Clculos Elctricos

FM

Version 3.7

Lista de Cargas del Sistema


N 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 Proyecto: Instalacin: TAG Datos generales Descripcin CAMARA (FUENTE) MICROONDAS (FUENTE) INFRAROJOS (fuente) EQUIPOS DE INTERFASE Ubicacin Alimentacin Consumo unitario T. Uso Factor Cant. Tipo Voltios Sist. Valor Unidad FP Eff % Horas Oper. 13 AC 240 1 Fase 120 VA 0.95 98 8 1.00 16 AC 240 1 Fase 0.2 A 0.95 98 8 1.00 26 AC 240 1 Fase 0.2 A 0.95 98 8 1.00 18 AC 240 1 Fase 333 VA 0.95 98 8 1.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00 110 0.00

TOMOPORO CERCA PERIMETAL

POTENCIA TOTAL VA 1560.00 768.00 1248.00 5994.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 Sub Total kVA 9.57 W 1482.00 729.60 1185.60 5694.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9091.50 VAR 487.11 239.81 389.69 1871.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2988.23

TOTAL [VA] 9570.00

Clculos Elctricos Para Motor


Nombre del Proyecto: Cdigo: Nombre del motor: Nombre Codigo Motor XXX Fecha 3/26/2013

Datos del Motor


Tipo de Motor: MOTOR DE INDUCCION Tipo de alimentacin: Trifasico Clase NEMA: B De propsito general Tipo de aislamiento NEMA: F 155C MAX (operacin) Codigo letra rotor bloqueado NEMA: G 5.6 - 6.29 kVA/HP Potencia: 15 HP Potencia Activa salida: 11.19 kW (Rotor) Potencia Activa entrada: 12.29 kW (Alimentacin) Potencia Reactiva entrada: 14.29 kVA Voltaje nominal: 220 V Frecuencia de alimentacin: 60 Hz Corriente nominal: 37.51 A Corriente de arranque: 234.02 A (6.23 In) FP: 0.86 Eff.: 91 % Factor de Servicio: 1.15 N de Polos: 4 Cerramiento: TEFC Velocidad de sincronismo: 1800 RPM Deslizamiento aprox: 2.54 % Totalmente Cerrado con Velocidad de operacin aprox: 1754 RPM ventilacin externa Frame NEMA: 254T

Corriente a plena carga en base a un motor de: 15 HP con un voltaje de operacin de: 208 V la corriente a plena carga es: 46.2 A, segn CEN 2004

Datos de Alimentador
Factor mult. de corriente: Corriente de diseo: Tabla aplicada: Material: Voltaje de Operacin: Temp. Op.: Fact. Temp: Calibre: Capacidad del cable: Conductores por fase: Cap. Total por fase: % carga en el cable: % Reserva: Material del ducto: Resistencia: Reactancia: Longitud del cable: Cada de tensin: Mxima cada permitida: Cada durante el arranque: Max cada al arranque: 125 % (CEN 2004 430.22) 46.2A X 125% = 57.75A 310-16 CEN 2004 COBRE 0 - 2000 V 0 60C 26-30 C 100% de la capacidad nominal del cable 6 AWG/MCM 55 A 1 55 A 105.00% @57.75A -5.00% PVC 1.610 Ohm/kM CEN 2004 Tabla 9 0.00161 0.167 Ohm/kM CEN 2004 Tabla 9 0.000167 20.0 M 0.87 % a corriente nominal 5 % 1.72 % 6 X In (FP=0,2 IEEE Std 399-1997) 15 %

Ohm/M Ohm/M

4/82

Datos de Canalizacin
Calibre de conductores: 6 AWG / MCM Aislante: THW rea del cable: 46.92 mm2 CEN 2004 Tabla 5 Cantidad de cables: 3 rea Total: 140.77 mm2 Tamao tubera: 4 " Tipo : Tubo de PVC Rigido, Sch. 40 y tubo de PE-AD rea Total: 8110.96 mm2 CEN 2004 Tabla 4 % de Ocupacin: 2%

Proteccin y Arranque
Proteccin contra cortocircuitos Tipo: Interruptor automatico de disparo instantaneo Caracterstica de motor: Polifasico todo tipo proteccion menos E Ajuste mximo del dispositivo: 800 % la corriente de diseo (CEN 2004 430-152) Cap. de corriente del dispositivo: 250 A Amperios Frame Mxima corriente de ajuste: 369.60 A Amperios de disparo Marca: Cualquiera Polos: 3 Voltaje Max: 600 V Contactor Arrancador / Proteccin contra sobrecarga Tipo de Arranque: Arranque directo. Tipo de contactor: No Reversible Caracterstica: Motores con un factor de servicio no menor a 1,15 Ajuste de corriente segn CEN: Articulo 430-32 Factor para ajuste de proteccin: 125 % In Mxima corriente de ajuste: 57.75 A Tipo de Contactor Tamao del contactor: 5 NEMA AC-3 Voltaje de operacin: 460/575 V Cap. Del contactor hasta: 200 HP Contactos auxiliares NA Amper-Frame: 270 A Contactos auxiliares NC Sistema de puesta a tierra Tipo de conductor: Cantidad de conexiones: Calibre mnimo:

Cant.
2 2

Desnudo 2 Puntos 2/0 AWG

CEN 2004 tabla 250-122

5/82

Gabinete de control / potencia


rea de instalacin Clase: No Clasificada Divisin: N/A Gabinete o Tablero Ubicacin: Exterior Cerramiento: 4x NEMA Tipo de proteccin: Sellado contra agua y resistente a la corrosin. Los gabinetes tipo 4X tienen las mismas caractersticas que los tipo 4, adems de ser resistentes a la corrosin.

Capacidad de las barras: 300 A Instalacin: Auto soportado Otras caracteristicas


Botn de START
Botn de STOP Selector de operacin Voltmetro Ampermetro Pantalla digital Ventilacin interna

Comunicacin con PLC


Comunicacin con RTU Calentador interno Botn paro de emergencia Luz indicadora 1 Luz indicadora 2 Luz indicadora 3

TX auxiliar para control


Fusibles para sist. control

Verde Roja Ambar

Notas

V3.7

fm

6/82

220 V

Barra

3(1 X 6 AWG/MCM)

Interruptor

250A (AF) / 369.6A (AT)

220 V NEMA 5 AC-3

Arrancador
57.75A (AT)

120 V

Circuito de Control

15 HP

Clculos Elctricos Para Transformador


Nombre del Proyecto: Cdigo: Nombre del transformador: Fecha 3/26/2013

Datos Elctricos
Potencia: Tipo de alimentacin: Impedancia base: Frecuencia: Relacin de Trans.: 75 kVA Trifasico 3.07 m 60 Hz 1:1 Clase del transformador : Transformadores Monofsicos de Distribucin Tipo Intemperie/Poste Enfriamiento: (IEEE C57.93) TIPO OA Sumergido en aceite, con enfriamiento natural.

Primario Tipo de conexin: Delta Hilos: 2 Voltaje de lnea: 0.48 kV L-L Voltaje de fase: 0.48 kV Corriente de lnea: 90.21 A Corriente de Fase: 52.08 A Conexin del neutro: No tiene

Secundario Estrella 3 0.48 kV L-L 0.27712813 kV 0 kV L-N Corriente de lnea: 90.21 A Corriente de Fase: 90.21 A Conexin del neutro: solidamente a tierra Tipo de conexin: Hilos: Voltaje de lnea: Voltaje(s) de fase:

(480 V) (0 V)

Alimentadores
Primario Factor mult. de corriente 125 % Corriente de diseo: 112.76 A Material: COBRE Voltaje de Operacin Cable: 5001-35000 V Tabla aplicada: Tabla 310.73 CEN 2004 Calibre 2 AWG / MCM Temp. Op. 90C 0 Fact. Temp 36-40 C Corriente nominal cable 150 A Conductores por fase 1 Cap. Total por fase 150 A % carga en el cable 75.18% % Reserva 24.82% Calibre del neutro: 4 AWG / MCM Conductores por neutro: 1 Secundario Factor mult. de corriente 125 % Corriente de diseo: 112.76 A Material: COBRE Voltaje de Operacin Cable: 0 - 2000 V Tabla aplicada: Tabla 310.16 CEN 2004 Calibre 1/0 AWG / MCM Temp. Op. 90C Fact. Temp 36-40 C Corriente nominal cable 154.7 A Conductores por fase 1 Cap. Total por fase 154.7 A % carga en el cable 72.89% % Reserva 27.11% Calibre del neutro: 4/0 AWG / MCM 0 Conductores del neutro: 2 0

Datos de canalizacin
Primario Calibre de conductores Aislante rea del cable Cantidad de cables rea Total Tamao tubera Tipo : rea Total % de Ocupacin 2 AWG / MCM THW Tabla 5 CEN 2004 86.14 mm2 3 (Fases + Neutro igual calibre) 258.42 mm2 4 " Tubo de PVC, Tipo A Tabla 4 CEN 2004 8946.53 mm2 2.89% Secundario Calibre de conductores Aislante rea del cable Cantidad de cables rea Total Tamao tubera Tipo : rea Total % de Ocupacin 1/0 AWG / MCM THW Tabla 5 CEN 2004 143.70 mm2 8 (Fases + Neutro igual calibre) 1149.58 mm2 4 " Tubo de PVC Rigido, Sch. 40 y tubo de PE-AD Tabla 4 CEN 2004 8110.96 mm2 14.17%

8/82

Protecciones
Primario Limitaciones sobre el lugar: Cualquiera % Impedancia del TX: Mas de 6% pero menos de 10% Tipo de proteccin: Fusible Tabla 450.3(B) CEN 2004 Ajuste max. del dispositivo: 250 % I de diseo Cap. de corriente del dispositivo: 15 A AF Max corriente de ajuste: 281.91 A AD Sistema de puesta a tierra Tipo de conductor: Cantidad de conexiones: Calibre mnimo: Secundario

