INFORME FINAL
MAYO DE 2014
1702
Informe de repotenciacin Ingenieros Emetres Per SAC
INDICE
INDICE ...........................................................................................................................................2
I. LINEA DE TRANSMISION ..............................................................................................5
1. ANTECEDENTES............................................................................................................5
2. OBJETIVO..........................................................................................................................5
3. NORMATIVA....................................................................................................................6
4. SITUACIN.......................................................................................................................6
5. CARACTERSTICAS GENERALES DE LA LNEA................................................7
6. DATOS DEL CONDUCTOR..........................................................................................7
7. CAPACIDAD MXIMA DE TRANSPORTE ............................................................8
7.1 CLCULO TEMPERATURA MXIMA DEL CONDUCTOR ................................................................................. 9
7.2 COMPARATIVA DE VALORES ....................................................................................................................... 11
Ref.03056-14 Informev2
1703
Informe de repotenciacin Ingenieros Emetres Per SAC
Ref.03056-14 Informev2
1704
Informe de repotenciacin Ingenieros Emetres Per SAC
Pgina 4 de 163
Ref.03056-14 Informev2
1705
Informe de repotenciacin Ingenieros Emetres Per SAC
I. LINEA DE TRANSMISION
1. ANTECEDENTES
2. OBJETIVO
Pgina 5 de 163
Ref.03056-14 Informev2
1706
Informe de repotenciacin Ingenieros Emetres Per SAC
3. NORMATIVA
4. SITUACIN
Pgina 6 de 163
Ref.03056-14 Informev2
1707
Informe de repotenciacin Ingenieros Emetres Per SAC
Cdigo: L-2240
Tensin: 220kV
Longitud: 83km
Ref.03056-14 Informev2
1708
Informe de repotenciacin Ingenieros Emetres Per SAC
Ref.03056-14 Informev2
1709
Informe de repotenciacin Ingenieros Emetres Per SAC
Conductor bearing is 202 (deg) (perpendicular to solar azimuth for maximum solar heating)
Sun time is 11 hours (solar altitude is 75 deg. and solar azimuth is 112 deg.)
Atmosphere is CLEAR
Day of year is 172 (corresponds to junio 21 in year 2014) (day of the year with most solar
heating)
Ref.03056-14 Informev2
1710
Informe de repotenciacin Ingenieros Emetres Per SAC
Solar heat input is 15.791 (Watt/m) (corresponds to Global Solar Radiation of 1079.371
(Watt/m^2) - which was calculated)
Cuando el conductor alcance los 52,5C la lnea objeto de ste informe podr
transportar los 250MVA necesarios.
Ref.03056-14 Informev2
1711
Informe de repotenciacin Ingenieros Emetres Per SAC
Calculo segn
Parmetro Proyecto original
PR-20 del SEIN
2 2
Radiacin solar 1.200 W/m 1.079 W/m
8. DATOS DE PARTIDA
Pgina 11 de 163
Ref.03056-14 Informev2
1712
Informe de repotenciacin Ingenieros Emetres Per SAC
Las distancias de seguridad verticales de los conductores sobre el nivel del piso
sern determinadas de acuerdo con lo sealado en la Regla 232 del CNE
Pgina 12 de 163
Ref.03056-14 Informev2
1713
Informe de repotenciacin Ingenieros Emetres Per SAC
DISTANCIA
DESCRIPCIN
(m)
A terrenos recorridos por vehculos, tales como cultivos, pastos, bosques, huertos,
8,7
etc.
Pgina 13 de 163
Ref.03056-14 Informev2
1714
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.1 T.2 55 7,2 7,12 14,30 terreno 0,045
Pgina 14 de 163
Ref.03056-14 Informev2
1715
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.12 T.13 55 7,2 0,02 7,20 terreno 4,911
Pgina 15 de 163
Ref.03056-14 Informev2
1716
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.33 T.34 55 7,2 3,76 11,00 terreno 14,761
Pgina 16 de 163
Ref.03056-14 Informev2
1717
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.54 T.55 55 7,2 9,94 17,10 terreno 24,986
Pgina 17 de 163
Ref.03056-14 Informev2
1718
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.75 T.76 55 7,2 0,46 7,70 lateral 35,521
Pgina 18 de 163
Ref.03056-14 Informev2
1719
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.96 T.97 55 7,2 5,23 12,40 terreno 45,172
Pgina 19 de 163
Ref.03056-14 Informev2
1720
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.117 T.118 55 7,2 1,48 8,70 terreno 54,897
Pgina 20 de 163
Ref.03056-14 Informev2
1721
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.138 T.139 55 7,2 0,58 7,80 terreno 63,517
Pgina 21 de 163
Ref.03056-14 Informev2
1722
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.159 T.160 55 7,2 2,43 9,60 terreno 72,465
Pgina 22 de 163
Ref.03056-14 Informev2
1723
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.180 T.181 55 7,2 2,05 9,20 terreno 80,306
Aunque todos los vanos, a excepcin de uno, cumplen con la distancia mnima
reglamentaria, existen algunos puntos singulares con un margen inferior al medio
metro que pueden ser objeto de un estudio ms detallado, en la tabla anterior se han
marcado en azul.
En el vano T.49 T.50 existe una distancia inferior a los 7,20 metros definidos como
mnimos para no tener una distancia a terreno crtica. Esto no significa que exista
una distancia antirreglamentaria en ste punto al ser la entidad que limita un lateral,
cuya componente transversal se desconoce y suma vectorialmente al valor de la
tabla.
Con el fin de verificar con mayor precisin distancias al terreno y datos ambientales,
se realizaron mediciones y registros en campo de los vanos muestreados, utilizando
el siguiente procedimiento:
Pgina 23 de 163
Ref.03056-14 Informev2
1724
Informe de repotenciacin Ingenieros Emetres Per SAC
10. OBSERVACIONES
Pgina 24 de 163
Ref.03056-14 Informev2
1725
Informe de repotenciacin Ingenieros Emetres Per SAC
Las catenarias del conductor en los vanos ms desnivelados difiere con la grafiada
en PLS-CADD, seguramente porqu a parte de lo comentado en el apartado
anterior, en el perfil de proyecto se utilizaron parbolas para representar el conductor
11. CONCLUSINES
Ref.03056-14 Informev2
1726
Informe de repotenciacin Ingenieros Emetres Per SAC
Pgina 26 de 163
Ref.03056-14 Informev2
1727
Informe de repotenciacin Ingenieros Emetres Per SAC
Pgina 27 de 163
Ref.03056-14 Informev2
1728
Informe de repotenciacin Ingenieros Emetres Per SAC
Pgina 28 de 163
Ref.03056-14 Informev2
1729
Informe de repotenciacin Ingenieros Emetres Per SAC
E l S a lt o P a it a Lo bo s de A f ue ra S a la v e rry C him bo t e
( T um be s ) ( P iura ) ( La m ba ye que ) ( La Libe rt a d) ( nc a s h)
A o
P ro P ro P ro P ro P ro
M n. M x. M n. M x. M n. M x. M n. M x. M n. M x.
m. m. m. m. m.
