del fluido ................ 69
7.2 Niveles del men ............................................... 38 10.3.5 Influencia de la presin operativa........................ 69
7.2.1 Indicador de procesos ....................................... 39 10.4 Datos tcnicos ................................................... 70
7.2.2 Cambio al nivel de configuracin (parametrizacin) 10.4.1 Prdida de presin............................................. 70
.......................................................................... 39 10.4.2 Rango de viscosidad ......................................... 70
7.2.3 Seleccin y modificacin de parmetros ............ 40 10.4.3 Lmites de temperatura C (F) ........................... 70
7.3 Resumen de los parmetros en el nivel de 10.4.4 Conexiones a proceso ....................................... 70
configuracin ..................................................... 41 10.4.5 Presin nominal ................................................. 70
7.4 Descripcin de los parmetros........................... 45 10.4.6 Carcasa como dispositivo de proteccin (opcional)
7.4.1 Men: *Prog. level.............................................. 45 70
7.4.2 Men: Language ................................................ 45 10.4.7 Directiva de equipos apresin ............................ 70
7.4.3 Men: Mode of operation ................................... 46 10.4.8 Materiales para el transmisor.............................. 71
7.4.4 Men: Concentration ......................................... 47 10.4.9 Materiales del sensor de caudal ......................... 71
7.4.5 Men: Unit ......................................................... 48 10.4.10 Cargas del material de las conexiones a proceso 71
7.4.6 Men: Flowmeter primary .................................. 49 10.4.11 Curvas de carga del material de los aparatos
7.4.7 Men: QmMax ................................................... 49 bridados ............................................................ 71
7.4.8 Men: Damping ................................................. 49
7.4.9 Men: Low cutoff setting ................................... 49 11 Datos tcnicos - Transmisor......................................... 72
7.4.10 Men: Field optimization .................................... 49 11.1 Generalidades.................................................... 72
7.4.11 Men: System Zero adj. ..................................... 50 11.2 Datos tcnicos ................................................... 72
7.4.12 Men: Alarm ...................................................... 50 11.2.1 Rango de medida .............................................. 72
7.4.13 Men: Display .................................................... 51 11.2.2 Tipo de proteccin ............................................. 72
7.4.14 Men: Totalizer .................................................. 52 11.2.3 Conexin elctrica ............................................. 72
7.4.15 Men: Pulse Output ........................................... 53 11.2.4 Suministro de energa ........................................ 72
7.4.16 Men: Current output 1 ..................................... 54 11.2.5 Tiempo de reaccin ........................................... 72
7.4.17 Men: Current output 2 ..................................... 55 11.2.6 Temperatura ambiente ....................................... 72
7.4.18 Men: Switch contacts ...................................... 56 11.2.7 Versin de caja .................................................. 72
7.4.19 Men: Label....................................................... 56 11.2.8 Medicin de caudal de avance / retorno............. 72
7.4.20 Men: Interface .................................................. 56 11.2.9 Indicador LCD.................................................... 72
7.4.21 Men: Function test ........................................... 57 11.2.10 Mando ............................................................... 73
7.4.22 Men: Status ..................................................... 59 11.2.11 Seguridad de datos ........................................... 73
7.4.23 Men: Versin del software ................................ 59 11.3 Especificaciones elctricas................................. 73
7.5 Medida de concentraciones DensiMass (slo 11.3.1 Salidas de corriente ........................................... 73
disponible para FCB350) ................................... 60 11.3.2 Salida de impulsos ............................................. 74
7.5.1 Precisin de la medida de concentraciones ....... 60 11.3.3 Salidas de contacto digitales.............................. 74
7.5.2 Introduccin de la matriz de concentraciones .... 60 11.3.4 Entradas de contacto digitales ........................... 74
7.5.3 Estructura de la matriz de concentraciones ........ 61
7.6 Historial de versiones del software ..................... 62 12 Datos tcnicos relevantes para la proteccin contra
explosiones conforme a ATEX / IECEx / NEPSI........... 75
8 Mensajes de error ......................................................... 62 12.1 Especificaciones elctricas................................. 75
8.1 Generalidades ................................................... 62 12.1.1 Resumen de las diferentes opciones de salida ... 75
8.2 Sinopsis............................................................. 63 12.1.2 Versin I: salidas de corriente activa / pasiva ...... 75
8.3 Mensajes de error .............................................. 64 12.1.3 Versin II: salidas de corriente pasiva / pasiva .... 76
8.4 Mensajes de advertencia ................................... 66 12.1.4 Condiciones especiales de conexin .................. 76
12.2 Modelo de sensor de caudal FCB3xx / FCH3xx . 77
9 Mantenimiento / Reparacin ........................................ 67 12.2.1 Clase de temperatura ........................................ 77
9.1 Generalidades ................................................... 67 12.2.2 Homologacin de proteccin contra explosiones
9.2 Limpieza ............................................................ 67 ATEX / IECEx / NEPSI ........................................ 78
9.3 Sensor de caudal............................................... 67 12.3 Transductor de diseo remoto Modelo FCT30079
9.4 Transmisor......................................................... 67 12.3.1 Homologacin de proteccin contra explosiones
9.4.1 Cambio.............................................................. 67 ATEX / IECEx / NEPSI ........................................ 79

10 Datos tcnicos - Sensor de caudal .............................. 68


10.1 Diseos ............................................................. 68
10.2 Dimetro nominal y rango de medicin .............. 68
10.2.1 Rango de caudal recomendado ......................... 68
10.3 Precisin............................................................ 68
10.3.1 Condiciones de referencia.................................. 68

4 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


13 Datos tcnicos relevantes para la proteccin Ex segn
cFMus ............................................................................ 80
13.1 Resumen de las diferentes opciones de salida ... 80
13.2 Datos elctricos para Div. 2 / Zona 2 ................. 80
13.2.1 Versin I: salidas de corriente activa / pasiva y
versin II: salidas de corriente pasiva / pasiva..... 80
13.3 Datos elctricos para Div. 1 / Zona 1 ................. 81
13.3.1 Versin I: salidas de corriente activa / pasiva ...... 81
13.3.2 Versin II: salidas de corriente pasiva / pasiva .... 81
13.3.3 Condiciones especiales de conexin.................. 81
13.4 Sensor de caudal Modelo FCB300 / FCH300.. 82
13.4.1 Clases de temperatura ....................................... 82
13.4.2 Homologacin de proteccin contra explosiones
cFMus ............................................................... 83
13.5 Transmisor de diseo remoto Modelo FCT300 85
13.5.1 Homologacin Ex cFMus ................................... 85

14 Anexo ............................................................................. 87
14.1 Homologaciones y certificados .......................... 87
14.2 Installation diagram 3KXF002126G0009 ............ 92

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 5


1 Seguridad 1.2 Uso conforme al fin previsto
El aparato sirve para:
1.1 Informaciones generales e indicaciones para la La conduccin de fluidos lquidos y gaseosos (tambin
lectura fluidos inestables).
Lea atentamente este manual de instrucciones antes de La medida directa del caudal msico.
proceder al montaje y la puesta en marcha! La medida indirecta del flujo volumtrico (mediante la
El manual de instrucciones es una parte integrante esencial medida de la densidad y del caudal msico).
del producto y deber guardarse para su uso posterior. La medida de la densidad del fluido.
Para asegurar una orientacin fcil, este manual no puede dar La medida de la temperatura del fluido.
una informacin exhaustiva sobre todas las versiones del
producto, ni tratar todas las formas posibles de instalacin, El uso conforme al fin previsto comprende tambin los
funcionamiento o conservacin. siguientes puntos:
Si precisa ms informacin o si surgen anomalas no descritas Se deben cumplir y seguir las instrucciones de este
con detalle en el presente manual de instrucciones, le manual.
rogamos se ponga en contacto con el fabricante para solicitar Se deben mantener los valores lmite indicados. Vase el
ms informacin. captulo "Valores tcnicos lmite".
El presente manual de instrucciones ni forma parte ni contiene Se deben utilizar exclusivamente los fluidos permitidos.
una modificacin de un acuerdo, una promesa o relacin Vase el captulo "Fluidos permitidos".
jurdica anterior o existente.
El producto cumple los requisitos de seguridad y los niveles 1.3 Uso contrario al fin previsto
tecnolgicos actuales. Ha sido examinado y ha salido de No est permitido el uso del aparato para:
fbrica en condiciones perfectas de seguridad. Para mantener utilizarlo como adaptador flexible en tuberas, como p. ej.,
estas condiciones durante el tiempo de servicio previsto, se para compensar desviaciones, vibraciones y dilataciones
deben observar y seguir las indicaciones del presente manual de las mismas, etc.
de instrucciones. utilizarlo como peldao, p. ej., para realizar trabajos de
Las modificaciones y reparaciones estn nicamente montage
permitidas en la forma descrita en el manual de instrucciones. utilizarlo como soporte para cargas externas, p. ej., como
Slo cuando se siguen y se observan las indicaciones de soporte para tuberas, etc.
seguridad y todos los smbolos de seguridad y advertencia del recubrirlo con otros materiales, p. ej., por sobrepintar la
manual de instrucciones, se garantiza que el personal placa de caractersticas o soldar piezas
operador y el medio ambiente estn protegidos contra arranque de material, p. ej. mediante perforacin de la
peligros posibles y que el aparato funcione correctamente. carcasa
Es absolutamente necesario que se observen y sigan los
smbolos e indicaciones que se encuentran en la carcasa del 1.4 Grupos destinatarios y cualificaciones
aparato. Asegrese de que sean perfectamente legibles. No La instalacin, puesta en marcha y mantenimiento del
est permitido eliminarlos. producto slo deben ser llevados a cabo por personal
especializado debidamente instruido que haya sido autorizado
por el propietario del equipo. El personal especializado tiene
que haber ledo y entendido el manual y debe seguir sus
indicaciones.
El usuario debe seguir bsicamente las disposiciones
nacionales vigentes en su pas relacionadas con la instalacin,
verificacin, reparacin y conservacin de productos
elctricos.

1.5 Suministro de garanta


Cualquier forma de uso que se no corresponda con el fin
previsto, as como el incumplimiento de este manual de
instrucciones o el empleo de personal insuficientemente
cualificado y modificaciones arbitrarias del aparato, excluyen
la responsabilidad del fabricante por daos y perjuicios que
resulten de ello. En este caso se extinguir la garanta del
fabricante.

6 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


1.6 Etiquetas y smbolos 1.6.2 Placa de caractersticas
1.6.1 Smbolos de seguridad / peligro, smbolos de
informacin IMPORTANTE (NOTA)
Las placas de caractersticas representadas son
PELIGRO Daos graves para la salud / solo ejemplos. Las placas de caractersticas
peligro de muerte! colocadas en el aparato pueden divergir de esta
Este smbolo indica, en combinacin con el representacin.
mensaje "PELIGRO", un peligro inminente. El
incumplimiento de esta indicacin de seguridad
causar la muerte o lesiones gravsimas.

PELIGRO Daos graves para la salud /


peligro de muerte!
Este smbolo indica, en combinacin con el
mensaje "PELIGRO", un peligro inminente por
corriente elctrica. El incumplimiento de esta
indicacin de seguridad causar la muerte o
lesiones gravsimas.

ADVERTENCIA Daos fsicos!


El smbolo indica, en combinacin con el mensaje
"ADVERTENCIA", una situacin que puede ser
peligrosa. El incumplimiento de esta indicacin de
seguridad puede causar la muerte o lesiones
gravsimas.

ADVERTENCIA Daos fsicos!


Este smbolo indica, en combinacin con el
mensaje "ADVERTENCIA", una situacin que
puede resultar peligrosa debido a la corriente
elctrica. El incumplimiento de esta indicacin de
seguridad puede causar la muerte o lesiones
gravsimas.

ATENCIN Lesiones leves!


El smbolo indica, en combinacin con el mensaje
"ATENCIN", una situacin que puede ser
peligrosa. El incumplimiento de esta indicacin de
seguridad puede causar lesiones leves o menos
graves. El smbolo puede ser utilizado tambin
para advertir de daos materiales. Fig. 1: Sensor de caudal con forma compacta (ejemplo)
1 Denominacin de modelo completa | 2 Cdigo para pedido |
3 Nmero de pedido | 4 Suministro de energa |
AVISO Daos materiales!
5 Dimetro nominal / modo de proteccin |
El smbolo indica una situacin que puede ser 6 Conexin a proceso / nivel de presin |
daina. 7 Material del tubo de medicin | 8 Coeficiente de calibracin |
El incumplimiento de esta indicacin de seguridad 9 Caudal mximo | 10 Rango de temperatura media |
puede ocasionar daos o la destruccin del 11 Versin del software | 12 Fabricante |
13 Ao de construccin (mes / ao) |
producto y/o de otros componentes del equipo. 14 Rango de temperatura ambiente | 15 Comunicacin |
16 Precisin de calibracin |
IMPORTANTE (NOTA) 17 Marca PED (directiva de equipos a presin) |
18 Consumo de potencia mximo | 19 Nmero de serie del sensor |
El smbolo indica consejos para el usuario o
20 Marca CE | 21 Homologacin Ex cFMus |
informaciones muy tiles o importantes sobre el 22 Homologacin Ex ATEX / IECEx
producto o sus ventajas adicionales. La
indicacin "IMPORTANTE (NOTA)" no advierte de
situaciones peligrosas o dainas.

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 7


1.7 Instrucciones de seguridad para el transporte 1.9 Instrucciones de seguridad para la instalacin
Deben observarse las siguientes indicaciones: elctrica
Durante el transporte, no exponer el aparato a humedad. La conexin elctrica debe efectuarse exclusivamente por
Embalar el aparato adecuadamente. personal tcnico autorizado y de acuerdo con los esquemas
Embalar el aparato de tal forma que queda protegido de conexiones.
contra choques o vibraciones (p. ej: embalaje con colchn Deben seguirse las instrucciones para la conexin elctrica
de aire). para no deshabilitar el modo de proteccin elctrica.
Segn el tipo de aparato, el centro de gravedad puede no Poner a tierra el sistema de medida siguiendo las indicaciones
estar en el centro del equipo. correspondientes.

1.8 Instrucciones de seguridad para el montaje 1.10 Instrucciones de seguridad relativas al


Antes de instalar los aparatos hay que asegurarse de que no funcionamiento
presenten daos por transporte inadecuado. Los daos de Asegrese, antes de conectar el aparato, de que se cumplen
transporte deben ser documentados. Todas las reclamaciones las condiciones ambientales indicadas en el captulo "Datos
de indemnizacin por daos debern presentarse tcnicos" o en la especificacin tcnica.
inmediatamente, y antes de la instalacin, ante el transportista Cuando sea de suponer que ya no es posible utilizar el
competente. aparato sin peligro, pngalo fuera de funcionamiento y
asegrelo contra arranque accidental.
El sentido de caudal debe corresponder con la
sealizacin (en caso de que exista). Fluidos calientes pueden causar quemaduras, por lo que hay
Debe mantenerse el par de apriete mximo en todos los que evitar tocar la superficie del aparato.
tornillos de las bridas. Los fluidos agresivos o corrosivos pueden daar las partes
Al montar el aparatos se deben evitar tensiones mojadas. Debido a ello, se pueden producir fugas de los
mecnicas (torsin, flexin). fluidos sometidos a presin.
Los aparatos bridados deben montarse con contrabridas La fatiga de las juntas de las conexiones a proceso (p. ej.,
planoparalelas. racor roscado asptico, Tri-Clamp, etc.) puede provocar fugas
Los aparatos deben ser aptos para las condiciones de de fluidos a presin.
servicio previstas y deben instalarse con juntas Juntas planas internas (si existen) pueden fragilizarse por
adecuadas. procesos CIP/SIP.
En caso de vibraciones de la tubera, utilizar fijaciones
apropiadas para los tornillos y tuercas de las bridas. ADVERTENCIA! Peligro de intoxicacin!
Las tuberas y fluidos pueden contaminarse por
bacterias y sustancias qumicas txicas.
En instalaciones segn EHEDG se deben
observar las indicaciones siguientes:

El vaciado automtico del caudalmetro, necesario segn


el montaje conforme a EHEDG, solo se garantiza con el
montaje en vertical.
Para instalaciones segn la normativa EHEDG, es
absolutamente necesario que la combinacin de conexin
a proceso y juntas realizada por el cliente o propietario
cumpla la normativa EHEDG. Para ello, tenga en cuenta
las indicaciones de la versin actual del documento
EHEDG Position Paper: "Hygienic Process connections to
use with hygienic components and equipment".

8 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


1.11 Valores tcnicos lmite 1.13 Instrucciones de seguridad para trabajos de
El aparato se ha concebido para utilizarse exclusivamente inspeccin y mantenimiento
dentro de los valores tcnicos lmite indicados en la placa de
caractersticas y en las especificaciones tcnicas. ADVERTENCIA - Peligro por corriente
Deben mantenerse los siguientes valores tcnicos lmite: elctrica!
La presin (PS) y temperatura (TS) permitidas del fluido no Cuando la caja est abierta, la proteccin CEM
deben exceder los valores de presin y temperatura no funciona y el usuario no est protegido contra
previstos (p/T-Ratings) (vase el captulo "Datos el riesgo de contacto accidental.
tcnicos"). Antes de abrir la caja hay que desconectar la
La temperatura de servicio no debe exceder o bajar por alimentacin elctrica.
debajo del valor lmite mximo/mnimo previsto.
No debe sobrepasarse la temperatura ambiente permitida. Los trabajos de reparacin y mantenimiento slo deben ser
Durante el uso del aparato deber mantenerse el modo de llevados a cabo por personal especializado debidamente
proteccin de la caja. instruido.
El sensor de caudal no debe instalarse en las Antes de desmontar el aparato hay que despresurizar el
proximidades de campos electromagnticos fuertes, p. aparato y, si existen, los conductos y recipientes
ej., motores, bombas, transformadores, etc. Se debe adyacentes.
mantener la distancia mnima de ~1 m (3,28 ft). Durante el Antes de abrir el aparato se debe controlar si han sido
montaje sobre/en piezas de acero (p. ej., soportes de utilizadas sustancias peligrosas. Es posible que el aparato
acero) debe mantenerse una distancia mnima de 100 mm contenga restos peligrosos que puedan salir cuando se
(4). (Estos valores se han determinado en conformidad abra el aparato.
con la norma IEC801-2 y/o IECTC77B).
En cuanto est previsto dentro del marco de responsabilidad
1.12 Fluidos permitidos del usuario, debern realizarse inspecciones peridicas para
Para utilizar los fluidos correctamente es necesario que se controlar los siguientes puntos:
observen y sigan las instrucciones siguientes: las paredes expuestas a la presin / el revestimiento del
Slo deben utilizarse fluidos en los que pueda asegurarse, aparato a presin
segn la tcnica actual o la experiencia de trabajo del la funcin tcnica de medicin
usuario/propietario, que las propiedades fsicas y qumicas la estanqueidad
de los materiales en contacto con el fluido no puedan el desgaste (corrosin)
perjudicarse y, a consecuencia de ello, mermar el tiempo
de servicio previsto. 1.14 Devolucin de aparatos
Por ejemplo, los fluidos que tengan un alto contenido de Para el envo de aparatos para reparacin o recalibracin
cloro pueden causar daos de corrosin invisibles en los deber utilizarse el embalaje original o un recipiente apropiado
componentes de acero inoxidable, que pueden destruir, de transporte.
en consecuencia, las partes mojadas y provocar fugas de El aparato debe enviarse acompaado del impreso de reenvo
fluido. El propietario/usuario deber controlar que los debidamente rellenado (vase el captulo "Anexo").
materiales utilizados sean apropiados para la aplicacin Segn la Directiva CE sobre Sustancias Peligrosas, los
prevista. propietarios de basuras especiales son responsables de su
Los fluidos con propiedades desconocidas o los fluidos correcta eliminacin y deben observar las siguientes
abrasivos slo deben utilizarse si el usuario puede instrucciones:
asegurar unas condiciones seguras del aparato mediante Todos los aparatos que se enven a ABB tendrn que estar
una comprobacin adecuada efectuada con regularidad. libres de sustancias peligrosas (cidos, lejas, soluciones,
Observe las especificaciones indicadas en la placa de etc.).
caractersticas.
Consulte al Servicio de atencin al cliente (direccin en la
pgina 2) para el establecimiento colaborador ms cercano.

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 9


1.15 Sistema de gestin integrado 1.16.1 Informacin sobre la directiva WEEE 2002/96/CE
La ABB Automation Products GmbH dispone de un sistema (residuos de aparatos elctricos y electrnicos)
de gestin integrado compuesto por: (Waste Electrical and Electronic Equipment)
El sistema de gestin de calidad ISO 9001:2008 El presente producto no est sujeto a la directiva WEEE
El sistema de gestin ambiental ISO 14001:2004 2002/96/CE ni a las leyes nacionales pertinentes (en Alemania,
El sistema de gestin de salud y salud ocupacional p. ej., ElektroG).
BS OHSAS 18001:2007 y El producto usado debe entregarse a una empresa de
El sistema de gestin de proteccin de datos e reciclaje especializada. Por favor, no utilice los puntos de
informacin. recogida de basura habituales. Estos deben utilizarse
solamente para productos de uso privado segn la directiva
La preocupacin por el medioambiente forma parte de la WEEE 2002/96/CE. La eliminacin adecuada evita
poltica de nuestra empresa. repercusiones negativas sobre el hombre y el medio ambiente
Durante la fabricacin, el almacenamiento, transporte, uso y la y permite el reciclaje de materias primas valiosas.
explotacin y eliminacin de nuestros productos y soluciones Si no existe ninguna posibilidad de eliminar el equipo usado
tcnicas, la carga contaminante al medio ambiente y a las debidamente, nuestro servicio posventa est dispuesto a
personas debe minimizarse al mximo. recoger y eliminar el equipo abonando las tasas
Esto requiere, en particular, que los recursos naturales se correspondientes.
utilicen con la precaucin debida. Nuestros folletos de
informacin sirven para llevar un dilogo abierto con el 1.16.2 Directiva ROHS 2002/95/CE
pblico. Con la ElektroG, Alemania transpone las Directivas europeas
2002/96/CE (WEEE) y 2002/95/CE (RoHS) en Derecho
1.16 Eliminacin de residuos nacional. Por un lado, la ElektoG regula cules productos
El presente producto est compuesto por materiales que deben recogerse y eliminarse de forma ordenada o reutilizarse
pueden reciclarse en plantas de reciclaje especializadas. en caso de eliminacin / al final de su duracin til. Por otro
lado, la ElektroG prohibe la comercializacin de equipos
elctricos y electrnicos que contengan cantidades
determinadas de plomo, cadmio, mercurio, cromo
hexavalente, bifenoles polibromurados (PBB) y difenilos
polibromurados (PBDE) (sustancias prohibidas).
Los productos suministrados por ABB Automation Products
GmbH no estn sujetos al mbito de aplicacin de la
prohibicin de sustancias peligrosas, o bien, la directiva sobre
restricciones en el uso de determinadas sustancias peligrosas
en equipos electrnicos y elctricos usados (segn ElektroG).
En el supuesto de que los componentes necesarios estn
disponibles a tiempo en el mercado, podremos renunciar, en
el futuro, a utilizar estas sustancias en desarrollos nuevos.