Tipo de proteccin: Interruptor automtico Tabla 450.3(B) CEN 2004 Ajuste max. del dispositivo: 125 % I de diseo Cap. de corriente del dispositivo: 200 A AF Max corriente de ajuste: 140.95 A AD

Desnudo 2 CEN 2004 tabla 250-122 2/0 0

AF: AMPERIOS FRAME AD: AMPERIOS DE DISPARO

Otras caractersticas
Indicador de temperatura Indicador de presin Indicador de nivel de liquido
Indicador de sobrecarga

Descargador de sobre voltajes Instalado en Interior Exterior

Color de pintura:

Gris

V3.7

fm

9/82

Proyecto: 0

TX:

Cargas del Transformador


0%
N 1 2 3 4 5 6 7 8 9 10 Descripcin Carga Unidad FP Ef. VA 0 0 0 0 0 0 0 0 0 0 Sub Total W 0 0 0 0 0 0 0 0 0 0 0.00 VAR 0 0 0 0 0 0 0 0 0 0 0.00

VA VA HP HP HP HP

0.707 90

Voltaje del sistema 480 V

100 %

P2 Q2

Total

0 VA

Nota: todas las cargas se consideran trifsicas para fines del calculo, a menos que se exprese directamente en VA

Uso

Reserva

Capacidad del Transformador

0.00% Uso 100.00% Reserva 75 kVA Reserva

75 kVA

Clculos Elctricos Banco de Baterias


Segn norma IEEE 1115-2000 Nombre del Proyecto: Cdigo: Identificador : Fecha 3/26/2013

Tension terminal de celda: Cap. Inicial del Banco: Temp. electrolito: Margen de diseo: Factor de envejecimiento

1.1 V A-H C 1.10 FD 1.25 FE

Tabla de carga Carga 1 2 3 4 5 6 Tiempo Inicio Descripcion (min) L1 0 L2 0 L3 0 L4 0 L5 0 L6 0 0 Tiempo Fin (min) 30 0 0 0 0 0 0 Duracion (min) 30.00 0.00 0.00 0.00 0.00 0.00 0.00 Corriente (A) 37.18 0 0 0 0 0 0 Capacidad (A-H) 18.59 0.00 0.00 0.00 0.00 0.00 0.00
Capacidad Preliminar

Aleatoria LA

TOTAL
Curva de carga
Corriente (A) 40 35

18.59 A-H

30 25 20 15
10 5

0
0 5 10 15 20 25 30 35 Tiempo (min)

Tabla de comportamiento general de carga SEC 1 2 3 4 5 6 7 8 9 10 Desde (min) 0 N/A N/A N/A N/A N/A N/A N/A N/A N/A Hasta (min) 30 N/A N/A N/A N/A N/A N/A N/A N/A N/A Duracion(min) 30.00 N/A N/A N/A N/A N/A N/A N/A N/A N/A Total A 37.18 N/A N/A N/A N/A N/A N/A N/A N/A N/A Capacidad (A-H) 18.59 N/A N/A N/A N/A N/A N/A N/A N/A N/A

11/82

Demanda Maxima: Demanda Minima: Demanda Promedio:

37.18 A 37.18 A 37.18 A Calculo del factor de capacidad T2 A para T1 A para T2 266 -

n 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

T (MIN) 30.000 -

T1 30 -

Factor K1 1.387 -

Factor K2 -

Factor Kt 1.387 -

Curva del factor de correccin por temperatura de electrolito 3


2.5 2 Factor Tt
1s - 10 min 30 min

1.5 1
0.5 0

60 min
3H

5-8H

-29

-20

-10

0
C

10

20

25

12/82

Hoja de seleccin de capacidad


Periodo Carga (A) Cambio de carga (A) Duracion (min) Tiempo final de seccion (min) Factor de Factor de capacidad (Kt) temperatura (Tt) Valor positivo (AH) Valor negativo (AH)

37

37

30.000

30.000

1.387

1.000 Sub total Total 1.000 #N/A Sub total Total 1.000 #N/A #N/A Sub total Total 1.000 #N/A #N/A #N/A Sub total Total 1.000 #N/A #N/A #N/A #N/A Sub total Total 1.000 #N/A #N/A #N/A #N/A #N/A Sub total Total 1.000 #N/A #N/A #N/A #N/A #N/A #N/A Sub total Total #N/A Total

52 51.58 51.58 51.58 0.00 0.00 0.00 52 0 0 0.00 0.00 52 0 0 0 0.00 0.00 52 0 0 0 0 0.00 0.00 52 0 0 0 0 0 0.00 0.00 52 0 0 0 0 0 0 0.00 0.00 0.000 0.00 51.57 AH

0 0.00

1 2

37.18 0.00

37 -37

30.000 0.000

30.000 0.000

1.387 #N/A

0.00 #N/A 0.00

1 2 3

37 0 0

37 -37 0

30.000 0.000 0.000

30.000 0.000 0.000

1.387 #N/A #N/A

0 #N/A 0 0.00

1 2 3 4

37 0 0 0

37 -37 0 0

30.000 0.000 0.000 0.000

30.000 0.000 0.000 0.000

1.387 #N/A #N/A #N/A

0 #N/A 0 0 0.00

1 2 3 4 5

37 0 0 0 0

37 -37 0 0 0

30.000 0.000 0.000 0.000 0.000

30.000 0.000 0.000 0.000 0.000

1.387 #N/A #N/A #N/A #N/A

0 #N/A 0 0 0 0.00

1 2 3 4 5 6

37 0 0 0 0 0

37 -37 0 0 0 0

30.000 0.000 0.000 0.000 0.000 0.000

30.000 0.000 0.000 0.000 0.000 0.000

1.387 #N/A #N/A #N/A #N/A #N/A

0 #N/A 0 0 0 0 0.00

1 2 3 4 5 6 7

37 0 0 0 0 0 0

37 -37 0 0 0 0 0

30.000 0.000 0.000 0.000 0.000 0.000 0.000

30.000 0.000 0.000 0.000 0.000 0.000 0.000

1.387 #N/A #N/A #N/A #N/A #N/A #N/A

0 #N/A 0 0 0 0 0 0.00

Aleatoria

0.000

0.000

#N/A

0.000

Tamao de la seccin mayor 51.57 AH + Seccin aleatoria 0AH = Tamao sin correccin:

Capacidad final :TSC X FD X FE =


V3.7

70.91

AH
fm

13/82

Cada de tensin sistemas Trifasico (Conductor de Cobre)


Carga: Longitud del circuito: Tensin del sistema FP: Calibre del Cable: Material de la tubera: R: X: 35000 VA 100 m 220 V 0.9 2 0.31 OHM/kM 0.074 OHM/kM 35 kVA

k
2 Cond. por fase

(r cos x 5 kV 2

V (%) (kVA

Cada de tensin:
Voltaje Final:

V(%) = 2.25
215.04 V

de Cobre)
k (r cos x sen ) 2 10 5 kV

k=0.0006

V (%) (kVA m) k

Regulacin Max.

Cada de tensin sistemas Monofasicos (Conduc


3%

5%

Carga: Longitud del circuito: Tensin del sistema FP: Calibre del Cable: Material de la tubera: R: X: 2

7210 VA 40 m 240 V 1

7.21 kVA

1 0.62 OHM/kM 0.148 OHM/kM

Cada de tensin:
Voltaje Final:
V3.7

V(%) = 0.62
238.5 V

ofasicos (Conductor de cobre)


k
Cond. por fase k=0.0021

(r cos x sen ) 5 kV 2

Distancia 0 0 0 0.00215278

V (%) (kVA m) k

0.62086111 1 3 1000 22 10

%) = 0.62

220

Caida de tension en sistemas DC


Resistividad del cobre: Distancia del tramo:
Tipo de carga Vatios Amperio

0.018 200

mm 2 m
m

Voltaje del sistema: Calibre del cable: Dimetro del cable: Resistencia del cable Resistencia de carga Voltaje en terminales Regulacin:

48

VDC

1.63 4.42 1152 47.82 0.38

mm VDC %

Calculo de corriente de corto circuito


Tension del sistema: 0.48 kV Lugar: Barra 480

Impedancias del sistema


Equipo Red Cable R 0.194 0.013 X 0.788 0.004

Rt = Xt = Zt = Icc = R/X = Factor K = Icc asimetrica =

Total 0.2072 0.7920 0.8186 0.34 kA sim 0.26

1.44
0.69 kA asim

IEC60909

Calculo de corriente de corto circuito


Motor Trifsico
Anlisis

Potencia: 15 HP Voltaje nominal: 0.22 kV en el lado de la falla Eficiencia: 91 % FP: 0.86 Tipo: Motor de alta velocidad

Sub Transitorio Transitorio

Motor de alta velocidad Motor de Baja velocidad Compensadores

Xd" 15 35 25

Xd 25 50 40

Xd 80 100 160

T1. Reactancias en % de motores y compensadores

Se tiene que:

Sn
Sn =

P FP
14.29 kW

Luego:

X=

X V 2 100 S n
25 846.59 mOhm 0.846594876

Xm =

Rm 0,2Xm
Rm = 169.32 mOhm

R X

m m

0.20 0.863360759 863.36 mOhm

Zt R X
2 t

2 t

Zt=

I cc , sim
Por lo tanto: Icc, sim =

V n2 3 Zt
147.12 A simtricos

Luego tenemos que:

K=

1.54

, para

Rt 0.20 Xt

( IEC 60909 )

I cc 2 K I cc,sim
Finalmente:
Basado en la norma UTE C 15-105 y IEC 60 909.

Icc =

320.61

A asimtricos
1.540952

Calculo de corriente de corto circuito


Transformador trifsico Potencia: 75 Voltaje en lado de falla (V2): 0.48 Voltaje de corto circuito %: 4 Ra: 0.2072322 Xa: 0.79197438 kVA Vcc (%) 630 4 800 4.5 kVA kV Tabla T1 Ohm Ohm 1000 5 1250 5.5

V1:

13.8 kV
Ohm reflejada Ohm reflejada

Rr 0.00025072 Xr 0.00095815 1600 6

T1. Tensin de cortocircuito Vcc normalizada para los transformadores MT/BT de distribucin pblica.