1988 24,6 21,8 26,9 23,2 19,3 28,3 18,8 16,0 22,6 18,9 16,4 22,4 19,6 16,9 22,7
1989 24,2 21,3 26,8 23,4 19,7 27,6 19,5 16,8 23,7 19,4 17,2 23,8 19,9 17,8 23,1
1990 24,6 21,8 26,9 22,9 19,6 26,3 19,4 16,5 22,6 19,7 17,2 22,9 20,4 18,0 23,4
1991 25,0 22,4 27,5 23,2 20,5 27,6 20,3 18,1 23,3 20,2 17,8 23,6 20,6 19,2 23,1
1992 25,4 22,8 28,2 24,2 20,4 28,7 21,2 17,6 26,4 21,2 17,5 26,0 21,5 19,1 25,3
1993 25,2 23,0 27,1 24,0 21,2 27,4 20,5 18,0 24,2 20,5 17,9 23,6 21,5 19,6 24,5
1994 24,6 21,4 26,7 23,6 20,6 26,4 19,4 16,9 22,4 19,7 17,4 22,1 20,6 18,4 22,4
1995 24,9 22,7 27,0 23,0 20,3 26,9 19,6 17,1 23,6 19,5 17,4 23,5 21,3 18,8 25,5
1996 23,8 21,4 26,5 22,4 19,4 25,6 18,4 16,0 21,9 18,5 16,3 21,7 19,5 15,7 22,9
1997 26,8 25,2 27,5 26,3 24,8 28,0 23,0 20,3 25,6 22,9 21,2 25,4 23,3 21,7 24,5
1998 26,0 23,4 28,1 25,0 21,7 28,5 21,9 17,6 27,8 21,5 17,2 27,3 21,9 17,7 28,2
1999 24,7 21,8 26,9 23,2 20,4 27,2 19,0 16,6 22,9 18,8 16,6 22,8 19,4 17,3 22,9
2000 25,0 23,5 26,5 23,1 20,3 26,5 19,5 17,2 22,8 19,3 17,5 22,4 19,7 17,4 22,6
2001 25,1 22,7 27,8 23,2 19,6 27,5 19,3 16,4 24,1 18,8 16,2 22,6 19,4 16,9 22,9
2002 26,0 23,6 28,1 23,9 20,6 28,0 20,3 17,1 25,6 19,8 17,2 23,3 20,1 17,2 24,9
2003 26,3 23,9 28,3 23,1 20,0 26,9 19,4 16,7 23,4 19,3 16,8 23,0 19,9 17,0 23,7
2004 25,2 23,3 27,1 22,9 19,3 26,8 19,4 16,7 23,1 19,2 16,9 22,9 20,1 17,6 24,0
2005 25,2 22,4 28,1 22,5 20,1 26,1 19,3 16,5 22,8 19,4 16,4 22,7 19,8 17,2 23,3
2006 25,2 23,2 27,2 23,2 21,1 26,2 20,0 18,2 23,8 19,8 18,0 23,0 20,9 18,8 23,7
2007 25,3 23,2 27,4 22,2 18,6 26,7 18,8 15,5 23,7 18,8 15,8 23,7 18,9 16,3 23,0
2008 25,5 24,5 26,7 23,4 20,9 26,9 20,3 17,6 25,1 20,3 18,3 24,6 20,8 18,2 27,0
2009 24,2 19,0 25,6 23,3 20,3 27,8 20,0 17,4 22,7 20,5 18,0 23,6 20,7 18,3 23,0
2010 24,3 21,7 26,3 23,4 20,3 26,9 19,5 15,9 24,0 19,7 16,2 24,3 20,2 16,1 24,8
2011 25,7 24,2 27,7 21,7 18,9 25,4 19,6 16,6 22,6 19,3 16,5 22,5 20,0 17,1 21,9
2012 27,1 22,5 33,5 20,6 18,2 23,1 21,0 18,5 23,4 21,3 18,8 23,3
pro m e dio lt im o s 10 a o s 23,43 23,37
Pgina 29 de 163
Ref.03056-14 Informev2
1730
Informe de repotenciacin Ingenieros Emetres Per SAC
Fuente:http://redpeia.minam.gob.pe/admin/files/item/4d77e7ad5bb27_Resumen_Escenarios_climaticos_del_Peru.pdf
Pgina 30 de 163
Ref.03056-14 Informev2
1731
Informe de repotenciacin Ingenieros Emetres Per SAC
Pgina 31 de 163
Ref.03056-14 Informev2
1732
Informe de repotenciacin Ingenieros Emetres Per SAC
Pgina 32 de 163
Ref.03056-14 Informev2
1733
Informe de repotenciacin Ingenieros Emetres Per SAC
Pgina 33 de 163
Ref.03056-14 Informev2
1734
Informe de repotenciacin Ingenieros Emetres Per SAC
Criteria Notes:
Ingenieros Emetres
WC Description Air Wind Wind Wire WireWireWire Ambient Weather NESC Wire Wind Wire
(Pa/(m/s)^2)(m/s) (Pa) (cm) (daN/dm^3) (daN/m) (deg C) (deg C) (daN/m) Model Factor
Pgina 34 de 163
Ref.03056-14 Informev2
1735
Informe de repotenciacin Ingenieros Emetres Per SAC
------------------------------------------------------------------------------------------------------------------------------------
# # Description Condition
-----------------------------------
1 2 T55C Creep RS
Survey Point Clearance and Danger Tree Locator functions are considering a Continuous Range
Pgina 35 de 163
Ref.03056-14 Informev2
1736
Informe de repotenciacin Ingenieros Emetres Per SAC
Survey Point Clearance functions are treating points with insufficient vertical clearance but
Required Clearances
to Spotting
Constraint
----------------(m)------------------
------------------------------------------------------------------------------
Pgina 36 de 163
Ref.03056-14 Informev2
1737
Informe de repotenciacin Ingenieros Emetres Per SAC
This report includes only survey points that do not have the following feature codes: 504 510 520 600
Pgina 37 de 163
Ref.03056-14 Informev2
1738
Informe de repotenciacin Ingenieros Emetres Per SAC
This report includes only survey points with a horizontal distance to wire of less than 15.24 (m).
Clearance to ground centerline is not being checked at regular intervals (only being checked at existing survey points) ??
PLS-CADD analyzes clearances for all of the weather cases specified in Criteria/Survey Point Clearances but
reports results only for the weather case it deems the worst case violation (lowest vertical clearance margin).
Detailed results for all weather cases and wind directions can be obtained through Terrain/Clearance if desired.
Ground clear controls: Constrained by required clearance to ground rather than required clearances for point Feature Code.
Point above wires: Aerial obstacle that is above wires for specified criteria.
Closer inspection may be required to ensure wires remain below obstacle at colder temperatures.
Point between wires: Aerial obstacle that is above some wires and below other wires for specified criteria.
Closer inspection may be required to ensure there are no violations when transitioning from cold to hot temperatures.
Nonprojectable: Point can't be projected onto span. Constrained by clearance to end of span.
Pgina 38 de 163
Ref.03056-14 Informev2
1739
Informe de repotenciacin Ingenieros Emetres Per SAC
Points simultaneously violating both horizontal and vertical clearance requirements are
A clearance value of 10000 indicates the program was unable to calculate a clearance
(no wires in span, no wires crossing point, unknown ground elevation, no points meeting above criteria...).