10 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


2 Diseo y funcin Funcin para clcular el fuerza de Coriolis

2.1 Generalidades
Los caudalmetros msicos de ABB Automation Products
funcionan segn el principio de Coriolis. Signo de frmula Descripcin
El modelo equipado con las tuberas de medida paralelas Fuerza de Coriolis
convencionales se distingue especialmente por su diseo Velocidad angular
compacto, el dimetro nominal grande y su ventaja econmica Velocidad de la masa
para el cliente. m Masa

2.2 Principio de medicin


Cuando a travs de una tubera vibrante fluyen masas, se
producen fuerzas de Coriolis que deforman la tubera. Estas
deformaciones muy pequeas de la tubera de medida se
registran y se evalan por sensores ptimamente dispuestos.
Como el desplazamiento de fase de las seales del sensor es
proporcional al caudal, el caudalmetro msico coriolis puede
medir directamente el caudal msico transportado a travs de
la tubera de medida. Este principio de medida funciona
independientemente de la densidad, temperatura, viscosidad,
presin y conductividad.
Las tuberas de medida vibran siempre en resonancia. Esta
frecuencia de resonancia depende de la forma geomtrica de
la tubera de medida, de las propiedades del material y de la
masa del fluido vibrante en la tubera de medida. As se
obtiene una informacin extacta sobre la densidad del fluido a
medir.
El aparato tiene incorporada un sensor de temperatura que
sirve para corregir los parmetros dependientes de la
temperatura. Resumiendo puede decirse que el caudalmetro Fig. 2: Representacin grfica simplificada del efecto dinmico de
la fuerza de Coriolis
msico coriolis permite medir al mismo tiempo el caudal
msico, la densidad y la temperatura. Partiendo de estos
valores se pueden calcular otras magnitudes de medida Fig. 2 Descripcin
como, p. ej., el flujo volumtrico o la concentracin. "A" Movimiento de las tuberas, hacia adentro, sin caudal
"B" Direccin de las fuerzas de Coriolis, con caudal y movimiento
de las tuberas hacia afuera
"C" Movimiento de las tuberas, hacia afuera, sin caudal
"D" Direccin de las fuerzas de Coriolis, con caudal y movimiento
de las tuberas hacia adentro

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 11


Change from two to one c olumn

2.3 Versiones del aparato

Sensor de caudal FCB300 y FCH300

Nmero de modelo FCB300 para aplicaciones estndar FCH300 para aplicaciones higinicas
Conexiones a proceso
Brida DIN 2501 / EN 1092-1 DN 10 200, PN 40 100 -
Brida ASME B16.5 DN 1/4 8 PN CL150 CL600 -
Racor DIN 11851 DN 10 100 (1/4" 4") DN 25 80 (1" 3")
Tri-Clamp DIN 32676 (ISO 2852) DIN 32676 (ISO 2852)
BPE Tri-Clamp BPE Tri-Clamp
DN 10 100 (1/4" 4") DN 20 100 (3/4" 4")
Otras conexiones Bajo pedido Bajo pedido
Materiales de partes mojadas Acero inoxidable Acero CrNi pulido 1.4404 (AISI 316L) o 1.4435 (AISI
Nickel-Alloy C4 / C22 316L)
Tipo de proteccin conforme a IP 65 / 67, NEMA 4X IP 65 / 67, NEMA 4X
EN 60529
Homologaciones y certificados
Proteccin contra explosiones ATEX / Zona 0, 1, 2, 21, 22 Zona 0, 1, 2, 21, 22
IECEx
Proteccin contra explosiones cFMus Class I Div. 1, Class I Div. 2, Zona 0, 1, 2, 20, 21 Class I Div. 1, Class I Div. 2, Zona 0, 1, 2, 20, 21
Proteccin contra explosiones NEPSI Zona 0, 1, 2, 21, 22 Zona 0, 1, 2, 21, 22
Homologaciones de normas sobre - EHEDG, conforme a FDA
higiene
Otras homologaciones Bajo pedido
Carcasa Diseo compacto, diseo remoto
Precisin de medicin de lquidos FCB330 FCB350 FCH330 FCH350
Caudal msico 1) 0,4 % y 0,25 % 0,1 % y 0,15 % 0,4 % y 0,25 % 0,1 % y 0,15 %
Caudal volumtrico 1) 0,4 % y 0,25 % 0,15 % 0,4 % y 0,25 % 0,15 %
Densidad 0,01 kg/l 0,002 kg/l 0,01 kg/l 0,002 kg/l
0,001 kg/l (opcional) 0,001 kg/l (opcional)
0,0005 kg/l 2) 0,0005 kg/l 2)
Temperatura 1K 0,5 K 1K 0,5 K
Precisin de medicin de gases 1) 1% 0,5 % 1% 0,5 %
Temperatura permitida del fluido -50 160 C -50 200 C -50 160 C -50 200 C
(-58 320 F) (-58 392 F) (-58 320 F) (-58 392 F)

1) Indicacin de la precisin en % del valor medido (% v. M.)


2) Precisin tras ajuste in situ en condiciones de funcionamiento

12 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


Transductor FCTXXX

Carcasa Diseo compacto Diseo remoto


Longitud del cable 10 m (33 pies) como mximo, solo para diseo remoto
Suministro de energa 100 230 V AC, 24 V AC/DC
Salida de corriente Salida de corriente 1: activa, 0/4 20 mA o pasiva, 4 20 mA
Salida de corriente 2: pasiva, 4 20 mA
Salida de impulsos Activa (no disponible para Zona 1 / Div. 1) o pasiva
Desconexin externa de la salida S
Puesta a cero externa del contador S
Medicin de caudal de avance / retorno S
Comunicacin Protocolo HART
Deteccin de tubera vaca S, mediante una alarma de densidad preajustada de < 0,5 kg/l
Supervisin automtica y diagnstico S
Visualizacin in situ / contador S
Optimizacin de campo, para el caudal y S
la densidad
Tipo de proteccin conforme a EN 60529 Diseo compacto: IP 65 / IP 67, NEMA 4X
Diseo remoto: IP 67, NEMA 4X

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 13


2.3.1 Cuadro sinptico del aparato ATEX, IECEx, NEPSI

Estndar / sin proteccin contra Zona 2, 21, 22 Zona 1, 21 (Zona 0)


explosiones
Nmero de modelo FCx3xx Y0 FCx3xx A2, S2 FCx3xx A1, S1
Diseo compacto
Estndar
Zona 2, 21, 22
Zona 1, 21
Zona 0

Nmero de modelo FCT3xx Y0 FCx3xx Y0 FCT3xx A2 FCx3xx A2, S2 FCT3xx A2, A1 FCx3xx A1, S1
Diseo remoto
Transductor de
medicin y sensor de
caudal
Estndar
Zona 2, 21, 22
Zona 1, 21
Zona 0
Nmero de modelo FCT3xx Y0 FCT3xx A2 FCx3xx A1, S1
Diseo remoto
Transductor de
medicin
Estndar
Zona 2, 21, 22
Sensor de caudal
Zona 1, 21
Zona 0

IMPORTANTE (NOTA)
Para ver informacin detallada, consulte el captulo "Datos tcnicos relevantes para la proteccin contra explosiones conforme
a ATEX / IECEx / NEPSI" o el certificado de homologacin.

14 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


2.3.2 Cuadro sinptico del aparato cFMus

Estndar / sin proteccin contra Class I Div. 2 Zone 2, 21 Class I Div. 1 Zone 0, 1, 20 ,21
explosiones
Nmero de modelo FCx3xx Y0 FCx3xx F2 FCx3xx F1
Diseo compacto
Estndar
Class I Div. 2
Class I Div. 1
Zone 2, 21
Zone 1, 21
Zone 0, 20
Nmero de modelo FCT3xx Y0 FCx3xx Y0 FCT3xx F2 FCx3xx F2 FCT3xx F1 FCx3xx F1
Diseo remoto
Transductor de
medicin y sensor de
caudal
Estndar
Class I Div. 2
Class I Div. 1
Zone 2, 21
Zone 1, 21
Zone 0, 20
Nmero de modelo FCT3xx Y0 FCT3xx F2 FCx3xx F1
Diseo remoto
Transductor de
medicin
Estndar
Class I Div. 2
Zone 2, 21
Sensor de caudal
Class I Div. 1
Zone 1, 21
Zone 0, 20

IMPORTANTE (NOTA)
Para ver informacin detallada, consulte el captulo "Datos tcnicos relevantes para la proteccin Ex segn cFMus" o el
certificado de homologacin.

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 15


Change from one to tw o c olumns

3 Transporte 3.2 Generalidades


Durante el transporte del aparato al punto de medicin debe
3.1 Controles tenerse en cuenta:
Inmediatamente despus de desembalarlos hay que El centro de gravedad no est en el centro del aparato.
asegurarse de que los aparatos no presenten daos por Los aparatos bridados no deben levantarse a travs de la
transporte inadecuado. carcasa del transmisor o de la caja de conexin.
Los daos de transporte deben ser documentados.
Todas las reclamaciones de indemnizacin por daos debern
presentarse inmediatamente, y antes de la instalacin, ante el
expedidor competente.
Change from two to one c olumn

Change from one to tw o c olumns

4 Montaje 4.2 Sensor de caudal


El aparato se puede instalar en cualquier zona de la tubera,
4.1 Generalidades siempre que se cumplan los requisitos de instalacin.
Durante el montaje se deben observar los siguientes puntos: 1. Desmontar las placas protectoras montadas en los lados
El sentido del caudal debe corresponder con la izquierdo y derecho del sensor de caudal (si existen).
sealizacin (en caso de que exista). 2. Montar el sensor de caudal de manera que se site
Asegrese al montar los tornillos de la brida de no planoparalela y cntricamente entre las tuberas.
sobrepasar el par mximo de apriete. 3. Colocar las juntas entre las superficies de junta.
Al montar el aparatos se deben evitar tensiones
mecnicas (torsin, flexin).
Los aparatos de brida/Wafer deben montarse con
contrabridas planoparalelas y solamente con juntas
apropiadas.
Las juntas utilizadas deben ser de un material resistente al
fluido y a la temperatura del fluido. En el caso de equipos
higinicos "Hygienic Design", usar material estanqueizante
adecuado.
Las juntas no deben penetrar en la zona de flujo, porque
se pueden producir turbulencias que afectan la precisin
del aparato.
La tubera no debe ejercer ninguna fuerza o par de torsin
sobre el aparato.
Los tapones de los pasacables no deben desmontarse
antes de que se monten los cables elctricos.
Asegrese de que las juntas de la tapa de la caja queden
asentadas correctamente. Cerrar la tapa correctamente.
Apretar las uniones roscadas de la tapa.
Transmisores externos deben instalarse en un lugar libre
de vibraciones.
Asegrese de que el transmisor y el sensor de caudal no
estn expuestos directamente a los rayos del sol; instalar
un dispositivo de proteccin contra rayos solares, si es
necesario.
Al instalar el transmisor en un armario de distribucin, es
necesario asegurar una refrigeracin suficiente.

16 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


Change from two to one c olumn

4.3 Transmisor
El transmisor debe instalarse en un lugar que, en lo posible, est libre de vibraciones (vase el captulo "Datos tcnicos"). No
deben sobrepasarse los valores lmite de temperatura indicados y la longitud mxima permitida del cable de seal entre el
transmisor y sensor de caudal.

IMPORTANTE (NOTA)
Asegrese al elegir el lugar de montaje de que el transmisor no est expuesto directamente a los rayos del sol.
Si no es posible evitar la radiacin directa del sol, hay que instalar un dispositivo de proteccin contra rayos
solares.
Deben mantenerse los valores lmite de la temperatura ambiente.

Caja de campo
La caja tiene el modo de proteccin IP 65 / 67, NEMA 4X (EN 60529) y debe fijarse con cuatro tornillos. Medidas: vese Fig. 3 y
Fig. 4.

4.3.1 Transmisor de diseo remoto (opcin F1 o F2)

Fig. 3: Medidas en mm (inch)


1 Caja de campo con ventana | 2 Racor atornillado para cables M20 x 1,5 1/2 NPT |
3 Agujeros de fijacin para el kit de montaje para tubos de 2"; kit de montaje bajo demanda (referencia de pedido: 612B091U07) |
4 Modo de proteccin IP 67

4.3.2 Transmisor de diseo remoto (opcin R1 o R2)


IP 65 / 67, NEMA 4X

Fig. 4: Medidas en mm (inch)

Change from one to tw o c olumns

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 17


4.4 Orientacin de la caja del transmisor y del indicador 4.4.2 Indicador LCD
LCD
Segn la posicin de montaje, es posible girar la caja del ADVERTENCIA - Peligro por corriente
transmisor compacto/indicador LCD y orientarla elctrica!
horizontalmente, para poder leer mejor la pantalla. Cuando la caja est abierta, la proteccin CEM
no funciona y el usuario no est protegido contra
4.4.1 Caja del transmisor el riesgo de contacto accidental.
Para girar la caja del transmisor, se deben realizar los pasos Antes de abrir la caja hay que desconectar la
siguientes. Un dispositivo de bloqueo en la caja del transmisor alimentacin elctrica.
impide su giro en exceso (>330).
Para girar el indicador LCD, se deben realizar los pasos
siguientes.

Fig. 6: Orientacin del indicador LCD

1. Desconectar la alimentacin elctrica.


2. Desmontar la tapa de la caja (1).
3. Aflojar los cuatro tornillos de fijacin (2) del indicador LCD.
A continuacin, el indicador LCD cuelga del mazo de
cables conectado a la unidad electrnica enchufable.
4. Fijar el indicador LCD en la posicin deseada. Asegrese
de no daar el mazo de cables.
5. Volver a montar la tapa de la caja (1).

AVISO Prdida del modo de proteccin de


la caja!
Fig. 5: Orientacin de la caja del transmisor Prdida del modo de proteccin de la caja por
1 Tornillo de fijacin | 2 Caja del transmisor asiento incorrecto o dao de la junta (junta
trica).
1. Aflojar los tornillos de fijacin (2 vueltas, Antes de cerrar la tapa de la caja, controlar la
aproximadamente) junta (junta trica) y cambiarla, si es necesario.
2. Girar cautelosamente la caja del transmisor, hasta Asegrese al cerrar la tapa de la caja de que la
alcanzar la posicin deseada. junta est asentada correctamente.
3. Apretar el tornillo de fijacin.

PELIGRO Peligro de explosin!


Posible riesgo de perjudicar la proteccin contra
explosin.
No desmontar el transmisor del sensor de caudal.

18 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


4.5 Instrucciones para el montaje En principio, no son necesarios dispositivos de apoyo ni
4.5.1 Requisitos de montaje / instrucciones de amortiguadores especiales en el dispositivo.
planificacin En el caso de equipos industriales y martimos concebidos
El CoriolisMaster FCB330, FCB350, FCH330, FCH350 puede segn las prcticas recomendadas, se amortiguan
instalarse tanto en el interior como en el exterior. El modelo suficientemente las fuerzas habituales que se generan en
estndar tiene el tipo de proteccin IP 67. El sensor de caudal el dispositivo. Esto tambin es vlido para montaje de
permite la medicin en ambas direcciones de flujo y puede dispositivos en serie o paralelo. Para ello, es
instalarse en cualquier posicin. El usuario ha de asegurarse imprescindible usar y montar el dispositivo de la forma
de que las tuberas de medicin puedan llenarse prevista.
completamente en cualquier momento. Adems, el fluido no Para evitar daos en las conexiones a proceso y las
debe afectar a la resistencia de las partes mojadas. tuberas por las fuerzas transversales, en el caso de
dispositivos con un gran peso se deben utilizar
Durante la instalacin, se deben observar los siguientes dispositivos de apoyo adecuados montados por el
puntos: propietario.
En la direccin de montaje preferida, el caudal fluye por el
sensor en el sentido de la flecha. En este caso, se indica 4.5.2 Tramos de entrada
un caudal positivo (opcionalmente, hay disponible un El sensor de caudal no necesita tramos de entrada. Asegrese
dispositivo de calibracin para caudal directo/inverso).- de que las vlvulas, compuertas, mirillas etc. instaladas en la
La formacin de burbujas de gas en el tubo de medicin proximidad del sensor de caudal no se caviten y no estn
puede aumentar el nmero de errores de medicin, expuestas a vibraciones causadas por el sensor de caudal.
especialmente durante la medicin de la densidad. Por
ello, el sensor de caudal no debe montarse en el punto 4.5.3 Modelos de diseo remoto
ms alto del sistema. Lo ideal es un lugar de montaje que Asegrese de que el sensor de caudal y el transmisor sean
se encuentre entre el punto ms bajo del sistema y tenga compatibles. Las placas de caractersticas de los aparatos
una tubera en forma de U. compatibles tienen los mismos nmeros finales, p. ej., X001 y
Asegrese de que los gases disueltos en el fluido no se Y001 o X002 y Y002.
liberen y de que las tuberas de medicin estn siempre
totalmente llenas. Para garantizar esto, se recomienda 4.5.4 Prdida de presin
aplicar una contrapresin de 0,2 bar (2,9 psi) como La prdida de presin vara en funcin de las propiedades del
mnimo. fluido y el caudal actual.
En la medicin de gases, asegrese de que los gases Para obtener ayuda para el clculo de la prdida de presin,
estn secos y libres de humedad. descargue el archivo correspondiente de la pgina
En caso de presin negativa en la tubera de medicin o www.abb.com/flow.
en aplicaciones de lquidos con bajo punto de ebullicin,
hay que asegurarse de que la presin de vapor del fluido 4.6 Posiciones de montaje
no caiga por debajo del valor lmite exigido. El caudalmetro funciona en cualquier posicin de montaje. La
Asegrese de que no se efectan transiciones de fase en posicin de montaje ptima es en vertical con flujo en sentido
el fluido durante el funcionamiento. En el caso de fluidos ascendente.
gaseosos, se debe evitar una fase lquida.
Se recomienda no instalar tuberas largas de cada detrs IMPORTANTE (NOTA)
del sensor de caudal, a fin de impedir que las tuberas de El vaciado automtico del caudalmetro, necesario segn el
medicin puedan vaciarse completamente. montaje conforme a EHEDG, solo se garantiza con el montaje
Los dispositivos se pueden montar directamente en vertical.
desde/hacia tubos angulares, vlvulas u otros
componentes, siempre que no causen cavitacin. 4.6.1 Montaje en vertical, en una tubera ascendente
El dispositivo est concebido para un uso industrial. Si el
entorno electromagntico del campo de aplicacin cumple
las prcticas recomendadas de las normas de la
"Declaracin de conformidad CE", no se requieren
medidas especiales. En caso de campos
electromagnticos que superan la medida normal, debe
guardarse suficiente distancia.
Asegrese de que el sensor de caudal no entre en
contacto con otros objetos. El sensor de caudal no debe
fijarse en la carcasa.

Fig. 7: Montaje en vertical, con vaciado automtico

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 19


4.6.2 Montaje en vertical, en una tubera descendente 4.6.3 Montaje en horizontal para la medicin de lquidos
Asegrese de que el sensor de caudal est completamente
lleno durante el proceso de medicin.
Para ello, es necesario instalar un estrangulador u obturador
debajo del sensor de caudal. La seccin transversal del
estrangulador u obturador debe ser inferior a la de la tubera,
para impedir que el sensor de caudal se vace durante el
proceso de medicin.

Fig. 9: Montaje en horizontal (lquidos)

4.6.4 Montaje en horizontal para la medicin de gases

Fig. 10: Montaje horizontal (gases)

Para la medicin de gases, el transductor o la caja de


conexiones deben apuntar hacia abajo.

Fig. 8: Montaje en vertical, en una tubera descendente


1 Depsito de reserva | 2 Sensor de cauda l
3 Estrangulador u obturador | 4 Vlvula | 5 Recipiente de recogida

20 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


4.6.5 Puntos de montaje problemticos para la medida 4.6.7 Ajuste del cero
de lquidos Los dispositivos de la serie CoriolisMaster no necesitan
En la medida de lquidos hay que tener en cuenta que obligatoriamente un ajuste del punto cero. Solo se recomienda
acumulaciones de aire o burbujas de gas en la tubera de utilizar un ajuste del punto cero en los siguientes casos:
medida pueden tener gran influencia sobre la precisin de Para mediciones en la zona de flujo inferior (por debajo del
medida. 10 % de QmxDN),
Para la medida de lquidos, se recomienda no instalar el Si son necesarias precisiones altas (0,1 % o mejor),
aparato en los puntos siguientes: Si las condiciones de funcionamiento (presin y
temperatura) difieren ampliamente de las condiciones de
referencia.

Fig. 11: Puntos de montaje problemticos Fig. 13: Tubera de derivacin

"A": Si el aparato se instala en el punto ms alto de la Para el ajuste del punto cero, es necesario un montaje de los
tubera, se pueden formar acumulaciones de aire o dispositivos de cierre delante (A) y detrs (B) del dispositivo
burbujas de gas en la tubera de medida, las cuales Se recomienda el montaje de una tubera de derivacin. As se
afectan la presin de medida. puede realizar el ajuste del punto cero durante un proceso en
"B": Si el sensor de caudal se instala en una tubera curso.
descendente, no est garantizado que la tubera de
medida pueda llenarse completamente durante el proceso Requisitos necesarios para el ajuste del cero en condiciones
de medicin. Esto puede influir muy negativamente sobre de servicio:
la precisin de medida. La tubera de medida est completamente llena.
La tubera de medida no contiene burbujas de gas o aire
4.6.6 Puntos de montaje problemticos para la medida (medida de lquidos).
de gases La tubera de medida no contiene condensados (medida
En la medida de gases hay que tener en cuenta que las de gases).
acumulaciones de lquido o de condensado en la tubera de La presin y temperatura en la tubera de medida
medida pueden tener gran influencia sobre la precisin de corresponden a las condiciones de servicio normales y
medida. son estables.
Para la medida de gases, se recomienda no instalar el aparato
en los puntos siguientes: En el caso de un punto cero elevado (> 0,1 %), compruebe si
la instalacin se ha realizado correctamente y asegrese de
que no hay componentes gaseosos en los fluidos, ni fluidos o
partculas en los gases. Asegrese de que el dispositivo est
completamente lleno.

Fig. 12: Puntos de montaje problemticos

Si el aparato se instala en el punto ms bajo de la tubera, se


pueden formar acumulaciones de lquidos o de condensado
en la tubera de medida, las cuales afectan la presin de
medida.

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 21


4.6.8 Instalacin en funcin de la temperatura del fluido 4.6.9 Instalacin en caso de uso de la opcin TE1
La posicin de montaje del sensor de caudal depende de la "Longitud ampliada de la torre"
temperatura del fluido Tmedium. Existen las variantes de
montaje siguientes: IMPORTANTE (NOTA)
El sensor de caudal solo se debe aislar en combinacin con la
opcin TE1 "Longitud ampliada de la torre", como se muestra
en Fig. 16.

Fig. 14: Posicin de montaje para Tmedium -50 120 C (-


58 248 F)

Fig. 16: Posicin de montaje para Tmedium -50 200 C (-


58 392 F)
1 Aislamiento

4.6.10 Notas sobre la conformidad EHEDG

ADVERTENCIA! Peligro de intoxicacin!


Las tuberas y fluidos pueden contaminarse por
bacterias y sustancias qumicas txicas.
En instalaciones segn EHEDG se deben
observar las indicaciones siguientes:
Fig. 15: Posicin de montaje para Tmedium -50 200 C (-
58 392 F)
El vaciado automtico del caudalmetro, necesario segn
el montaje conforme a EHEDG, solo se garantiza con el
montaje en vertical.
Para instalaciones segn la normativa EHEDG, es
absolutamente necesario que la combinacin de conexin
a proceso y juntas realizada por el cliente o propietario
cumpla la normativa EHEDG. Para ello, tenga en cuenta
las indicaciones de la versin actual del documento
EHEDG Position Paper: "Hygienic Process connections to
use with hygienic components and equipment".

22 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


5 Conexiones elctricas 5.2 Indicaciones para el cableado
Al instalar los cables de conexin en el sensor de caudal hay
5.1 Instrucciones para conectar la alimentacin elctrica que preveer un lazo de goteo (trampa de agua).
En caso de montaje vertical del sensor de caudal, orientar
IMPORTANTE (NOTA) hacia abajo la entrada de cables. Girar la caja del transmisor,
Se deben mantener los valores lmite de la si es necesario.
alimentacin elctrica (vase el captulo
"Datos tcnicos").
Tener en cuenta la cada de tensin, si se
utilizan cables largos con dimetro pequeo.
La tensin conectada a los terminales del
aparato no debe bajar por debajo del valor
mnimo necesario.
Realizar la conexin elctrica siguiendo los
esquemas de conexin.

La placa de caractersticas del transmisor indica la tensin de


conexin y el consumo de corriente.
En la lnea de alimentacin elctrica del transmisor se debe
instalar un cortacircuito automtico con una corriente nominal
mxima de 16 A.
El dimetro del cable de alimentacin y el cortacircuito Fig. 17: Colocacin de los cables de conexin
automtico utilizado deben cumplir la norma VDE 0100 y 1 Lazo de goteo

corresponder al consumo de corriente del caudalmetro


instalado. Las lneas deben ser conformes a IEC 227 o IEC
245.
Se recomienda instalar el cortacircuito automtico cerca del
transmisor y marcarlo como parte del aparato.
La conexin de la alimentacin elctrica se realizar segn las
especificaciones indicadas en la placa de caractersticas, a
travs de los terminales L (fase), N (cero) o 1+, 2- y PE.
El transmisor y el sensor de caudal deben conectarse a tierra.

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 23


5.3 Diseo compacto IMPORTANTE (NOTA)
En los modelos de diseo compacto, los terminales de Para conectar los cables correctamente se deben
conexin se encuentran detrs de la tapa, en la cara posterior utilizar virolas de cable apropiadas.
de la caja del transmisor.
La cara interior de la tapa muestra el esquema de conexin. Conexin del aparato:
La configuracin del aparato se marcar. 1. Desmontar la tapa del compartimento de conexin.
2 Confeccionar los terminales del cable e introducirlos en el
compartimento de conexin (pasndolos por las entradas
de cables).
3. Desmontar la tapa de los terminales y conectar el cable
de alimentacin siguiendo los esquemas de conexin
correspondientes.
4. Volver a montar la tapa de los terminales.
5. Conectar el cable para las entradas y salidas de seal
siguiendo los esquemas de conexin. Conectar los
apantallamientos del cable (si existen) utilizando al efecto
la abrazadera de puesta a tierra correspondiente.
6. Volver a montar la tapa del compartimento de conexin.

AVISO Prdida del modo de proteccin de


la caja!
Prdida del modo de proteccin de la caja por
asiento incorrecto o dao de la junta (junta
trica).
Antes de cerrar la tapa de la caja, controlar la
junta (junta trica) y cambiarla, si es necesario.
Asegrese al cerrar la tapa de la caja de que la
junta est asentada correctamente.