2000 7

Se tiene que:

Z t Vcc
Zt =

Vn2 Sn

Z del transformador

Por lo tanto:

122.88 m

0.12288

Se tiene que:

X t Zt
Xt =

X del transformador

Por lo tanto:

122.88 m

Xr =0.958m

Se tiene que:

Rt 0,20 X t
Rt =

R del transformador

Por lo tanto:

24.576 m

Rr =0.25m

Luego:

R X

total total

0.20

0.126302234

Ztotal (Rt Rr )2 (Xt Xr )2


Se tiene que:

Zt =

126.30

I cc , sim
Icc, sim =

V n2 3 Zt
2.19 kA simetricos

Por lo tanto:

Luego tenemos que:

K = 1.54

, para

Rt 0.20 Xt

( IEC 60909 )

I cc 2 K I cc,sim
Finalmente:
Basado en la norma UTE C 15-105 y IEC 60 909.

Icc =

4.78

kA asimetricos
1.540138128

Calculo de corriente de corto circuito


Aporte de corriente de la red electrica

Tension Nominal: Icc: Scc: Icc Asimetrica: Ra/Za: Za: Xa: Ra: Ra/Xa: Factor K:

13.8 17 234.6 35.27

kV kA sim MVA kA asim

0.239 0.812 0.788 0.194 0.246 1.467

(IEC 60909)

Red electrica

13.8kV 17kA sim

N 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

PDVSA 90619.1.089 Cada de tensin mtodo amperios pie Potencia de lmparas: 430 W Voltaje de operacin: 220 V Distancia entre lmparas: 30 M Tramo inicial: 20.00 M Cantidad de Luminarias: 12 Distancia entre lmpara: 98.424 FT Distancia Amperios Distancia (FT) A-pie (M) 65.6 20.00 -1.95 65.6 20.00 128.2 1.95 131.2 40.00 256.4 1.95 196.8 60.00 384.7 1.95 262.4 80.00 512.9 1.95 328.0 100.00 641.1 1.95 393.6 120.00 769.3 1.95 459.2 140.00 897.5 1.95 524.8 160.00 1025.7 1.95 590.4 180.00 1154.0 1.95 656.0 200.00 1282.2 1.95 721.6 220.00 1410.4 1.95 787.2 240.00 1538.6 1.95 852.8 260.00 0.0 1.95 918.4 280.00 0.0 1.95 984.0 300.00 0.0 1.95 1049.6 320.00 0.0 1.95 1115.2 340.00 0.0 1.95 1180.8 360.00 0.0 1.95 1246.4 380.00 0.0 1.95 1312.0 400.00 0.0 1.95 1377.6 420.00 0.0 Total Calibre del conductor: Factor K: Area: 10001.0 A-P

21.4

66360

Mil Circular

Caida de tension: % de Caida de tension:

3.23 V 1.47%

Calculo de cada de tensin para circuitos monofsicos de iluminacin

Tensin del sistema Factor de potencia Cantidad de Postes P. Poste D0 DEP Potencia [VA] 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 0

0.12 kV 0.95 29 100 VA 114 m 5m Paso de Distancia [m] 114 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 Distancia [m] 114 119 124 129 134 139 144 149 154 159 164 169 174 179 184 189 194 199 204 209 214 219 224 229 234 239 244 249 254 0 kVA x m 11.4 11.9 12.4 12.9 13.4 13.9 14.4 14.9 15.4 15.9 16.4 16.9 17.4 17.9 18.4 18.9 19.4 19.9 20.4 20.9 21.4 21.9 22.4 22.9 23.4 23.9 24.4 24.9 25.4 0

Calibre del cable: Canalizacion: Resistencia: Reactancia:

N 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

(r cos x sen ) 5 kV 2

k = 0.005

V (%) (kVA m) k
V(%) = 3.07

Voltaje Final:

Total

533.6 kVA x m

ofsicos de iluminacin

re del cable: 0.39 /km 0.144 /km

(r cos x sen ) 5 kV 2

3.07904976 0.00577033 0.31756043 0.3122499

V (%) (kVA m) k

116.31 V

Calculo de Alimentador Datos de la Carga Carga nominal: 9000 Tension del sistema: 220 Fp: 1 Eff: 100 Factor de diseo: 125 Corriente: 23.62

W V % % A

Datos del Conductor Calibre: 10 AWG/MCM Capacidad nominal: 30 A Factor correcion Temp: 1 Conductores por fase: 2 Capacidad Total: 60.00 A

Lista de Cables Monopolares


Cant. Act.X Fase
1 1 2 2 1

Distancia (M)

Calibre

TAG

COVENIN 398
3(1#4/0 AWG) 3(1#16 AWG) 3(2#500 MCM) 3(2#16 AWG) 1(1#16 AWG)+1T#16 AWG (#) (#) (#) (#) (#) (#) (#) (#) (#) (#) (#) (#) (#) (#) (#) (#) (#) (#) (#) (#) (#) (#) (#) (#) (#)

Tension Oper (V)

Tension Max (V)

Tipo Aislante XLPE-PVC XLPE-PVC XLPE-PVC XLPE-PVC THHN

Desdes

Hasta

P-001

13800 13800 220 480 480

15000 15000 600 600 600

250 300 260 100 100

TEST TEST TEST TEST TEST

TEST TEST TEST TEST TEST

4/0 AWG 16 AWG 500 MCM 16 AWG 16 AWG

3 3 3 3 1

Calibre Neutro

Fases

Proyecto:

Nomenclatura COVENIN

X (n Y ) mN # Y ' pT # Y ' '

Indicacin de X fases de n conductores monopolares por fase, calibre Y, mas m conductores de neutro (N) calibre Y, mas p Links Aralven (Cables)

Cantidad Cond. Tierra (M)

Cant. Neutro X GF

Cant. Tierra X GF

Cantidad Cond. Neutro (M)

Cantidad Cond. Activo (M)

Cond Act.

Calibre Tierra

Observaciones

3 3 6 6

16 AWG

1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

750 900 1560 600 100 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 100 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Y, mas m conductores de neutro (N) calibre Y, mas p conductores de tierra (T) calibre Y.

AISLANTES DE CONDUCTORES
Tipo Descripcion

DESNUDO Sin recubrimiento FXT TFF TWF Los conductores flexibles de cobre tipo FXT, TFF y TW-F son utilizados para alambrado de aparatos, c elctricos de control, bateras de vehculos, instalaciones generales industriales y comerciales donde se flexibilidad debido a las dificultades de trabajo y en general como cables sometidos a continuo movimie especifica en el National Electrical Code. Este tipo de conductor puede ser usado en lugares secos y h mxima de operacin es 60 C y su tensin de servicio para todas las aplicaciones es 600 V. RHHN THHN AISLANTE DE MATERIAL TERMOPLASTICO, XLPE 600 V. - 90 C, ANTILLAMA.

Los conductores de cobre tipo THHN o THWN-2 son utilizados para circuitos de fuerza y alumbrado en industriales, comerciales y residenciales, son especialmente aptos para instalaciones especiales por du en zonas abrasivas o contaminadas con aceites, grasas, gasolinas, etc. y otras sustancias qumicas co solventes, etc., tal como se especifica en el National Electrical Code. Este tipo de conductor cuando es puede ser usado en lugares secos con temperatura mxima de operacin de 90 C, pero si es utilizado ser usado en lugares secos y hmedos con temperatura mxima de operacin de 90 C, as mismo cua aceites, grasas, pinturas, solventes qumicos, etc., su temperatura mxima de operacin es 75 C. En c servicio, para todas las aplicaciones, es de 600 V.

THW

Los conductores de cobre tipo THW son utilizados para circuitos de fuerza y alumbrado en edificacione comerciales y residenciales donde se requiera de mayor seguridad, tal como se especifica en el Nation tipo de conductor puede ser usado en lugares secos y hmedos, su temperatura mxima de operacin de servicio para todas las aplicaciones es 600 V.

TTU

Los conductores de cobre tipo TTU-0.6 KV. son utilizados para circuitos de fuerza y alumbrado en edific comerciales, son especialmente aptos para instalaciones a la intemperie o directamente enterrados, tal el National Electrical Code. Este tipo de conductor puede ser usado en lugares secos y hmedos, su te operacin es 75 C y su tensin de servicio para todas las aplicaciones es 600 V.

TW

Los conductores de cobre tipo TW son utilizados para circuitos de fuerza y alumbrado en edificaciones comerciales y residenciales, tal como se especifica en el National Electrical Code. Este tipo de conducto lugares secos y hmedos, su temperatura mxima de operacin es 60 C y su tensin de servicio para es 600 V

XHHW

Los conductores de cobre tipo XHHW son utilizados para circuitos de fuerza y alumbrado en edificacion comerciales, son especialmente aptos para instalaciones a la intemperie, tal como se especifica en el N Este tipo de conductor puede ser utilizados en lugares secos y hmedos, su temperatura mxima de op tensin de servicio para todas las aplicaciones es 600 V.

ORES

para alambrado de aparatos, cableado de tableros striales y comerciales donde se requiera de gran sometidos a continuo movimiento, tal como se er usado en lugares secos y hmedos, su temperatura licaciones es 600 V.