Number Number Case Vert. Horiz. Violations or Between Point Feature Station Offset Z Height
Description
------------------------------------------------------------------------------------------------------------------------------------------------
T.1 T.2 T55C 7.12 -7.20 OK 0 0 DXFterreno 44.74 -0.00 367.64 0.00
T.2 T.3 T55C 2.25 -3.40 OK 0 0 DXF Lnea electrica 582.96 -0.00 365.29 0.00
T.3 T.4 T55C 2.11 -7.20 OK 0 0 DXFterreno 1129.89 -0.00 395.87 0.00
Pgina 39 de 163
Ref.03056-14 Informev2
1740
Informe de repotenciacin Ingenieros Emetres Per SAC
T.4 T.5 T55C 8.01 -7.20 OK 0 0 DXFterreno 1628.32 -0.00 400.08 0.00
T.5 T.6 T55C 1.55 -7.20 OK 0 0 DXFterreno 1915.80 -0.00 418.30 0.00
T.6 T.7 T55C 10.48 -7.20 OK 0 0 DXFterreno 2273.36 -0.00 435.78 0.00
T.7 T.8 T55C 7.29 -7.20 OK 0 0 DXFterreno 2384.18 -0.00 446.19 0.00
T.8 T.9 T55C 0.74 -7.20 OK 0 0 DXFterreno 3378.43 -0.00 378.91 0.00
T.9 T.10 T55C 4.41 -7.20 OK 0 0 DXFterreno 3785.00 -0.00 429.03 0.00
T.10 T.11 T55C 0.81 -7.20 OK 0 0 DXFterreno 3978.58 -0.00 434.56 0.00
T.11 T.12 T55C 11.26 -5.12 OK 0 0 DXFterreno 4210.26 -0.00 430.63 0.00
T.12 T.13 T55C 0.02 -7.20 OK 0 0 DXFterreno 4911.41 -0.00 469.09 0.00
T.13 T.14 T55C 3.17 -7.20 OK 0 0 DXF lateral 5116.02 -0.00 461.42 0.00
T.14 T.15 T55C 9.53 -7.20 OK 0 0 DXF lateral 5961.02 -0.00 413.68 0.00
T.15 T.16 T55C 8.14 -7.20 OK 0 0 DXF lateral 6688.58 -0.00 335.05 0.00
T.16 T.17 T55C 2.94 -7.20 OK 0 0 DXFterreno 6838.11 -0.00 319.51 0.00
T.17 T.18 T55C 2.61 -7.20 OK 0 0 DXFterreno 7312.25 -0.00 305.33 0.00
T.18 T.19 T55C 4.30 -7.20 OK 0 0 DXFterreno 7648.87 -0.00 312.58 0.00
T.19 T.20 T55C 0.64 -7.20 OK 0 0 DXF lateral 8374.35 -0.00 339.74 0.00
T.20 T.21 T55C 12.28 -7.20 OK 0 0 DXFterreno 8860.42 -0.00 273.86 0.00
Pgina 40 de 163
Ref.03056-14 Informev2
1741
Informe de repotenciacin Ingenieros Emetres Per SAC
T.21 T.22 T55C 0.52 -7.20 OK 0 0 DXFterreno 9198.66 -0.00 272.90 0.00
T.22 T.23 T55C 7.20 -7.20 OK 0 0 DXF lateral 9570.48 -0.00 273.06 0.00
T.23 T.24 T55C 10.07 -7.20 OK 0 0 DXFterreno 10199.48 -0.00 325.20 0.00
T.24 T.25 T55C 10.52 -7.20 OK 0 0 DXFterreno 10411.52 -0.00 299.72 0.00
T.25 T.26 T55C 4.14 -7.20 OK 0 0 DXFterreno 10889.10 -0.00 263.90 0.00
T.26 T.27 T55C 3.26 -7.20 OK 0 0 DXFterreno 11148.02 -0.00 267.08 0.00
T.27 T.28 T55C 4.26 -7.20 OK 0 0 DXFterreno 12020.01 -0.00 312.84 0.00
T.28 T.29 T55C 11.50 -6.11 OK 0 0 DXFterreno 13082.92 -0.00 333.18 0.00
T.29 T.30 T55C 8.33 -7.20 OK 0 0 DXF lateral 13426.59 -0.00 339.26 0.00
T.30 T.31 T55C 8.00 -7.20 OK 0 0 DXF lateral 13452.09 -0.00 339.30 0.00
T.31 T.32 T55C 0.38 -7.20 OK 0 0 DXFterreno 14066.49 -0.00 292.31 0.00
T.32 T.33 T55C 4.90 -7.20 OK 0 0 DXFterreno 14303.89 -0.00 273.41 0.00
T.33 T.34 T55C 3.76 -7.20 OK 0 0 DXFterreno 14761.38 -0.00 251.47 0.00
T.34 T.35 T55C 2.50 -7.20 OK 0 0 DXF lateral 14958.08 -0.00 267.03 0.00
T.35 T.36 T55C 7.75 -7.20 OK 0 0 DXFterreno 15674.33 -0.00 231.49 0.00
T.36 T.37 T55C 9.72 -7.20 OK 0 0 DXFterreno 15817.13 -0.00 234.10 0.00
T.37 T.38 T55C 9.33 -7.20 OK 0 0 DXFterreno 16819.06 -0.00 222.70 0.00
Pgina 41 de 163
Ref.03056-14 Informev2
1742
Informe de repotenciacin Ingenieros Emetres Per SAC
T.38 T.39 T55C 0.09 -7.20 OK 0 0 DXFterreno 17044.07 -0.00 230.44 0.00
T.39 T.40 T55C 8.97 -7.20 OK 0 0 DXFterreno 17365.04 -0.00 243.55 0.00
T.40 T.41 T55C 8.46 -7.20 OK 0 0 DXF lateral 17713.62 -0.00 258.90 0.00
T.41 T.42 T55C 8.18 -7.20 OK 0 0 DXF lateral 18198.25 -0.00 302.22 0.00
T.42 T.43 T55C 9.20 -7.20 OK 0 0 DXF lateral 18914.53 -0.00 291.91 0.00
T.43 T.44 T55C 7.14 -7.20 OK 0 0 DXF lateral 19295.22 -0.00 318.25 0.00
T.44 T.45 T55C 6.99 -3.49 OK 0 0 DXF lateral 19295.22 -0.00 318.25 0.00
T.45 T.46 T55C 2.73 -7.20 OK 0 0 DXFterreno 20007.14 -0.00 217.28 0.00
T.46 T.47 T55C 8.63 -7.12 OK 0 0 DXF lateral 20704.32 -0.00 281.84 0.00
T.47 T.48 T55C 8.61 -7.20 OK 0 0 DXF lateral 20704.32 -0.00 281.84 0.00
T.48 T.49 T55C 4.82 7.64 OK 0 0 DXF lateral 22174.21 -0.00 267.52 0.00
T.49 T.50 T55C -0.59 -7.20 NG 7 0 DXF lateral 22177.46 -0.00 268.77 0.00
T.50 T.51 T55C 10.34 -7.20 OK 0 0 DXFterreno 22390.84 -0.00 221.30 0.00
T.51 T.52 T55C 10.96 -7.20 OK 0 0 DXFterreno 23874.16 -0.00 272.14 0.00
T.52 T.53 T55C 3.20 -7.20 OK 0 0 DXF lateral 23932.66 -0.00 276.07 0.00
T.53 T.54 T55C 3.61 -7.20 OK 0 0 DXFterreno 24599.48 -0.00 243.40 0.00
T.54 T.55 T55C 9.94 -7.20 OK 0 0 DXFterreno 24986.24 -0.00 281.63 0.00
Pgina 42 de 163
Ref.03056-14 Informev2
1743
Informe de repotenciacin Ingenieros Emetres Per SAC
T.55 T.56 T55C 3.00 -7.20 OK 0 0 DXFterreno 25606.91 -0.00 163.35 0.00
T.56 T.57 T55C 0.57 -7.20 OK 0 0 DXFterreno 26012.85 -0.00 152.53 0.00
T.57 T.58 T55C 1.33 -7.20 OK 0 0 DXFterreno 26460.95 -0.00 145.22 0.00
T.58 T.59 T55C 1.21 -7.20 OK 0 0 DXFterreno 26865.37 -0.00 144.56 0.00
T.59 T.60 T55C 4.86 -7.20 OK 0 0 DXF lateral 27410.98 -0.00 196.22 0.00
T.60 T.61 T55C 8.87 -7.20 OK 0 0 DXFterreno 27847.59 -0.00 270.20 0.00
T.61 T.62 T55C 0.44 -7.20 OK 0 0 DXF lateral 28929.61 -0.00 251.58 0.00
T.62 T.63 T55C 6.38 -7.20 OK 0 0 DXF lateral 28974.53 -0.00 251.08 0.00