Fig. 18: Terminales de conexin


1 Tapa del compartimento de conexin |
2 Empleo de las conexiones | 3 Entradas de cables |
4 Terminales de conexin para la alimentacin elctrica |
5 Terminales de conexin para las entradas y salidas de seal |
6 Tapa de los terminales

24 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


5.4 Diseo remoto 5.4.3 Conexin del cable de seal
En caso de los modelos de diseo remoto, el transmisor se
montar por separado. Su conexin al sensor de caudal se IMPORTANTE (NOTA)
realizara a travs de un cable de seal. Para conectar los cables correctamente se deben
utilizar virolas de cable apropiadas.
5.4.1 Especificacin del cable

Cable de seal
Denominacin LI2YCY PiMF
5 x 2 x 0,5 mm2
Apantallamiento Par blindado con conductor de tierra y
pantalla de trenza de cobre
Rango de temperatura -30 ... 70 C (-22 ... 158 F)
Resistencia de bucle mximo: 78,4 /km
Inductividad ~ 0,4 mH/km
Longitud mx. del cable 10 m (33 ft)

5.4.2 Colocacin del cable de seal


Durante la colocacin del cable deben observarse los
siguientes puntos:
El cable de seal conduce una seal de tensin de slo
unos milivoltios y, por lo tanto, debe ser tan corto como
sea posible. La longitud mxima permitida del cable de
seal es de 10 m (33 ft). Fig. 19: Confeccin del cable de seal, medidas en mm (inch)
Evite colocar el cable cerca de mquinas elctricas 1 Pantalla trenzada |
2 Conductores de tierra de las pantallas de lmina (retorcidos) |
grandes y elementos de conmutacin que pueden
3 Pantalla de lmina | 4 Abrazadera de puesta a tierra |
producir interferencias, impulsos de conexin e 5 Conductor de tierra | 6 Virolas de cable
inducciones. Si esto no es posible, instalar el cable de
seal en un tubo metlico de proteccin y conectar el 1. Pelar el cable de seal como se muestra en la figura.
tubo al potencial de tierra de la red. 2. Cortar unos 15 mm (0,59 inch) de la pantalla trenzada.
Para aislarlo contra interferencias magnticas, el cable 3. Separar el alma del cable y la pantalla de lmina de los
dispone de una pantalla exterior conectada al potencial de pares de conductores.
tierra de la red. 4 Pelar los conductores y dotarlos de virolas de cable.
Debe evitarse que el cable de seal discurra cerca de 5. Retorcer los conductores de tierra de las pantallas de
cajas de unin o regletas de bornes. lmina y envolver con ellos la pantalla trenzada. Para la
conexin al aparato, sujetar debajo de la abrazadera de
puesta a tierra la pantalla trenzada y los conductores de
tierra retorcidos.
6. Conectar al transmisor y sensor de caudal el cable de
seal siguiendo los esquemas de conexin.
7. Conectar al transmisor el cable para las entradas y salidas
de seal siguiendo los esquemas de conexin. Conectar
los apantallamientos del cable a la abrazadera de puesta a
tierra correspondiente.
8. Conectar al transmisor el cable de alimentacin siguiendo
los esquemas de conexin.
9. Volver a montar todas las tapas de los compartimentos de
conexin del transmisor y sensor de caudal.

AVISO Prdida del modo de proteccin de


la caja!
Prdida del modo de proteccin de la caja por
asiento incorrecto o dao de la junta (junta
trica).
Antes de cerrar las tapas de la cajas, controlar la
junta (junta trica) y cambiarla, si es necesario.
Asegrese al cerrar las tapas de que la junta est
asentada correctamente.

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 25


5.5 Comunicacin digital Integracin en el sistema:
5.5.1 Protocolo HART En combinacin con el software DTM disponible para el
El aparato est registrado en la HART Communication aparato (Device Type Manager), la comunicacin
Foundation. (configuracin, parametrizacin) puede realizarse mediante las
aplicaciones de tramas correspondientes segn FDT 0.98
1.2 (DSV401 R2).
Otras formas de integracin en el sistema/herramientas (p.ej.:
Emerson AMS / Siemens SCS7) pueden suministrarse bajo
demanda.
Los archivos DTM y otros archivos necesarios se pueden
descargar de la pgina www.abb.com/flow.

Fig. 20: Comunicacin mediante el protocolo HART

Protocolo HART
Configuracin Directamente en el aparato
Mediante software DSV401 + HART-DTM
Transmisin Modulacin FSK sobre la salida de corriente de
4 ... 20 mA, segn estndar Bell 202
Velocidad en baudios 1200 baud
Indicacin Lgico 1: 1200 Hz
Lgico 0: 2200 Hz
Amplitud mxima de la 1,2 mAss
seal
Carga en la salida de 250 560
corriente (en la zona Ex: mx. 300 )

Cable
Diseo Cable de dos conductores AWG 24, retorcido
Longitud mxima 1500 m (4921 ft)

Para informacin detallada, vase la descripcin de la interfaz


correspondiente.

26 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


Change from two to one c olumn

5.6 Esquemas de conexin


5.6.1 Conexin de modelos de transductor a equipos perifricos
Modelos FCB330, FCB350, FCH330, FCH350, FCT330, FCT350

Fig. 21
1 Suministro de energa | 2 Salida de corriente 1 | 3 Salida de corriente 2 | 4 Salida de impulsos | 5 Salida de contacto digital |
6 Entrada de contacto digital | 7 Conexin equipotencial (PA)

IMPORTANTE (NOTA)
Si el aparato se utiliza en zonas potencialmente explosivas, se deben respetar las indicaciones de conexin adicionales del
captulo "Datos tcnicos relevantes para la proteccin contra explosiones".

Terminal Funcin
L / N / PE Suministro de energa, 100 230 V AC, 50/60 Hz
1+ / 2- / PE Suministro de energa
24 V AC, 50/60 Hz
24 V DC
31 / 32 Salida de corriente 1, activa
0/4 20 mA , (0 R B 560 , FCT300-A1/F1:1 0 RB 300 )
Salida de corriente 1, pasiva
4 20 mA (0 RB 600 ), tensin de fuente 12 Uq 30 V
33 / 34 Salida de corriente 2, pasiva
4 20 mA (0 RB 600 ), tensin de fuente 12 Uq 30 V
51 / 52 Salida de impulsos, pasiva
fmx = 5 kHz, ancho de impulso = 0,1 2000 ms, 0,001 ... 1000 impulsos/unidad
"cerrada": 0 V UCEL 2 V, 2 mA I CEL 220 mA
"abierta": 16 V UCEH 30 V DC, 0 mA I CEH 0,2 mA
Salida de impulsos activa, U = 16 30 V, carga 150 , fmx = 5 kHz
41 / 42 Salida de contacto digital, pasiva
"cerrada": 0 V UCEL 2 V, 2 mA I CEL 220 mA
"abierta": 16 V UCEH 30 V DC, 0 mA I CEH 0,2 mA
81 / 82 Entrada de contacto digital, pasiva
Entrada "activada": 16 V UKL 30 V
Entrada "desactivada": 0 V UKL 2 V
- Conexin equipotencial "PA"
Si se conecta el transductor FCT300 al sensor de caudal FCB3xx / FCH3xx, el transductor tambin se debe conectar a la conexin
equipotencial "PA".

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 27


5.6.2 Ejemplos de conexin con perifricos
Salidas de corriente (incl. comunicacin HART)

Fig. 22: Salidas de corriente activa / pasiva


"A" activa | "B" pasiva | I interna | E externa

Salida y entrada de contacto digitales

Fig. 23
"A" Salida del control del sistema, alarmas Mx./Mn. tubera de medida vaca o sealizacin de directo/inverso |
"B" Entrada para la puesta a cero externa del totalizador o desconexin externa de la salida | I interna | E externa

Salida de impulsos

Fig. 24: Salida de impulsos activa / pasiva


"A" activa | "B" pasiva (optoacoplador) | I interna | E externa

28 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


5.6.3 Conexin del transductor al sensor de caudal
Transductor FCT330, FCT350 al sensor de caudal FCB330, FCB350, FCH330, FCH350

Fig. 25
1 Conexin equipotencial (PA)

Terminal Color del conductor Funcin Terminal Color del conductor Funcin
85 Blanco Sensor A 91 Gris Excitador
86 Marrn Sensor A 92 Rosa Excitador
87 Verde Sensor B 93 - No se utiliza
88 Amarillo Sensor B 94 - No se utiliza
89 Negro Temperatura 95 Azul Temperatura
90 Violeta Temperatura 96 Rojo Temperatura

IMPORTANTE (NOTA)
La posicin exacta de los terminales de conexin equipotencial puede variar segn el tipo de dispositivo. Los terminales estn
marcados de forma acorde. Si se conecta el transductor FCT330, FCT350 al sensor de caudal FCB330, FCT350, FCH330,
FCH350, tambin debe conectarse a la conexin equipotencial "PA".
Estn permitidas las siguientes combinaciones de sensor de caudal y transductor:
Sensor de caudal FCB330, FCH330 con transductor FCT330
Sensor de caudal FCB350, FCH350 con transductor FCT350

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 29


5.6.4 Conexin del transductor al sensor de caudal en Zona 1 / Div. 1
Transductor FCT330, FCT350 al sensor de caudal FCB330, FCB350, FCH330, FCH350

Fig. 26
1 Conexin equipotencial (PA)

Terminal Color del conductor Funcin Terminal Color del conductor Funcin
85 Blanco Sensor A 91 Gris Excitador
86 Marrn Sensor A 92 Rosa Excitador
87 Verde Sensor B 93 - No se utiliza
88 Amarillo Sensor B 94 - No se utiliza
89 Negro Temperatura 95 Azul Temperatura
90 Violeta Temperatura 96 Rojo Temperatura

IMPORTANTE (NOTA)
Se deben conectar conductores de pares para garantizar la proteccin CEM.
Estn permitidas las siguientes combinaciones de sensor de caudal y transductor:
Sensor de caudal FCB330, FCH330 con transductor FCT330
Sensor de caudal FCB350, FCH350 con transductor FCT350
Change from one to tw o c olumns

30 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


6 Puesta en marcha 6.3 Ajustes bsicos

6.1 Controles antes de la puesta en funcionamiento IMPORTANTE (NOTA)


Antes de la puesta en servicio se debern controlar los Para informacin detallada sobre el uso del
siguientes puntos: indicador LCD, vase el captulo "Configuracin,
La asignacin correcta del transmisor al sensor de caudal. parametracin / Manejo".
El cableado correcto descrito en el captulo "Conexiones Para una descripcin detallada de todos los
elctricas". mens y parmetros, vase el captulo
La puesta a tierra correcta del sensor de caudal. "Configuracin, parametracin / Descripcin de
El nmero de serie del mdulo de almacenamiento de los parmetros".
datos (FRAM externo) debe corresponder con el nmero
de serie del sensor de caudal. Si el cliente lo desea, el aparato se entregar ajustado a los
El mdulo de almacenamiento de datos (FRAM externo) valores especificados. Cuando falten estos datos, el aparato
debe estar enchufado en la ranura prevista (vase el se entregar con los ajustes de fbrica.
captulo "Mantenimiento / Reparacin"). Para ajustar el aparato in situ, basta seleccionar o introducir
Las condiciones ambientales deben corresponder con los unos pocos parmetros.
valores indicados en la especificacin tcnica. Antes de la puesta en servicio del aparato es necesario que se
La alimentacin elctrica debe corresponder con los datos controlen y ajusten los parmetros siguientes:
indicados en la placa de caractersticas.
Valor lmite superior del rango de medida
6.2 Conectar la alimentacin de corriente (Parmetro "QmMax" y submen "Unit").
Conectar la alimentacin de corriente. El aparato est ajustado por defecto al valor lmite mximo
Despus de conectar la alimentacin de corriente, los datos posible del rango de medida, siempre que el cliente no
del sensor memorizados en la FRAM externo se compararn especifique otros valores.
con los valores guardados internamente.
Si los datos no son idnticos, los datos del transmisor se Salidas de corriente
intercambiarn automticamente. Poco despus aparecer el (Submen "Current output 1" y "Current output 2").
mensaje "Ext. Data loaded". El caudalmetro est listo para el Seleccionar el rango de corriente deseado (0 20 mA 4
funcionamiento. 20 mA).
La pantalla LCD indicar el caudal actual.
Salida de impulsos
6.2.1 Medidas de control despus de conectar la (Parmetro "Pulse" y submen "Unit").
alimentacin de corriente Para ajustar el nmero de impulsos por cada unidad
Despus de la puesta en servicio se debern controlar los volumtrica, hay que seleccionar primero, en el submen
siguientes puntos: "Unit", la unidad del totalizador (p. ej., kg. o t). A continuacin
La configuracin de los parmetros debe corresponder hay que introducir, bajo el parmetro "Pulse", el nmero de
con las condiciones ambientales. impulsos deseado.
Debe haberse realizado un ajuste del cero.
Ancho de impulso
Informaciones generales: (Parametro "Pulse width").
En el caso de que el indicador de caudal seale que el Para el procesamiento externo de los impulsos de contaje se
sentido de flujo sea incorrecto, pueden haberse puede ajustar un ancho de impulso de entre 0,1 y 2000 ms.
confundido los conductores del cable de seal entre el
sensor de caudal y el transmisor. Ajuste del cero del sistema
La posicin y los valores de los fusibles se indican en la (Submen "System Zero adj.").
lista de repuestos. Para ello es necesario detener completamente el lquido
contenido en el sensor de caudal. El sensor de caudal debe
estar completamente lleno. Seleccionar el men "System Zero
adj.". Pulsar la tecla ENTER. Pulsar la tecla STEP para llamar
la opcin "System Zero adj. Function automatic?" y pulsar
ENTER para activar el ajuste automtico. Se puede elegir un
mtodo de ajuste lento o rpido. El mtodo lento es
normalmente ms apropiado para obtener un ajuste ms
preciso del cero.

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 31


6.4 Configuracin de la salida de impulsos 6.5 Interruptor de proteccin contra modificaciones no
La configuracin (activa, pasiva) de la salida de impulsos se autorizadas
establece en el transductor mediante un puente enchufable.
Para modificar la configuracin, se debe sacar de la carcasa la
unidad de enchufe del transductor.

Fig. 28: Interruptor de proteccin contra modificaciones no


autorizadas

Adicionalmente a la proteccin por contrasea, hay la


posibilidad de activar la proteccin de hardware contra
escritura.
El bloqueo de programacin puede activarse o desactivarse
girando el interruptor (1) en el sentido o contra el sentido de
Fig. 27: Posicin del puente enchufable las agujas del reloj.
1 Puente enchufable para configurar la salida de impulsos En el caso de que se deban modificar parmetros y el bloqueo
de programacin est activado, aparecer el mensaje de
Posicin Funcin advertencia: Operating protection" y el programa denegar el
"A" Salida de impulsos 51 / 52 pasiva acceso.
"B" Salida de impulsos 51 / 52 activa (no disponible en En tal caso, incluso es posible sellar la tapa del aparato de
modelos con proteccin contra explosiones) diseo compacto mediante un tornillo de retencin con
agujero, para impedir que modificaciones de los parmetros
IMPORTANTE (NOTA) relevantes para la calibracin se queden sin descrubrir.
Tenga en cuenta que, en los dispositivos con
certificado para Zona 1 / Div. 1, el puente
enchufable est en la posicin "B" (activa),
aunque la salida de impulsos est configurada
como pasiva.

32 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


6.6 Instrucciones para el funcionamiento seguro en 6.6.2 Circuitos elctricos de salida
zonas potencialmente explosivas (ATEX) Instalacin con seguridad intrnseca "i" o seguridad
6.6.1 Controles elevada "e"
Los circuitos elctricos de salida estn diseados de manera
PELIGRO Peligro de explosin! que puedan conectarse a circuitos con o sin seguridad
Peligro de explosin al abrir la carcasa. intrnseca.
Antes de abrir la carcasa se deben observar los No est permitido combinanar circuitos elctricos con y sin
puntos siguientes: seguridad intrnseca.
El propietario debe disponer de un certificado A lo largo de la seccin de la lnea del circuito intrnsicamente
que autorice la utilizacin de fuego. seguro deber establecerse una conexin equipotencial.
Asegrese de que no haya peligro de La tensin de clculo de los circuitos elctricos sin seguridad
explosin. intrnseca es UM = 60 V.
Antes de abrir la caja hay que desconectar la
alimentacin elctrica. IMPORTANTE (NOTA)
En el estado de entrega, los racores atornillados
ATENCIN - Peligro de quemadura! para cables estn diseados en color negro. En el
Peligro de quemadura por contacto con fluidos caso de que las salidas de seal se conecten a
calientes. No tocar el sensor de caudal! La circuitos intrnsicamente seguros, se recomienda
temperatura superficial depende de la que para la entrada de cable se utilice la tapa de
temperatura del fluido y puede alcanzar ms de color azul claro, que se encuentra en el
70 C (158 F)! compartimento de conexin.
Asegrese antes de realizar trabajos en el sensor
de caudal de que el aparato se haya enfriado IMPORTANTE (NOTA)
suficientemente. Los datos tcnicos de seguridad de los circuitos
elctricos intrnsecamente seguros pueden verse
La puesta en servicio tendr que realizarse de acuerdo con el en el Certificado CE de homologacin de
ElexV (reglamento sobre instalaciones elctricas en zonas modelos de construccin.
potencialmente explosivas) y la norma EN 60079-14 (montaje
de instalaciones elctricas en zonas potencialmente Asegrese de que la tapa del enchufe de alimentacin de
explosivas) o las disposiciones nacionales pertinentes. corriente est cerrada correctamente. Los circuitos
El montaje, la puesta en funcionamiento y los trabajos de elctricos de salida intrnsecamente seguros permiten
mantenimiento y reparacin en la zona Ex deben ser abrir el compartimento de conexin.
realizados, exclusivamente, por personal debidamente Se recomienda que los racores atornillados para cables
cualificado. que van incluidos en el suministro (no disponible para la
La puesta en funcionamiento descrita en este documento se versin de -40 C (-40 F)), se utilicen para los circuitos
realizar despus del montaje y la conexin elctrica del elctricos de salida, de acuerdo con el tipo de proteccin
caudalmetro instalado. 'e' pertinente. Con seguridad intrnseca: azul. Sin
La alimentacin elctrica est desconectada. seguridad intrnseca: negro
El uso de polvos inflamables est sujeto a la norma El sensor y la caja del transmisor deben conectarse a la
EN 61241-0:2006. conexin equipotencial. A lo largo de los circuitos
Por favor consulte la explicacin "3KXF002126G0009" del elctricos de las salidas de corriente intrnsecamente
anexo. seguras deber establecerse una conexin equipotencial.
Despus de desconectar la alimentacin de corriente y
antes de abrir la caja del transmisor es necesario observar
un tiempo de espera de t > 2 min.
Asegrese de que la puesta en servicio se realice de
acuerdo con la norma EN61241-1:2004 para aplicaciones
en zonas con polvo inflamable.
El propietario/usuario tendr que asegurar, cuando
conecte el conductor protector (PE), que en caso de fallo
no se produzcan diferencias de potencial entre el
conductor protector (PE) y la conexin equipotencial (PA).
Durante el uso en las zonas Ex-polvo, la temperatura
superficial mxima es de 85 C (185 F).
Es posible que la temperatura de proceso del conducto
conectado sobrepase 85 C (185 F).

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 33


6.6.3 Contacto NAMUR 6.6.6 Uso en la zona 2, con la clase de proteccin "a
prueba de vapor" (nR)
La carcasa del transductor de medida (rectangular o redonda,
diseo compacto o remoto) est aprobada para el uso en la
zona 2, con la clase de proteccin "a prueba de vapor" (nR).

ADVERTENCIA Prdida del modo de


proteccin
Despus de los trabajos de instalacin o
mantenimiento o despus de abrir la carcasa, el
usuario debe someter el aparato a un control
segn la norma IEC 60079-15 (vase captulo
"Indicaciones importantes para el control del
aparato").

Fig. 29: Posicin de los puentes enchufables Indicaciones importantes para el control del aparato
"A" Conexin estndar | "B" Conexin NAMUR Obsrvense los siguientes puntos conforme a la norma IEC
1 Puente enchufable BR902 | 2 Puente enchufable BR901
60079-15, captulo 23.2.3.2.1.2 "Requisitos para el control
rutinario de carcasas a prueba de vapor; aparatos sin
Puente Posicin Funcin conexin de prueba":
enchufable En condiciones de temperatura constante, el periodo de
BR902 1 Configuracin estndar preferida para tiempo en el que se reduce a la mitad la presin de la
BR901 1 Ex "e" (configuracin por defecto) carcasa de al menos 0,3 kPa (30 mm.c.d.a.) no puede ser
BR902 2 Configuracin NAMUR preferida para Ex "i" inferior a 180 segundos.
BR901 2
Como alternativa, se pueden emplear tambin los siguientes
Los puentes enchufables permiten conectar un amplificador procedimientos de control con el fin de reducir su tiempo:
NAMUR, es decir, la salida de contacto y salida de impulsos En condiciones de temperatura constante, el periodo de
(terminales 41, 42 y 51, 52) pueden conectarse internamente tiempo en el que se reduce la presin de la carcasa de
de manera que funcionen como contacto NAMUR. 0,3 kPa (30 mm.c.d.a.) a 0,27 kPa (27 mm.c.d.a.) no
puede ser inferior a 27 segundos.
6.6.4 Entradas de cables En condiciones de temperatura constante, el periodo de
Indicaciones especiales para modelos con certificado tiempo en el que se reduce la presin de la carcasa de
para Amrica del Norte. 3,0 kPa (300 mm.c.d.a.) a 2,7 kPa (270 mm.c.d.a.) no
Los modelos con certificado para Amrica del Norte slo puede ser inferior a 27 segundos.
estn equipados con roscas 1/2 NPT (sin racor atornillado
para cables). IMPORTANTE (NOTA)
Si durante el control surge algn problema con la
6.6.5 Aislamiento del sensor de caudal presin ms baja (0,3 kPa (30 mm.c.d.a.)), puede
Si es necesario aislar el sensor de caudal, se debern seguir realizarse el control con la presin 10 veces ms
las indicaciones del captulo "Montaje / Posiciones de montaje alta (3,0 kPa (300 mm.c.d.a.)).
/ Montaje con uso del componente opcional TE1 "Longitud
ampliada del torre".

34 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


Cmo realizar el control IMPORTANTE (NOTA)
1. Espere al menos dos minutos antes de conectar el Para la impermeabilizacin de la carcasa deben
suministro de energa y de abrir la carcasa. utilizarse exclusivamente repuestos originales.
2. Retire un racor de cables no utilizado. Normalmente se Los repuestos pueden adquirirse a travs del
utilizan racores de cables con certificado ATEX o IECEx Servicio de ABB:
(p. ej., M20 x 1,5 o roscas NPT 1/2"). Consulte al Servicio de atencin al cliente
3. Conecte el equipo de ensayo para la prueba de presin en (direccin en la pgina 2) para el establecimiento
lugar del racor de cables extrado. Asegrese de que el colaborador ms cercano.
equipo de ensayo est instalado y sellado correctamente.
4. Realice el control con el equipo de ensayo (vase captulo IMPORTANTE (NOTA)
"Indicaciones importantes para el control del aparato"). Asegrese al elegir el lugar de montaje de que el
5. Retire el equipo de ensayo y vuelva a montar transductor de medida no est expuesto
correctamente el racor de cables. directamente a los rayos del sol.
Si no es posible evitar la radiacin directa del sol,
Antes de conectar el suministro de energa, se deber realizar hay que instalar un dispositivo de proteccin
una inspeccin visual de la carcasa, las selladuras, las roscas contra rayos solares.
y las boquillas de paso. Asegrese de que no se hayan Deben mantenerse los valores lmite de la
producido daos. temperatura ambiente.

Change from two to one c olumn

6.6.7 Cambio de tipo de proteccin


Para la instalacin en DIV. 1 / Zona 1 se pueden operar las salidas de seal INPUT / OUTPUT de los modelos FCB330/350,
FCH330/350 y FCT330/350 con modos de proteccin diferentes:
Salida de seales INPUT / OUTPUT en modo autoprotegido ia(ib) / IS
Salida de seales INPUT / OUTPUT en modo no autoprotegido

Instalacin original Instalacin nueva Pasos de control necesarios


DIV. 1 / Zona 1: DIV. 1 / Zona 1: 500 V AC/1 mn. o 500 x 1,414 = 710 V DC/1 mn.
Salida de seales INPUT / Salida de seales INPUT / Prueba entre los terminales 31 / 32, 33 / 34, 41 / 42, 51 / 52, 81 / 82 y/o 97 / 98 y los
OUTPUT en modo no OUTPUT en modo terminales 31, 32, 33, 34, 41, 42, 51, 52, 81, 82, 97, 98 y entre la carcasa.
autoprotegido autoprotegido ia(ib) / IS Inspeccin visual, en especial de las tarjetas electrnicas.
Inspeccin visual: no deben presentarse daos o daos por explosin.

