HIPOTESIS 1: CARGAS PERMANENTES + SOBRECARGA

L3
CARGAS L2
go (Kg/m2) 80
po (Kg/m2) 30 L1
wo (Kg/m2) 80 H
S (m) 4.5 Lo h
L (m) 14.66
H (m) 1.5
h (m) 0.75
L
MaxD2 C2
11.57
L3 = 7.48 m
L2 = 3.74 m X
L1 = 3.74 m
Lo = 7.33 m A2
i (%) = 20.46 %

CALCULOS ESTATICOS REACCIONES L


q1 (Kg/m): 484.95
q2 (Kg/m): 99.24 L3 q1 MOMENTOS
MD ( Kg/m) : 848.34 L2 MD
A1 (Kg) : 1133.86
C1 (Kg) : 1133.86 L1 C1 max.Ms
D1 (Kg) : 1360.63 H
X (Kg) : -6786.74 D1 h
( ) : 66.86 HA
C2 (Kg) : -5529.58 max.Mi
MaxD2 ( Kg) : -12549.78
A2 (Kg) : -12921.03 VA L
VA (kg) : 3701.30 A1
HA (Kg) : 1110.84 Esfuerzos Normales
MaxMs ( Kg/m) : 477.19
MaxMi ( Kg/m) : 477.19
ING. MARCELO GEREZ
SERVICIOS DE INGENIERIA ESTRUCTURAL
AVDA. ALEM 1871 -5D -S.M. TUCUMAN CEL. 153574009
OBRA: HOJA N 1 FECHA:08/07/16
ESCALA: S/E REVISO: Ing. M.Gerez
UBICACIN: CALCULO: Ing. M. Gerez

COMITENTE: ESTRUCTURA DE PARES


ESTRUCTURA DE PARES
DATOS
7.48
SOLCITACIONES 2.5mm 3.74
qmx(Kg/m2) 495
Mmax(kgm) 848.34 1.5 3.74
Qmx(Kg) 1133.86
Nmx -( Kg) -12921.03 h = 200 mm 7.33 0.75
Nmx +( Kg) 6786.74
GEOMETRICOS Y MECANICOS
F (cm2) 19.68
W (cm3) 122.52 14.66
J (cm4) 1225.2
g (kg/m) 8.92
h ( cm ) 200 8 cm
e (mm ) 2.5 FLEXION
b (cm) 8
a (cm) 2 flexion 692.41 Kg/cm2 VERIFICACION DE PUENTE

NORMAL NORMAL

L.p = 374.10 cm flexion 344.85 Kg/cm2 VERIFICA


i= 7.89 cm
47.41
1.20
So (cm3)= 72.27
normal -656.56 Kg/cm2
TENSIONES MAXIMAS ING. MARCELO GEREZ
servicio 1348.97 Kg/cm2 VERIFICA SERVICIOS DE INGENIERIA ESTRUCTURAL
AVDA. ALEM 1871 -5D -S.M. TUCUMAN TEL: 4366438-CEL156446027
CORTE OBRA: VIVIENDA HOJA N 2 FECHA:10/08/09
ESCALA: S/E REVISO: Ing. M.Gerez
servicio 133.76 Kg/cm2 VERIFICA UBICACIN: CALCULO: Ing. M. Gerez

COMITENTE: ARQ. ERNESTO TANJUN ESTRUCTURA DE PARES


ESTRUCTURA DE PARES
DATOS

SOLCITACIONES
qmx(Kg/m2) 495
Mmax(kgm) 848.34
Qmx(Kg) 1133.86
Nmx -( Kg) -12921.03 h = 20 cm
Nmx +( Kg) 6786.74
GEOMETRICOS Y MECANICOS
F (cm2) 33.4
W (cm )3
214
J (cm4) 2140
g (kg/m) 26.2
h ( cm ) 20 9 cm
e (mm ) 7.5 FLEXION
a (cm) 9
flexion 396.42 Kg/cm2

NORMAL

L.p = 374.10 cm
i= 8.00 cm
46.74
1.20

normal -386.86 Kg/cm2


TENSIONES MAXIMAS
servicio 783.28 Kg/cm2 VERIFICA
AVDA. ALEM 1871 -5D -S.M. TUCU
CORTE OBRA:

servicio 58.99 Kg/cm2 VERIFICA UBICACIN:

COMITENTE:
7.48
3.74

1.5 3.74

7.33 0.75

14.66

VERIFICACION DE PUENTE

NORMAL

flexion 203.20 Kg/cm2 VERIFICA

ING. MARCELO GEREZ


SERVICIOS DE INGENIERIA ESTRUCTURAL
VDA. ALEM 1871 -5D -S.M. TUCUMAN TEL: 4366438-CEL156446027
ESCUELA HOJA N 2 FECHA:10/11/2015
ESCALA: S/E REVISO: Ing. M.Gerez
CALCULO: Ing. M. Gerez

COBA SRL ESTRUCTURA DE PARES