T.63 T.64 T55C 0.64 -7.20 OK 0 0 DXF lateral 29902.38 -0.00 185.81 0.00
T.64 T.65 T55C 7.89 -7.20 OK 0 0 DXFterreno 30559.02 -0.00 143.37 0.00
T.65 T.66 T55C 0.89 -7.20 OK 0 0 DXFterreno 30906.20 -0.00 144.43 0.00
T.66 T.67 T55C 0.60 -7.20 OK 0 0 DXFterreno 31413.57 -0.00 139.15 0.00
T.67 T.68 T55C 8.75 -7.20 OK 0 0 DXFterreno 31780.33 -0.00 137.77 0.00
T.68 T.69 T55C 1.49 -7.20 OK 0 0 DXFterreno 32160.63 -0.00 139.00 0.00
T.69 T.70 T55C 11.04 -7.20 OK 0 0 DXFterreno 32557.61 -0.00 144.52 0.00
T.70 T.71 T55C 0.40 -7.20 OK 0 0 DXFterreno 32756.25 -0.00 149.20 0.00
T.71 T.72 T55C 6.74 -7.20 OK 0 0 DXFterreno 33553.69 -0.00 238.03 0.00
Pgina 43 de 163
Ref.03056-14 Informev2
1744
Informe de repotenciacin Ingenieros Emetres Per SAC
T.72 T.73 T55C 7.40 -7.20 OK 0 0 DXF lateral 33868.36 -0.00 197.30 0.00
T.73 T.74 T55C 3.96 -7.20 OK 0 0 DXF lateral 34648.19 -0.00 212.26 0.00
T.74 T.75 T55C 3.78 7.56 OK 0 0 DXF lateral 35490.01 -0.00 307.08 0.00
T.75 T.76 T55C 0.46 -7.20 OK 0 0 DXF lateral 35520.60 -0.00 305.88 0.00
T.76 T.77 T55C 5.44 -0.83 OK 0 0 DXF lateral 35653.57 -0.00 294.08 0.00
T.77 T.78 T55C 8.47 -7.20 OK 0 0 DXFterreno 36524.77 -0.00 163.92 0.00
T.78 T.79 T55C 10.28 -7.20 OK 0 0 DXFterreno 37578.06 -0.00 208.21 0.00
T.79 T.80 T55C 6.76 -7.20 OK 0 0 DXFterreno 38022.40 -0.00 141.35 0.00
T.80 T.81 T55C 3.70 -7.20 OK 0 0 DXFterreno 38358.38 -0.00 138.33 0.00
T.81 T.82 T55C 1.08 -7.20 OK 0 0 DXFterreno 38819.76 -0.00 135.97 0.00
T.82 T.83 T55C 1.41 -7.20 OK 0 0 DXFterreno 39260.24 -0.00 130.59 0.00
T.83 T.84 T55C 1.27 -7.20 OK 0 0 DXFterreno 39625.92 -0.00 128.07 0.00
T.84 T.85 T55C 1.13 -7.20 OK 0 0 DXFterreno 40061.04 -0.00 134.72 0.00
T.85 T.86 T55C 0.82 -7.20 OK 0 0 DXFterreno 40435.21 -0.00 134.40 0.00
T.86 T.87 T55C 0.92 -9.20 OK 0 0 DXFcaminos 40962.55 -0.00 119.88 0.00
T.87 T.88 T55C 1.38 -7.20 OK 0 0 DXFterreno 41308.48 -0.00 122.73 0.00
T.88 T.89 T55C 1.28 -7.20 OK 0 0 DXFterreno 41739.23 -0.00 121.94 0.00
Pgina 44 de 163
Ref.03056-14 Informev2
1745
Informe de repotenciacin Ingenieros Emetres Per SAC
T.89 T.90 T55C 0.72 -7.20 OK 0 0 DXFterreno 42197.39 -0.00 121.51 0.00
T.90 T.91 T55C 1.68 -7.20 OK 0 0 DXFterreno 42615.09 -0.00 119.64 0.00
T.91 T.92 T55C 1.41 -7.20 OK 0 0 DXFterreno 43093.46 -0.00 117.71 0.00
T.92 T.93 T55C 1.01 -7.20 OK 0 0 DXFterreno 43584.25 -0.00 112.38 0.00
T.93 T.94 T55C 0.11 -7.20 OK 0 0 DXFterreno 44014.76 -0.00 105.30 0.00
T.94 T.95 T55C 1.17 -7.20 OK 0 0 DXFterreno 44416.94 -0.00 99.82 0.00
T.95 T.96 T55C 0.88 -9.20 OK 0 0 DXFcaminos 44794.63 -0.00 98.34 0.00
T.96 T.97 T55C 5.23 -7.20 OK 0 0 DXFterreno 45172.39 -0.00 111.13 0.00
T.97 T.98 T55C 8.13 -7.20 OK 0 0 DXFterreno 45455.04 -0.00 128.53 0.00
T.98 T.99 T55C 10.02 -7.20 OK 0 0 DXFterreno 46073.92 -0.00 78.86 0.00
T.99 T.100 T55C 8.88 -7.20 OK 0 0 DXFterreno 46494.53 -0.00 72.85 0.00
T.100 T.101 T55C 8.24 -7.20 OK 0 0 DXFterreno 46945.68 -0.00 70.30 0.00
T.101 T.102 T55C 8.73 -7.20 OK 0 0 DXFterreno 47370.72 -0.00 67.99 0.00
T.102 T.103 T55C 5.00 -3.40 OK 0 0 DXF Lnea electrica 47703.01 -0.00 77.89 0.00
T.103 T.104 T55C 7.72 -7.20 OK 0 0 DXFterreno 48235.49 -0.00 66.47 0.00
T.104 T.105 T55C 10.04 -7.20 OK 0 0 DXFterreno 48653.29 -0.00 65.80 0.00
T.105 T.106 T55C 7.90 -7.20 OK 0 0 DXFterreno 49073.54 -0.00 66.08 0.00
Pgina 45 de 163
Ref.03056-14 Informev2
1746
Informe de repotenciacin Ingenieros Emetres Per SAC
T.106 T.107 T55C 9.76 -7.20 OK 0 0 DXFterreno 49435.87 -0.00 64.51 0.00
T.107 T.108 T55C 8.62 -7.20 OK 0 0 DXFterreno 49880.38 -0.00 63.54 0.00
T.108 T.109 T55C 6.05 -7.20 OK 0 0 DXFterreno 51044.97 -0.00 226.54 0.00
T.109 T.110 T55C 8.45 -7.20 OK 0 0 DXFterreno 51803.36 -0.00 95.16 0.00
T.110 T.111 T55C 5.58 -3.40 OK 0 0 DXF Lnea electrica 51989.49 -0.00 97.82 0.00
T.111 T.112 T55C 1.25 -7.20 OK 0 0 DXFterreno 52337.38 -0.00 84.72 0.00
T.112 T.113 T55C 1.31 -7.20 OK 0 0 DXFterreno 52712.95 -0.00 88.16 0.00
T.113 T.114 T55C 2.04 -7.20 OK 0 0 DXF lateral 52961.36 -0.00 92.45 0.00
T.114 T.115 T55C 4.18 -7.20 OK 0 0 DXFterreno 53497.81 -0.00 74.98 0.00
T.115 T.116 T55C 6.87 -3.40 OK 0 0 DXF Lnea electrica 54029.64 -0.00 85.22 0.00
T.116 T.117 T55C 0.73 -7.20 OK 0 0 DXFterreno 54380.19 -0.00 76.51 0.00
T.117 T.118 T55C 1.48 -7.20 OK 0 0 DXFterreno 54896.98 -0.00 74.90 0.00
T.118 T.119 T55C 0.74 -7.20 OK 0 0 DXFterreno 55160.43 -0.00 73.80 0.00
T.119 T.120 T55C 0.34 -7.20 OK 0 0 DXFterreno 55554.98 -0.00 71.82 0.00
T.120 T.121 T55C 0.87 -7.20 OK 0 0 DXFterreno 56016.39 -0.00 73.04 0.00
T.121 T.122 T55C 0.77 -7.20 OK 0 0 DXFterreno 56321.06 -0.00 75.79 0.00
T.122 T.123 T55C 1.50 -7.20 OK 0 0 DXFterreno 56645.29 -0.00 74.67 0.00
Pgina 46 de 163
Ref.03056-14 Informev2
1747
Informe de repotenciacin Ingenieros Emetres Per SAC
T.123 T.124 T55C 1.13 -7.20 OK 0 0 DXFterreno 57048.69 -0.00 74.78 0.00
T.124 T.125 T55C 0.79 -7.20 OK 0 0 DXFterreno 57449.40 -0.00 71.54 0.00
T.125 T.126 T55C 0.86 -7.20 OK 0 0 DXFterreno 57971.97 -0.00 70.73 0.00
T.126 T.127 T55C 0.64 -7.20 OK 0 0 DXFterreno 58372.61 -0.00 70.35 0.00
T.127 T.128 T55C 1.70 -7.20 OK 0 0 DXFterreno 58835.95 -0.00 68.30 0.00