DIV. 1 / Zona 1: DIV. 1 / Zona 1: Inspeccin visual: las roscas no deben presentar daos (tapa, racores de cables
Salida de seales INPUT / Salida de seales INPUT / NPT 1/2").
OUTPUT en modo OUTPUT en modo no
autoprotegido ia(ib) / IS autoprotegido

IMPORTANTE (NOTA)
Para ms detalles sobre la proteccin contra explosin, tipos de proteccin y modelos de los aparatos, consulte el
diagrama de instalacin FCB 3KXF002126G0009 (vase captulo "Anexo").
Change from one to tw o c olumns

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 35


6.7 Instrucciones para el funcionamiento seguro en 6.7.2 Entradas de cables
zonas potencialmente explosivas (cFMus) Indicaciones especiales para modelos con certificado
6.7.1 Controles para Amrica del Norte.
Los modelos con certificado para Amrica del Norte slo
PELIGRO Peligro de explosin! estn equipados con roscas NPT (sin racor atornillado para
Peligro de explosin al abrir la carcasa. cables).
Antes de abrir la carcasa se deben observar los
puntos siguientes: 6.7.3 Conexin elctrica
El propietario debe disponer de un certificado
que autorice la utilizacin de fuego. IMPORTANTE (NOTA)
Asegrese de que no haya peligro de La caja del transmisor y del sensor de caudal
explosin. debe conectarse al conductor de conexin
Deconecte la alimentacin elctrica antes de equipotencial PA. El propietario deber asegurar
abrir la carcasa y mantenga un tiempo de que cuando se conecte el conductor protector
espera de t > 2 minutos. PE, no se produzcan diferencias de potencial
entre el conductor protector PE y la conexin
ATENCIN - Peligro de quemadura! equipotencial PA.
Peligro de quemadura por contacto con fluidos
calientes. No tocar el sensor de caudal! La Los clculos Ex se basan en las temperaturas producidas en
temperatura superficial depende de la la entrada de cables [70 C (158 F)]. Por ello es necesario
temperatura del fluido y puede alcanzar ms de que para la alimentacin elctrica y las salidas y entradas de
70 C (158 F)! seal se utilicen cables que cumplan con una especificacin
Asegrese antes de realizar trabajos en el sensor mnima de 70 C (158 F).
de caudal de que el aparato se haya enfriado
suficientemente. Puesta a tierra

Adems, se deben seguir las instrucciones siguientes:


El montaje, la puesta en funcionamiento y los trabajos de
mantenimiento y reparacin en la zona Ex deben ser
realizados, exclusivamente, por personal debidamente
cualificado.
Cuando la carcasa est abierta, la proteccin CEM y la
proteccin contra contacto accidental estn desactivadas.
La conexin a tierra del sensor y del transmisor debe
cumplir los estndares internacionales vigentes.
La conexin entre el sensor de caudal y el transmisor slo
debe realizarse mediante el cable de sealizacin
suministrado por ABB Automation Products.
En la versin con diseo remoto, la longitud del cable de
seal entre el sensor y el transmisor debe ser de
5 m (16,4 ft) como mnimo.
Se debern mantener estrictamente las clases de Fig. 30
temperatura aprobadas, indicadas en el captulo "Datos
tcnicos relevantes para proteccin Ex segn cFMus". Segn el estndar NEC, la conexin a tierra entre el
Por favor consulte la explicacin "3KXF002126G0009" del transmisor y el sensor de caudal se puede realizar de la
anexo. siguiente forma:
1. Pelar el cable de seal 100 ... 120 mm (3.94 ... 4,72 inch).
2. Deshilar 10 ... 15 mm (0,39 ... 0,59 inch) de la malla de
blindaje del cable de seal. Trenzar los hilos destrenzados
de la malla de blindaje hasta obtener un haz completo.
3. Introducir el haz en el tubo protector flexible suministrado
(verde/amarillo), hasta que en su extremo sobren 10 mm
(0,39 inch) (acortar el tubo protector flexible, si es
necesario).
4. Montar a presin el terminal de cable anular
suministrado (2).
5. Conectar el cable a la toma de tierra (3).

36 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


6.7.4 Process sealing Para impedir que los fluidos de proceso penetren en el
Segn "North American Requirements for Process Sealing sistema elctrico, los instrumentos van dotados de un juego
between Electrical Systems and Flammable or Combustible de juntas de aislamiento que cumplen los requisitos de la
Process Fluids". norma ANSI / ISA 12.27.01. Los caudalmetros msicos de
IMPORTANTE (NOTA) efecto Coriolis estn diseados como "Single Seal Devices".
El aparato es apropiado para uso en Canad. Segn los requisitos de la norma ANSI / ISA 12.27.01, es
Si se utiliza en los entornos Class II, Groups E, F necesario reducir los valores lmite de funcionamiento para la
and G, la temperatura superficial no debe temperatura, la presin y las partes presurizadas y ajustarlos a
sobrepasar el mximo permitido [165 C los valores lmite siguientes:
(329 F)].
Todos los conductos para cables (conduits) Valores lmite
deben sellarse dentro de una distancia de 18 inch Material de las bridas o tuberas Todos los materiales del modelo
(457.20 mm) desde el aparato. suministrado
Dimetros nominales DN 20 ... 150 (1/2 ... 6)
Los caudalmetros de ABB han sido diseados para el Temperatura de servicio -50 C ... 200 C (-58 F ... 392 F)
mercado industrial internacional y son apropiados, entre otras Presin de proceso PN100 / Class 600
aplicaciones, para la medida de fluidos y lquidos inflamables y
combustibles y para el montaje en tuberas de proceso.
Entre otras cosas, los aparatos que van equipados con
conductos de cables (conduits), estn conectados a la
instalacin elctrica, lo que hace posible que los fluidos de
proceso puedan entrar en el sistema elctrico.
Change from two to one c olumn

6.7.5 Cambio del tipo de proteccin


Los modelos FCB330/350, FCH330/350 y FCT330/350 pueden utilizarse en distintos tipos de proteccin contra explosiones:
Como dispositivo con seguridad intrnseca (IS), si se conecta a un circuito con seguridad intrnseca en Div. 1.
Como dispositivo con blindaje antideflagrante (XP), si se conecta a un circuito elctrico sin seguridad intrnseca en Div 1.
Como dispositivo que no produce chispas (NI), si se conecta a un circuito elctrico sin seguridad intrnseca en Div. 2.
En el caso de que un dispositivo instalado deba utilizarse con otro tipo de proteccin contra explosiones, se tendrn que llevar
a cabo las siguientes medidas o comprobaciones de aislamiento, segn la normativa vigente.

1. Tipo de proteccin 2. Tipo de proteccin Medida /comprobacin necesaria


contra explosiones contra explosiones
Housing: XP, Umax = 60 V Housing: XP 500 V AC/1min o 500 x 1,414 = 710 V DC/1min
Outputs non IS Outputs: IS Prueba entre los terminales 31 / 32, 33 / 34, 41 / 42, 51 / 52, 81 / 82 y/o 97 / 98 y
entre los terminales 31, 32, 33, 34, 41, 42, 51, 52, 81, 82, 97, 98 y la carcasa.
Durante esta prueba no se deben producir descargas de tensin en el interior o
exterior del aparato.
Inspeccin visual, en especial de las placas electrnicas.
Inspeccin visual: no debe haber daos o explosiones visibles.
Housings: Div 2 500 V AC/1min o 500 x 1,414 = 710 V DC/1min
Outputs: NI Prueba entre los terminales 31 / 32, 33 / 34, 41 / 42, 51 / 52, 81 / 82 y/o 97 / 98 y
entre los terminales 31, 32, 33, 34, 41, 42, 51, 52, 81, 82, 97, 98 y la carcasa.
Durante esta prueba no se deben producir descargas de tensin en el interior o
exterior del aparato.
Inspeccin visual, en especial de las placas electrnicas.
Inspeccin visual: no debe haber daos o explosiones visibles.
Outputs: IS Housing: XP Inspeccin visual: las roscas no deben estar daadas (tapa, racores de cable NPT 1/2").
Housing: XP Outputs: non IS
Housing: XP No se requieren medidas especiales
Outputs: NI
Housing: XP, Umax = 60 V Housing: XP 500 V AC/1min o 500 x 1,414 = 710 V DC/1min
Outputs: NI Outputs: IS Prueba entre los terminales 31 / 32, 33 / 34, 41 / 42, 51 / 52, 81 / 82 y/o 97 / 98 y
entre los terminales 31, 32, 33, 34, 41, 42, 51, 52, 81, 82, 97, 98 y la carcasa.
Durante esta prueba no se deben producir descargas de tensin en el interior o
exterior del aparato.
Inspeccin visual, en especial de las placas electrnicas.
Inspeccin visual: no debe haber daos o explosiones visibles.
Housing: XP Inspeccin visual: las roscas no deben estar daadas (tapa, racores de cable NPT 1/2").
Outputs: non IS
Change from one to tw o c olumns

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 37


7 Configuracin, parametracin Control mediante puntero magntico
El puntero magntico permite la programacin cuando la tapa
7.1 Manejo de la caja est cerrada.
7.1.1 Navegacin por mens Para activar esta funcin hay que apuntar con el puntero
magntico a los puntos correspondientes de la pantalla LCD.
Los puntos estn marcados con el smbolo .

Uso de la tecla ENTER en caso de control mediante


puntero magntico
El puntero magntico no puede utilizarse para activar dos
botones al mismo tiempo. En caso de control mediante
puntero magntico, la funcin ENTER se ejecutar activando
durante ms de tres segundos el punto .
El indicador LCD comenzar a parpadear, para confirmar que
la funcin ENTER se haya ejecutado correctamente.

7.2 Niveles del men


3 Lnea 1 El nivel de configuracin se halla por debajo del indicador de
4 Lnea 2 procesos.
Fig. 31: Indicador LCD
1 Puntos para la programacin mediante el puntero magntico |
2 Botones de control para navegar por el men | Indicador de
3 1. lnea del indicador LCD | 3 2. lnea del indicador LCD
procesos
Durante la programacin, el transmisor permanecer en lnea,
es decir, las salidas de corriente y de impulsos seguirn Nivel de
indicando el estado actual de funcionamiento. configuracin
Language
Funciones de los botones de control Mode of operation
Las teclas de control o sirven para desplazarse por el Concentration
men o para seleccionar valores de una lista. Unit
Segn la posicin en el men, los botones de control pueden Flowmeter primary
tener funciones adicionales. QmMax
Damping
Smbolo Significado Low cutoff setting
Cambio entre el indicador de procesos y el men Field optimization
Salida del submen System Zero adj.
Desplazamiento hacia adelante en el men o en una Alarm
lista de parmetros Display
Aumento de los valores numricos (incremento) Totalizer
Desplazamiento hacia atrs en el men o en una lista Pulse Output
de parmetros Current output 1 / 2
Reduccin de los valores numricos (decremento) Switch contacts
Seleccin de la posicin siguiente para introducir Label
valores numricos y alfanumricos Interface
Funcin ENTER Function test
La funcin ENTER se puede ejecutar pulsando Status
simultneamente las teclas . Versin del software
Selecciona un parmetro que se debe modificar
Confirmacin de un valor / parmetro introducido Indicador de El indicador de procesos muestra los valores
Salto al submen procesos actuales del proceso.
Nivel de El nivel de configuracin contiene todos los
IMPORTANTE (NOTA) configuracin parmetros necesarios para la puesta en
Los datos introducidos se someten a un control marcha y la configuracin del equipo. Desde
de plausabilidad. En el caso de que los datos no aqu se puede modificar la configuracin del
se acepten y se rechacen aparecra un mensaje aparato.
correspondiente en la pantalla LCD.

38 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


7.2.1 Indicador de procesos 7.2.2 Cambio al nivel de configuracin (parametrizacin)
Una vez conectado el aparato, en la pantalla LCD aparecer el En el nivel de configuracin se pueden ver y modificar los
indicador de procesos. All se muestra informacin sobre el parmetros del equipo.
equipo y los valores de proceso actuales.
IMPORTANTE (NOTA)
V 98.14 % 1 El mensaje "Error bloqueo de programacin" en
V 12.000 m3 2 la pantalla LCD indica la activacin de la
Fig. 32: Indicador de procesos proteccin de hardware contra escritura a travs
1 1. lnea del indicador de procesos | del interruptor de proteccin contra
2 2. lnea del indicador de procesos | modificaciones no autorizadas.

Para modificar la representacin en pantalla de los valores de V 98.14 %


proceso actuales indicados en las lneas 1 y 2, hay que V 12.000 m3
cambiar al nivel de configuracin.
1. Pulsar para pasar al nivel de configuracin. A
Smbolo Descripcin continuacin, el indicador LCD muestra una opcin
Indicacin del totalizador de caudal directo cualquiera del men.
Indicacin del totalizador de caudal inverso 2. Pulsar o para llamar el submen "Nivel. prog."
y, a continuacin, pulsar (funcin ENTER)
Mensajes de error del indicador LCD para modificar el ajuste correspondiente.
En caso de fallo aparecer un mensaje de error en la pantalla
del indicador de procesos. El texto mostrado da una *Prog. level
indicacin sobre el rea en la que se ha producido el error. Blocked

Indicador de procesos 3. Pulsar o para seleccionar el nivel de acceso


Mensaje de error "Specialist".
4. Pulsar (funcin ENTER), para confirmar el
ajuste efectuado.
IMPORTANTE (NOTA)
Para una descripcin detallada de los errores y Si se ha definido una contrasea (Prog. Prot. Code), introducir
obtener informacin sobre cmo corregir los la contrasea correspondiente.
errores, vase el captulo 8 "Mensajes de error".
Prog. Prot. Code
****

5. Pulsar para ajustar el valor deseado (la decimal se


incrementa con cada pulsacin de la tecla).
6. Pulsar para seleccionar la decimal siguiente.
7. Pulsar (funcin ENTER), para confirmar el
ajuste efectuado.

Una vez introducida la contrasea se autorizar el acceso al


nivel de programacin corrrespondiente. Si se ha
seleccionado el nivel de acceso "Service" hay que introducir la
contrasea de servicio.
A continuacin, la pantalla LCD muestra la opcin de men
primera del nivel de configuracin.

8. Pulsar o para elegir un men.


9. Pulsar (funcin ENTER), para confirmar el
men elegido.

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 39


Niveles de acceso Entrada numrica
En la entrada numrica se ajusta un valor al introducir los
IMPORTANTE (NOTA) decimales.
Hay cuatro niveles de acceso. Para los niveles de
acceso "Standard" y "Specialist" se puede definir QmMx
una contrasea. 180.00 kg/h
No hay una contrasea por defecto.
1. Seleccionar en el men el parmetro a ajustar.
Nivel de acceso Descripcin 2. Pulsar (funcin ENTER) para seleccionar el
Blocked En el nivel "Blocked" todas las opciones estn parmetro a editar. El valor anterior se borra y en la
bloqueadas. posicin primera aparece un cursor ( _ ).
Los mens / parmetros slo pueden leerse.
No es posible modificarlos. QmMx
Standard Indicacin y modificacin de todos los mens / 254.50 kg/h
parmetros necesarios para el funcionamiento
del aparato. 3. Pulsar para ajustar el valor deseado (la decimal se
Specialist Indicacin y modificacin de todos los mens / incrementa con cada pulsacin de la tecla).
parmetros accesibles para el cliente. 4. Pulsar para seleccionar la decimal siguiente.
Service Visualizacin del men de servicio despus de 5. Si es necesario, seleccionar y ajustar otras decimales
introducir la contrasea de servicio (slo para el siguiendo los pasos 3 a 4.
personal de servicio de ABB). 6. Pulsar (funcin ENTER), para confirmar el
ajuste efectuado.
7.2.3 Seleccin y modificacin de parmetros El ajuste del parmetro ha terminado.
Entrada de datos desde una tabla
En la entrada de datos desde una tabla, los valores se
seleccionan de una lista de valores paramtricos.

Submen
Unidad

1. Seleccionar en el men el parmetro a ajustar.


2. Pulsar (funcin ENTER) para seleccionar el
parmetro a editar.
3. Pulsar o para seleccionar el valor deseado.
4. Pulsar (funcin ENTER), para confirmar la
seleccin.

40 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


Change from two to one c olumn

7.3 Resumen de los parmetros en el nivel de configuracin

IMPORTANTE (NOTA)
En este resumen de parmetros se indican todos los mens y parmetros disponibles del dispositivo. Segn el
equipamiento y la configuracin del dispositivo, puede que en el dispositivo no aparezcan todos los mens y
parmetros.
En este resumen de parmetros, y por motivos de espacio, la funcin ENTER solo puede representarse
mediante el smbolo .

*Prog. level Blocked


Standard
Specialist
Service

Language

Mode of operation Flow indication


Directional display
Signal Level
DensiMass Code
DensiMass
Min Density

Concentration Medium
Variable Matrix Configuration Number matrices
Number temp.
Label Number conc.
Unit name Enter conc. in %
Min. concentr. Reset matrix
Max. concentr.
Matrix 1 / 2 Temperature
Unit Unit Qm Concentration in unit
Unit Qv Enter matrix finish Concentration in percent
Density unit Density
Totalizer Unit Volume Matrix calculation
Totalizer Unit Mass
Prog. Unit Qm Unit name
Units factor
Prog. Unit Qv Unit name
Units factor
Temp. unit
Unit concentration

Flowmeter primary Meter tube


QmMax meter tube
Order no.

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 41


QmMax
Damping
Low cutoff setting

Field optimization D correction


Qm correction
C correction tab. 1
C correction tab. 2

System Zero adj. System Zero adj. System Zero adj. Slow?
Function automatic? System Zero adj. Fast?
System Zero adj. System Zero adj.
manual?

Alarm Min Alarm Qm


Max Alarm Qm
Min Alarm density
Max Alarm density
Min Alarm Temp.
Max Alarm Temp.
Min Alarm Concentr.
Max Alarm Concentr.

Display 1st Line


2nd Line
1st Line Multiplex
2nd Line Multiplex

Totalizer Totalizer mass Counter > F


Overflow > F
Totalizer volume Totalizer < R
Overflow < R
Totalizer net. mass

Totalizer Reset

Pulse Output Output of


QvMax pulse
Qm% max pulse
Pulse
Pulse width

42 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


Current output 1 Output of
Qv l = 100 %
Density l = 0 %
Density l = 100 %
Temp l = 0 %
Temp l = 100 %
Qm% l = 100 %
Concentr. l = 0 %
Concentr. l = 100 %
Current output
Iout for Alarm
Low Alarm
High Alarm

Current output 2 Output of


Qv l = 100 %
Density l = 0 %
Density l = 100 %
Temp l = 0 %
Temp l = 100 %
Qm% l = 100 %
Concentr. l = 0 %
Concentr. l = 100 %
Iout for Alarm
Low Alarm
High Alarm

Switch contacts Contact input


Contact output

Label TAG number


Descriptor
Date
Unit number
TAG number

Interface Communication
Unit address

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 43


Function test Function test pulse Pulse Output
Output
Function test Iout 1 Iout 1

Function test Iout 2 Iout 2

Function test Contact Contact input


input
Function test Contact Contact output
output
Function test HART
Transmitter
Function test HART
Command
Function test Memory
Simulation Simulation
Qm
Qm
Density
Density
Temperature
Temp. housing
Temperature
Temp. housing

Status Error log Number: 3 7 (Set) Temp. Measurement


9a (current) Density
Warning Register measurement
Number: 1
Power outage
Status Reset
4 (Set) Ext. Cut-off

CoriolisMaster 03.2012
FCB FW

44 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


7.4 Descripcin de los parmetros
7.4.1 Men: *Prog. level

/ *Prog. level
Mscaras Rango de valores Descripcin
*Prog. level Blocked Seleccin del nivel de acceso.
Standard Si se ha definido una contrasea (cdigo de proteccin del programa), introducir a continuacin
Specialist la contrasea correspondiente.
Service Despus de introducir la contrasea, seleccionar a continuacin el nivel de acceso deseado. Si la
contrasea es "0000" (valor por defecto), el nivel de acceso puede seleccionarse sin introducir la
contrasea.
"Blocked": En el nivel "Bloqueado" todas las opciones estn bloqueadas. Los mens /
parmetros slo pueden leerse. No es posible modificarlos.
"Standard": Indicacin y modificacin de todos los mens / parmetros necesarios para el
funcionamiento del aparato.
"Specialist":Indicacin y modificacin de todos los mens / parmetros accesibles para el
cliente.
"Service":Indicacin adicional del men de servicio despus de introducir la contrasea de
servicio
(slo para el personal de servicio de ABB).
Prog. Prot. Code Seleccin del submen "Prog. Prot. Code".

/ *Prog. level / Prog. Prot. Code


Mscaras Rango de valores Descripcin
Old Prog. Prot. (PS) 0 9999 Cmo cambiar la contrasea
code? Para poder modificar la contrasea es necesario introducir primero la contrasea actual.
Confirmar la entrada pulsando .
New Prog. Prot. (PS) 0 9999 Introducir una contrasea nueva. Confirmar la entrada pulsando .
code?

7.4.2 Men: Language

/ Language
Mscaras Rango de valores Descripcin
Language German Seleccin del idioma del men.
English

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 45


7.4.3 Men: Mode of operation

/ Mode of operation
Interfaz Valores permitidos Descripcin
Flow indication Forward / Return Seleccin del sentido de flujo.
Forward "Forward / Return": Indicacin de la medicin del caudal en sentido de avance y de retorno
"Forward": Indicacin de la medicin del caudal solo en sentido de avance. Cuando el sensor
de caudal mide el caudal de retorno, en el indicador LCD parpadea el smbolo R y el caudal
indicado es de 0 %. Adems, aparecer el mensaje de advertencia "Q de retorno".
IMPORTANTE (NOTA)
En el modo de funcionamiento "Forward / Return", la salida de impulsos transmite
impulsos para ambas direcciones de flujo.
Directional display Normal, Reverse Inversin del sentido de flujo indicado. En este punto debe tenerse en cuenta que la precisin de
la medicin de caudal depende de si el dispositivo se ha calibrado nicamente en sentido de
avance o en ambos sentidos.
"Normal": Indicacin del sentido de flujo de avance
"Reverse": Indicacin del sentido de flujo de retorno.
Signal Level automatic, High, Low Seleccin del comportamiento del nivel de seal.
"automatic": Segn la densidad.
"High": Densidad < 0,4 kg/i -> cambio del nivel de seal a "High".
"Low": Densidad > 0,5 kg/l -> cambio del nivel de seal a "Low".
IMPORTANTE (NOTA)
Nivel de seal "Low" = o,5 * nivel de seal "High".

DensiMass Code - Si el dispositivo integra la opcin DensiMass, aqu aparecer el cdigo especfico del dispositivo.
Si posteriormente se desea utilizar esta opcin, debe ponerse en contacto con el servicio
posventa o el representante de ABB.
DensiMass On, Off, Code invalid Indicador de estado de la funcin DensiMass. Si aparece "Code invalid", se ha introducido un
cdigo de desbloqueo incorrecto.
Min Density 0 3,5 kg/l El parmetro Min Density establece un lmite de densidad inferior para casos en los que las
tuberas de medicin estn vacas o se produzca una gran formacin de burbujas. Dado que el
modelo CoriolisMaster tambin puede medir gases, este valor est ajustado de serie en
0=desconectado.
Si no se alcanza este lmite de densidad, se emitir la alarma "9b" y se pausarn la medicin de
caudal y de densidad.
La respuesta detallada del contador y de la salida se encuentra en la tabla del captulo "Mensajes
de error / Resumen". Este error es ms preciso que la alarma de densidad del submen "Alarma".
La histresis de este error es de 0,001kg/l.

46 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


7.4.4 Men: Concentration

/ Concentration
Mscaras Rango de valores Descripcin
Medium Variable Matrix Seleccin de la matriz para el clculo de la concentracin
Sodium hydro Para ms informacin al respecto, vase el captulo "Software de medida de concentracin
Alcohol in water DensiMass".
Wheat starch
Corn starch
Sugar in H2O (BRIX)
Variable Matrix Seleccin del submen "Variable Matrix".

/ Concentration / Variable Matrix


Mscaras Rango de valores Descripcin
Configuration Seleccin del submen "Configuration".
Label Aqu se puede definir un nombre para la matriz.
Unit name Alfanumrico, con un Introduccin del nombre de la unidad para la matriz variable.
mx. de 20 caracteres
Min. concentr. 0 100 % Introduccin de la concentracin mnima permitida para la matriz variable.
Max. concentr. 0 100 % Introduccin de la concentracin mxima permitida para la matriz variable.
Matrix 1 / 2 Seleccin del submen "Matrix 1 / 2".
Enter matrix finish Termina la introduccin de matrices. Los valores introducidos se almacenan o se borran
automticamente.

/ Concentration / Variable Matrix / Configuration


Mscaras Rango de valores Descripcin
Number matrices 1, 2 Introduccin del nmero de matrices. Se pueden crear 2 matrices diferentes, como mximo.
Number temp. 2 20 Introduccin del nmero de valores de temperatura de una matriz.
Number conc. 2 20 Introduccin del nmero de valores de concentracin de una matriz.
Enter conc. in % S, no Seleccin de la unidad para la concentracin
En el caso de que la unidad de la concentracin sea distinta a %, se puede seleccionar
adicionalmente la unidad %.
Esto es absolutamente necesario para poder calcular los caudales msicos netos!
Reset matrix Resetea la matriz introducida y restablece los valores por defecto.

/ Concentration / Variable Matrix / Matrix 1 / 2

IMPORTANTE (NOTA)
Para informacin detallada sobre cmo introducir las matrices, vase el captulo "Software de medida de
concentracin DensiMass".

Mscaras Rango de valores Descripcin


Temperature Introduccin de los valores de temperatura para la matriz seleccionada (1 2).
Concentration in unit Introduccin de los valores de concentracin para la matriz seleccionada (1 2).
Concentration in Introduccin de los valores de concentracin [en %] para la matriz seleccionada (1 2).
percent
Density Introduccin de los valores de densidad para la matriz seleccionada (1 2).
Los valores entrados se marcan con "E"; los valores calculados por interpolacin o extrapolacin
se marcan con "B".
Matrix calculation Clculo de la matriz a base de las entradas efectuadas. Los valores que falten se calcularn por
interpolacin o extrapolacin.