TILLAMA.

uitos de fuerza y alumbrado en edificaciones nstalaciones especiales por ductos difciles y usarse y otras sustancias qumicas corrosivas como pinturas, e tipo de conductor cuando es utilizado como THHN n de 90 C, pero si es utilizado como THWN-2 puede racin de 90 C, as mismo cuando estn expuestos a ma de operacin es 75 C. En cuanto a su tensin de

za y alumbrado en edificaciones industriales, omo se especifica en el National Electrical Code. Este peratura mxima de operacin es de 75 C y su tensin

de fuerza y alumbrado en edificaciones industriales y o directamente enterrados, tal como se especifica en gares secos y hmedos, su temperatura mxima de s 600 V.

y alumbrado en edificaciones industriales, cal Code. Este tipo de conductor puede ser usado en C y su tensin de servicio para todas las aplicaciones

erza y alumbrado en edificaciones industriales y , tal como se especifica en el National Electrical Code. su temperatura mxima de operacin es 90 C y su

Metros de cable por nivel de tension (TOTAL)

V / Calibr e

600 0 800 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1560 0 0 0 0 0 0 0 0 0 0

5000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

15000 0 900 0 0 0 0 0 0 0 0 0 0 0 0 750 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

3500 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

18 AWG 16 AWG 14 AWG 12 AWG 10 AWG 8 AWG 6 AWG 4 AWG 3 AWG 2 AWG 1 AWG 1/0 AWG 2/0 AWG 3/0 AWG 4/0 AWG 250 MCM 300 MCM 350 MCM 400 MCM 500 MCM 600 MCM 700 MCM 750 MCM 800 MCM 900 MCM 1000 MCM 1250 MCM 1500 MCM 1750 MCM 2000 MCM

Ocupacion de ductos
Cable Monopolar N 1 2 3 4 5 Calibre Aislante Cantidad 6 0 0 0 0 Diametro* mm 14.53 4.60 4.60 4.60 4.60 Area por cable Total Grupo mm2 mm2 165.81 16.62 16.62 16.62 16.62 Area Total 994.88 0.00 0.00 0.00 0.00 994.88 mm2

Tipo de Ducto:

Diametro: Pulgadas Dimetro mnimo recomendado 2 1/2 " Diametro** Area Total 101.5 mm 8091.37 mm2

Max. Ocupacion
*Fabricante del cable: Aralven ** Segn tabla del CEN 2004

40.00%

Ocupacin

12.30%

Potencia

Factor de Potencia Potencia: FP (%): Cos(): Sen(): 18600 60 0.6 0.80

Aparente [VA]

Activa [W]

Reactiva [VAR]

S P Q

31000.00 VA 18600.00 W 24800.00 VAR

S VA W VAR 18600 31000 23250

P 11160 18600 13950

Q 14880 24800 18600

x p Q S 0 18600.00 18600.00 18600.00 0 18600.00 0 24800.00

y 0 0 0 24800.00 0 24800.00 18600.00 0

eje

Triangulo de potencia
30000 25000 20000
(VAR)

15000 10000 5000 0 0 5000 10000 15000


(W)

20000

25000

30000

TABLERO ELECTRICO
Tipo de Tablero: NLAB Polos: 18 Voltaje del Tablero [V]: 240 Instalacion: Auto soportado Cerramiento NEMA: 3R Corriente de Barras [A]: 100 C. Interrupcin [kA]: 22 Color: GRIS INDUSTRIAL Interruptor principal 3P [A]: 400 Fases: Proyecto: 3 Alimentador Principal: Calibre Aislante 250 MCM A B THHN C ejemplo Instalacion: Cnd X fase 1 Conduit 4 Entrada Superior Nombre del Tablero: ejemplo ejemplo

Tuberia Carga Conectada VA 1500 Carga N 1 1500 1500 500 CARGA 4 500 500 1000 RESERVA 1000 1000 PVC 2 1 PVC 2 1 Material Diametro [pul] Cond. por fase

Conductor Aislante Calibre

Interruptor Tipo In [A] 3P N 1 N 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36

Interruptor In [A] 3P Tipo Calibre

Conductor Aislante Cond. por fase

Tuberia Diametro [pul] Material VA 1000 Carga Conectada

THHN

6 AWG

QC

20

3 5 7

30

THQC

250 MCM

TTU

PVC

1000 1000 1250

Carga N 2

THHN

14 AWG

QC

20

9 11 13 15 17 19 21 23 25 27 29 31 33 35

90

THQC

14 AWG

TTU

PVC

1250 1250 1000 1000 1000

CARGA 3

RESERVA

VA A B C
V3.7

A 15.04 15.04 15.04

% POT. 0.33 0.33 0.33

RESERVA 6000.00 32.00% VA

BARRA DE TIERRA BARRA DE NEUTRO

6250 6250 6250 18750

TOTAL

TABLERO ELECTRICO
Tipo de Tablero: NLAB Polos: 36 Voltaje del Tablero [V]: 240 Instalacion: Auto soportado Cerramiento NEMA: 3R Corriente de Barras [A]: 100 C. Interrupcin [kA]: 22 Color: GRIS INDUSTRIAL Interruptor principal 3P [A]: 400 Fases: Proyecto: 3 Alimentador Principal: Calibre Aislante Cnd X fase 1/0 AWG A B THHN 2 ejemplo Instalacion: Conduit 4 Entrada Superior Nombre del Tablero: ejemplo ejemplo

Tuberia Carga Conectada carga 1 carga 4 VA 1500 1500 Material PVC PVC Diametro [pul] 2 2 Cond. por fase 1 1

Conductor Aislante THW THW Calibre 12 AWG 12 AWG

Interruptor Tipo QC QC In [A] 3P 20 20 N 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 N 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36

Interruptor In [A] 3P PVC PVC Tipo 2 2 Calibre 1 1

Conductor Aislante THW THW Cond. por fase 12 AWG 12 AWG

Tuberia Diametro [pul] QC QC Material 20 20 VA 1500 1500 Carga Conectada carga 2 reserva

VA A B 3000 3000

A 7.22 7.22

% POT. 50.00 50.00

RESERVA 1500.00 25.00% VA


BARRA DE TIERRA BARRA DE NEUTRO

V3.7

TOTAL

6000

SEPARACIN MINIMA RECOMENDADA ENTRE DUCTOS Y BANDEJAS


NIVELES 1.- APLICACIONES ALTAMENTE SUSCEPTIBLES A RUIDOS.
SEALES DE INSTRUMENTOS DE 4-20 mA 24Vdc, OTRAS SEALES ANLOGAS < 50Vdc Y TRASMISORES DIGITALES SEALES DISCRETAS DE 24 Vdc BUSES DE COMUNICACIONES DE INSTRUMENTOS ANALGICOS +- 50Vdc BUSES DE COMUNICACIONES DE INSTRUMENTOS DIGITALES +- 24Vdc CIRCUITOS DE TERMOCUPLA Y RTD CIRCUITOS TELEFNICOS

2.- APLICACIONES MEDIANAMENTE SUSCEPTIBLES A RUIDOS


ILUMINACION E INTERRUPTORES DE 24Vdc O MENOS SEALES ANALOGICAS > 50 Vdc < 28 Vac DE RIZO

3.- APLICACIONES BAJAMENTE SUSCEPTIBLES A RUIDOS


ALIMENTADORES EN 120/240 Vac DE MENOS DE 20 A ILUMINACION E INTERRUPTORES DE 24Vdc O MAS SEALES ANALOGICAS > 50 Vdc < 28 Vac DE RIZO

4.- APLICACIONES DE POTENCIA INTERMEDIA


PRIMARIOS Y SECUNDARIOS DE TRANSFORMADORES < 5kVA BARRAS AC O DC 0-800 V CON CORRIENTES MAYORES A 20 A

5.- APLICACIONES DE ALTA POTENCIA


BARRAS AC O DC> 1kW Y/O CORRIENTES MAYORES A 800 A

CASO DE ESTUDIO CASO: NIVEL A: 1 NIVEL B: 5

SEPARACIN MINIMA RECOMENDADA:

26 IN
NOTAS
1 Esta hoja no aplica para ductos no metlicos

66.04 CM

2 La distancia definida aqu, indica el espacio mnimo entre el tope y el fondo de las bandejas o el espacio lateral entre ellas. 3 Estas distancias tambin aplican como el espacio entre bandejas y equipos de potencia menores a 100kVA 4 Las distancia mnimas de los ductos se indican en referencia al exterior de los mismos 5 Cuando seales de distintos niveles deban cruzarse, deben hacer en un ngulo de 90. Cuando no sea posible mantener las distancias de separacin se debe interponer una barrera metlica aterrada. 6 Los niveles 3 y 4 pueden ser canalizados en la misma bandeja siempre que se coloque una barrea entre ellos 7 Cuando sea impractico separarlos, los niveles 1 y 2 pueden ser usados en la misma bandeja, siempre que tenga una barrera metlica aterrada entre ellos. 8 Las bandejas de todos los niveles deben ser metlicas solidamente aterradas. 9 Bandejas y ductos de los niveles 1 y 2 no podrn ser llevadas en paralelo con equipos de alta potencia cerrados mayores a 100kVA a 150 cm de las bandejas y 80 cm de los ductos. 10 Cunado no se posible mantener el espacio indicado arriba, se debe minimizar el recorrido en paralelo de las rutas, en tal caso, el recorrido no podr superar los 150 cm de longitud. Fuentes: PIP PCCEL001 IEEE 518

BANDEJAS PORTACABLES
Caso de Estudio

Lista de Cables Tipo de Bandeja: Material: Carga de Trabajo: Espacio entre soportes: Clase NEMA: 8C Calculado: Ancho Seleccionado: 22.30 cm 22.5 cm Lbs/ft. ft. CABLES MONOPOLARES
Cables 1000kCMIL o mayores Cables 250kCMIL a 1000kCMIL Cables Mayores a 1000kCMIL con menores a 1000 kCMIL

Con algun cable instalado entre 1/0 y 4/0

CABLES MULTICONDUCTORES
Calibres 4/0 o Mayores Calibres menores a 4/0 Cables 4/0 o mayores con cables menores a 4/0 Cables control / alumbrado / sealizacion

Bandeja de ancho menor a la requerida

2 Tipo de bandeja Escalera Perforado ranurado

3 1 Carga de Trabajo Distancia entre soportes 50 8 75 12 100 16 20

2 Material Altura Aluminio Acero Inoxidable Acero Galvanizado Fibra de Vidrio

Seleccin 2 3 4 5 6

ancho de bandejas 15 22.5 30 45 60 75 90

Bandejas #### 22.30 33.75 11.09 68.60 24.15 49.81 9.70

Lista de Cables

Seleccin

Bandejas

CABLE MONOPOLAR
Bandejas de fondo escalera o ventilado

Cables 1000 kCMIL o mayores


Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2) Area Total (mm2) Ancho Requerido (cm)