T.128 T.129 T55C 2.88 -7.20 OK 0 0 DXFterreno 59202.76 -0.00 64.71 0.00
T.129 T.130 T55C 0.67 -7.20 OK 0 0 DXFterreno 59738.38 -0.00 62.50 0.00
T.130 T.131 T55C 5.44 -7.20 OK 0 0 DXFterreno 60178.65 -0.00 57.53 0.00
T.131 T.132 T55C 1.26 -7.20 OK 0 0 DXFterreno 60500.60 -0.00 56.01 0.00
T.132 T.133 T55C 0.69 -7.20 OK 0 0 DXFterreno 60968.78 -0.00 53.33 0.00
T.133 T.134 T55C 1.09 -7.20 OK 0 0 DXFterreno 61415.72 -0.00 50.33 0.00
T.134 T.135 T55C 0.04 -7.20 OK 0 0 DXFterreno 61801.73 -0.00 46.35 0.00
T.135 T.136 T55C 0.42 -7.20 OK 0 0 DXFterreno 62289.75 -0.00 42.50 0.00
T.136 T.137 T55C 0.70 -7.20 OK 0 0 DXFterreno 62628.49 -0.00 43.39 0.00
T.137 T.138 T55C 0.03 -7.20 OK 0 0 DXFterreno 63150.11 -0.00 41.51 0.00
T.138 T.139 T55C 0.58 -7.20 OK 0 0 DXFterreno 63517.45 -0.00 45.24 0.00
T.139 T.140 T55C 2.41 -7.20 OK 0 0 DXFterreno 63834.58 -0.00 46.58 0.00
Pgina 47 de 163
Ref.03056-14 Informev2
1748
Informe de repotenciacin Ingenieros Emetres Per SAC
T.140 T.141 T55C 3.90 -7.20 OK 0 0 DXFterreno 64229.76 -0.00 51.44 0.00
T.141 T.142 T55C 2.15 -7.20 OK 0 0 DXFterreno 65071.75 -0.00 171.46 0.00
T.142 T.143 T55C 10.45 -7.20 OK 0 0 DXFterreno 65197.10 -0.00 160.41 0.00
T.143 T.144 T55C 8.30 -7.20 OK 0 0 DXFterreno 66396.76 -0.00 174.14 0.00
T.144 T.145 T55C 2.28 -7.20 OK 0 0 DXFterreno 67045.57 -0.00 81.49 0.00
T.145 T.146 T55C 4.97 7.73 OK 0 0 DXFterreno 67058.31 -0.00 79.63 0.00
T.146 T.147 T55C 5.84 -7.20 OK 0 0 DXFterreno 67954.78 -0.00 100.30 0.00
T.147 T.148 T55C 7.32 2.73 OK 0 0 DXFterreno 68236.68 -0.00 81.38 0.00
T.148 T.149 T55C 3.92 -7.20 OK 0 0 DXFterreno 68514.46 -0.00 58.58 0.00
T.149 T.150 T55C 10.47 7.29 OK 0 0 DXFterreno 68585.14 -0.00 52.70 0.00
T.150 T.151 T55C 10.51 -0.53 OK 0 0 DXFterreno 69155.25 -0.00 38.08 0.00
T.151 T.152 T55C 5.70 -7.20 OK 0 0 DXFterreno 69371.73 -0.00 26.14 0.00
T.152 T.153 T55C 13.41 -7.20 OK 0 0 DXFterreno 69753.57 -0.00 17.47 0.00
T.153 T.154 T55C 5.42 -7.20 OK 0 0 DXFterreno 70202.09 -0.00 13.58 0.00
T.154 T.155 T55C 1.82 -7.20 OK 0 0 DXFterreno 70501.86 -0.00 17.62 0.00
T.155 T.156 T55C 2.07 -7.20 OK 0 0 DXFterreno 70865.22 -0.00 13.66 0.00
T.156 T.157 T55C 0.85 -7.20 OK 0 0 DXFterreno 71208.99 -0.00 15.65 0.00
Pgina 48 de 163
Ref.03056-14 Informev2
1749
Informe de repotenciacin Ingenieros Emetres Per SAC
T.157 T.158 T55C 1.44 -7.20 OK 0 0 DXFterreno 71657.92 -0.00 11.00 0.00
T.158 T.159 T55C 1.42 -7.20 OK 0 0 DXFterreno 71982.35 -0.00 9.75 0.00
T.159 T.160 T55C 2.43 -7.20 OK 0 0 DXFterreno 72465.11 -0.00 7.93 0.00
T.160 T.161 T55C 2.23 -7.20 OK 0 0 DXFterreno 72823.28 -0.00 7.86 0.00
T.161 T.162 T55C 1.32 -4.00 OK 0 0 DXF Lnea telefono 73157.60 -0.00 19.13 0.00
T.162 T.163 T55C 7.82 -7.20 OK 0 0 DXFterreno 73732.31 -0.00 9.09 0.00
T.163 T.164 T55C 0.59 -4.00 OK 0 0 DXF Lnea telefono 73856.87 -0.00 18.57 0.00
T.164 T.165 T55C 0.10 -7.20 OK 0 0 DXFterreno 74369.45 -0.00 9.03 0.00
T.165 T.166 T55C 1.12 -7.20 OK 0 0 DXFterreno 74768.30 -0.00 9.24 0.00
T.166 T.167 T55C 1.51 -6.20 OK 0 0 DXF Edificaciones 75112.74 -0.00 11.07 0.00
T.167 T.168 T55C 1.55 -7.20 OK 0 0 DXFterreno 75519.53 -0.00 9.51 0.00
T.168 T.169 T55C 2.35 -7.20 OK 0 0 DXFterreno 75909.61 -0.00 11.20 0.00
T.169 T.170 T55C 1.93 -7.20 OK 0 0 DXFterreno 76332.24 -0.00 14.57 0.00
T.170 T.171 T55C 1.24 -7.20 OK 0 0 DXFterreno 76569.94 -0.00 16.53 0.00
T.171 T.172 T55C 5.05 -7.20 OK 0 0 DXFterreno 77012.12 -0.00 10.87 0.00
T.172 T.173 T55C 0.81 -9.20 OK 0 0 DXFCtra 77280.41 -0.00 9.36 0.00
T.173 T.174 T55C 1.17 -6.20 OK 0 0 DXF Edificaciones 77601.52 -0.00 12.52 0.00
Pgina 49 de 163
Ref.03056-14 Informev2
1750
Informe de repotenciacin Ingenieros Emetres Per SAC
T.174 T.175 T55C 1.77 -6.20 OK 0 0 DXFvalla 78044.43 -0.00 13.89 0.00
T.175 T.176 T55C 2.25 -7.20 OK 0 0 DXFterreno 78331.56 -0.00 10.52 0.00
T.176 T.177 T55C 1.04 -7.20 OK 0 0 DXFterreno 78646.63 -0.00 11.19 0.00
T.177 T.178 T55C 1.07 -7.20 OK 0 0 DXFterreno 79093.68 -0.00 12.79 0.00
T.178 T.179 T55C 2.94 -6.20 OK 0 0 DXFvalla 79482.27 -0.00 11.78 0.00
T.179 T.180 T55C 2.46 -7.20 OK 0 0 DXFterreno 79873.89 -0.00 9.77 0.00
T.180 T.181 T55C 2.05 -7.20 OK 0 0 DXFterreno 80306.19 -0.00 12.23 0.00
T.181 T.182 T55C 2.09 -7.20 OK 0 0 DXFterreno 80640.82 -0.00 12.21 0.00
T.182 T.183 T55C 2.17 -6.20 OK 0 0 DXFvalla 80971.52 -0.00 13.87 0.00
T.183 T.184 T55C 2.31 -6.20 OK 0 0 DXFvalla 81345.65 -0.00 12.79 0.00
T.184 T.185 T55C 5.44 -7.20 OK 0 0 DXFterreno 81659.04 -0.00 10.60 0.00
T.185 T.186 T55C 4.96 -3.40 OK 0 0 DXF Lnea electrica 82065.41 -0.00 17.09 0.00
T.186 T.187 T55C 5.63 -7.20 OK 0 0 DXFterreno 82334.37 -0.00 11.79 0.00
T.187 T.188 T55C 9.74 -6.20 OK 0 0 DXFvalla 82713.92 -0.00 23.62 0.00
T.188 T.189 T55C 9.56 -7.20 OK 0 0 DXFterreno 82780.03 -0.00 21.51 0.00
Pgina 50 de 163
Ref.03056-14 Informev2
1751
Informe de repotenciacin Ingenieros Emetres Per SAC
Pgina 51 de 163
Ref.03056-14 Informev2
1752
Informe de repotenciacin Ingenieros Emetres Per SAC
Conductor bearing is 202 (deg) (perpendicular to solar azimuth for maximum solar heating)
Sun time is 11 hours (solar altitude is 75 deg. and solar azimuth is 112 deg.)