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 47


7.4.5 Men: Unit
/ Unit
Interfaz Valores permitidos Descripcin
Unit Qm g/s, g/min, g/h, kg/s, Seleccin de la unidad del caudal msico.
kg/min, kg/h, kg/d, t/min, La unidad elegida es vlida para los parmetros "QmMx" y "QmMx tubera de medicin", y para
t/h, t/d, lb/s, lb/min, lb/h, la indicacin del caudal msico actual.
lb/d, abc/s, abc/min,
abc/h, abc/d
Unit Qv l/s, l/min, l/h, m3/s, Seleccin de la unidad del caudal volumtrico.
m3/min, m3/h, m3/d, La unidad elegida indica el caudal volumtrico y aparece, p. ej, durante la indicacin del caudal
ft3/s, ft3/min, ft3/h, ft3/d, volumtrico o al introducir los lmites mn. y mx. de la salida de corriente, siempre que el valor
ugl/s, ugl/min, ugl/h, del caudal volumtrico deba indicarse a la salida de corriente.
mgl/d, igps, igpm, igph,
igpd, bbl/s, bbl/min,
bbl/h, bbl/d, abc/s,
abc/min, abc/h, abc/d
Density unit g/ml, g/l, g/cm3, kg/l, Seleccin de la unidad de la densidad.
kg/m3, lb/ft3, lb/ugl
Totalizer Unit Volume abc, l, m3, ft3, ugl, igl, Seleccin de la unidad del contador volumtrico.
bbl
Totalizer Unit Mass g, kg, t, lb, abc Seleccin de la unidad del contador msico.
Prog. Unit Qm Seleccin del submen "Prog. Unit Qm" (unidad de masa programada).
Prog. Unit Qv Seleccin del submen "Prog. Unit Qv" (unidad de volumen programada).
Temp. unit C, K, F Seleccin de la unidad de la temperatura.
Unit concentration %, BRIX, Baum, Seleccin de la unidad de la concentracin. Consulte tambin el men "Concentration".

/ Unit / Prog. Unit Qm


Este men permite seleccionar una unidad de masa definida (programada) por el usuario. Esta unidad se puede seleccionar en
los mens y parmetros correspondientes.

Interfaz Valores permitidos Descripcin


Unit name ASCII, 3 caracteres Introduccin del nombre de la unidad de masa definida por el usuario o la unidad del volumen
como mximo normal (p. ej. "Nm3").
Units factor 0,00001 5000000 kg Introduccin del factor kg/unidad para la unidad de masa definida por el usuario.
Este factor tambin puede utilizarse en la Prog. Unit Qm para indicar el volumen normal durante
la medicin de gases.
Introduzca la densidad de referencia como factor en este submen. Introduzca la densidad de
referencia con la unidad [kg/x], sustituyendo "x" por la unidad de volumen normal deseada.
Ejemplo:
Gas con una densidad de referencia de 1,28kg/m3
Units factor = 1,28; Unit name = Nm3
Para poder indicar el volumen normal, seleccione esta nueva unidad en el submen "Unit" y
seleccione "Qm" o "Masa" en el men de salida deseado.

/ Unit / Prog. Unit Qv


Este men permite seleccionar una unidad de volumen definida (programada) por el usuario. Esta unidad se puede seleccionar
en los mens y parmetros correspondientes.

Interfaz Valores permitidos Descripcin


Unit name ASCII, 3 caracteres Introduccin del nombre de la unidad de volumen definida por el usuario.
como mximo
Units factor 0,00001 5000000 l Introduccin del factor l/unidad para la unidad de volumen definida por el usuario.

48 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


7.4.6 Men: Flowmeter primary

/ Flowmeter primary
Mscaras Rango de valores Descripcin
Meter tube slo visualizacin Indicacin del dimetro nominal del aparato.
QmMax meter tube slo visualizacin Indicacin del valor QmMx (caudal msico mximo) para el dimetro nominal del aparato
Order no. slo visualizacin Indicacin del nmero de pedido. El nmero de pedido indicado corresponde a los datos
indicados en la placa de caractersticas y la memoria de datos externa.

7.4.7 Men: QmMax

/ QmMax
Mscaras Rango de valores Descripcin
QmMax 0.01 1.0 x QmMax Introduccin del rango de medida.
meter tube Para determinar los lmites del rango de medida se pueden entrar valores de entre 0,01 y 1,0
QmMxTubo de medida. El rango de medida ajustado es vlido para ambas direcciones de flujo.
QmMx es el valor al cual se refieren el valor de corriente Qm, el caudal bajo y las alarmas Qm.
(QmMx = 20 mA para la salida corriente Qm).
IMPORTANTE (NOTA)
Al introducir un dimetro nominal nuevo, el parmemtro QmMax se pondr
automticamente al valor 1,0 x QmMax meter tube.

7.4.8 Men: Damping

/ Damping
Mscaras Rango de valores Descripcin
Damping (5 tau) 1 100 s Introduccin del valor de amortiguacin
El valor de amortiguacin indica el tiempo dentro el cual el transmisor reacciona a un salto de
escaln unitario (un 99% del valor final).

7.4.9 Men: Low cutoff setting

/ Low cutoff setting


Mscaras Rango de valores Descripcin
Low cutoff setting 0 10 % Introduccin del valor para el caudal bajo, en % de QmMax.
El caudal bajo mximo es del 10 %. La histresis de conmutacin es del 0,1 %. Si se introduce
un caudal bajo de un 0 %, se desactivar tambin la histresis de conmutacin.

7.4.10 Men: Field optimization

/ Field optimization
Mscaras Rango de valores Descripcin
D correction -50 50 g/l Introduccin del factor de correccin para la densidad.
Para obtener en la medida de densidad una precisin que equivalga aproximadamente a la
reproducibilidad de 0.0001 g/ml, ste factor puede ser utilizado para realizar una optimizacin en
el campo. Los lmites de esta correccin se situan entre 0,50 g/ml (0,05 g/ml).
Qm correction -5 5 % Introduccin del factor de correccin para la medida de caudal.
Para obtener en la medida de caudal una precisin que equivalga aproximadamente o sea incluso
superior a una reproducibilidad de un mnimo del 0,1 % del valor medido, ste factor puede ser
utilizado para realizar una optimizacin en el campo. Este valor tiene el efecto de corregir el valor
medido del caudal msico actual. Se entra en forma de porcentajes del valor actual medido.
Los valores lmite correspondientes se situan entre un 5 % del valor medido.
C correction tab. 1 -1000 1000 % Introduccin del factor de correccin para la medida de concentracin.
C correction tab. 2 Para obtener en la medida de concentracin una precisin que equivalga aproximadamente o sea
incluso superior a la reproducibilidad, ste factor puede ser utilizado para realizar una
optimizacin en el campo. Este valor tiene el efecto de corregir el valor medido de la
concentracin actual.
Se introduce en forma de la unidad de concentracin actualmente ajustada. El valor de
correccin depende de la matriz de concentracin actualmente seleccionada. Si se trata de una
matriz fija, est disponible un solo valor de correccin. Las matrices variables soportan dos.

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 49


7.4.11 Men: System Zero adj.

IMPORTANTE (NOTA)
Asegure los puntos siguientes antes de iniciar el ajuste del punto cero del sistema:
La tubera de medida del sensor de caudal debe estar completamente llena.
Asegrese de que no circule ningn fluido por la tubera de medida del sensor (cierre las vlvulas, dispositivos
de cierre, etc.).
No se deben producir golpes de presin en el fluido de medida.
Asegrese de que el sensor de caudal no est expuesto a vibraciones.
En el fluido de medida no deben encontrarse burbujas de gas.
El ajuste del cero debe realizarse en condiciones normales de operacin (temperatura de funcionamiento,
presin de servicio etc.).

/ System Zero adj.


Mscaras Rango de valores Descripcin
System Zero adj. Seleccin del submen "System Zero adj. Function automatic?".
Function automatic?
System Zero adj. Seleccin del submen "System Zero adj. manual?".
manual?

/ System Zero adj. / System Zero adj. Function automatic?


Mscaras Rango de valores Descripcin
System Zero adj. Slow? Inicio del ajuste lento del cero del sistema.
System Zero adj. Fast? Inicio del ajuste rpido del cero del sistema.

/ System Zero adj. / System Zero adj. manual?


Mscaras Rango de valores Descripcin
System Zero adj. x.xxx % Introduccin del valor para el ajuste manual del cero.

7.4.12 Men: Alarm


Introduccin de los valores lmite (mnimo y mximo) para las magnitudes Caudal msico, Densidad, Concentracin y
Temperatura. El contacto de salida digital 41 / 41 permite sealar si se sobrepasan los valores lmite (mn., mx.) ajustados. La
configuracin se realiza a travs del men " / Switch contacts / Contact output".

/ Alarm
Mscaras Rango de valores Descripcin
Min Alarm Qm 0 105 % Introduccin del valor lmite inferior del caudal msico. El valor debe ser inferior a "Max Alarm
Qm".
Max Alarm Qm 0 105 % Introduccin del valor lmite superior del caudal msico. El valor debe ser superior a "Min Alarm
Qm".
Min Alarm density 0.5 3.5 kg/l Introduccin del valor lmite inferior de la densidad. El valor debe ser inferior a "Max Alarm
density".
Max Alarm density 0.5 3.5 kg/l Introduccin del valor lmite superior de la densidad. El valor debe ser superior a "Min Alarm
density".
Min Alarm Temp. -50 200 C Introduccin del valor lmite inferior de la temperatura. El valor debe ser inferior a "Max Alarm
Temp.".
Max Alarm Temp. -50 200 C Introduccin del valor lmite superior de la temperatura. El valor debe ser superior a "Min Alarm
Temp.".
Min Alarm Concentr. -5 105,0 % Introduccin del valor lmite inferior de la concentracin. El valor debe ser inferior a "Max Alarm
Concentr.".
Max Alarm Concentr. -5 105,0 % Introduccin del valor lmite superior de la concentracin. El valor debe ser superior a "Min Alarm
Concentr.".

50 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


7.4.13 Men: Display
Configuracin del indicador de proceso del transmisor. Hay dos lneas para poder indicar por separado dos valores diferentes.
Adems, es posible activar el modo Multiplex. Cuando el modo Multiplex est activado, en cada lnea se indican dos valores
que se alternan automticamente (cada 3 segundos).

/ Display
Mscaras Rango de valores Descripcin
1st Line Vese la tabla siguiente Seleccin del valor indicado.
2nd Line
1st Line Multiplex
2nd Line Multiplex

Valor Descripcin
Q [Bargraph] Indicacin del caudal en forma de barras.
Qm Indicacin del caudal msico [en forma de la unidad definida].
Qv Indicacin del flujo volumtrico [en forma de la unidad definida].
Q [%] Indicacin del caudal msico [en porcentajes].
Temperature Indicacin de la temperatura del fluido [en forma de la unidad definida].
Density Indicacin de la densidad [en forma de la unidad definida].
Concentr. Unit Indicacin de la concentracin [en forma de la unidad definida].
Concentr. Percent Indicacin de la concentracin [en porcentajes].
Qm Concentration Indicacin del caudal msico neto en funcin de la concentracin actual.
TAG Nummer Indicacin del nmero TAG definido.
Totalizer Mass Indicacin de los totalizadores de caudal msico directo/inverso, en funcin del sentido de flujo
Totalizer Mass>F Indicacin del totalizador de caudal msico directo.
Totalizer Mass<R Indicacin del totalizador de caudal msico inverso.
Totalizer Volumes Indicacin de los totalizadores de flujo volumtrico directo/inverso, en funcin del sentido de flujo.
Totalizer Vol.>V Indicacin del totalizador de flujo volumtrico directo.
Totalizer Vol.<R Indicacin del totalizador de flujo volumtrico inverso.
Totalizer Net Mass Indicacin del totalizador de caudal msico neto en funcin del caudal masco neto.
Total. Net Mass >F Indicacin del totalizador de caudal msico neto directo.
Total. Net Mass <R Indicacin del totalizador de caudal msico neto inverso.
Pipe frequency Frecuencia de la tubera de medida.
Blank -
Off Modo Multiplex desactivado (slo para modo Multiplex).

IMPORTANTE (NOTA)
Las unidades de los valores indicados se corresponden con las indicadas en el men " / Unit".

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 51


7.4.14 Men: Totalizer
Todos los cuatro/seis totalizadores cuentan hasta 10 milliones (en forma de la unidad elegida para el totalizador). Una vez que el
totalizador llegue a 10 milliones, el valor del totalizador se trasladar al contador de desbordamiento correspondiente y el
totalizador volver a cero.
Para visualizar est operacin en la pantalla del indicador de procesos aparecer en la pantalla un aviso correspondiente. Se
pueden contar hasta 65535 desbordamientos por cada totalizador.
Cada totalizador puede activarse o ponerse a cero por separado (entrando 0). Al activar (o poner a cero) un totalizador, el
contador de desbordamiento correspondiente se pondr automticamente a cero.
Si en el men " / Mode of operation / Flow indication" se ha seleccionado la opcin "Forward", en el men "Totalizer"
slo aparecern los parmetros de los totalizadores de caudal directo.

/ Totalizer
Mscaras Rango de valores Descripcin
Totalizer mass Seleccin del submen "Totalizer mass".
Totalizer volume Seleccin del submen "Totalizer volume".
Totalizer net. mass Seleccin del submen "Totalizer net. mass".
Totalizer Reset Puesta a cero de todos los totalizadores (despus de confirmar la advertencia pulsando
. Todos los totalizadores se pondrn a cero. Para poner a cero un totalizador individual hay
que poner a cero el parmetro correspondiente.

/ Totalizer / Totalizer mass


/ Totalizer / Totalizer volume
/ Totalizer / Totalizer net. mass
Mscaras Rango de valores Descripcin
Counter > F 0 10.000.000 Introduccin e indicacin del valor indicado por el totalizador de caudal directo.
Overflow > F Slo visualizacin Indicacin de los debordamientos del totalizador de caudal directo correspondiente. Un
desbordamiento equivale a la cifra 10.000.000. Se pueden indicar 65.636 desbordamientos,
como mximo.
Totalizer < R 0 10.000.000 Introduccin e indicacin del valor indicado por el totalizador de caudal inverso.
Overflow < R Slo visualizacin Indicacin de los debordamientos del totalizador de caudal inverso correspondiente. Un
desbordamiento equivale a la cifra 10.000.000. Se pueden indicar 65.636 desbordamientos,
como mximo.

52 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


7.4.15 Men: Pulse Output

/ Pulse Output
Mscaras Rango de valores Descripcin
Output of Mass Seleccin del valor medido emitido en la salida de impulsos.
Volume Mass: Indicacin del caudal msico
Qm Concentration Volume: Indicacin del flujo volumtrico
Qm Concentration: Indicacin del caudal msico neto
QvMax pulse Indicacin del caudal por impulso (slo cuando se indica el flujo volumtrico).
Qm% max pulse Indicacin de la masa por impulso (slo cuando se indica el caudal msico).
Pulse 0.001 1000 Introduccin de los impulsos por unidad (valor de impulso).
imp/unidad Si es necesario, el valor introducido se corregir por el transmisor, ya que la frecuencia lmite de
la salida de impulsos es de 5000 Hz.
IMPORTANTE (NOTA)
Un aumento del valor de impulso puede reducir el ancho de impulso!

Pulse width 0.1 2000 ms Introduccin del ancho de impulso. El valor de impulso y ancho de impulso dependen uno del
otro y se corregirn por el transmisor, si es necesario.

Ejemplos
Ejemplo 1
Ajustes Introduccin Resultado
QmMx = 24 kg/min = 0,4 kg/s Ancho de impulso nuevo: 0,4 kg/s x 100 impulsos/kg = 40 impulsos/s = 40 Hz
Unidad del totalizador: kg 10 ms Duracin del perodo = 25 ms
Valor de impulso: 100 impulsos/kg Ancho de impulso mximo = duracin del perodo / 2 = 12,5 ms
Resultado: Se acepta el ancho de impulso introducido [10 ms].

Ejemplo 2
Ajustes Introduccin Resultado
QmMx = 6 kg/min = 0,1 kg/s = 100 g/s Valor de impulso nuevo: 100g/s x 60 impulsos/g = 6000 impulsos/s = 6000 Hz
Unidad del totalizador: g 60 impulsos/g Se ha sobrepasado la frecuencia lmite de 5000 Hz. El
Ancho de impulso: 10 ms transmisor pondr el valor de impulso automticamente a 50
impulsos/g y la duracin del perodo a 0,2 ms (5 kHz), porque
sto corresponde exactamente a 5000 Hz.
Ancho de impulso mximo = duracin del perodo /2 = 0,1 ms
Resultado: Es necesario reducir el valor de impulso introducido
y, adicionalmente, el ancho de impulso.

IMPORTANTE (NOTA)
Si se utiliza un totalizador mecnico recomendamos utilizar un ancho de impulso de 30 ms y una frecuencia
lmite [fmx] de 3 kHz.

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 53


7.4.16 Men: Current output 1

/ Current output 1
Mscaras Rango de valores Descripcin
Output of Qm, Qv, Density, Seleccin del valor medido emitido en la salida de corriente 1 (31 / 32).
Temperature,
Concentration
Qv l = 100 % 0.1 10.000.000 Introduccin del caudal volumtrico a partir del cual la salida de corriente alcanza su valor
mximo (20 mA) (slo visible si el caudal volumtrico se transmite a travs de la salida de
corriente).
Density l = 0 % 0.5 3.5 g/cm3 Introduccin de la densidad a partir de la cual la salida de corriente alcanza su valor mnimo (0
mA)
(slo visible si la densidad se transmite a travs de la salida de corriente).
Density l = 100 % 0.5 3.5 g/cm3 Introduccin de la densidad a partir de la cual la salida de corriente alcanza su valor mximo (20
mA)
(slo visible si la densidad se transmite a travs de la salida de corriente).
Temp l = 0 % -50 200 C Introduccin del valor de temperatura a partir del cual la salida de corriente alcanza su valor
mnimo (0 mA)
(slo visible si el valor de temperatura se transmite a travs de la salida de corriente).
Temp l = 100 % -50 200 C Introduccin del valor de temperatura a partir del cual la salida de corriente alcanza su valor
mximo (20 mA)
(slo visible si el valor de temperatura se transmite a travs de la salida de corriente).
Qm% l = 100 % - Introduccin del caudal msico neto a partir del cual la salida de corriente alcanza su valor
mximo (20 mA) (slo visible si el caudal msico neto se transmite a travs de la salida de
corriente).
Concentr. l = 0 % Introduccin de la concentracin a partir de la cual la salida de corriente alcanza su valor mnimo
(0 mA)
(slo visible si la concentracin se transmite a travs de la salida de corriente).
Concentr. l = 100 % Introduccin de la concentracin a partir de la cual la salida de corriente alcanza su valor mximo
(20 mA)
(slo visible si la concentracin se transmite a travs de la salida de corriente).
Current output 0 20 mA, 4 20 mA Seleccin del modo de operacin de la salida de corriente. Si est activada la comunicacin
HART, se debe elegir '4 ... 20 mA'.
IMPORTANTE (NOTA)
La comunicacin HART se realiza a travs de la salida de corriente 1. Para poder
utilizar la comunicacin HART, hay que elegir el modo de operacin 4 20 mA.
Si se utiliza el modo de operacin 0 20 mA y se activa la comunicacin HART,
aparecer un mensaje de error y el tipo de comunicacin no puede modificarse.
Si se ha activado la comunicacin HART y se activa el modo de operacin 0
20 mA, aparecer un mensaje de error y la comunicacin HART se desactivar
automticamente.
Iout for Alarm Low, High Seleccin del estado de la salida de corriente 1 en caso de fallo. El ajuste de la corriente emitida
"Low" o "High" se realizar en los menes siguientes.
Low Alarm 2 3.6 mA Seleccin de la corriente para alarma Low.
El valor depende del rango de salida de corriente elegido.
Para el rango de salida de corriente 0 ... 20 mA, la corriente de alarma es de 0 mA.
Para el rango de salida de corriente 4 ... 20 mA, la corriente de alarma Low puede modificarse
dentro de los lmites 2 ... 3,6 mA.
Si se modifica el rango de salida de corriente, el transmisor modificar automticamente la
corriente de alarma Low adaptndola al rango de salida de corriente nuevo (el rango 0 ... 20 mA
cambiar a 0 mA y el rango 4 ... 20 mA a 2 mA).
High Alarm 21 26 mA Seleccin de la corriente para alarma High.
El valor es independiente del rango de salida de corriente elegido, ya que el lmite superior de
ambos rangos es de 20 mA. El rango de corriente de alarma High comienza en 21 mA y acaba en
26 mA.

54 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


7.4.17 Men: Current output 2
A diferencia de la salida de corriente 1, la salida de corriente 2 no es apta para HART y dispone unicamente de un solo rango
de salida de corriente (4 ... 20 mA).

/ Current output 2
Mscaras Rango de valores Descripcin
Output of Qm, Qv, Density, Seleccin del valor medido emitido en la salida de corriente 1 (31 / 32).
Temperature,
Concentration
Qv l = 100 % 0.1 10.000.000 Introduccin del caudal volumtrico a partir del cual la salida de corriente alcanza su valor
mximo (20 mA)
(slo visible si el caudal volumtrico se transmite a travs de la salida de corriente).
Density l = 0 % 0.5 3.5 g/cm3 Introduccin de la densidad a partir de la cual la salida de corriente alcanza su valor mnimo (0
mA)
(slo visible si la densidad se transmite a travs de la salida de corriente).
Density l = 100 % 0.5 3.5 g/cm3 Introduccin de la densidad a partir de la cual la salida de corriente alcanza su valor mximo (20
mA)
(slo visible si la densidad se transmite a travs de la salida de corriente).
Temp l = 0 % -50 200 C Introduccin del valor de temperatura a partir del cual la salida de corriente alcanza su valor
mnimo (0 mA)
(slo visible si el valor de temperatura se transmite a travs de la salida de corriente).
Temp l = 100 % -50 200 C Introduccin del valor de temperatura a partir del cual la salida de corriente alcanza su valor
mximo (20 mA)
(slo visible si el valor de temperatura se transmite a travs de la salida de corriente).
Qm% l = 100 % - Introduccin del caudal msico neto a partir del cual la salida de corriente alcanza su valor
mximo (20 mA) (slo visible si el caudal msico neto se transmite a travs de la salida de
corriente).
Concentr. l = 0 % Introduccin de la concentracin a partir de la cual la salida de corriente alcanza su valor mnimo
(0 mA)
(slo visible si la concentracin se transmite a travs de la salida de corriente).
Concentr. l = 100 % Introduccin de la concentracin a partir de la cual la salida de corriente alcanza su valor mximo
(20 mA)
(slo visible si la concentracin se transmite a travs de la salida de corriente).
Iout for Alarm Low, High Seleccin del estado de la salida de corriente 1 en caso de fallo. El ajuste de la corriente emitida
"Low" o "High" se realizar en los menes siguientes.
Low Alarm 2 3.6 mA Seleccin de la corriente para alarma Low.
High Alarm 21 26 mA Seleccin de la corriente para alarma High.

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 55


7.4.18 Men: Switch contacts

/ Switch contacts
Mscaras Rango de valores Descripcin
Contact input No function, Seleccin de la funcin de la entrada de contacto digital (81 / 82).
Totalizer reset. Concentr. No function: Entrada de contacto sin funcin.
Table, Totalizer reset. Concentr. Table: Cambio de las tablas (Marix 1 / 2) para el clculo de la
Ext. output Shut-off, concentracin.
Totalizer reset. Ext. output Shut-off: La salida de corriente y salida de impulsos se ponen en cero. Los
totalizadores se pararn.
Totalizer reset.: Todos los totalizadores se ponen en cero.
Contact output Vese la tabla siguiente Seleccin de la funcin de la salida de contacto digital (41 / 42).
Para la funcin elegida, la salida puede configurarse opcionalmente como contacto de cierre o
contacto de reposo.

Funcin Contact output Descripcin


No function Sin funcin, salida abierta.
F/R-Signal _ Indicacin del sentido de flujo; salida cerrada en caso de flujo inverso.
F/R-Signal / Indicacin del sentido de flujo; salida abierta en caso de flujo inverso.
General alarm _ Salida cerrada (no hay alarma colectiva). Abre en caso de fallo.
General alarm / Salida abierta (no hay alarma colectiva). Cierra en caso de fallo.
MAX/MIN Alarm _ Salida cerrada (no hay alarma Mn / Mx). Abre en caso de alarma Mn / Mx.
MAX/MIN Alarm / Salida abierta (no hay alarma Mn / Mx). Cierra en caso de alarma Mn / Mx.
MIN Alarm _ Salida cerrada (no hay alarma Mn). Abre en caso de alarma Mn.
MIN Alarm / Salida abierta (no hay alarma Mn). Cierra en caso de alarma Mn.
MAX Alarm _ Salida cerrada (no hay alarma Mx). Abre en caso de alarma Mx.
MAX Alarm / Salida abierta (no hay alarma Mx). Cierra en caso de alarma Mx.

7.4.19 Men: Label

/ Label
Mscaras Rango de valores Descripcin
TAG number ASCII, 8 caracteres, Introduccin de un nmero TAG para identificar el punto de medicin (protocolo HART).
como mximo.
Descriptor ASCII, 16 caracteres, Introduccin del descriptor HART.
como mximo.
Date 1.1.1900 31.12.2155 Fecha del fichero HART.
Unit number Slo visualizacin Indicacin del nmero de aparato.

