CONDUCTORES

Elctricos
Tabla de ocupacin mxima de
conductores en un tubo conduit
Tipo de Conductor

TW, THW, THW-LS,


THHW-LS y XHHW

RHW Y RHH
(Sin cubierta exterior)

TW, THW, THW-LS,


THHW-LS y XHHW
Sin cubierta exterior

RHW Y RHH (Sin


cubierta exterior)

THWW y THHN

Calibre del
conductor
AWG KCM
14*
14
12*
12
10*
10
8

Diametro nominal del tubo mm (pulg)


13 (1/2")

19 (3/4")

25 ( 1" )

32 (11/4")

38 (11/2")

51 (2")

63 (21/2")

9
8
7
6
5
4
2

16
14
12
11
10
8
4

25
22
20
17
15
13
7

45
39
35
30
27
23
13

61
54
48
41
37
32
17

78
68
61
52
28

40

14*
14
12*
12
10*
10
8

6
5
4
4
4
3
1

10
9
8
7
7
6
3

16
15
13
12
11
9
5

29
26
24
21
19
17
10

40
36
33
29
26
23
13

65
59
54
47
43
38
22

61
53
32

6
4
2
1/0
2/0
3/0
4/0
250
300
350
400
500
14*
14
12*
12
10*
10
8
6
4
2
1/0
2/0
3/0
4/0
250
300
350
400
500

1
1
1

2
1
1
1
1
1

4
3
2
1
1
1
1
1

3
3
3
3
2
2
1
1
1

6
6
5
5
4
4
4
2
1
1
1
1

10
9
9
8
7
6
4
2
1
1
1
1
1
1

7
5
4
2
1
1
1
1
1
1
1
1
18
17
16
14
13
12
7
5
3
3
1
1
1
1
1
1
1

10
7
5
3
3
2
1
1
1
1
1
1
25
23
21
19
18
16
9
7
5
4
2
2
1
1
1
1
1
1
1

16
12
9
5
5
4
3
2
2
1
1
1
41
38
35
32
29
26
16
11
8
7
4
3
3
2
1
1
1
1
1

23
17
13
8
7
6
5
4
3
3
2
1
58
53
50
45
41
37
22
15
12
9
6
5
4
4
3
3
2
1
1

13
11
10
8
6
5
3
2
1
1

24
20
18
15
11
9
5
4
2
1
1
1
1

37
32
28
23
18
15
9
6
4
3
1
1
1
1
1
1

67
57
43
36
21
15
9
7
4
3
3
2
1
1
1
1
1

71
59
35
25
16
11
7
6
5
4
3
3
2
1
1

49
36
22
16
10
8
7
6
4
4
3
3
2

14*
14
12*
12
10*
10
8
6
4
2
1/0
2/0
3/0
4/0
250
300
350
400
500

66
57
49
42
32
26
15
11
7
5
3
2
1
1
1
1
1
1
1

76 (3")

101 (4")

49
36
27
20
12
10
9
7
6
5
4
4
3

47
34
21
18
15
13
10
9
8
7
6

35
24
18
14
9
8
7
6
5
4
4
3
3

41
31
24
16
14
12
10
8
7
6
6
5

56
34
25
15
13
11
9
7
6
5
5
4

42
26
22
18
15
12
11
9
8
7

CABLES
Desnudos de Aluminio
ACSR
Alambre de aluminio en temple duro
cableados concntricamente

APLICACIN:
Se utiliza en lneas areas de distribucin, transmisin y subestacines, con distancias interpostales largas para baja y alta tensin.
CARACTERSTICAS:
Cable formado por alambres de aluminio puro temple duro, cabelludos sobre un ncleo de alambre o alambres de acero galvanizado.
Calibre
AWG o KCM

2
1/0
3/0
266.8
336.4
477.0
795.0
795.0
900.0
1113.0

AL

Acero

Carga
de
ruptura
Kg

6
6
6
26
26
26
54
26
54
45

1
1
1
7
7
7
7
7
7
7

1265
1940
3030
5100
6375
8820
12928
14152
14651
14016

Nmero de
Alambres

Coeficiente de
Dilatacin Lineal
inicial
final
10-6/C
10-6/C
18.50
18.57
18.57
17.53
17.53
17.53
18.28
17.40
18.28
20.53

18.97
18.95
18.95
18.82
18.82
18.82
19.26
18.82
19.26
20.80

Mdulo de
Elasticidad
inicial
final
Kg/cm2
Kg/cm2

Resistencia
C.D. a 20C
ohm / km

713,550
726,200
726,200
585,600
585,600
585,600
520,220
534,980
520,220
548,340

811,970
795,800
795,800
764,860
764,860
764,860
667,850
715,650
667,850
658,710

0.834
0.524
0.330
0.210
0.166
0.117
0.071
0.070
0.062
0.051

Numero de Dimetro
de Alambres
aluminio
acero
mm
mm

Dimetro
total
Aprox.
mm

Peso
Nominal
kg/km

4.01
4.49
5.03
5.66
6.35
6.35
7.14
8.03
8.25
9.02
10.11
11.35

33.8
42.0
53.5
67.6
85.0
99.2
108.0
135.1
158.0
170.5
214.9
271.0

*Datos aproximados y sujetos a tolerancias de manufacturas

CABLES DE ALUMINIO CON REFUERZO DE ACERO (ACSR)