Atmosphere is CLEAR
Day of year is 172 (corresponds to junio 21 in year 2014) (day of the year with most solar
heating)
Ref.03056-14 Informev2
1753
Informe de repotenciacin Ingenieros Emetres Per SAC
Solar heat input is 15.791 (Watt/m) (corresponds to Global Solar Radiation of 1079.371
(Watt/m^2) - which was calculated)
Para esta temperatura del conductor de 61C la tabla de distncias queda como
sigue:
Pgina 53 de 163
Ref.03056-14 Informev2
1754
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.1 T.2 61 7,20 6,98 14,20 terreno 0,045
Pgina 54 de 163
Ref.03056-14 Informev2
1755
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.22 T.23 61 7,20 7,15 14,40 lateral 9,570
Pgina 55 de 163
Ref.03056-14 Informev2
1756
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.43 T.44 61 7,20 7,13 14,30 lateral 19,295
Pgina 56 de 163
Ref.03056-14 Informev2
1757
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.64 T.65 61 7,20 7,65 14,90 terreno 30,557
Pgina 57 de 163
Ref.03056-14 Informev2
1758
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.85 T.86 61 7,20 0,55 7,80 terreno 40,435
Pgina 58 de 163
Ref.03056-14 Informev2
1759
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.106 T.107 61 7,20 9,49 16,70 terreno 49,437
Pgina 59 de 163
Ref.03056-14 Informev2
1760
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.127 T.128 61 7,20 1,38 8,60 terreno 58,836
Pgina 60 de 163
Ref.03056-14 Informev2
1761
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.148 T.149 61 7,20 3,70 10,90 terreno 68,514
Pgina 61 de 163
Ref.03056-14 Informev2
1762
Informe de repotenciacin Ingenieros Emetres Per SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.169 T.170 61 7,20 1,65 8,80 terreno 76,332
Pgina 62 de 163
Ref.03056-14 Informev2
1763
Informe de repotenciacin Ingenieros Emetres Per SAC
De la tabla anterior se desprende que sera necesario verificar los siguientes vanos:
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mnima (m) total (km)
(C) (m) (m)
T.12 T.13 61 7,20 -0,19 7,00 terreno 4,911
Pgina 63 de 163
Ref.03056-14 Informev2
1764
Informe de repotenciacin Ingenieros Emetres Per SAC
Direccin
Viento
2 m/s
DV = 9.87 m
Datos de medicin:
Fecha : 04.04.2014
Hora : 14:35
Equipos utilizados :
Pgina 64 de 163
Ref.03056-14 Informev2
1765
Informe de repotenciacin Ingenieros Emetres Per SAC
Direccin
Viento
2.5 m/s
DV = 10.36 m
Datos de medicin:
Fecha : 04.04.2014
Hora : 18:15
Equipos utilizados :
Pgina 65 de 163
Ref.03056-14 Informev2
1766
Informe de repotenciacin Ingenieros Emetres Per SAC
Direccin
Viento
4.3 m/s
DV = 8.57 m
Datos de medicin:
Fecha : 10.04.2014
Hora : 14:05
Equipos utilizados :
Pgina 66 de 163
Ref.03056-14 Informev2
1767
Informe de repotenciacin Ingenieros Emetres Per SAC
Direccin
DV = 13.68 m Viento
3.2 m/s
Datos de medicin:
Fecha : 10.04.2014
Hora : 15:15
Equipos utilizados :
Pgina 67 de 163
Ref.03056-14 Informev2
1768
Informe de repotenciacin Ingenieros Emetres Per SAC
Direccin
Viento
3.3 m/s
DV = 8.50 m
Datos de medicin:
Fecha : 10.04.2014
Hora : 17:22
Equipos utilizados :
Pgina 68 de 163
Ref.03056-14 Informev2
1769
Informe de repotenciacin Ingenieros Emetres Per SAC
Direccin
Viento
3.2 m/s
DV = 9.70 m
Datos de medicin:
Fecha : 04.04.2014
Hora : 12:26
Equipos utilizados :
Pgina 69 de 163
Ref.03056-14 Informev2
1770
Informe de repotenciacin Ingenieros Emetres Per SAC
Pgina 70 de 163
Ref.03056-14 Informev2
1771
1772
1773
1774
1775
1776
1777
1778
1779
1780
1781
1782
1783
1784
1785
1786
1787
1788
1789
1790
1791
1792
1793
1794
1795
1796
1797
1798
1799
1800
1801
1802
1803
1804
1805
1806
1807
1808
1809
1810
1811
1812
1813
1814
1815
1816
1817
1818
1819
Informe de repotenciacin Ingenieros Emetres Per SAC
12. METRADO
Ref.03056-14 Informev2
1820
Informederepotenciacin IngenierosEmetresPerSAC
delalneadetransmisinde220kV Ref.0305614Informev2
ChiclayoOesteCarhuaquero Rev.2
METRADOYVALORREFERENCIAL(dolaresamericanos)
REPOTENCIACIONLINEADETRANSMISION220KV:CHICLAYOCARHUAQUERO
TOTAL 27,500.00
LongituddelaLinea(km) 40.00
Costoporkm(US/km) 687.50
PROYECTODEREPOTENCIACINDELALNEADETRANSMISINDE220kV 1821
CHICLAYOOESTECARHUAQUERO
Ref.0305614Informev2
Pgina120
Informe de repotenciacin Ingenieros Emetres Per SAC
SUBESTACIONES
1.INTRODUCCIONYOBJETIVO
El presente documento tiene como objetivo realizar una evaluacin para los equipos
de las subestaciones de cabecera, en las celdas de la lnea en 220kV para las
Subestacin Chiclayo Oeste y Carhuaquero, como parte del proyecto
Repotenciacin de la lnea 220kV Chiclayo Oeste/Carhuaquero a 250MVA, y
determinar una actuaciones necesarias para lograr dicha finalidad.