7.4.20 Men: Interface

/ Interface
Mscaras Rango de valores Descripcin
Communication Off, HART Seleccin del tipo de comunicacin para la comunicacin digital.
Off: sin comunicacin digital.
HART: comunicacin HART activada, a travs de la salida de corriente 1. Configurar antes el
modo de operacin poniendo la salida de corriente 1 en 4 20 mA.
Unit address 0 15 Introduccin de la direccin HART. El protocolo HART permite la instalacin de un bus con hasta
15 equipos (1 ... 15).
IMPORTANTE (NOTA)
Si la direccin ajustada es superior a 0, el aparato trabajar en modo Multidrop. La
salida de corriente est fijado a 4 mA. A continuacin, se realizar solamente la
comunicacin HART a travs de la salida de corriente.

56 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


7.4.21 Men: Function test

/ Function test
Mscaras Rango de valores Descripcin
Function test pulse Seleccin del submen "Function test pulse Output".
Output
Function test Iout 1 Seleccin del submen "Function test Iout 1".
Function test Iout 2 Seleccin del submen "Function test Iout 2".
Function test Contact Seleccin del submen "Function test Contact input".
input
Function test Contact Seleccin del submen "Function test Contact output".
output
Function test HART 1200 Hz, 2200 Hz Seleccin de la frecuencia HART simulada.
Transmitter
Function test HART Slo visualizacin Indicacin del ltimo comando HART recibido.
Command
Function test Memory Activacin de la prueba de funcionamiento de la memoria.
Simulation Seleccin del submen "Simulation".

/ Function test / Function test pulse Output


Mscaras Rango de valores Descripcin
Pulse Output 0.001 5000 Hz Introduccin de la tasa de impulsos para la prueba funcional de la salida de impulsos. Para
cancelar, pulsar una tecla cualquiera.

/ Function test / Function test Iout 1


/ Function test / Function test Iout 2
Mscaras Rango de valores Descripcin
Iout 1 0 26 mA Introduccin de la corriente de salida para la prueba funcional de la salida de corriente 1. Para
cancelar, pulsar una tecla cualquiera.
Iout 2 3.5 26 mA

/ Function test / Function test Contact input


Mscaras Rango de valores Descripcin
Contact input On, Off Prueba de funcionamiento de la entrada de contacto. Para cancelar, pulsar una tecla cualquiera.

/ Function test / Function test Contact output


Mscaras Rango de valores Descripcin
Contact output On, Off Prueba funcional de la entrada de contacto. Para cancelar, pulsar una tecla cualquiera.

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 57


/ Function test / Simulation
El men 'Simulacin' contiene opciones que permiten poner en valores programables las magnitudes de medida individuales o
todas las magnitudes de medida del transmisor. Cuando la simulacin est activada aparecen las opciones adicionales del
submen 'Simulacin'.
stas permiten definir para cada magnitud individual si la magnitud se debe medir o simular, as como el valor que la misma
debe tener. Para ello, se puede elegir entre las posibilidades siguientes:

Valor Descripcin
Medida Se indicar el valor real medido de la magnitud correspondiente.
Introduccin El valor de la magnitud se simular. A continuacin, se puede seleccionar un men para ponerlo en un valor fijo.
Step La magnitud se simular y se podr aumentar o reducir gradualmente a travs de las teclas STEP y DATA siempre que
aparezca el indicador de procesos.

Mscaras Rango de valores Descripcin


Simulation On, Off Activacin de las funciones de simulacin.
Qm Medicin, introduccin, Seleccin de la funcin de simulacin.
Step
Qm -115 +115 % Introduccin del caudal msico a simular [en %].
Density Medicin, introduccin, Seleccin de la funcin de simulacin.
Step
Density 0,001 g/ml Introduccin de la densidad a simular [en g/ml].
Temperature Medicin, introduccin, Seleccin de la funcin de simulacin.
Step
Temp. housing Medicin, introduccin, Seleccin de la funcin de simulacin.
Step
Temperature -60 210 C Introduccin de la temperatura a simular [en C]
Temp. housing -60 210 C Introduccin de la temperatura a simular [en C]

58 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


7.4.22 Men: Status

/ Status
Mscaras Rango de valores Descripcin
Error log Number: 3 Indicacin del nmero de mensajes de error almacenados y seleccin del submen "Memoria de
errores".
Warning Register Indicacin del nmero de mensajes de advertencia almacenados y seleccin del submen
Number: 1 "Memoria de advertencias".
Power outage Slo visualizacin Indicacin del nmero de fallos de red.
Status Reset Puesta a cero de todos los totalizadores de errores, advertencias y fallos de red (despus de
confirmar la advertencia pulsando . Todos los totalizadores se pondrn a cero.

/ Status / Memoria de errores


Mscaras Rango de valores Descripcin
7 (Set) Temp. Slo visualizacin Indicacin del ltimo error ocurrido, con nmero de error y estado (actual o puesto).
Measurement (ejemplo) Si hay otros errores, se pueden utilizar las teclas o para hojear en la lista de errores.
9a (current) Density IMPORTANTE (NOTA)
measurement El orden en el que los errores aparecen en la lista no responde a su prioridad!

/ Status / Memoria de advertencias


Mscaras Rango de valores Descripcin
4 (Set) Ext. Cut-off Slo visualizacin Indicacin del ltimo error ocurrido, con nmero de error y estado (actual o puesto).
(ejemplo) Si hay otros errores, se pueden utilizar las teclas o para hojear en la lista de errores.
IMPORTANTE (NOTA)
El orden en el que los errores aparecen en la lista no responde a su prioridad!

7.4.23 Men: Versin del software

/ Versin del software


Mscaras Rango de valores Descripcin
CoriolisMaster 03.2012 Slo visualizacin Indicacin de la versin del software
FCB FW (ejemplo) En la primera lnea se indican el cdigo de identificacin del aparato y la fecha de revisin del
software. En la segunda lnea se indican el nmero de identificacin y nivel de revisin del
software.

Adems de la versin del software indicada en el men, en el lado superior de la unidad de transmisor enchufable se encuentra
una placa indicadora con el nmero de identificacin del software.

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 59


Change from one to tw o c olumns

7.5 Medida de concentraciones DensiMass (slo 7.5.2 Introduccin de la matriz de concentraciones


disponible para FCB350) La matriz de concentraciones se introduce a travs del men
El transmisor puede calcular la concentracin actual partiendo " / Concentration / Variable Matrix". Los datos de la
de la densidad y temperatura medidas y utilizando las matriz deben estar disponibles (vase el captulo "Estructura
matrices de concentracin. de la matriz de concentraciones").
El transmisor viene configurado con las siguientes matrices de
concentracin predefinidas: Paso 1:
Concentracin de hidrxido de sodio en agua Men " / Concentration / Variable Matrix".
Concentracin de alcohol en agua Introduccin del nombre de la unidad para la matriz variable,
Concentracin de hidratos de carbono en agua introduccin de los valores lmite superior e inferior para la
Concentracin de almidn de maz en agua concentracin.
Concentracin de almidn de trigo en agua
Paso 2:
Adems, se pueden introducir dos matrices (de hasta 100 Introduccin de los ajustes bsicos de la matriz en el men
valores) especificadas por el usuario. " / Concentration / Variable Matrix / Configuration".
Aqu se fija el nmero de matrices (1 2), el nmero de
7.5.1 Precisin de la medida de concentraciones valores de temperatura y el nmero de valores de
La precisin de la medida concentraciones depende primero concentracin.
de la calidad de las matrices introducidas.
Sin embargo, como el clculo se basa en las magnitudes Paso 3:
iniciales Densidad y Temperatura, la precisin de la medida de Introduccin de los datos de las matrices en el men
concentraciones se determina, en fin de cuentas, por la " / Concentration / Variable Matrix / Matrix 1 / 2".
precisin de la medida de la temperatura y densidad. Aqu se introducen los valores de temperatura, valores de
concentracin (en la unidad deseada o en %) y los valores de
Ejemplo: densidad.
densidad: un 0% de alcohol en agua, temperatura: Una vez introducidos los datos, la matriz se calcular a travs
20 C [68 F] = 998,23 g/l de la opcin de men "Matrix calculation". Los valores que
falten se calcularn por interpolacin o extrapolacin.
densidad: un 100 % de alcohol en agua, temperatura:
20 C [68 F] = 789,30 g/l Paso 4:
Almacenamiento de las matrices en el men " /
Concentracin Densidad Concentration / Variable Matrix" (a travs de la opcin de
100 % 208,93 g/l men "Enter matrix finish").
0,48 % 1 g/l
0,69 % 2 g/l La introduccin de las matrices ha terminado.

Por consiguiente, la clase de precisin de la medida de


densidad determina directamente la precisin de la medida de
concentraciones.

60 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


Change from two to one c olumn

7.5.3 Estructura de la matriz de concentraciones

Respecto al software, se distinguen dos valores de concentracin diferentes:


1. concentracin indicada en unidades (p. ej.: % o B)
El rango de valores no est limitado; el valor puede transmitirse a la salida de corriente; el valor puede seleccionarse en el
submen Unidades.

2. Concentracin en porcentajes (%)


El rango de valores est limitado al 0 ... 103,125 %. Este valor slo se utiliza para el clculo interno del caudal msico neto.
El valor del caudal msico neto puede transmitirse a la salida de corriente y la salida de impulsos.

Lmites de concentracin MIN / MAX: -5.0 ... 105,0.

La matriz para el clculo de concentraciones tiene la siguiente estructura:

Temperatura 1 Temperatura n
Valor 1 Concentracin en Valor 1 Concentracin
Valor 1,1 Densidad Valor n,1 Densidad
% indicada en unidades (p.
ej. % o B)
.
Valor m Concentracin en Valor m Concentracin
Valor 1, m Densidad Valor n,m Densidad
% indicada en unidades (p.
ej. % o B)

Al entrar los valores en la matriz deben observarse las siguientes reglas:


si se utiliza una sola matriz: 2 N 20; 2 M 20; N * M 100
si se utilizan dos matrices: 2 N 20; 2 M 20; N * M 50

Los valores de densidad de una columna deben estar odenados de forma ascendente debido al algoritmo utilizado en el
software del transmisor.
Density x,1 < < Density x,2 << Density x,M para 1 x M

Los valores de temperatura deben estar ordenados de forma ascendente de la izquierda a la derecha debido al algoritmo
utilizado en el software del transmisor.
Temperatura 1 << Temperatura x << Temperatura N para 1 x N

Los valores de concentracin deben estar ordenados de forma montonamente ascendente o descendiente desde arriba hacia
abajo debido al algoritmo utilizado en el software del transmisor.
Concentr. 1 << Concentr. x < < Concentr. N para 1 x N
o
Concentr. 1 >> Concentr. x > > Concentr. N para 1 x N

Ejemplo:
10 C (50 F) 20 C (68 F) 30 C (86 F)
0% 0 BRIX 0,999 kg/l 0,982 kg/l 0,979 kg/l
10 % 10 BRIX 1,010 kg/l 0,999 kg/l 0,991 kg/l
40 % 30 BRIX 1,016 kg/l 1,009 kg/l 0,999 kg/l
80 % 60 BRIX 1,101 kg/l 1,018 kg/l 1,011 kg/l

Change from one to tw o c olumns

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 61


Change from two to one c olumn

7.6 Historial de versiones del software


Segn la recomendacin NAMUR NE53, ABB ofrece un historial del software claro y fcilmente comprensible.

Versin estndar y versin HART

Software FCB FW
Versin de
Fecha de revisin Tipo de modificacin Descripcin
software
00.01.xx 03/2012 Versin nueva -
00.02.xx 06/2013 Actualizacin Introduccin de una nueva funcin: la densidad mn. genera el error "9b"

Change from two to one c olumn

8 Mensajes de error
8.1 Generalidades
Los listados de alarmas indicados en forma de tabla en las pginas siguientes describen el comportamiento del transmisor en
caso de errores y fallos funcionales.
La tabla lista todos los fallos posibles del transmisor, as como su influencia sobre los valores de las magnitudes medidas, el
comportamiento de las salidas de corriente y la salida de alarma.
Las celdas vacas de la tabla indican que el fallo no tiene efecto sobre la magnitud medida o la sealizacin de alarmas por la
salida correspondiente. Si las celdas de la columna 'Salida de corriente' slo indican 'Alarma', la alarma se sealar solamente
como 'alarma alta' o 'alarma baja', segn la opcin seleccionada en el men de salidas de corriente.
El orden de los errores en la tabla corresponde a su prioridad.
El asiento primero tiene la prioridad ms alta, el ltimo la prioridad mas baja.
Si se producen varios errores al mismo tiempo, el error con la prioridad ms alta determinar el estado de alarma de la
magnitud medida y de la salida de corriente, respectivamente. En cambio, si un error de alta prioridad no tiene influencia sobre
una salida o magnitud medida, el estado de las mismas ser determinado por el error con la prxima prioridad ms baja.

Ejemplo:
Si se produce el error 7a "T Pipe measurement", se puede ver en la tabla que este error cambia la magnitud Temperatura
(temp. constante 20 C [68 F]).
Como la medida de temperatura es elemental para calcular la densidad y, por consiguiente, el valor Qv, las salidas de corriente
asignadas a estos parmetros cambiarn al estado de alarma programado (alarma High o Low).

62 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


8.2 Sinopsis

Magnitudes de medida Contador Salida de corriente

Concentracin [unidad]

Concentracin [unidad]
Caudal msico neto

Caudal msico neto


Concentracin [%]
Densidad [g/cm 3]

Temperatura [C]

Salida de alarma
Texto de error

Temperatura
N. de error

Masa neta

Densidad
Prioridad

Volumen
Qm [%]

Qv [%]

Masa

Qm

Qv
1 5a Internal FRAM 0 0 1 20 0 0 0
2 5b External FRAM 0 0 1 20 0 0 0
3 10 DSP communication 0 0 1 20 0 0 0
4 1 AD Transmitter 0 0 1 20 0 0 0
5 11d Sensor 0 0 1 0 0 0
6 0 Sensor amplitude 0 0 1 0 0 0
7 2a Driver 0 0 1 0 0 0
8 2b Driver current 0 0 1 0 0 0
9 9a Density measurement 0 4 0 0 0
10 9b Min Density 0 0 2) 2) 2) 0
11 7a T Pipe measurement 20 0 0 0
12 7b T Housing measurement 20
13 3 Flowrate >103.25 % 103 Qm = Qm =
103 103
14 12 Concentration (Percent) 0 0
15 4 Ext. zero return
16 8a Iout 1 to large
17 8b Iout 1 to small
18 8c Iout 2 to large
19 8d Iout 2 to small
20 6a Totalizer Mass -> V 1)
21 6b Totalizer Mass <- R 1)
22 6c Totalizer Vol.-> V 1)
23 6d Totalizer Vol.<- R 1)
24 6e Totalizer Net Mass -> V 1)
25 6f Totalizer Net Mass <- R 1)
26 11a Sensor A 0 0 1 0 0 0
27 11b Sensor B 0 0 1 0 0 0

Los estados actuales de los contadores, de las salidas de corriente y de la salida de alarma se representan con iconos;
consulte la tabla siguiente.

Icono Descripcin
Parada del contador
Sin modificacin
1) Al producirse el error, el contador correspondiente vuelve a contar partiendo de 0.
2) Al producirse el error, la magnitud de medida se restablece al valor de la densidad mnima.
Alarma (general)
Alarma High
Alarma Low

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 63


8.3 Mensajes de error

Mensaje de error Prioridad Descripcin Causa posible Indicaciones para la correccin


Error: 0 6 La amplitud del sensor, que El error se produce nicamente Reducir la concentracin de gas,
Sensor amplitude depende del dimetro nominal, cuando el sensor est lleno? cambiar el fluido
es inferior a 10 mV. "Fluido que absorbe energa" en el
sensor (p. ej. alta concentracin de
gas, fluidos muy viscosos), por lo
que la corriente de excitacin es
insuficiente
Perturbaciones mecnicas o Desacoplar el sensor de las fuentes
hidrulicas muy fuertes en la tubera de perturbaciones
Versin con proteccin para Utilizar un cable ms corto, reducir la
explosiones y diseo remoto: resistencia creando una conexin en
La resistencia elctrica del cable del paralelo o utilizando un cable de bajo
excitador es excesiva ohmiaje
Error: 1 4 El convertidor A/D est saturado La tensin del sensor es excesiva Comprobar las amplitudes del sensor
AD Transmitter o no responde y controlar si la amplitud ajustada es
correcta
Convertidor A/D averiado Cambiar la placa DSP
Error: 2a 7 El sensor no vibra Interrupcin del circuito de En versiones de diseo remoto:
Driver regulacin; el sensor no es comprobar el cableado entre el
compatible con el transductor sensor y el transductor
Error: 2b 8 Reaccin del limitador de Consulte el error 0 Consulte el error 0
Driver current corriente del excitador, debido a
una insuficiencia de la corriente
de excitacin
Error: 3 13 El valor inferior QmMx ajustado Rango de medicin ajustado Aumentar el rango de medicin
Flowrate >103.25 % se excede en ms del 5 % insuficiente (QmMx)
Caudal excesivo Reducir el caudal
Error: 4 14 El caudal se pone en cero, por lo La entrada de contacto externa est Establecer la entrada de contacto
Ext. zero return que los contadores se paran establecida en "High" externa en "Low"
automticamente
Error: 5b 2 Prdida de la base de datos Base de datos errnea Desconectar y reconectar el
External FRAM externa dispositivo; realizar una
comprobacin de funcionamiento del
transductor
Falta la memoria de datos externa Instalar la memoria de datos externa
La memoria de datos externa est Cargar la memoria de datos externa
vaca
Error: 6a 19 El contador de caudal msico de Reprogramar el contador
Totalizer Mass -> V avance est averiado
Error: 6b 20 El contador de caudal msico de Reprogramar el contador
Totalizer Mass <- R retorno est averiado
Error: 6c 21 El contador de caudal Reprogramar el contador
Totalizer Vol.-> V volumtrico de avance est
averiado
Error 6d 22 El contador de caudal Reprogramar el contador
Totalizer Vol.<- R volumtrico de retorno est
averiado
Error: 6e El contador de caudal msico Reprogramar el contador
Totalizer Net Mass -> V neto est averiado
Error: 6f El contador de caudal msico Reprogramar el contador
Totalizer Net Mass <- R neto est averiado

64 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


Mensaje de error Prioridad Descripcin Causa posible Indicaciones para la correccin
Error: 7a 11 Error durante la medicin de Cableado incorrecto Revisar el cableado entre el
T Pipe measurement temperatura (solo en versiones de diseo remoto) transductor y el sensor de caudal
Para la compensacin de El Pt 100 est averiado Controlar en el sensor la resistencia
temperatura de los valores de del Pt 100
medicin Qm y Densidad, se parte
ahora de 20 C, es decir, la medicin
se realiza correctamente a una
temperatura del fluido de ~20 C
Error: 7b 12 Error durante la medicin de Cableado incorrecto Revisar el cableado entre el
T Housing temperatura (solo en versiones de diseo remoto) transductor y el sensor de caudal
measurement Para la compensacin de El Pt 100 est averiado Controlar en el sensor la resistencia
temperatura de los valores de del Pt 100
medicin Qm y Densidad, se parte
ahora de 20 C, es decir, la medicin
se realiza correctamente a una
temperatura del fluido de ~20 C
Error: 8a 15 Se ha sobrepasado el rango mximo Rango ajustado insuficiente Aumentar el rango
Iout 1 to large programado para la salida de
corriente 1
Error: 8b 16 No se ha alcanzado el rango mnimo Rango ajustado insuficiente Aumentar el rango
Iout 1 to small programado para la salida de
corriente 1
Error: 8c 17 Se ha sobrepasado el rango mximo Rango ajustado insuficiente Aumentar el rango
Iout 2 to large programado para la salida de
corriente 2
Error: 8d 18 No se ha alcanzado el rango mnimo Rango ajustado insuficiente Aumentar el rango
Iout 2 to small programado para la salida de
corriente 2
Error: 9a 9 La densidad del fluido medida en el Este error suele aparecer junto con Consulte los errores 1 y 9
Density measurement sensor fuera de la especificacin los errores 1 y 9.
Consutle los errores 1 y 9
Error: 9b 10 Consulte la pgina 46, men "Mode Parmetro "Min Density" definido. Comprobar que el sensor de caudal
Min Density of operation / Min Density". no est funcionando vaco y evitar la
formacin de burbujas de gas en el
caso de lquidos
O bien, establecer el parmetro "Min
Density" en "0".
Error: 11a 23 Falta la seal del sensor A Sensor A averiado o interrupcin del Medir la resistencia del sensor A
Sensor A circuito de regulacin de amplitud En versiones de diseo remoto:
comprobar el cablado entre el sensor
y el transductor
Error: 11b 24 Falta la seal del sensor B Sensor B averiado o interrupcin del Medir la resistencia del sensor B
Sensor B circuito de regulacin de amplitud En versiones de diseo remoto:
comprobar el cablado entre el sensor
y el transductor
Error: 11d 5 Faltan las seales de al menos dos Hay al menos dos sensores Medir la resistencia de los sensores
Sensor sensores averiados o bien una interrupcin en En versiones de diseo remoto:
el circuito de regulacin de amplitud comprobar el cablado entre el sensor
y el transductor
Error: 12 Concentracin en porcentajes < 0 % Concentracin en porcentajes < 0 % Ajustar los datos de la matriz en el
Concentration o > 103,125 % o > 103,125 % submen Concentracin
(Percent)
Error No se pueden cambiar los Est activado el interruptor de Desactivar el interruptor de
Operating protection parmetros proteccin contra modificaciones no proteccin contra modificaciones no
autorizadas autorizadas

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 65


8.4 Mensajes de advertencia

Advertencia Prioridad Descripcin Causa posible Indicaciones para la


correccin
Advertencia: 1 16 El modo de simulacin est activado En el submen Prueba de funcionamiento Desactivar el modo de
**Simulation** est activado el modo de simulacin simulacin
Advertencia: 2 1 Un contador se ha puesto a cero - -
totalizer reset
Advertencia: 5a 3 Valor Qm por debajo del lmite de alarma Valor Qm por debajo del lmite de alarma Reducir el lmite de alarma
Min Alarm Qm MN. ajustado MN. ajustado MN.
Advertencia: 5b 5 Valor de densidad por debajo del lmite Valor de densidad por debajo del lmite de Reducir el lmite de alarma
Min Alarm Density de alarma MN. ajustado alarma MN. ajustado MN.
Advertencia: 5c 7 Valor de temperatura por debajo del Valor de temperatura por debajo del lmite Reducir el lmite de alarma
Min Alarm Temp. lmite de alarma MN. ajustado de alarma MN. ajustado MN.
Advertencia: 5d Valor de concentracin por debajo del Valor de concentracin por debajo del Reducir el lmite de alarma
Min Alarm Conc. lmite de alarma MN. ajustado La lmite de alarma MN. ajustado MN.
histresis de conmutacin es de 0,1 de
la unidad de concentracin ajustada.
Advertencia: 6a 2 Valor Qm por encima del lmite de alarma Valor Qm por encima del lmite de alarma Aumentar el lmite de
Max Alarm Qm MX. ajustado MX. ajustado alarma MX.
Advertencia: 6b 4 Valor de densidad por encima del lmite Valor de densidad por encima del lmite Aumentar el lmite de
Max Alarm Density de alarma MX. ajustado de alarma MX. ajustado alarma MX.
Advertencia: 6c 6 Valor de temperatura por encima del Valor de temperatura por encima del Aumentar el lmite de
Max Alarm Temp. lmite de alarma MX. ajustado lmite de alarma MX. ajustado alarma MX.
Advertencia: 6d Valor de concentracin por encima del Valor de concentracin por encima del Aumentar el lmite de
Max Alarm Conc. lmite de alarma MX. ajustado La lmite de alarma MX. ajustado alarma MX.
histresis de conmutacin es de 0,1 de
la unidad de concentracin ajustada.
Advertencia: 7 9 Aparece en el indicador durante 1 min Se ha cambiado la memoria de datos -
Ext. Data loaded tras el encendido externa (FRAM)
Advertencia: 8a 10 Aparece en el indicador durante 1 min Se ha realizado una actualizacin del -
Update int. data tras el encendido software Se ha cambiado la memoria de
datos externa (FRAM)
Advertencia: 8b 11 Aparece en el indicador durante 1 min Se ha realizado una actualizacin del -
Update ext. data tras el encendido software Se ha cambiado la memoria de
datos externa (FRAM)
Advertencia: 9a 12 Desbordamiento del contador de caudal Desbordamiento del contador de caudal Poner a cero el contador
Overflow -> F Mass msico de avance msico de avance Nota: Si se aumental a
Advertencia: 9b 13 Desbordamiento del contador de caudal Desbordamiento del contador de caudal unidad, se puede
Overflow <- R Mass msico de retorno msico de retorno prolongar el tiempo hasta
Advertencia: 9c 14 Desbordamiento del contador de caudal Desbordamiento del contador de caudal el prximo
Overflow -> F Volume msico de avance msico de avance desbordamiento.
Advertencia: 9d 14 Desbordamiento del contador de caudal Desbordamiento del contador de caudal
Overflow <- R Volume volumtrico de retorno volumtrico de retorno
Advertencia: 9e Desbordamiento del contador de caudal Desbordamiento del contador de caudal
Overflow -> F %M msico neto de avance msico neto de avance
Advertencia: 9f Desbordamiento del contador de caudal Desbordamiento del contador de caudal
Overflow <- R %M msico neto de retorno msico neto de retorno
Advertencia: 10 17 El dispositivo trabaja en sentido de El modo de funcionamiento del dispositivo -
Reverse Q retorno est ajustado en sentido de avance, pero
el fluido en el sensor de caudal fluye en
sentido de retorno

Change from one to tw o c olumns

66 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


9 Mantenimiento / Reparacin 9.4 Transmisor
9.4.1 Cambio
9.1 Generalidades Todos los parmetros de ajuste se almacenan en una
memoria de datos externa. En caso de cambio de transmisor,
ADVERTENCIA - Peligro por corriente los parmetros de ajuste se extraen por lectura de la memoria
elctrica! de datos externa y se transfieren al transmisor nuevo.
Cuando la caja est abierta, la proteccin CEM Los datos del sensor de caudal y los parmetros de ajuste del
no funciona y el usuario no est protegido contra cliente se importan automticamente.
el riesgo de contacto accidental. Al cambiar el transmisor el usuario deber asegurarse de que
Antes de abrir la caja hay que desconectar la el nmero de serie de la memoria de datos externa
alimentacin elctrica. corresponda exactamente con el nmero de serie del sensor
de caudal.
AVISO - Dao de los componentes! Cuando sea necesario cambiar el transmisor, nuestro servico
Los componentes electrnicos en las placas de tcnico estar siempre a su disposicin para asesorarle y
circuitos impresos pueden daarse por contestar sus preguntas.
electricidad esttica (observar las directivas sobre Para cambiar un transmisor por otro con una versin anterior
componentes expuestos a riesgos por del software, recomendamos contactar siempre con nuestro
electricidad esttica (ESD)). servicio posventa.
Antes de tocar los componentes electrnicos,
asegurarse de que la electricidad esttica de su Posicin de la memoria de datos externa (FRAM)
cuerpo se descargue.