5 10 10 36 36
392-10(a) (1) NEC 2008 Fuente: lugsdirect.com

25.40 28.40 31.11 33.60 35.92

506.71 633.47 760.13 886.68 1013.36

2533.54 6334.71 7601.34 31920.59 36480.86

12.7 28.4 31.11 120.96 129.312 322.48 64.50

Ancho de conductores 20% Reserva:

Ancho total de Bandeja (cm)

386.98

Cables 250kCMIL a 1000kCMIL


Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2) Area Total (mm2) Ancho Requerido (cm)

5 8 5 2 5
392-10(a) (2) NEC 2008 Fuente: Aralven

13.51 13.51 19.42 14.66 19.42

143.35 143.35 296.20 168.79 296.20

716.75 1146.81 1481.01 337.59 1481.01

2.58 4.13 5.33 1.22 5.33 18.59 3.72

Ancho Minimo (cm) 20% Reserva:

Ancho total de Bandeja (cm)

22.30

Cables mayores a 1000kCMIL con menores a 1000kCMIL


Cables Mayores o iguales a 1000kCMIL
Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2) Area Total (mm2) Ancho Requerido (cm)

6 1
Cantidad Tipo de Conductor Calibre

25.40 31.11 Cables menores a 1000kCMIL


Diam. (mm)

506.71 760.13

3040.24 760.13

15.24 3.11

Area (mm2)

Area Total (mm2)

Ancho Requerido (cm)

5 2 2
392-10(a) (3) NEC 2008 Fuente: Aralven

25.52 4.47 8.93

511.51 15.69 62.63

2557.53 31.39 125.26

9.21 0.11 0.45 28.12 5.62

Ancho Minimo (cm) 20% Reserva:

Ancho total de Bandeja (cm)

33.75

Con algun cable instalado entre 1/0 y 4/0


Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2) Area Total (mm2) Ancho Requerido (cm)

5 0 0 0 0
392-10(a) (4) NEC 2008 Fuente: Aralven

18.48 13.51 17.46 17.46 17.46

268.22 143.35 239.43 239.43 239.43

1341.11 0.00 0.00 0.00 0.00

9.24 0 0 0 0 9.24 1.85

Ancho de conductores 20% Reserva:

Ancho total de Bandeja (cm)

11.09

CABLE MULTICONDUCTOR
Bandejas de fondo escalera o ventilado

CALIBRES 4/0 O MAYORES


Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2) Area Total (mm2) Ancho Requerido (cm)

2 5 3 1 2
NEC 2008 392.9 (a) (1) Los cables deben ser instalados en una sola capa Fuente: Manual de gedisa

34.88 25.52 54.86 55.90 76.90

955.53 511.51 2364.09 2454.22 4644.54

1911.05 2557.53 7092.28 2454.22 9289.08

6.98 12.76 16.46 5.59 15.38 57.17 11.43

Ancho de conductores 20% Reserva:

Ancho total de Bandeja (cm)

68.60

CABLES MENORES A 4/0


Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2) Area Total (mm2) Ancho Requerido (cm)

10 5 2 3 0
NEC 2008 392.9 (a) (2) Fuente: Manual de gedisa

13.51 15.96 18.90 36.30 36.30

143.35 200.06 280.55 1034.91 1034.91

1433.51 1000.29 561.10 3104.73 0.00

4.73 3.30 1.85 10.25 0.00 20.13 4.03

Ancho Minimo (cm) 20% Reserva:

Ancho total de Bandeja (cm)

24.15

CABLES 4/0 O MAYORES CON CABLES MENORES


Cables Mayores a 4/0
Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2) Area Total (mm2) Ancho Requerido (cm)

6 1
Cables menores a 4/0

34.88 76.90

955.53 4644.54

5733.16 4644.54

20.93 7.69

2 5 2 2
NEC 2008 392.9 (a) (3) Todos los cables mayores a 4/0 se deben instalar en una sola capa Fuente: Manual de gedisa

13.51 13.51 30.40 30.40

143.35 143.35 725.83 725.83

286.70 716.75 1451.67 1451.67

0.95 2.37 4.79 4.79 41.51 8.30

Ancho Minimo (cm) 20% Reserva:

Ancho total de Bandeja (cm)

49.81

CABLES CONTROL / ALUMBRADO / SEALIZACION


N Conductores Tipo de Aislante Calibre Diam. (mm) Area (mm2) Area Total (mm2) Ancho Requerido (cm)

11.10 23.20 16.30 16.30 14.40


NEC 2008 392.9 (b) Se considera la altura de la bandeja como 10cm Fuente: Manual de gedisa

96.77 422.73 208.67 208.67 162.86

2419.22 0.00 0.00 0.00 814.30

6.05 0.00 0.00 0.00 2.04 8.08 1.62

Ancho de conductores 20% Reserva:

Ancho total de Bandeja (cm)

9.70

Canalizacion
Tamao
Diametro Area total Area 31% Area 40% Area 53%

4" Tuberia No Metalica Electrica


0 mm
0.00 mm2 0.00 mm2 0.00 mm2 0.00 mm2

Tamao

Tuberia Metalica Electrica

Tuberia No Metalica Electrica

Tubo Metalico Flexible

Tubo Metalico Intermedio IMC

3/8 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 3 1/2 4 5 6

0 15.8 20.9 26.6 35 40.9 52.5 69.4 85.2 97.4 110 0 0

0 14.2 19.3 25.4 34 39.8 51.3 0 0 0 0 0 0

9.7 16.1 20.9 25.9 32.4 39 51.8 63.5 76.2 88.9 101.6 0 0

0 16.8 21.9 28.1 36.8 42.7 54.6 64.9 80.7 93.2 105.8 0 0

Tubo No Flexible hermetico a los liquidos (Tipo FNMC-B) 12.5 16 21.1 26.8 35.4 40.3 51.6 0 0 0 0 0 0

Tubo No Flexible hermetico a los liquidos (Tipo FNMCA-A*) 12.6 16 21 26.5 35.1 40.7 52.4 0 0 0 0 0 0

Tubo No Flexible hermetico a los liquidos 12.5 16 21.1 26.8 35.4 40.3 51.6 63.3 78.3 89.4 102.1 0 0

Tubo Metalico Rigido

Tubo de PVC Rigido, Sch. 80

0 16 21.2 27 35.4 41.2 52.9 63.2 78.5 90.7 102.9 128.8 154.8

0 13.4 18.3 23.8 31.9 37.5 48.6 58.2 72.7 84.5 96.2 121.1 145

Tubo de PVC Rigido, Sch. 40 y tubo de PE-AD 0 15.2 20.4 26.1 34.5 40.4 52 62.1 77.3 89.4 101.5 127.4 153.2

Tubo de PVC, Tipo A

Tubo de PVC, Tipo EB

0 17.8 23.1 29.8 38.1 43.7 54.7 66.9 82 93.7 106.6 0 0

0 0 0 0 0 0 56.4 0 84.8 96.6 108.9 135 160.9

CALIBRE 14

AISLANTE Cant Cables THW 1

Diametro Area
Area Total

4.14 mm 13.49 mm2

13.49 mm2
THHN Seccion mm2 Diametro

THW Calibre 18 16 14 12 10 8 6 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900 1000 1250 1500 1750 2000

CEN 1999 Tabla 5 TW Diametro Seccion mm2 Diametro 0 0.00 0 0.00 13.49 3.38 4.14 16.80 3.86 4.62 21.53 4.47 5.23 35.98 5.99 6.76 46.92 7.72 62.92 8.94 73.32 9.65 86.14 10.46 123.02 12.5 143.70 13.51 169.67 14.68 201.55 16 240.28 17.47 297.23 19.43 341.60 20.83 385.22 22.12 427.78 23.31 510.74 25.47 629.20 28.27 711.88 30.07 753.18 30.93 793.65 31.75 876.70 33.37 956.19 34.85 1203.02 39.09 1402.72 42.21 1602.09 45.11 1798.85 47.8

8.99 11.73 15.73 28.25

2.82 3.3 4.16 5.48 6.45 8.23 8.94 9.75 11.33 12.34 13.51 14.83 16.3 18.06 19.45 20.75 21.94 24.1 26.69 28.5 29.36 30.17 31.8 33.27

Resistencia y reactancia de conductores


Calibre: Mat. de la tuberia: Distancia:
2 Acero 20 M

Conductore por fase

Resistencia Reactancia

0.660 0.187

Ohm/kM Ohm/kM

R: 0.013 X: 0.004

CALIBRE 8 Cap. Nominal Factor Correc.