2.ANTECEDENTES
3.CONDICIONESAMBIENTALES
El tipo de clima presente en esta localidad es del tipo seco, templado y soleado
durante el da. Refrigerado durante la noche. Clima de selva alta, menos clido por
encontrarse a mayor altitud, ms nuboso y extremo lluvioso. Las condiciones
ambientales con la que debern ser capaces de trabajar el equipo especificado son
las siguientes:
Pgina121de165
PROYECTODEREPOTENCIACINDELALNEADETRANSMISINDE220kV
CHICLAYOOESTECARHUAQUERO
Ref.0305614Informev2
1822
Informe de repotenciacin Ingenieros Emetres Per SAC
CONDICIONES PARAMETROS
Humedad Relativa 70 %
Frecuencia Hz 60
N de fases - 3
Efectivamente conectado a
Neutro del sistema -
tierra
Ref.03056-14 Informev2
1823
Informe de repotenciacin Ingenieros Emetres Per SAC
Ref.03056-14 Informev2
1824
Informe de repotenciacin Ingenieros Emetres Per SAC
6.2UBICACINS/ECARHUAQUERO
La subestacin Carhuaquero se ubica al noreste del Per, en el departamento de
Cajamarca, al este de la ciudad de Chiclayo y es de propiedad de la empresa Duke
Energy Per. Cuenta con instalaciones en 220 y 10kV.
7.CONFIGURACIONYDESCRIPCIONDELAS/ECHICLAYOOESTE
La subestacin Chiclayo Oeste es una subestacin de 220/60kV, cuenta con una
configuracin de doble barra tanto en el nivel de 220kV como en el nivel de 60kV.
Pgina124de165
PROYECTODEREPOTENCIACINDELALNEADETRANSMISINDE220kV
CHICLAYOOESTECARHUAQUERO
Ref.0305614Informev2
1825
Informe de repotenciacin Ingenieros Emetres Per SAC
En 220kV:
Pgina125de165
PROYECTODEREPOTENCIACINDELALNEADETRANSMISINDE220kV
CHICLAYOOESTECARHUAQUERO
Ref.0305614Informev2
1826
Informe de repotenciacin Ingenieros Emetres Per SAC
Pgina126de165
PROYECTODEREPOTENCIACINDELALNEADETRANSMISINDE220kV
CHICLAYOOESTECARHUAQUERO
Ref.0305614Informev2
1827
Informe de repotenciacin Ingenieros Emetres Per SAC
En 60kV:
Pgina127de165
PROYECTODEREPOTENCIACINDELALNEADETRANSMISINDE220kV
CHICLAYOOESTECARHUAQUERO
Ref.0305614Informev2
1828
Informe de repotenciacin Ingenieros Emetres Per SAC
Pgina128de165
PROYECTODEREPOTENCIACINDELALNEADETRANSMISINDE220kV
CHICLAYOOESTECARHUAQUERO
Ref.0305614Informev2
1829
Informe de repotenciacin Ingenieros Emetres Per SAC
Un transformador de tensin.
Pgina129de165
PROYECTODEREPOTENCIACINDELALNEADETRANSMISINDE220kV
CHICLAYOOESTECARHUAQUERO
Ref.0305614Informev2
1830
Informe de repotenciacin Ingenieros Emetres Per SAC
S/E Chiclayo Oeste: Equipos primarios existentes del baha de linea Chiclayo Oeste
Carhuaquero.
Trampa de Onda 2
8.CONFIGURACIONYDESCRIPCIONDELAS/ECARHUAQUERO
La subestacin Carhuaquero 220/10 kV cuenta con una configuracin de simple
barra tanto en el nivel de 220kV como en el nivel de 10kV. Actualmente la
subestacin cuenta con el siguiente equipamiento:
En 220kV:
Pgina130de165
PROYECTODEREPOTENCIACINDELALNEADETRANSMISINDE220kV
CHICLAYOOESTECARHUAQUERO
Ref.0305614Informev2
1831
Informe de repotenciacin Ingenieros Emetres Per SAC
Pgina131de165
PROYECTODEREPOTENCIACINDELALNEADETRANSMISINDE220kV
CHICLAYOOESTECARHUAQUERO
Ref.0305614Informev2
1832
Informe de repotenciacin Ingenieros Emetres Per SAC
Un autotransformador 220/10kV.
Un interruptor SF6 con una bobina de cierre y dos bobinas de disparo, 245kV,
2000A.
Un interruptor SF6 con una bobina de cierre y dos bobinas de disparo, 245kV, 2000
A.
PROYECTODEREPOTENCIACINDELALNEADETRANSMISINDE220kV
CHICLAYOOESTECARHUAQUERO
Ref.0305614Informev2
1833
Informe de repotenciacin Ingenieros Emetres Per SAC
En 10kV:
Un autotransformador 220/10kV.
Un interruptor SF6 con una bobina de cierre y dos bobinas de disparo, 12kV, 1250A,
25kA.
Un interruptor SF6 con una bobina de cierre y dos bobinas de disparo, 12kV, 1250A,
25kA.
Un interruptor SF6 con una bobina de cierre y dos bobinas de disparo, 245kV,
2000A.
Pgina133de165
PROYECTODEREPOTENCIACINDELALNEADETRANSMISINDE220kV
CHICLAYOOESTECARHUAQUERO
Ref.0305614Informev2
1834
Informe de repotenciacin Ingenieros Emetres Per SAC
Pararrayos 190kV 3
Trampa de Onda 2
Ref.03056-14 Informev2
1835
Informe de repotenciacin Ingenieros Emetres Per SAC
Parmetros Unidades
Cantidad de Alambres y
37/4,18
Dimetro
En el anexo se encuentra una tabla completa con las caractersticas elctricas para
este conductor.
Ref.03056-14 Informev2
1836
Informe de repotenciacin Ingenieros Emetres Per SAC
Considerando:
Es decir;
Ahora se determinara la nueva corriente que transporta la lnea por los equipos de la
baha en condiciones de operacin normal para una potencia de 250MVA.
Considerando:
Es decir;
Ref.03056-14 Informev2
1837
Informe de repotenciacin Ingenieros Emetres Per SAC
i. S/E Carhuaquero
Interruptor
Parmetros Unidades
Rango de frecuencia 60 Hz
Se puede apreciar que la nueva corriente nominal de operacin est dentro de los
rangos de funcionamiento del interruptor ya que es menor que 2000 A.
Ref.03056-14 Informev2
1838
Informe de repotenciacin Ingenieros Emetres Per SAC
Parmetros Unidades
Rango de corriente de 40 kA
cortocircuito
Rango de frecuencia 60 Hz
Se puede apreciar que la nueva corriente nominal de operacin est dentro de los
rangos de funcionamiento del interruptor ya que es menor que 1600 A.
Parmetros Unidades
Rango de corriente de
40 kA
cortocircuito
Rango de frecuencia 60 Hz
Se puede apreciar que la nueva corriente nominal de operacin est dentro de los
rangos de funcionamiento del interruptor ya que es menor que 1600 A.
Pgina 138 de 163
Ref.03056-14 Informev2
1839
Informe de repotenciacin Ingenieros Emetres Per SAC
Transformadores de corriente
Parmetros Unidades
Rango de frecuencia 60 Hz
Se puede apreciar que la nueva corriente nominal de operacin est sobre los
valores nominales de corriente del primario, esto provoca que se obtengan valores
de medida con errores mayores a los permitidos en el secundario del trasformador
de corriente, ocasionando malas lecturas de las protecciones en esa baha. Por esto
es necesario remplazar los transformadores de corriente por unos que tenga mayor
corriente nominal en el primario.
Slo se debern reajustar los valores de actuacin de los rels de proteccin segn
las nuevas condiciones de operacin de la lnea.
Ref.03056-14 Informev2
1840
Informe de repotenciacin Ingenieros Emetres Per SAC
Trampas de onda
Parmetros Unidades
Inductancia 0.2 mH
Se puede apreciar que la nueva corriente nominal de operacin est sobre el valor
de corriente nominal del equipo, ocasionando el mal funcionamiento de la trampa de
onda y pudiendo comprometer el equipo. Por esto es necesario remplazar la trampa
de onda por una con mayor corriente nominal.
Conductor de barras
Parmetros Unidades
Cantidad de Alambres y
37/4,18
Dimetro
Ref.03056-14 Informev2
1841
Informe de repotenciacin Ingenieros Emetres Per SAC
En el anexo se encuentra una tabla completa con las caractersticas elctricas para
este conductor.