Todos los trabajos de reparacin y mantenimiento debern


realizarse, exclusivamente, por el personal tcnico cualificado
del servicio posventa.
Si se cambian o se reparan componentes individuales, se
debern instalar repuestos originales.

9.2 Limpieza
Al limpiar la superficie de las cajas de los aparatos de medida,
asegurarse de que el agente limpiador utilizado no dae las
juntas y la superficie de la cajas.
Para la limpieza nicamente debe utilizarse un pao
humedecido, para impedir cargas electrostticas que daen el
aparato.

9.3 Sensor de caudal


El sensor casi no necesita mantenimiento.
Se recomienda controlar anualmente los siguientes puntos:
Condiciones ambientales (ventilacin, humedad)
Estanqueidad de las conexiones a proceso
Entradas de cables y tornillos de la tapa,
Seguridad funcional de la alimentacin de corriente, la Fig. 33: Posicin del mdulo FRAM
proteccin contra los rayos y la tierra de la red. 1 FRAM (enchufable)

Reparacin del sensor de caudal La memoria de datos externa (FRAM) del sensor de caudal se
En el caso de que sea necesario reparar el sensor de caudal, encuentra en la posicin indicada en la figura (depende del
se debern observar y seguir las indicaciones del captulo diseo compacto o remoto).
"Seguridad / Devolucin del aparato".
ADVERTENCIA - Peligro por corriente
IMPORTANTE (NOTA) elctrica!
El uso de medidores desarrollados para zonas Cuando la caja est abierta, la proteccin CEM
potencialmente explosivas est sujeto a las no funciona y el usuario no est protegido contra
normas vigentes en el lugar de destino. Vase al el riesgo de contacto accidental.
respecto tambin los captulos 6.6, 6.7, 12 y 13. Antes de abrir la caja hay que desconectar la
alimentacin elctrica.

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 67


10 Datos tcnicos - Sensor de caudal 10.3 Precisin
10.3.1 Condiciones de referencia
10.1 Diseos
Medio de calibracin Agua
Temperatura: 25 C (77 F) 5 K
Presin: 2 4 bar (29 58 psi)
Temperatura ambiente 25 C (77 F) +10 K / -5 K
Alimentacin elctrica Tensin de alimentacin segn la
placa de caractersticas UN 1 %
Fase de calentamiento 30 minutos
Instalacin Instalacin segn se describe en
"Instrucciones de montaje" y
"Posiciones de montaje"
Fig. 34: Sensor de caudal FCB3xx / FCH3xx Sin fase gaseosa visible
1 Diseo compacto | 2 Diseo remoto (sin transmisor) Sin trastornos mecnicos o
hidrulicos exteriores,
10.2 Dimetro nominal y rango de medicin especialmente: cavitacin
Calibracin de la salida Salida de impulsos
Dimetro nominal Qmax en kg/h (lb/h) Influencia de la salida Igual que la salida de impulsos
DN 15 (1/2) 0 8.000 (0 17.637) analgica sobre la precisin de 0,1 % del valor medido
DN 25 (1) 0 35.000 (0 77.162) medida
DN 50 (2) 0 90.000 (0 198.416)
DN 80 (3) 0 250.000 (0 551.156) 10.3.2 Desviacin del valor medido
DN 100 (4) 0 520.000 (0 ... 1.146.404) La desviacin del caudal medido se calcula de la siguiente
DN 150 (6) 0 860.000 (0 1.895.975) manera:

10.2.1 Rango de caudal recomendado Caso 1:


Lquidos: Si
El rango de caudal recomendado es de 5 % 100 % del Estabilidad del cero
Caudal
valor Q max. (precisin bsica / 100)
Se deben evitar los caudales < 1 % del valor Qmax. se considera que:
Desviacin del valor medido mxima:
Gases: precisin bsica en % del valor medido
La velocidad del flujo de gases en el tubo de medicin no Repetibilidad:
debe superar los 0,3 Mach (aprox. 100 m/s [328 pies/s]). 1/2 x precisin bsica en % del valor medido
A partir de una velocidad de flujo de aprox. 80 m/s
(262 pies/s), se debe calcular una desviacin mayor en la Caso 2:
repetibilidad. Si
El rango de caudal mximo de los gases depende de la Estabilidad del cero
Caudal <
densidad operativa. En la pgina www.abb.com/flow hay (precisin bsica / 100)
disponibles recursos de ayuda para el diseo. se considera que:
Desviacin del valor medido mxima:
(estabilidad del cero / valor medido) x 100 % del valor
medido
Repetibilidad:
1/2 x (estabilidiad del cero / valor medido) x 100 % del
valor medido

68 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


10.3.3 Estabilidad del cero

Dimetro nominal kg/h (lb/h)


DN 15 (1/2) 0,64 (1,41)
DN 25 (1) 2,16 (4,76)
DN 50 (2) 7,20 (15,87)
DN 80 (3) 20 (44)
DN 100 (4) 41,6 (91,7)
DN 150 (6) 68,8 (151,68)

10.3.4 Influencia de la temperatura del fluido


Para el caudal, inferior al 0,0015 % del valor Q max / 1 K.
Fig. 35: Clculo de la desviacin del valor medido con Para la densidad, inferior a 0,0001 kg/dm3 / 1 K.
FCB350 DN15 (ejemplo)
10.3.5 Influencia de la presin operativa
Dinmica de Caudal Desviacin mxima
medicin del valor medido Dimetro nominal Caudal [% del valor Densidad
100:1 80 kg/h (176,4 lb/h) 0,8 % del valor medido medido / bar] [kg/dm 3 / bar]
50:1 160 kg/h (352,7 lb/h) 0,4 % del valor medido DN 15 (1/2) -0,002 Ninguna
10:1 800 kg/h (1763,7 lb/h) 0,1 % del valor medido DN 25 (1) -0,013 0,00035
2:1 4000 kg/h (8818,5 lb/h) 0,1 % del valor medido DN 50 (2) -0,010 0,00027
1:1 8000 kg/h (17637 lb/h) 0,1 % del valor medido DN 80 (3) -0,006 0,00019
DN 100 (4) -0,009 0,00024
Desviacin del valor medido y precisin bsica para lquidos DN 150 (6) -0,035 0,00045

FCx330 FCx350
Caudal msico 0,4 % del valor 0,15 % del valor
medido medido
0,25 % del valor 0,1 % del valor
medido medido (opcional)
Caudal volumtrico 0,4 % del valor
0,15 % del valor
medido
medido
0,25 % del valor
medido
Densidad 0,010 kg/l 1) 0,002 kg/l 1)
0,001 kg/l 2)
0,0005 kg/l (opcional) 3)
Reproducibilidad 0,002 kg/l 1)
para la densidad 0,002 kg/l 0,001 kg/l 2)
0,00025 kg/l (opcional)
3)

Temperatura 1K 0,5 K

1) Para el rango de densidad 0,5 1,8 kg/dm


2) Igual que la indicada en 1 y para el rango de temperatura de fluido -10 50 C
(14 122 F)
3) Igual que la indicada en 2 y tras un ajuste de campo en condiciones de
funcionamiento

Desviacin del valor medido y precisin bsica para gases

FCx330 FCx350
Caudal msico 1 % del valor 0,5 % del valor
medido medido
Temperatura 1K 0,5 K

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 69


10.4 Datos tcnicos 10.4.4 Conexiones a proceso
10.4.1 Prdida de presin Diseo bridado segn EN / ASME / JIS
Tri-Clamp segn DIN 32676 (ISO 2852)
DN 15 100 (1/2 4): lnea 3
BPE Tri-Clamp
DN 15 100 (1/2 4)

10.4.5 Presin nominal


PN 16, PN 40, PN 100, PN 160
CL 150, CL 300, CL 600, CL 900, CL 1500

La presin de servicio mxima permitida depende de la


conexin a proceso utilizada, la temperatura del fluido, los
tornillos y del material de las juntas.

10.4.6 Carcasa como dispositivo de proteccin (opcional)


Estndar:
Presin de estallido 60 bar (870 psi)

Opcional:
Presin de estallido elevada hasta 100 bar (1450 psi),
posible para los dimetros nominales DN15 ... DN100
(1/2" 4").
Presin de estallido elevada hasta 150 bar (2175 psi),
posible para los dimetros nominales DN15 ... DN80
(1/2" 3").
Hay conexiones de lavado bajo pedido.

10.4.7 Directiva de equipos apresin


Fig. 36: Curva de prdida de presin (medida con agua, Evaluacin de conformidad segn la categora III, grupo de
viscosidad: 1 mPas) fluidos 1, gas
Asegrese de que el material de la tubera de medida sea
10.4.2 Rango de viscosidad resistentes a los efectos corrosivos del fluido.
En el caso de viscosidades dinmicas 1 Pas (1000 mPas =
1000 cP), pngase en contacto con ABB.

10.4.3 Lmites de temperatura C (F)

IMPORTANTE (NOTA)
Si el dispositivo se utiliza en zonas potencialmente explosivas,
se debern observar las especificaciones de temperatura
adicionales del captulo "Datos tcnicos relevantes para la
proteccin contra explosiones".

Rango de temperatura del fluido


FCx330: -50 160 C (-58 320 F)
FCx350: -50 200 C (-58 392 F)

Rango de temperatura ambiente


Estndar: -20 60 C (-4 140 F)
Opcional: -40 60 C (-40 140 F)

70 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


10.4.8 Materiales para el transmisor

Caja
Metal ligero fundido, pintado
Color de la carcasa
Parte central: RAL 7012
Tapa: RAL 9002
Espesor de la capa de pintura: 80 120 m

10.4.9 Materiales del sensor de caudal

Partes mojadas
Acero inoxidable
1.4404 (AISI 316L) o 1.4435 (AISI 316L) Fig. 38: Brida ASME de acero inoxidable 1.4571 / 1.4404
Acero inoxidable pulido (316Ti / 316L) hasta DN 200 (8)
1.4404 (AISI 316L) o 1.4435 (AISI 316L) con certificado de material
del sensor de caudal conforme a EHEDG (AISI 316L)
Nickel-Alloy C4 1) (2.4610) o Nickel-Alloy C22 1) (2.4602)
Opcional: fabricacin conforme a NACE MR0175 y MR0103 (ISO 15156)

Carcasa
Acero inoxidable 1.4404 (AISI 316L),1.4301 (AISI 304), 1.4308
(ASTM CF8)
1) Hastelloy C es una marca registrada de Haynes International Nickel-Alloy C4 y
C22 son equivalentes a Hastelloy C4 y Hastelloy C22.

10.4.10 Cargas del material de las conexiones a proceso

Diseo Dimetro PSmax TSmax TSmin Fig. 39: Brida DIN de Nickel-Alloy C4 (2.4610) o Nickel-Alloy C22
nominal (2.4602) hasta DN 200 (8)

Racor roscado (DIN DN 15 40 40 bar 140 C -40 C


11851) (1/2 1 1/2) (580 psi) (284 F) (-40 F)
DN 50 100 25 bar 140 C -40 C
(2 4) (363 psi) (284 F) (-40 F)
Tri-Clamp DN 15 50 16 bar 120 C -40 C
(DIN 32676) (1/2 2) (232 psi) (248 F) (-40 F)
DN 65 100 10 bar 120 C -40 C
(2 1/2 4) (145 psi) (248 F) (-40 F)

10.4.11 Curvas de carga del material de los aparatos


bridados

Fig. 40: Brida ASME de Nickel-Alloy C4 (2.4610) o Nickel-Alloy C22


(2.4602) hasta DN 200 (8)

Fig. 37: Brida DIN de acero inoxidable 1.4571 / 1.4404 (316Ti / 316L)
hasta DN 200 (8)

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 71


11 Datos tcnicos - Transmisor 11.2.7 Versin de caja

11.1 Generalidades Carcasa


Metal ligero fundido, pintado
Color de la carcasa
Parte intermedia: RAL 7012
Tapa: RAL 9002
Espesor de la capa de pintura: 80 120 m

11.2.8 Medicin de caudal de avance / retorno


El sentido de flujo se indica mediante flechas (en la pantalla
LCD del transmisor) y la salida de contacto digital (si est
programada).

11.2.9 Indicador LCD


Fig. 41: Transmisor FCT3xx en caja de campo Indicador LCD, 2 lneas, con pantalla retroiluminada.
Ambas lneas de la pantalla LCD se pueden configurar
11.2 Datos tcnicos libremente.
11.2.1 Rango de medida Se pueden indicar los siguientes valores:
El rango de medida es ajustable entre 0,01 1 Qmax. Caudal msico
Caudal volumtrico
11.2.2 Tipo de proteccin Densidad o temperatura
IP 65 / IP 67, NEMA 4X Totalizacin de caudal, 7 dgitos con contador de
desbordamiento e indicacin de la unidad fsica para la
11.2.3 Conexin elctrica masa o el volumen.
Racor atornillado para cables M20 x 1,5 o 1/2 NPT.
En caso del modelo de diseo remoto, la longitud mxima del En el caso de los modelos de diseo remoto, la caja del
cable de seal no debe ser superior a 50 m (164 ft) (cables transmisor puede girarse unos 180 en cada direccin. El
ms largos: bajo demanda). indicador LCD puede girarse en cuatro posiciones para
optimizar la legibilidad de la pantalla.
11.2.4 Suministro de energa

Voltaje de alimentacin 100 230 V AC, 47 63 Hz


(Tolerancia -15 % / +10 %)
20,4 26,4 V AC, 47 63 Hz
20,4 31,2 V DC
(Ondulacin armnica: 5 %)
Consumo de potencia S 25 VA

11.2.5 Tiempo de reaccin


Como funcin escalonada del 0 ... 99 % (corresponde a 5 )
1s

11.2.6 Temperatura ambiente


Estndar: -20 60 C (-4 140 F)
Opcional: -40 60 C (-40 140 F)

En el caso de uso a temperaturas inferiores a -20 C (-4 F),


ya no se puede leer la pantalla y se recomienda utilizar el
sistema electrnico de manera que las vibraciones se
reduzcan al minimo posible.
La plena funcionalidad se obtiene a temperaturas superiores a
-20 C (-4 F).

72 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


11.2.10 Mando Salida de corriente 1 pasiva
El control del transmisor y la introduccin de los paramtros Seal de salida Pasiva, 4 20 mA
se efectan a travs de las tres teclas de control del Carga 0 R B 600
transmisor. Alternativamente, es posible programar el aparato Tensin de fuente 12 V Uq 30 V
con un puntero magntico cuando la caja del transmisor est Inseguridad de < 0,1 % del valor medido
cerrada. medicin
Terminales 31 / 32
Valores medidos Caudal msico, flujo volumtrico, densidad y
temperatura (libremente programable
mediante el software)

Salida de corriente 2 pasiva


Seal de salida Pasiva, 4 20 mA
Carga 0 R B 600
Tensin de fuente 12 V Uq 30 V
Inseguridad de < 0,1 % del valor medido
medicin
Fig. 42: Manejo con puntero magntico Terminales 33 / 34
1 FRAM (enchufable) | 2 Puntero magntico Valores medidos Caudal msico, flujo volumtrico, densidad y
temperatura (libremente programable

11.2.11 Seguridad de datos mediante el software)

El almacenamiento de datos se realiza mediante la memoria


FRAM interna del transmisor. Los datos se almacenan durante
un perodo de tiempo de ms de 10 aos, sin alimentacin
elctrica adicional.
El reconocimiento de hardware y software se realiza de
acuerdo con la recomendacin NAMUR NE53.

IMPORTANTE (NOTA)
El aparato cumple la Directiva CEM 2004/108/CE y la
Directiva de baja tensin 2006/95/CE (EN 61010-1).
Fig. 43: Tensin de fuente permitida en funcin de la resistencia de
11.3 Especificaciones elctricas la carga a I max = 22 mA
1 Rango permitido
11.3.1 Salidas de corriente

Salida de corriente 1, activa


Seal de salida activa, 0 20 mA 4 20 mA, conmutable
Carga 0 R B 560
Inseguridad de < 0,1 % del valor medido
medicin
Terminales 31 / 32
Valores medidos Caudal msico, flujo volumtrico, densidad y
temperatura (libremente programable Fig. 44
mediante el software)
IMPORTANTE (NOTA)
Informacin de fallo segn la recomendacin NAMUR NE43

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 73


11.3.2 Salida de impulsos 11.3.4 Entradas de contacto digitales
Salida de impulsos normalizada (mx. 5 kHz) con valor de La funcin de conmutacin puede programarse mediante el
impulso ajustable entre 0,001 1000 impulsos por unidad. El software.
ancho de impulso es ajustable entre 0,1 ... 2000 ms. La salida
est separada galvnicamente de las salidas de corriente. Funcin de Desconexin externa de la salida
conmutacin Puesta a cero externa del totalizador
Pasiva Activa Entrada "On" 16 V UKL 30 V
Tensin de servicio 16 V UCEH 30 V DC 16 V U 30 V DC Entrada "Off" 0 V UKL 2 V
0 V UCEL 2 V Carga 150 Resistencia interna Ri = 2 k
Corriente de servicio 0 mA I CEH 0,2 mA - Terminales 81 / 82
2 mA I CEL 220 mA
fmx 5 kHz 5 kHz Todas las entradas y salidas estn separadas galvnicamente
Ancho de impulso 0,1 2000 ms 0,1 2000 ms entre s.
Terminales 51 / 52 51 / 52

IMPORTANTE (NOTA)
Si se utiliza un totalizador mecnico recomendamos utilizar un
ancho de impulso de 30 ms y una frecuencia lmite [fmx] de
3 kHz.

11.3.3 Salidas de contacto digitales


La funcin de conmutacin puede programarse mediante el
software.

Funcin de Control del sistema (contacto de reposo o


conmutacin contacto de cierre).
Directo / Inverso (cerrada en el caso de
caudal directo)
Alarma Mn./Mx. (contacto de reposo o
contacto de cierre)
Salida "cerrada" 0 V UCEL 2 V
2 mA I CEL 220 mA
Salida "abierta" 16 V UCEH 30 V DC
0 mA I CEH 0,2 mA
Terminales 41 / 42

74 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


Change from two to one c olumn

12 Datos tcnicos relevantes para la proteccin contra explosiones conforme a


ATEX / IECEx / NEPSI
12.1 Especificaciones elctricas
12.1.1 Resumen de las diferentes opciones de salida

Versiones ATEX, IECEx, NEPSI Zona 2 ATEX, IECEx, NEPSI Zona 1


Versin I Salida de corriente 1: activa Salida de corriente 1: activa
Opcin de salida A1, A2, H1, H2 Salida de corriente 2: pasiva Salida de corriente 2: pasiva
en la referencia Salida de impulsos: activa / pasiva, conmutable Salida de impulsos: pasiva
Entrada y salida de contacto: pasiva Entrada y salida de contacto: pasiva
Versin II Salida de corriente 1: pasiva
Opcin de salida A3, H3 Salida de corriente 2: pasiva
en la referencia Salida de impulsos: pasiva
Entrada y salida de contacto: pasiva

12.1.2 Versin I: salidas de corriente activa / pasiva

Modelo: FCx3xx-A1, FCT3xx-A1 o FCx3xx-A2, FCT3xx-A2 o FCx3xx-S2, FCT3xx-S2


Tipo de proteccin Valores generales Tipo de proteccin Tipo de proteccin contra explosiones "ib"
contra explosiones de contra explosiones (Zona 1)
nA (Zona 2) funcionamiento "e" (Zona 1)
Salida de corriente 1, activa Ui (V) I i (mA) Ub (V) I b (mA) U (V) I (mA) Uo Io Po Co Co pa Lo
Terminales 31 / 32 (V) (mA) (mW) (nF) (nF) (mH)
El terminal 32 est 20 100 500 217 0 3,8
conectado a "PA" 30 30 30 30 60 35 Ui Ii Pi Ci Ci pa Li
(V) (mA) (mW) (nF) (nF) (mH)
60 100 500 2,4 2,4 0,17
Salida de corriente 2, 30 30 30 30 60 35 30 100 760 2,4 2,4 0,17
pasiva
Terminales 33 / 34
El terminal 34 est
conectado a "PA"
Salida de impulsos, pasiva 30 65 30 65 60 35 15 30 115 2,4 2,4 0,17
Terminales 51 / 52
Salida de contacto, pasiva 30 65 30 65 60 35 15 30 115 2,4 2,4 0,17
Terminales 41 / 42
Entrada de contacto, pasiva 30 10 30 10 60 35 30 60 500 2,4 2,4 0,17
Terminales 81 / 82

Todas las entradas y salidas estn aisladas galvnicamente entre s y del suministro de energa. Solo las salidas de corriente 1 y
2 no estn aisladas galvnicamente entre s en la versin para Zona 1.

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 75


12.1.3 Versin II: salidas de corriente pasiva / pasiva

Modelo: FCx3xx-A1, FCT3xx-A1 o FCx3xx-A2, FCT3xx-A2 o FCx3xx-S2, FCT3xx-S2


Tipo de proteccin Tipo de proteccin Tipo de proteccin contra explosiones "ia"
Valores generales
contra explosiones contra explosiones (Zona 1)
de funcionamiento
nA (Zona 2) "e" (Zona 1)
Ui (V) I i (mA) Ub (V) I b (mA) U (V) I (mA) Ui Ii Pi Ci Ci pa Li
(V) (mA) (mW) (nF) (nF) (mH)
Salida de corriente 1, 30 30 30 30 60 35 60 300 2000 0,47 0,47 0,17
pasiva
Terminales 31 / 32
Salida de corriente 2, 30 30 30 30 60 35 60 300 2000 0,47 0,47 0,17
pasiva
Terminales 33 / 34
Salida de impulsos, 30 65 30 65 60 35 60 300 2000 0,47 0,47 0,17
pasiva
Terminales 51 / 52
Salida de contacto, 30 65 30 65 60 35 60 300 2000 0,47 0,47 0,17
pasiva
Terminales 41 / 42
Entrada de contacto, 30 10 30 10 60 35 60 300 2000 0,47 0,47 0,17
pasiva
Terminales 81 / 82

Todas las entradas y salidas estn aisladas galvnicamente entre s y del suministro de energa.
Change from one to tw o c olumns

12.1.4 Condiciones especiales de conexin En el estado de entrega, los racores atornillados para cables
Los circuitos elctricos de salida estn diseados de manera estn diseados en color negro. En caso de que las salidas de
que puedan conectarse a circuitos con o sin seguridad seal se conecten a circuitos intrnsicamente seguros, se
intrnseca. recomienda que para las entradas de cable correspondientes
No estn permitidas combinaciones de circuitos elctricos con se utilicen las tapas de color azul claro suministradas.
y sin seguridad intrnseca. Al cambiar el tipo de proteccin 'e'
se deben seguir las instrucciones del captulo 6.6.7. IMPORTANTE (NOTA)
A lo largo de la seccin de la lnea de los circuitos Si el conductor protector (PE) se conecta en el espacio de
intrnsicamente seguros deber establecerse una conexin conexin del caudalmetro, debe asegurarse de que en la zona
equipotencial. potencialmente explosiva no pueda producirse una diferencia
La tensin de clculo de los circuitos sin seguridad intrnseca de potencial peligrosa entre el conductor protector (PE) y la
es UM = 60 V. conexin equipotencial (PA).
Para conectar un amplificador NAMUR, la salida de contacto y
la salida de impulsos (terminales 41 / 42, 51 / 52) pueden
conectarse internamente de manera que funcionen como
contacto NAMUR.
Change from two to one c olumn

76 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


12.2 Modelo de sensor de caudal FCB3xx / FCH3xx
12.2.1 Clase de temperatura

Modelo FCx3xx-A1Y o FCx3xx-S1Y en Zona 1


Temperatura ambiente 40 C (104 F) 50 C (122 F) 60 C (140 F)

Clase de temperatura
T1 200 C (392 F) 200 C (392 F) 200 C (392 F)
T2 200 C (392 F) 200 C (392 F) 200 C (392 F)
T3 185 C (365 F) 180 C (356 F) 180 C (356 F)
T4 125 C (257 F) 120 C (248 F) 120 C (248 F)
T5 85 C (185 F) 85 C (185 F) 75 C (167 F)
T6 65 C (149 F) 65 C (149 F) 60 C (140 F)

Modelo FCx3xx-A2Y o FCx3xx-S2Y en Zona 2


Temperatura ambiente 40 C (104 F) 50 C (122 F) 60 C (140 F)

Clase de temperatura
T1 200 C (392 F) 200 C (392 F) 180 C (356 F)
T2 200 C (392 F) 200 C (392 F) 180 C (356 F)
T3 180 C (356 F) 180 C (356 F) 180 C (356 F)
T4 115 C (239 F) 115 C (239 F) 115 C (239 F)
T5 80 C(176 F) 80 C(176 F) 75 C (167 F)
T6 60 C (140 F) 60 C (140 F) 60 C (140 F)

Condiciones ambientales y de proceso:


T amb -20 ... 60 C (-4 ... 140 F)
T amb, optional -40 ... 60 C (-40 ... 140 F) (solo para dispositivos de diseo compacto)
T medium -50 ... 200 C (-58 ... 392 F)
Clase de IP 65, IP 67 y NEMA 4X
proteccin

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 77


12.2.2 Homologacin de proteccin contra explosiones ATEX / IECEx / NEPSI
Segn la versin del sensor de caudal (diseo compacto o remoto), se aplica una designacin especfica conforme a ATEX,
IECEx o NEPSI.