TEMP. 75C

MATERIAL COBRE

COR. Temp. 36-40

50 A 0.88

Capacidad
Tabla 310.16 CEN 1999

44 A

Ampacidades admisibles de los conductores aislados para tensiones nominales de 0 a 2000 V y 60c a 90c con no mas de tres conductores portadores de corriente en una canalizacin, cable o directamente enterrados, basadas en una temperatura ambiente de 30c Calibre 60C COBRE 75C 90C 60C ALUMINIO 75C 90C

AWG/kcmil

TW*, UF*

TBS, SA, SIS, FEP*, FEPB*, MI, FEPW*, RHH*, RHWRH*, RHW*, 2, THHN*, THHW*, THHW*, THW*, THW-2*, THWN*, THWN-2*, XHHW*, USE-2, XHH, USE*, ZW* XHHW*, XHHW-2, ZW-2 0 0 20 25 35 50 65 85 100 115 130 150 175 200 230 255 285 310 335 380 420 460 475 490 520 545 590 625 650 665 14 18 25 30 40 55 75 95 110 130 150 170 195 225 260 290 320 350 380 430 475 520 535 555 585 615 665 705 735 750

TW*, UF*

TBS, SA, SIS, THHN*, THHW*, RH*, RHW*, THW-2, THHW*, THWN-2, THW*, RHH*, RHWTHWN*, 2, USE-2, XHHW*, XHH, USE* XHHW, XHHW-2, ZW-2 0 0 0 20 30 40 50 65 75 90 100 120 135 155 180 205 230 250 270 310 340 375 385 395 425 445 485 520 545 560 0 0 0 25 35 45 60 75 85 100 115 135 150 175 205 230 255 280 305 350 385 420 435 450 480 500 545 585 615 630

18 16 14 12 10 8 6 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900 1000 1250 1500 1750 2000

0 0 20 25 30 40 55 70 85 95 110 125 145 165 195 215 240 260 280 320 355 385 400 410 435 455 495 520 545 560

0 0 0 0 25 30 40 55 65 75 85 100 115 130 150 170 190 210 225 260 285 310 320 330 355 375 405 435 455 470

TEMP AMB. 21-25 26-30 31-35 36-40 41-45 46-50 51-55 56-60 61-70 71-80

1.08 1 0.91 0.82 0.71 0.58 0.41

1.05 1 0.94 0.88 0.82 0.75 0.67 0.58 0.33

1.04 1 0.96 0.91 0.87 0.82 0.76 0.71 0.58 0.41

1.08 1 0.91 0.82 0.71 0.58 0.41

1.05 1 0.94 0.88 0.82 0.75 0.67 0.58 0.33

1.04 1 0.96 0.91 0.87 0.82 0.76 0.71 0.58 0.41

CALIBRE 2 Cap. Nominal

TEMP. 90C

Tension 2001-5000 V

130 A

Capacidad
Tabla 310.73 CEN 1999

130 A

Ampacidades de cables triples aislados o de tres conductores de cobre sencillos, en un conducto fsicamente aislado, al aire libre, basadas en temperaturas de conductor de 90C en una temperatura ambiente de 40C Calibre AWG/kcmil 8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000 2001-5000 V 90C 105C 55 61 75 84 97 110 130 145 155 175 180 200 205 225 240 270 280 305 315 355 385 430 475 530 600 665 690 770 5001-35000 V 90C 105C 83 110 150 170 195 225 260 295 330 395 480 585 675 93 120 165 190 215 255 290 330 365 440 535 655 755

CALIBRE 4/0 Cap. Nominal

TEMP. 90C

Tension 5001-35000 V

230 A

Capacidad
Tabla 310.74 CEN 1999

230 A

Ampacidades de cables triples aislados o de tres conductores de aluminio sencillos, en un conducto fsicamente aislado, al aire libre, basadas en temperaturas de conductor de 90C en una temperatura ambiente de 40C Calibre AWG/kcmil 8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000 2001-5000 V 90C 105C 43 48 58 65 76 85 100 115 120 135 140 155 160 175 190 210 215 240 250 280 305 340 380 425 490 545 580 645 5001-35000 V 90C 105C 65 84 115 130 150 175 200 230 255 310 385 485 565 72 94 130 150 170 200 225 260 290 350 430 540 640

A AAC AACS AC ACSR ACSR-AG AL ACSR-AW AF Al Alta frecuencia AM Amplitud Ancho de banda Apertura numrica Armadura

Atenuacin ATM AW AWG AWM Baja Frecuencia Bel BIL Bit Blindaje C c.a.

c.c. c.d.

Capacitador Capacitancia

Capacitancia mutua Capacitor CATV CCS CCTV Circuito en serie Circuito paralelo CL2 CL3 CM Conductividad Constante dielctrica CP CPE CSA Cu CuSn CV CW CXC DCS DGN Diafona Dielctrico Dispersin

Dispersin cromtica

Dispersin modal DIT DRS DS Efecto piel EIA/TIA Electromagntic o EP(R) EPDM f FA Fan-out Fase FCC FDDI FEP FM FOA FOW FTP G G-GC Glosario de trminos relacionados con conductores elctricos y cables para telecomunicaciones H HDPE Higroscpico Hilo dren HMWP HP HPN

HPOF Hz I I2R IACS ICEA IEC IEEE Iexc Impedancia Indice de refraccin Inductancia ISO ITU Jumper kCM kV l LAN LDPE Lnea balanceada Lnea de transmisin Longitud de onda de Malla lpi Longitudinal lpof m.s.n.m Malla Mc Mi

MIC mp mp-gc MTW Multimodo Multiplexar MV mw NEC Neopreno NFPA NM NM-B o NMC-B NMC NMX NOM Non break out NZ OA Ohm OTDR OW Pantalla PCC PCG PCM PE Prdidas por doblez PFA PFAH

PG Pig-tail PILC Plstico Plastificante Plenum PMD Polietileno celular Polilam

Polmero POT psi PVC PVDF RDI REA (RUS) Reactancia Resistencia a la abrasin RG/U RH/RW RHH RHW RHW-2 SA SBR SDH SE SF SFF

SH SHD SHD-GC SHD. SIC

SIS SJ SJO SJT SJ SMT SNM

SO SONET SPT ST STP SU SV SVT SVTO TA TAGA TAGT TC

TEFLON* TF

TFE TFF TFFN TFN THHN THHW THW1 THW-21 THWN TP TPT TP
TTU

TW UD UF UHF UL Unimodo URD USE USG UTP V VA Velocidad de la luz Velocidad de propagacin VHF Volt VW-1

W WDM XHHW XHHW-2 XLP XT

Ampere: Unidad utilizada para denominar la intensidad de corriente elctrica. All Aluminum Conductor: conductor o cable de hilos de aluminio. Aluminum Alloy Standed Conductor: cable de aleacin de aluminio. Armored Cable: cables provistos de una armadura metlica flexible. Aluminum Conductor Steel Reinforced: conductor de aluminio con centro de acero ACSR con aleacin de aluminio para alta temperatura (150C) y acero de alta resistencia. Smbolo del aluminio. ACSR con centro de acero recubierto con aluminio (Alumo-Weld). Tambin conocido como Audio Frecuencia: Rango de frecuencias que caen dentro del rango perceptible del odo humano: aproximadamente 20 a 20, 000 Hz Smbolo del aluminio. La banda de 3 MHz a 1 GHz. Amplitud Modulada. El valor mximo de variacin de una onda. Es la diferencia entre los valores superior e inferior de una banda de frecuencias dada. Se expresa en Hertz. Es la medida de aceptacin angular de una fibra ptica, que es aproximadamente el seno de la mitad del ngulo del cono de aceptacin de la fibra. Cinta corrugada de acero que tiene la funcin de proteger el cable contra maltrato mecnico y ataque de roedores. En aplicaciones especiales se llegan a usar armaduras de cinta engargolada o de alambres de acero. Es el decremento en magnitud de una onda mientras esta viaja en medio transmisor, sea un cable o un circuito. La atenuacin se mide como una razn o como logartimo de la razn Siglas en ingls para la tcnica de codificacin y conmutacin en bloques llamada Asynchronous Transfer Mode y que permite multiplexar seales de velocidades distintas en American Wire Gauge: escala de calibres americanos para alambres y cables, tambin conocida como b&s (Brown and Sharpe) Wire Gauge. American Wire Gauge: Escala de calibres americanos para alambres y cables, tambin conocida como B&S (Brown and Sharpe) Wire Gauge. Appliance Wiring Material: Conductores destinados al alambrado interno de aparatos La banda de 30-300 KHz. Es una unidad que representa el logaritmo de la razn de dos niveles. Basic Impulse Insulation Level: nivel bsico de aislamiento al impulso. Es un dgito binario. Capa conductiva en un cable que tiene la funcin de reducir la interferencia electomagntica. Puede ser una malla de alambres, una cinta metlica o una cinta plstica metalizada. Smbolo de capacitancia y grados centgrados. Corriente alterna: Es una corriente que perodicamente revierte la direccin del flujo de electrones. La razn en la que un ciclo completo ocurre por unidad de tiempo (normalmente un segundo) se le denomina frecuencia de la corriente. Corriente continua (ver c.d.) Corriente directa: Es la corriente elctrica donde los electrones fluyen en una sola direccin.

Dos superficies conductoras separadas por un material dielctrico. La capacitacin es determinada por el rea de las superficies, tipo de dielctrico y el espaciamiento entre los Es la propiedad que tiene un material dielctrico situado en medio de dos conductores de almacenar electricidad cuando existe una diferencia de potencial entre los conductores. La unidad de medida es el Farad, que es el valor de capacitancia que almacenar una carga de un Cuolomb cuando exista una diferencia de potencial de un volt entre los conductores. Es la capacitancia que existe entre dos concluctores cuando los dems conductores estn conectados entre s. Dos superficies conductoras separadas por un material dielctrico. La capacitancia es determinada por el rea de las superficies, tipo de dielctrico y el espaciamiento entre los Community Antena TeleVision: trmino empleado para los cables coaxiales destinados a los sistemas de televisin comunitaria. Siglas en lngls para conductores de acero cubierto cle cobre (Copper Cladded Steel). Circuito Cerrado cle TeleVisin. Es un circuito cuyos componentes distribuidos a lo largo de camino comn. Es un circuito en el cual un mismo voltaje se presenta en todos los componentes, con corriente dividida entre estos de acuerdo a su resistencia o impedancias. Cables para circuitos Clase 2, segn NEC-725, bajo voltaje y potencia. Idem a CL2, para 300 volts mximo, bajo potencia. Circular Mil: rea de un circuito con un dimetro de 1/1000 de pulgada. La capacidad de un material para permitir el flujo de electrones, medido por la corriente por unidad de voltaje aplicado. Es el recproco de la resistividad. Tambin se llama permitividad. Es aquella propiedad del dielctrico que determina la cantidad de energa electrstatica que puede almacenarse cuando es aplicado un voltaje. Caballos de Potencia: tambin conocido como HP. Chlorinated PolyEthylene: polietileno clorado. Canadian Standard Association: Institucin canadiense para la certificacin de equipo elctrico y electrnico acorde a las normas que ellos mismos publican. Smbolo del cobre. Smbolo que denota cobre estaado. Continuous Vulcanization: proceso de vulcanizacin en lnea con la extrusin. CopperWeld: varilla de acero, con recubrimiento de cobre. Designacin de cable coaxial por CSA (Canadian Standars Association). Cables para Distribucin Comercial Subterrnea. Direccin General de Normas de la Secretara de Comercio y Fomento Industrial. Transferencia no deseada de seal entre distintos canales de un equipo a cable. Es un medio aislante (no-conductivo). Fenmeno por el cual componentes de la luz transmitida por la fibra sufren retrasos distintos. Es la suma de varios efectos, principalmente dispersin modal y dispersin cromtica. Puede limitar la velocidad de transmisin. Es el retraso diferente que sufren las distintas longitudes de onda que componen a luz portadora, por tener velocidades distintas en la fibra. En fibras con diseo estndar la dispersin cromtica tiene un valor mnimo o nulo en la ventana de 1310 nm.