Interruptor
Parmetros Unidades
Rango de corriente de 40 kA
cortocircuito
Rango de frecuencia 60 Hz
Ref.03056-14 Informev2
1842
Informe de repotenciacin Ingenieros Emetres Per SAC
Se puede apreciar que la nueva corriente nominal de operacin est dentro de los
rangos de funcionamiento del interruptor ya que es menor que 2500 A.
Parmetros Unidades
Rango de corriente de 40 kA
cortocircuito
Rango de frecuencia 60 Hz
Se puede apreciar que la nueva corriente nominal de operacin est dentro de los
rangos de funcionamiento del interruptor ya que es menor que 1600 A.
Parmetros Unidades
Rango de corriente de 40 kA
cortocircuito
Rango de frecuencia 60 Hz
Ref.03056-14 Informev2
1843
Informe de repotenciacin Ingenieros Emetres Per SAC
Se puede apreciar que la nueva corriente nominal de operacin est dentro de los
rangos de funcionamiento del interruptor ya que es menor que 1600 A.
Transformadores de corriente
Slo se debern reajustar los valores de actuacin de los rels de proteccin segn
las nuevas condiciones de operacin de la lnea.
Trampas de onda
Conductor de barras
Parmetros Unidades
Ref.03056-14 Informev2
1844
Informe de repotenciacin Ingenieros Emetres Per SAC
Cantidad de Alambres y
61/3,56 mm
Dimetro
En el anexo se encuentra una tabla completa con las caractersticas elctricas para
este conductor.
TABLA RESUMEN
SUBESTACION CARHUAQUERO
Ref.03056-14 Informev2
1845
Informe de repotenciacin Ingenieros Emetres Per SAC
Barras
10. CONCLUSIONES
Se puede apreciar que frente a esta repotenciacin de la lnea, para los equipos de
la baha correspondiente a la lnea de salida a la subestacin Carhuaquero, como el
interruptor, los seccionadores con o sin puesta a tierra, no tienen problemas ya que
soportan la nueva corriente que circula por ellos. En el caso de los transformadores
de corriente, la corriente nominal de la lnea en el nuevo escenario excede la
nominal de los equipos, esto provoca que se obtengan medidas y lecturas
incorrectas. Por esta razn se debern remplazar por unos que tengan el rango de
corriente nominal del primario superior al de rgimen permanente de operacin de la
lnea. Pasa lo mismo en el caso de la trampa de onda, la corriente nominal de la
lnea excede la nominal del equipo provocando mal funcionamiento y
comprometiendo el equipo. Por esta razn se debern remplazar por unos que
tengan el rango de corriente nominal superior al de rgimen permanente de
operacin de la lnea.
Para el caso de la subestacin Chiclayo Oeste, se puede apreciar que frente a esta
repotenciacin de la lnea, para los equipos de la baha de la lnea, que tanto el
interruptor, los seccionadores con o sin puesta a tierra, no tienen problemas ya que
soportan la nueva corriente que circula por ellos.
Pgina 145 de 163
Ref.03056-14 Informev2
1846
Informe de repotenciacin Ingenieros Emetres Per SAC
Por otro lado se puede concluir, que a simple vista, el conductor de barra soporta la
nueva corriente de la lnea pero es necesario realizar un anlisis ms exhaustivo
mediante una simulacin de flujo de potencia en las barras de las subestaciones de
la lnea involucrada, ya que con esto se obtienen las capacidades de la barra en
operacin y los datos con mayor exactitud en relacin a la nueva potencia de la
lnea.
Pgina146de165
PROYECTODEREPOTENCIACINDELALNEADETRANSMISINDE220kV
CHICLAYOOESTECARHUAQUERO
Ref.0305614Informev2
1847
Informe de repotenciacin Ingenieros Emetres Per SAC
11. ANEXO
Ref.03056-14 Informev2
1848
Informe de repotenciacin Ingenieros Emetres Per SAC
Ref.03056-14 Informev2
1849
Informe de repotenciacin Ingenieros Emetres Per SAC
Ref.03056-14 Informev2
1850
Informe de repotenciacin Ingenieros Emetres Per SAC
SE CHICLAYO OESTE
Ref.03056-14 Informev2
1851
Informe de repotenciacin Ingenieros Emetres Per SAC
Ref.03056-14 Informev2
1852
Informe de repotenciacin Ingenieros Emetres Per SAC
Ref.03056-14 Informev2
1853
Informe de repotenciacin Ingenieros Emetres Per SAC
Ref.03056-14 Informev2
1854
Informe de repotenciacin Ingenieros Emetres Per SAC
Ref.03056-14 Informev2
1855
Informe de repotenciacin Ingenieros Emetres Per SAC
Ref.03056-14 Informev2
1856
Informe de repotenciacin Ingenieros Emetres Per SAC
Ref.03056-14 Informev2
1857
Informe de repotenciacin Ingenieros Emetres Per SAC
SE CARHUAQUERO
Ref.03056-14 Informev2
1858
Informe de repotenciacin Ingenieros Emetres Per SAC
Ref.03056-14 Informev2
1859
Informe de repotenciacin Ingenieros Emetres Per SAC
Ref.03056-14 Informev2
1860
Informe de repotenciacin Ingenieros Emetres Per SAC
Ref.03056-14 Informev2
1861
Informe de repotenciacin Ingenieros Emetres Per SAC
Ref.03056-14 Informev2
1862
Informederepotenciacin IngenierosEmetresPerSAC
delalneadetransmisinde220kV Ref.0305614Informev2
ChiclayoOesteCarhuaquero Rev.2
METRADOYVALORREFERENCIAL(dolaresamericanos)
SUBESTACIONCHICLAYO220KVSUMINISTROSDEEQUIPOSYMATERIALES
METRADOYVALORREFERENCIAL(dolaresamericanos)
SUBESTACIONCHICLAYO220KVMONTAJEDEEQUIPOSYMATERIALES
TOTAL 22,300.00
PROYECTODEREPOTENCIACINDELALNEADETRANSMISINDE220kV 1863
CHICLAYOOESTECARHUAQUERO
Ref.0305614Informev2
Pgina162
Informederepotenciacin IngenierosEmetresPerSAC
delalneadetransmisinde220kV Ref.0305614Informev2
ChiclayoOesteCarhuaquero Rev.2
METRADOYVALORREFERENCIAL(dolaresamericanos)
SUBESTACIONCARHUAQUERO220KVSUMINISTROSDEEQUIPOSYMATERIALES
METRADOYVALORREFERENCIAL(dolaresamericanos)
SUBESTACIONCARHUAQUERO220KVMONTAJE
TOTAL 22,300.00
PROYECTODEREPOTENCIACINDELALNEADETRANSMISINDE220kV 1864
CHICLAYOOESTECARHUAQUERO
Ref.0305614Informev2
Pgina163
Informederepotenciacin IngenierosEmetresPerSAC
delalneadetransmisinde220kV Ref.0305614Informev2
ChiclayoOesteCarhuaquero Rev.2
METRADOYVALORREFERENCIAL(dolaresamericanos)
REPOTENCIACIONLINEADETRANSMISION220KV:CHICLAYOCARHUAQUERO
TOTAL 27,500.00
LongituddelaLinea(km) 40.00
Costoporkm(US/km) 687.50
PROYECTODEREPOTENCIACINDELALNEADETRANSMISINDE220kV 1865
CHICLAYOOESTECARHUAQUERO
Ref.0305614Informev2
Pgina164
Informederepotenciacin IngenierosEmetresPerSAC
delalneadetransmisinde220kV Ref.0305614Informev2
ChiclayoOesteCarhuaquero Rev.2
PRESUPUESTOREFERENCIAL(dolaresamericanos)
RESUMENREPOTENCIACIONLINEADETRANSMISION220KV:CHICLAYOCARHUAQUERO
PROYECTODEREPOTENCIACINDELALNEADETRANSMISINDE220kV 1866
CHICLAYOOESTECARHUAQUERO
Ref.0305614Informev2
Pgina165