IMPORTANTE (NOTA)
ABB se reserva el derecho de realizar modificaciones a la designacin de proteccin contra explosiones. La codificacin exacta
se indica en la placa de caractersticas de los dispositivos.

Modelo FCx3xx-A2A o FCx3xx-S2A (diseo remoto en Zona 2)


Homologacin Designacin Comentarios
ATEX II 3 G Ex nA IIC T6 T2 -
II 2 D Ex tD IIIC T85C .. Tmedium
IECEx o NEPSI Ex nA IIC T6 .. T2 Gc -
Ex tb IIIC T85C Tmedium

Modelo FCx3xx-A1A o FCx3xx-S1A (diseo remoto en Zona 1)


Homologacin Designacin Comentarios
ATEX II 1 G Ex ia IIC T6 T2 -
II 1 D Ex ia IIIC T85C Tmedium
IECEx o NEPSI T2 Ga -
Ex ia IIIC T85C .. Tmedium Da

Modelo FCx3xx-A2Y o FCx3xx-S2Y (diseo compacto en Zona 2)


Homologacin Designacin Comentarios
ATEX II 3 G Ex nA nR IIC T6 T2 -
II 2 D Ex tD IIIC T85C .. Tmedium
IECEx o NEPSI Ex nA nR IIC T6 .. T2 Gc -
Ex tb IIIC T85C Tmedium Db

Modelo FCx3xx-A1Y o FCx3xx-S1Y (diseo compacto en Zona 1)


Homologacin Designacin Comentarios
ATEX
Versin II II 1/2 G Ex d e ia IIC T6 .. T2 2 salidas analgicas pasivas, salidas "ia" / "e", segn el modo
II 2 D Ex ia tb IIIC T85C .. Tmedium de conexin especificado por el usuario
Versin I II 1/2 G Ex d e ia ib IIC T6 .. T2 or II 1/2 G Ex d e ia IIC
T6 .. T2 Salidas analgicas activa / pasiva, salidas "ib" / "e", segn el
II 2 D Ex ia ia tb IIIC T85C .. Tmedium or II 2 D Ex ia tb IIIC modo de conexin especificado por el usuario
T85C .. Tmedium
IECEx o NEPSI
Versin II Ex d e ia IIC T6 .. T2 Ga/Gb 2 salidas analgicas pasivas, salidas "ia" / "e", segn el modo
Ex ia tb IIIC T85C .. Tmedium de conexin especificado por el usuario
Versin I Ex d e ia ib IIC T6 .. T2 Ga/Gb or Ex d e ia IIC T6 .. T2 Ga/Gb Salidas analgicas activa / pasiva, salidas "ib" / "e", segn el
Ex ia ib tb IIIC T85C .. Tmedium or Ex ia tb IIIC T85C .. modo de conexin especificado por el usuario
Tmedium

78 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


12.3 Transductor de diseo remoto Modelo FCT300

Condiciones ambientales y de proceso:


T amb -20 ... 60 C (-4 ... 140 F)
Clase de IP 65, IP 67 y NEMA 4X / Tipo 4X
proteccin

12.3.1 Homologacin de proteccin contra explosiones ATEX / IECEx / NEPSI


Segn la versin del sensor de caudal (diseo compacto o remoto), se aplica una designacin especfica conforme a ATEX,
IECEx o NEPSI.

IMPORTANTE (NOTA)
ABB se reserva el derecho de realizar modificaciones a la designacin de proteccin contra explosiones. La codificacin exacta
se indica en la placa de caractersticas de los dispositivos.

Modelo FCT3xx-Y0 (transductor montado fuera de la zona de proteccin contra explosiones, sensor de caudal en Zona 0, 1 o 2)
Homologacin Designacin Comentarios
ATEX II (1) G [Ex ia] IIC -
IECEx o NEPSI [Ex ia Ga] IIC -

Modelo FCT3xx-A2 o FCT3xx-S2 (transductor en Zona 2, sensor de caudal en Zona 0, 1 o 2)


Homologacin Designacin Comentarios
ATEX II 3(2) G Ex nA nR [ia] IIC T6 -
II 2 D Ex tb [ia] IIIC T85C
IECEx o NEPSI Ex nA nR [ia] IIC T6 Gc (Gb) -
Ex tb [ia] IIIC T85C Db

Modelo FCT3xx-A1 o FCT3xx-S1 (transductor en Zona 1, sensor de caudal en Zona 0, 1 o 2)


Homologacin Designacin Comentarios
ATEX
Versin II II 2 (1) G Ex d e ia IIC T6 2 salidas analgicas pasivas, salidas "ia" / "e", segn el
II 2 (1) D Ex ia tb IIIC T85C modo de conexin especificado por el usuario
Versin I II 2 (1) G Ex d e ib [ia] IIC T6 or II 2 (1) G Ex d e [ia] IIC T6 Salidas analgicas activa / pasiva, salidas "ib" / "e", segn
II 2 (1) D Ex ib tb [ia] IIIC T85C or II 2 (1) D Ex tb [ia] IIIC T85C el modo de conexin especificado por el usuario
IECEx o NEPSI
Versin II Ex d e ia IIC T6 Gb (Ga) 2 salidas analgicas pasivas, salidas "ia" / "e", segn el
Ex ia tb IIIC T85C Db (Da) modo de conexin especificado por el usuario
Versin I Ex d e ib [ia Ga] IIC T6 Gb or Ex d e [ia Ga] IIC T6 Gb Salidas analgicas activa / pasiva, salidas "ib" / "e", segn
Ex ib tb [ia Da] IIIC T85C Db or Ex tb [ia Da] IIIC T85C Db el modo de conexin especificado por el usuario

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 79


13 Datos tcnicos relevantes para la proteccin Ex segn cFMus
13.1 Resumen de las diferentes opciones de salida

Versiones Clase I Div. 2 Clase I Div. 1


Versin I Salida de corriente 1: activa Salida de corriente 1: activa
Opcin de salida A1, A2, H1, H2 Salida de corriente 2: pasiva Salida de corriente 2: pasiva
en la referencia Salida de impulsos: activa / pasiva, conmutable Salida de impulsos: pasiva
Entrada y salida de contacto: pasiva Entrada y salida de contacto: pasiva
Versin II Salida de corriente 1: pasiva
Opcin de salida A3, H3 Salida de corriente 2: pasiva
en la referencia Salida de impulsos: pasiva
Entrada y salida de contacto: pasiva

13.2 Datos elctricos para Div. 2 / Zona 2


13.2.1 Versin I: salidas de corriente activa / pasiva y versin II: salidas de corriente pasiva / pasiva

Modelo FCx3xx-F2, FCT3xx-F2


Tipo de proteccin contra explosiones NI
Umxo (V) Imxo
[mA]
Salida de corriente 1 30 30
Terminales 31 / 32
Salida de corriente 2 30 30
Terminales 33 / 34
Salida de impulsos 30 65
Terminales 51 / 52
Salida de contacto 30 65
Terminales 41 / 42
Entrada de contacto 30 10
Terminales 81 / 82

Todas las entradas y salidas estn aisladas galvnicamente entre s y del suministro de energa.

80 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


13.3 Datos elctricos para Div. 1 / Zona 1
13.3.1 Versin I: salidas de corriente activa / pasiva

Modelo FCx3xx-F1, FCT3xx-F1


Tipo de proteccin contra Tipo de proteccin con IS
explosiones sin IS
Umxo (V) Imxo Umxo (V) Imxo P o (mW) Co (nF) Co PA (nF) L 0 (mH)
[mA] [mA]
Salida de corriente 1, activa 30 30 20 100 500 217 0 3,8
Terminales 31 / 32 UMx (V) I Mx (mA) P i (mW) Ci (nF) Ci PA (nF) L i (mH)
60 100 500 2,4 2,4 0,17
Salida de corriente 2, pasiva 30 30 30 100 760 2,4 2,4 0,17
Terminales 33 / 34
Salida de impulsos, activa o pasiva 30 65 15 30 115 2,4 2,4 0,17
Terminales 51 / 52
Salida de contacto, pasiva 30 65 15 30 115 2,4 2,4 0,17
Terminales 41 / 42
Entrada de contacto, pasiva 30 10 30 60 500 2,4 2,4 0,17
Terminales 81 / 82

Todas las entradas y salidas estn aisladas galvnicamente entre s y del suministro de energa. Solo las salidas de corriente 1 y
2 no estn aisladas galvnicamente entre s.

13.3.2 Versin II: salidas de corriente pasiva / pasiva

Modelo FCx3xx-F1, FCT3xx-F1


Tipo de proteccin contra Tipo de proteccin con IS
explosiones sin IS
Umx (V) Imx (mA) Umx (V) Imx (mA) P i (mW) Ci (nF) Ci PA (nF) L i (mH)
Salida de corriente 1, pasiva 30 30 60 300 2000 0,47 0,47 0,17
Terminales 31 / 32
Salida de corriente 2, pasiva 30 30 60 300 2000 0,47 0,47 0,17
Terminales 33 / 34
Salida de impulsos, activa o pasiva 30 65 60 300 2000 0,47 0,47 0,17
Terminales 51 / 52
Salida de contacto, pasiva 30 65 60 300 2000 0,47 0,47 0,17
Terminales 41 / 42
Entrada de contacto, pasiva 30 10 60 300 2000 0,47 0,47 0,17
Terminales 81 / 82

Todas las entradas y salidas estn aisladas galvnicamente entre s y del suministro de energa.
Change from one to tw o c olumns

13.3.3 Condiciones especiales de conexin La seguridad intrnseca se mantiene siempre que durante la
Los circuitos elctricos de salida estn diseados de manera conexin de circuitos elctricos externos sin seguridad
que puedan conectarse a circuitos con o sin seguridad intrnseca no se supere la tensin de clculo UM = 60 V.
intrnseca.
No estn permitidas combinaciones de circuitos elctricos con IMPORTANTE (NOTA)
y sin seguridad intrnseca. Al cambiar el tipo de proteccin 'e' La caja del transmisor y del sensor de caudal debe conectarse
se deben seguir las instrucciones del captulo 6.7.5. al conductor de conexin equipotencial PA. El propietario
A lo largo de la seccin de la lnea de los circuitos debe asegurar que cuando se conecte el conductor protector
intrnsicamente seguros deber establecerse una conexin PE, no se produzcan diferencias de potencial entre el
equipotencial. conductor protector PE y la conexin equipotencial PA.
La tensin de clculo de los circuitos sin seguridad intrnseca
es UM = 60 V.
Change from two to one c olumn

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 81


13.4 Sensor de caudal Modelo FCB300 / FCH300
13.4.1 Clases de temperatura

Modelo FCx3xx-F1, en Clase I Div. 1


Temperatura ambiente 40 C (104 F) 50 C (122 F) 60 C (140 F)

Clase de temperatura
T1 200 C (392 F) 200 C (392 F) 200 C (392 F)
T2 200 C (392 F) 200 C (392 F) 200 C (392 F)
T3 185 C (365 F) 180 C (356 F) 180 C (356 F)
T4 125 C (257 F) 120 C (248 F) 120 C (248 F)
T5 85 C (185 F) 85 C (185 F) 75 C (167 F)
T6 65 C (149 F) 65 C (149 F) 60 C (140 F)

Modelo FCx3xx-F2, en Clase I Div. 2


Temperatura ambiente 40 C (104 F) 50 C (122 F) 60 C (140 F)

Clase de temperatura
T1 200 C (392 F) 200 C (392 F) 180 C (356 F)
T2 200 C (392 F) 200 C (392 F) 180 C (356 F)
T3 180 C (356 F) 180 C (356 F) 180 C (356 F)
T4 115 C (239 F) 115 C (239 F) 115 C (239 F)
T5 80 C (176 F) 80 C (176 F) 75 C (167 F)
T6 60 C (140 F) 60 C (140 F) 60 C (140 F)

Condiciones ambientales y de proceso:


T amb -20 ... 60 C (-4 ... 140 F)
T amb, optional -40 ... 60 C (-40 ... 140 F) (solo para dispositivos de diseo compacto)
T medium -50 ... 200 C (-58 ... 392 F)
Clase de IP 65, IP 67 y NEMA 4X / Tipo 4X
proteccin

IMPORTANTE (NOTA)
En la versin de diseo remoto, la longitud del cable de seal entre el sensor de caudal y el transductor debe ser de un mnimo
de 5 m (16,4 ft). Deben colocarse juntas de conducto cada 18 in. (45 cm).

82 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


13.4.2 Homologacin de proteccin contra explosiones cFMus
Segn la versin del sensor de caudal (diseo compacto o remoto), se aplica una designacin especfica conforme a FM.

IMPORTANTE (NOTA)
ABB se reserva el derecho de realizar modificaciones a la designacin de proteccin contra explosiones. La codificacin exacta
se indica en la placa de caractersticas de los dispositivos.

Modelo FCx3xx-F2A (diseo remoto en Zona 2, Div. 2)


Homologacin Designacin Comentarios
FM (marking US) NI: CL I,II,III, DIV 2, GPS ABCDEFG -
CL I, ZN2, AEx nA IIC T6 ... T2
ZN 21 AEx tb IIIC T85C ... T165C
FM (marking Canada) NI: CL I, II, III, Div 2 GPS ABCDEFG -
Ex nA IIC T6 T2

Modelo FCx3xx-F2Y (diseo remoto en Zona 2, Div. 2)


Homologacin Designacin Comentarios
FM (marking US) NI: CL I, II, III, Div 2 GPS ABCDEFG -
DIP: CL II Div 1 GPS EFG
DIP : CL III, Div 1,2
CL I, ZN 2, AEx nA nR IIC T6 ... T2
ZN 21 AEx tb IIIC T85C ... T165C
FM (marking Canada) NI: CL I, II, III, Div 2 GPS ABCDEFG -
DIP: CL II Div 1 GPS EFG
DIP : CL III, Div 1,2
Ex nA nR IIC T6 T2

Modelo FCx3xx-F1A (diseo remoto en Zona 1, Div. 1)


Homologacin Designacin Comentarios
FM (marking US) CL I, II, III, Div 1, GPS ABCDEFG -
CL I, ZN0, AEx ia IIC T6 ... T2
ZN 20 AEx ia IIIC T85C ... T165C
FM (marking Canada) CL I, II, III, Div 1, GPS ABCDEFG -
Ex ia IIC T6 T2

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 83


Modelo FCx3xx-F1Y (diseo compacto en Zona 1, Div. 1)
Homologacin Designacin Comentarios
FM (marking US)
Versin II IS: CL I, Div 1, GPS ABCD 2 salidas analgicas pasivas, salidas "ia" / "e", segn el
NI: CL I,II,III, DIV2, GPS ABCDEFG modo de conexin especificado por el usuario
XP: CL I, Div 1, GPS ABCD
DIP: CL II, Div 1, GPS EFG
DIP: CL III, Div 1, 2
CL I, ZN1, AEx d ia IIC T6
ZN 21 AEx ia tb IIIC T85C to T165C
Versin I IS: CL I, Div 1, GPS ABCD Salidas analgicas activa / pasiva, salidas "ib" / "e", segn
NI: CL I, II, III, DIV2, GPS ABCDEFG el modo de conexin especificado por el usuario
XP: CL I, Div 1, GPS ABCD
DIP: CL II, Div 1, GPS EFG
DIP: CL III, Div 1, 2
CL I, ZN 1, AEx d ia ib IIC T6 or CL I, ZN 1, AEx d ia IIC
T6
ZN 21 AEx ib ia tb IIIC T85C or ZN21 AEx tb ia IIC T6
FM (marking Canada) -
Versin II IS: CL I, Div 1, GPS ABCD 2 salidas analgicas pasivas, salidas "ia" / "e", segn el
NI: CL I,II,III, Div 2, GPS ABCDEFG modo de conexin especificado por el usuario
XP: CL I, Div 1, GPS BCD
DIP CL II, Div 1, GPS EFG
DIP CL III, Div 1, 2
Ex d ia IIC T6
Versin I IS: CL I, Div 1, GPS ABCD Salidas analgicas activa / pasiva, salidas "ib" / "e", segn
NI: CL I, II, III, Div 2, GPS ABCDEFG el modo de conexin especificado por el usuario
XP: CL I, Div 1, GPS BCD
DIP: CL II, Div 1, GPS EFG
DIP: CL III, Div 1, 2
Ex d ia ib IIC T6 or Ex d ia IIC T6

84 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


13.5 Transmisor de diseo remoto Modelo FCT300

Condiciones ambientales y de proceso:


T amb -20 ... 60 C (-4 ... 140 F)
Clase de proteccin IP 65, IP 67 y NEMA 4X / Type 4X

13.5.1 Homologacin Ex cFMus


Segn el diseo del sensor de caudal (compacto o remoto) se aplicar una codificacin especfica segn la norma FM (Factory
Mutual System).

IMPORTANTE (NOTA)
ABB se reserva modificaciones de la codificacin Ex. La codificacin exacta se indica en la placa de caractersticas de los
aparatos suministrados.

Modelo FCT3xx-Y0 (transmisor en general purpose y sensor de caudal en Zona 2, Div 2 o Zona 0, 1 Div 1)
Homologacin Marca Observacin
FM (marking US) NI: CL I, II, III, Div 2 GPS ABCDEFG -
DIP: CL II Div 1 GPS EFG
DIP: CL III, Div 1,2
FM (marking Canada) NI: CL I, II, III, Div 2 GPS ABCDEFG -
DIP: CL II Div 1 GPS EFG
DIP: CL III, Div 1,2

Modelo FCT3xx-F2 (transmisor y sensor de caudal instalados en Zona 2, Div 2)


Homologacin Marca Observacin
FM (marking US) NI: CL I, II, III, Div 2 GPS ABCDEFG -
DIP: CL II Div 1 GPS EFG
DIP: CL III, Div 1,2
CL I, ZN 2, AEx nA nR [ia] IIC T6
ZN 21 AEx tb [ia] IIIC T85C
FM (marking Canada) NI: CL I, II, III, Div 2 GPS ABCDEFG -
DIP: CL II Div 1 GPS EFG
DIP: CL III, Div 1,2
Ex nA nR [ia] IIC T6

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 85


Modelo FCT3xx-F1 (transmisor instalado en Zona 1, Div 1, sensor de caudal en la zona 0, 1 2, Div 2 o Div 1)
Homologacin Marca Observacin
FM (marking US)
Versin II IS: CL I, Div 1, GPS ABCD 2 salidas analgicas pasivas, salidas "ia" / "e", segn el
NI: CL I, II, III, DIV2, GPS ABCDEFG modo de conexin especificado por el usuario.
XP: CL I, Div 1, GPS ABCD
DIP: CL II, Div 1, GPS EFG
DIP: CL III, Div 1, 2
CL I, ZN1, AEx d ia IIC T6
ZN 21 AEx ia tb IIIC T85C
Versin I IS: CL I, Div 1, GPS ABCD Salidas analgicas activas / pasivas, salidas "ib" / "e",
NI: CL I, II, III, DIV2, GPS ABCDEFG segn el modo de conexin especificado por el usuario
XP: CL I, Div 1, GPS ABCD
DIP: CL II, Div 1, GPS EFG
DIP: CL III, Div 1, 2
CL I, ZN 1, AEx d ib [ia] IIC T6 or CL I, ZN1, AEx d [ia] IIC T6
ZN21 AEx ib tb [ia] IIIC T85C or ZN21 AEx tb [ia] IIC T6
FM (marking Canada)
Versin II IS: CL I, Div 1, GPS ABCD 2 salidas analgicas pasivas, salidas "ia" / "e", segn el
NI: CL I, II, III, Div 2, GPS ABCDEFG modo de conexin especificado por el usuario.
XP: CL I, Div 1, GPS BCD
DIP: CL II, Div 1, GPS EFG
DIP: CL III, Div 1, 2
Ex d ia IIC T6
Versin I IS: CL I, Div 1, GPS ABCD Salidas analgicas activas / pasivas, salidas "ib" / "e",
NI: CL I, II, III, Div 2, GPS ABCDEFG segn el modo de conexin especificado por el usuario
XP: CL I, Div 1, GPS BCD
DIP: CL II, Div 1, GPS EFG
DIP CL III, Div 1, 2
Ex d ib [ia] IIC T6 or Ex d [ia] IIC T6

Change from one to tw o c olumns

Marcas registradas
HART es una marca registrada de HART Communication Foundation
Hastelloy C-4 es una marca registrada de Haynes International
Hastelloy C-22 es una marca registrada de Haynes International

Change from two to one c olumn


Hastelloy C-276 es una marca registrada de Haynes International

86 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


Change from two to one c olumn

14 Anexo
14.1 Homologaciones y certificados

Marca CE El modelo de aparato comercializado por nuestra empresa cumple las normas de las siguientes Directivas CE:
Directiva CEM 2004/108/CE
Directa 2006/95/CE sobre bajas tensiones
Directiva de Equipos a Presin (PED) 97/23/CE
Directiva ATEX 94/9/CE
Proteccin contra Marca para indicar el uso conforme al fin previsto en zonas potencialmente explosivas, de acuerdo con:
explosin

Directiva ATEX (marca adicional a la marca CE)

IECEx Normas IEC

NEPSI

cFMus Approvals for Canada and United States

IMPORTANTE (NOTA)
Todas las documentaciones, declaraciones de conformidad y certificados pueden descargarse de la pgina web
de ABB.
www.abb.com/flow

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 87


88 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350
CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 89
90 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350
CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 91
14.2 Installation diagram 3KXF002126G0009
Page 1 of 4

92 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


Page 2 of 4

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 93


Page 3 of 4

94 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


Page 4 of 4

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 95


Declaracin sobre la contaminacin de aparatos y componentes

La reparacin y/o el mantenimiento de aparatos y componentes se realizar solamente cuando el impreso de declaracin est
rellenado completamente.
En caso contrario es posible rechazar el envo. Esta declaracin debe ser rellenada y firmada, exclusivamente, por el personal
tcnico autorizado del propietario.

Datos referentes al cliente:


Empresa:
Direccin:
Persona de contacto: Telfono:
Fax: Email:

Datos referentes al equipo:


Tipo: N. de serie:
Motivo del envo / descripcin del defecto:

Ha sido utilizado el aparato para realizar trabajos con sustancias que pueden causar un riesgo o peligro para la salud?
S No
En el caso afirmativo indique el tipo de contaminacin! (mrquese con una cruz)
biolgico corrosivo/irritante inflamable (ligera /altamente inflamable)
txico explosivo otras sustancias nocivas
radioactivo

Qu sustancias han estado en contacto con el aparato?


1.
2.
3.

Confirmamos que los aparatos / componentes enviados han sido limpiados y estn libres de cualquier sustancia txica o
peligrosa segn el Reglamento de Sustancias Peligrosas.

Ciudad, fecha Firma y sello

96 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


Notas

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 97


Notas

98 OI/FCB300/FCH300-ES Rev. F | CoriolisMaster FCB330, FCB350, FCH330, FCH350


Notas

CoriolisMaster FCB330, FCB350, FCH330, FCH350 | OI/FCB300/FCH300-ES Rev. F 99


Contacto

ASEA BROWN BOVERI, S.A. Nota

OI/FCB300/FCH300-ES Rev. F 05.2014


Nos reservamos el derecho a realizar cambios
Process Automation
tcnicos o modificar el contenido de este
Divisin Instrumentacin documento sin previo aviso. En relacin a las
C/San Romualdo 13 solicitudes de compra, prevalecen los detalles
28037 Madrid acordados. ABB no acepta ninguna
responsabilidad por cualquier error potencial o
Spain
posible falta de informacin de este documento.
Tel: +34 91 581 93 93
Fax: +34 91 581 99 43 Nos reservamos los derechos de este documento,
los temas que incluye y las ilustraciones que
contiene. Cualquier reproduccin, comunicacin a
ABB S.A.
terceras partes o utilizacin del contenido total o
Process Automation parcial est prohibida sin consentimiento previo
Av. Don Diego Cisneros por escrito de ABB.
Edif. ABB, Los Ruices
Copyright 2014 ABB
Caracas
Todos los derechos reservados