Es el retraso diferente que presentan los modos de propagacin en una fibra multimodo por viajar en ngulos distintos, no existe en las fibras unimodo en las que se transmite un modo Dispositivo de Interconexin Terminal: es el lmite entre la red pblica y la que es Cables para Distribucin Residencial Subterrnea (tipo URD). Siglas en ingls para dispersin corrida, son las fibras unimodo con dispersin mnima enla ventana de 1550 nm. Es la tendencia que tiene la corriente alterna de viajar en el permetro del conductor con el incremento de la frecuencia. Asociacin de las industrias electrnica y de comunicaciones en EUA. Se reflere a la combinacin de campos elctricos y magnticos originado por el movimiento de los electrones por el conductor. Fluorinated Ethylene Propylene: aislamiento de etileno-propileno fluorado.Ethylene Propylene (Rubber): aislamiento a base de etileno-propileno. Ethylene Propylene Dionomer: etileno-propileno dieno monmero. Frecuencia: El nmero de veces que una accin peridica ocurre en un lapso de tiempo: Es el nmero de Hertz en los que una corriente elctrica completa 1 seg. Forced Air: enfriamiento con aire forzado. Cable ptlco para conectorizar, que permite separar las fibras individuales sin necesidad de darles proteccin adicional. Es la relacin angular entre ondas. Flexible Control Cable: cable control, flexible. Fiber Distribution Digital Interface: especificacin para la red de datos 100% ptica a 100 Nombre abreviado para tetrafluoruroetileno-exafluoruropropileno, material aislante con excelentes propiedades elctricas y qumicas que se usan en cables categora plenum. Frecuencia modulada. Forced Oil and Air: enfriamiento con aceite forzado y aire. Forced Oil and Water: enfriamiento con aceite forzado y agua. Foiled Twisted Pair: cables multipares para datos blindados por medio de una cinta plstica aluminizada con hilo dren. Ground: cable flexible para minas con conductores para conexin a tierra, 600 2000 volts. Ground-Ground Check: cable flexible para minas, con conductores para conexin a tierra y un conductor aislado para verificar la continuidad de los conductores de tierra, 600 2000 rio de trminos relacionados con conductores elctricos y cables para telecomunicaciones Henry: Es la unidad prctica de inductancia que producir un incremento de voltaje de 1 Volt cuando la corriente cambie a razn de un ampere/seg. High Density PolyEthylene (PE): polietileno de alto densidad. Propiedad de algunos materiales de absorber agua del ambiente. Las cintas e hilos usados en cables no deben hacerlo. Es un alambre desnudo que est en contacto con el blindaje del cable a lo largo de toda su High Molecular Weight Polyethylene: polietileno de alto peso molecualr. Horse Power: caballo de potencia. Heater Cord Parallel Neoprene: cordn paralelo de dos conductores flexibles con aislamiento elastomrico para aparatos electrodomsticos resistentes al calor, 90 C, 600 volts.

High Pressure Oil Filled: cables tipo Pipe (tubo) de alta tensin con aislamiento de papel impregnado instalados dentro de un tubo de acero con aceite a alta presin. Hertz: Es la unidad de medida de frecuencia: 1 ciclo por segundo. Smbolo utilizado para designar corriente. Frmula de potencia en Watts, donde I=corriente en amperes, R=resistencia en Ohms. International Annealed Copper Standard: patrn internacional para la conductividad del cobre (igual al 100% para el cobre electroltico recocido). Insulated Cable Engineers Association: nombre actual de IPCEA (Power), asociacin norteamericana para la normalizacin de conductores elctricos. International Electrotechnical Commission: organizacin internacional encargada de la normalizacin de productos elctricos. Institute of Electrical and Electronic Engineers: principal asociacin a nivel mundial de ingenieros en electricidad, electrnica y materias afines. Corriente de excitacin. Es la oposicin total de un circuito, cable, o algn componente al paso de la corriente alterna. Esta incluye a la resistencia y a la reactancia. La unidad de medida es el Ohm y su smbolo Es un promedio del ndice de refraccin para las longitudes de onda en la ventana de transmisin; es un dato necesario que se debe conocer para medir la distancia de un enlace Es la propiedad de un conductor o un circuito que se resiste al cambio de corriente. Su unidad de medida es el Henry y su smbolo es L. International Standards Organization: organizacin internacional de normalizacin. International Telecomunication Union: organizacin para normalizacin internacional en Cable para conexiones en un distribuidor, puede ser un par de cobre o una fibra Monotel con kiloCircularMil:unidad de rea del sistema norteamericano de calibres de conductores elctricos, igual a 1000 circular mils (CM). Anteriormente conocida como MCM. kiloVolt: unidad de medida de tensin elctrica igual a 1000 volts. Smbolo utilizado para designar corriente. Local Area Network: red de datos de corta longitud en un edificio o conjunto de edificios. Low Density PolyEthylene (PE): polietileno de bajo densidad, Es un cable que tiene 2 conductores idnticos con las mismas caractersticas electromagnticas en relacin a los dems conductores y tierra. Es el arreglo de dos o ms conductores o una gua de onda que se utiliza para transferir seales de un lugar a otro. Es la distancia entre picos o nodos sucesivos de una onda. Paper Insulated: proceso para la fabricacin de cables telefnicos con aislamiento de papel aplicado longitudinalmente. Low Pressure Oil Filled: cables con aislamiento de papel impregnado tipo Autocontenidos . Metros sobre el nivel del mar. Es un grupo de filamentos metlicos entretejidos para formar una esfructura tubular la Metal Clad: cable armado con una cubierta metlica del tipo interlock o tubo corrugado. Mineral Insulated: cable con aislamiento mineral de xido de magnesio y cubierta de tubo de cobre o acero, para alta temperatura y resistencia al fuego, 90 a 250 C.

Tcnica de modulacin en que la amplitud de una seal analgica en cierto momento se expresa con un nmero binario de 8 cifras. Mine Power Feeder Cable: cable alimentador para minas con tres conductores de fase y tres conductores para conexin a tierra. MP-Ground Check: MP con un conductor aislado para verificar la continuidad de los Machine Tool Wire: conductor con aislamiento termoplstico para alambrado de mquinas Fibras que tienen un ncleo relativamente grande (50 micras o ms), que permiten transmitir varios haces luminosos llamados modos de propagacin. Combinacin de varias seales para enviarlas por un solo canal de transmisin. Medium Voltage Cable: cables cona aislamiento slido para tensiones de 2001 a 35,000 Micro m Wave: microonda. Natinal Electrical Code: Norma general sobre productos e instalaciones Policloropreno, hule sinttico empleado como aislamiento y cubierta de cables flexibles. National Fire Protection Association: asociacin americana para la proteccin contra incendios responsable de la publicacin del NEC. Non-Metallic Sheathed Cable: conductores aislados y con cubierta no metlica resistente a la humedad, retardante de la flama; sugerido para ambientes secos. NM o NMC con aislamiento de THHN. NM con cubierta elastomrica resistente a la corrosin; para ambientes secos o hmedos. Norma Mexicana; documentos publicados por organismos privados autorizados. Son de uso Norma Oficial Mexicana: documentos publicados por la DGN para la normalizacin y especificacin de productos. Cable ptico para distribucin en edificios en el que las fibras no tienen proteccin individual para separarlas del resto. Fibras pticas de baja dispersin cromtica, pero nunca igual a una de 1530 a 1560 mm, permite transmisin de varios portadores (ver WDM). Oil and Air: enfriamiento natural aire-aceite. Es la unidad elctrica de resistencia. Es el valor de resistencia a travs del cual una diferencia de potencial de 1 Volt mantendr una corriente de un ampere. Reflectmetro ptico en dominio de tiempo, es un equipo que inyecta un pulso de luz a la fibra y detecta las reflexiones, permite medir atenuacin y longitud de un enlace. Oil and Water: enfriamiento con aceite-agua. Vea blindaje. Designacin de CSA para los cables de uso interior (Premises Comunication Cable). Portable Cable Control and Ground conductors: cable flexible para minas con conductores de control y para conexin a tierra, 600 2000 volts. Siglas en ingls para la tcnica de modulacin llamada en espaol MIC (Modulacin por Polietileno, puede ser de los tipos HMWP,HDPE y LDPE. Es la forma que toma la curva de atenuacin que es causada por: a)Una fibra ptica curveada alrededor de un radio de curvatura cerrado, o b) Microdobleces causados por PerFluoro-Alkoxy: cables para alta temperatura; ambiente seco, con aislamiento de PerfluoroAlkoxy, hasta 200 C. PerFluoro-Alkoxy Heat: PFA con temperaturas mayores de hasta 250 C.

Portable Cable Ground Conductor: cable flexible para minas con conductores de fase y para conexin a tierra, 600 2000 volts. Fibra ptica Monotel con conector en una punta. Papel Insulated Lead Cover: cable para media tensin aislado con papel impregnado y con Sustancia polimricas que incluyen tanto materiales naturales como sintticos. Es un qumico que se agrega al plstico pare hacerlo ms suave y flexible. Cables que cumplen con las normas de seguridad parta poder instalarse sin tubo conduit Siglas en ingls para el fenmeno de dispersin por polarizacin de modos, en el que existe una diferencia de velocidad entre los componentes de campo elctrico y magntico de un Tcnica de introducir burbujas en el plstico del aislamiento pare bajar la capacitancia del cable. Cinta de aluminio de acero con espesor entre 0. 15 y 0.2 mm que tiene un recubrimiento plstico en una o ambas caras, lo que permite que se adhiera a la cubierta de polietileno de un cable formando una barrera contra la humedad. Es una substancia hecha de muchas unidades qumicas moleculares. El trmino polmero es regularmente usado en vez de plstico, hule o elastmero. Cordn paralelo con aislamiento termoplstico para 300 volts, 60 C. pounds per square inch: libras por pulgada cuadrada. PolyVinyl Chloride: cloruro cle poli-vinilo, compuesto ampliamente usado como aislamiento y PolyVinyliDene Fluoride: compuesto termoplstico a base de fluor usado generalmente como cubierta en cables para construccin. Red Digital Integrada; servicio de alta velocidad para grandes usuarios a travs de la red Rural Electrification Administracion: oficina norteamericana del Departamento de Agricultura encargada de normalizacin de equipos ofrecidos por las compaas telefnicas Es una medida de los efectos combinados de capacitancia e inductancia en corriente alterna. Es la variacin que dicha oposicin tiene con la frecuencia de la corriente. Su smbolo es X. Capacidad de resistir desgaste superficial. Radio Frecuency Guide, Universal: designacin para cables coaxiales para radiofrecuencias. Rubber Heat, Rubber Moisture (Water): cables con aislamiento y cubierta de hules sintticos para 75 C en ambiente seco y 60 C en hmedo, 600 volts. Rubber High Heat: cables con aislamiento y cubierta de hule sinttico, para 90 C, 600 V. Rubber Heat Moisture (Water): cables con aislamiento y cubierta de hules sintticos para75 C en ambiente seco y hmedo. Igual a RHW pero con aislamiento de 90 C en ambiente seco y hmedo. Silicone Asbestos: cables aislados con hule silicn y malla de asbesto o fibra de vidrio. Styrene Butadiene Rubber: elastmero sinttico a base de Estireno y Butadieno, empleado para aislamiento y cubierta de cordones flexibles, se conoca como GRS (Government Siglas en ingls pare el sistema de transmisin ptica sincrono (Synchronous Digital Service Entrance: uno o ms conductores con o sin cubierta exterior usados para Silicone Rubber Fiber Glass: alambre o cable de 7 hilos aislados con hule silicn y malla de fibra de vidrio, 200 C. Silicone Rubber Fiber Glass Flexible: SF con conductor ms flexible, 150 C.

Shielded Mining Cable Single Conductor: cable monopolar flexible para minas con pantalla y cubierta para uso pesado. Shielded mining Cable with Ground Conductors: cable trifsico flexible para minas con pantalla. "D" significa que cada conductor de fase lleva pantalla y que el cable tres Ground Check: SHD con un conductor aislado para el circuito de comprobacin de continuidad de conexin a tierra y dos conductores de tierra. Specific Inductive Capacity: inductancia capacitiva especfica, constante dielctrica de un material que es la relacin que existe entre un condensador con el material como dielctrico y el mismo condensador con aire como dielctico. Synthetic Insulated Switchboard Cable: cable para tableros con aislamiento elastomrico sinttico, 90 C, 600 volts. Hard Service Cord Junior: cordn uso rudo para servicio ligero con aislamiento elastomrico, SJ Oil Resistant: SJ con aislamiento resistente al aceite. Thermoplastic: SJ con aislamiento y cubierta termoplstica, 60 C, 300 volts (90 y105 C con aislamiento de PVC). Construccin igual al SPT pero con conductores clase M. Shielded Non-Metallic-Sheathed Cable: dos o ms conductores aislados con un ncleo de material resistente a la humedad y retardante de la llama; sobre el conjunto lleva una pantalla a base de hilos y cintas; cubierta exterior de material no metlico resis Service Cord Oil Resistant: cordn uso rudo para servicio pesado; aislamiento y cubierta elastomrica; la cubierta es resistente al aceite, hasta 90 C, 600 volts. Siglas en ingls para el sistema de transmisin ptica sincrono de EUA (Synchronous Optical Service Parallel Thermoplastic: cordn paralelo con aislamiento de PVC para servicio ligero, 60 C, 300 volts. (90 y 105 C con aislamiento de PVC). Hard Service Cord Thermoplastic: cable o cordn uso rudo para servicio pesado con aislamiento y cubierta termoplstica, 60 a 105 C, 600 volts. Shielded Twisted Pair: cables multipares para datos, blindados con una cinta plstica aluminizada y una malla de hilos de cobre estaado. Trmino empleado para denominar la tubera de PVC Subterrnea. Service Cord Vacuum Cleaner: cordn tipo uso rudo flexible para conexin de aspiradoras con aislamiento y cubierta elastomrica, 60 C, 300 volts.SV con cubierta de neopreno. SV con aislamiento y cubierta Termoplstica, 60 a 90 C, 300 volts. SVT Oil Resistant: SVT con cubierta resistente al aceite, 60 C. Thermoplastic Asbestos: cable para alambrado de tableros con aislamiento termoplstico; carda de asbesto y trenza de algodn retardante a la llama, 90 C, 600 volts (En desuso). Tefln*-Asbestos-G lass-Asbestos: conductor con aislamiento de Tefln trenza de asbesto, trenza de fibra de vidrio y malla de eabesto para circuitos de fuerza y control, 250 C, 600 TAGA sustituyendo la cubierta final de asbesto por una cinta de Tefln*. Power and Control Tray Cable: dos o ms conductores aislados con o sin conductor de tierra y con una cubierta exterior de material no metlico, y aprobado para usarse en instalaciones en charolas, canalizaciones o soportado por un hilo mensajero. Marca registrada de DuPont para el poli-tetraflouretileno, tambin denominado PTFE. Thermoplastic Fixture: alambre o cable de 7 hilos para alambrado de aparatos elctricos , aislamiento de PVC, 60 C, 600 volts.

Cable para alta temperatura aislado con Tefln*, 250 C. TF Flexible: TF pero con conductor flexible. Thermoplastic Fixture Flexible Nylon: TFN con conductor flexible. TF Nylon: TF con aislamiento de PVC y cubierta de nylon, 90 C, 600 volts. Thermoplastic High Heat Nylon: alambre o cable con aislamiento de PVC y cubierta de nylon, 90 C en ambiente seco, 600 volts. Thermoplastic High Heat Moisture (Water) Resistant: cable aislado con PVC para 90 C en ambientes secos y 75 C en hmedos, 600 volts. Thermoplastic Heat and Moisture (Water) Resistant: alambre o cable con aislamiento de PVC par a75 C en ambientes secos o hmedos, 600 volts. THW para 90 C en ambientes secos y hmedos THW con cubierta de nylon, resistente a la humedad, aceites e hidrocarburos, 75 C en ambientes hmedos, 600 volts. Tinsel Cord Parallel: dos conductores paralelos extraflexibles con aislamiento y cubierta elastomrica para uso ligero en dispositivos de hasta 50 watts. Thermoplastic: TP pero con aislamiento y cubierta termoplsticos, 125 volts. Thermoplastic (or Thermoset) Insulation, Thermoplastic Jacket. Underground Thermoplastic Building Wire Moisture (Water) Resistant: alambre o cable aislado con PVC resistente a la humedad, 60 C, 600 volts. Underground Distribution: cables para distribucin subterrnea, tambin conocidos como Underground Feeder: cable de uno o varios conductores con aislamiento y cubierta termoplstica para acometidas subterrneas en baja tensin. Ultra High Frequency: ultra alto frecuencia. Es la banda de 300 a 3000 MHz. Underwrites Laboratories, Inc.: institucin (privada) dedicada al reconocimiento y aprobacin de productos elctricos y electrnicos, acorde a sus propias normas. Fibras que tienen un ncleo pequeo que permite transmitir un solo haz luminoso llamado modo de propagacin. Underground Residential Distribution: cables de distribucin residencial subterrnea, tambin conocidos como DRS. Underground Service Entrance: cable para acometidas subterrneas en baja tensin, aislamiento y cubiertas elastomricas. United States Standard Gauge: escala para calibres de lmina de acero. Unshielded Twisted Pair: cables multipares para datos, sin blindaje. Volt: unidad utilizada para denominar tensin elctrica. Volt Ampere: unidad de potencia aparente para transformadores. 2.998x108 m/seg. La velocidad de transmisin de la energa elctrica en una longitud de cable comparado con la velocidad que tendr en el aire. Se estima generalmente en porcentaje. Very High Frecuency: extra alta frecuencia, 30 a 300 MHz. Es la unidad de tensin elctrica: 1 Volt ser la tensin elctrica que causar que 1 ampere de corriente fluya a travs de una resistencia de 1 Ohm. Vertical Wire Flame Test: prueba de resistencia a la flama colocando el especimen en

Cables flexibles para minas: redondos o planos de uno o varios conductores con aislamiento y cubiertas elastomricas para servicio extrapesado. Siglas en ingls para la multiplexacin por divisin de longitud de onda. En estos sistemas se transmiten en forma simultnea varias longitudes de onda independientes. Cross (X)-Linked Polyethylene High Heat and Moisture (Water) Resistant: cable con aislamiento de polietileno de cadena cruzada, 90 C ambiente seco y 75 C en ambiente XHHW para 90 C en ambientes secos y hmedos. Cross (X)-Linked Polyethylene: polietileno de cadena cruzada, tambin conocida como polietileno vulcanizado o XLPE. Xmas Tree Cord: cordn paralelo, dos conductores aislados con PVC para series de rboles

CLCULOS ELCTRICOS