Cdigo
Mundial

Wren
Warbler
Turkey
Trush
Swan
Swanate
Swallow
Sparrow
Sparate
Robin
Raven
Quail

rea nominal
del aluminio

Calibre equivalente
cobre duro

mm2

AWG KCM

mm2

AWG KCM

8.38
10.58
13.28
16.78
21.15
21.15
26.69
33.65
33.65
42.48
53.54
67.50

8
7
6
5
4
4
3
2
2
1
1/0
2/0

5.26
6.36
8.38
10.58
13.28
13.28
16.78
21.15
21.15
26.69
33.65
42.48

10
9
8
7
6
6
5
4
4
3
2
1

6 x 1.33
6 x 1.49
6 x 1.68
6 x 1.89
6 x 2.12
7 x 1.96
6 x 2.38
6 x 2.67
7 x 2.47
6 x 3.00
6 x 3.37
6 x 3.78

1 x 1.33
1 x 1.49
1 x 1.68
1 x 1.89
1 x 2.12
1 x 2.62
1 x 2.38
1 x 2.67
1 x 3.30
1 x 3.00
1 x 3.37
1 x 3.78

CABLES
Desnudos de Aluminio
ACSR
CABLES DE ALUMINIO CON REFUERZO DE ACERO (ACSR)
Cdigo
Mundial

Pigeon
Penguin
Owl
Partridge
Ostrich
Merlin
Linnet
Oriole
Ibis
Lark
Hawk
Hen
Dove
Eagle
Peacock
Grosbeak
Egret
Flamingo
Starling
Redwing
Crow
Drake
Mallard
Tern
Cndor
Crane
Canary
Rail
Cardinal
Ortolan
Curlew
Bluejay
Finch
Bunting
Grackle
Bitern
Pheasant
Dipper
Martin
Bobolink
Plover
Nuthatch
Parrot
Lapwing
Falcn

mm2

AWG O KCM

mm2

AWG O KCM

aluminio
mm

acero
mm

Dimetro
total
Aprox.
mm

84.99
107.20
135.2
135.2
152.0
152.0
170.6
170.6
201.3
201.3
241.9
241.9
253.1
282.0
282.0
306.5
322.3
322.3
322.3
337.7
337.7
362.6
362.6
362.6
403.0
4.30.0
403.0
403.0
443.5
455.2
483.3
483.3
524.1
524.1
564.2
564.2
604.2
604.2
644.7
644.7
684.8
684.6
725.2
752.2
765.8
765.8
805.7
805.7

3/0
4/0
266.8
266.8
300.0
300.0
336.4
336.4
397.5
397.5
477.0
477.0
500.0
556.5
556.5
605.0
636.0
636.0
636.0
666.6
666.6
715.5
715.5
715.5
795.0
795.0
795.0
795.0
874.5
900.0
954.0
954.0
1033.5
1033.5
1113.0
1113.0
1195.5
1192.5
1272.0
1272.0
1351.5
1351.5
1431.0
1431.0
1510.5
1510.0
1590.0
1590.7

54.54
67.50
84.99
84.99
95.6
95.6
107.2
107.2
126.8
126.8
152.0
152.0
159.7
177.6
177.6
192.5
202.6
202.6
202.6
212.8
212.8
228.0
228.0
228.0
253.1
253.1
253.1
253.1
279.3
286.3
303.7
303.7
328.8
328.8
354.2
354.2
379.3
379.3
404.6
404.6
431.2
431.2
455.2
455.2
481.3
481.3
505.8
505.8

1/0
2/0
3/0
3/0
188.7
188.7
4/0
4/0
250
250
300
300
315
350
350
380
400
400
400
420
420
450
450
450
500
500
500
500
550
565
600
600
650
650
700
700
750
750
800
800
851
851
900
900
950
950
1000
1000

6 x 4.25
6 x 4.77
6x 5.35
26 x 2.57
26 x 2.12
30 x 2.54
26 x 2.89
30 x 2.69
26 x 3.14
30 x 2.92
26 x 3.44
30 x 3.20
30 x 3.28
26 x 3.72
30 x 3.46
54 x 2.96
26 x 3.97
30 x 3.70
54 x 2.75
24 x 4.23
54 x 2.82
26 x 4.21
30 x 3.92
54 x 2.92
26 x 4.44
30 x 4.13
45 x 3.37
54 x 3.08
54 x 3.23
54 x 3.28
45 x 3.70
54 x 3.37
45 x 3.85
54 x 3.51
45 x 3.99
54 x 3.65
45 x 4.13
54 x 3.77
45 x 4.27
54 x 3.90
45 x 4.40
54 x 4.02
45 x 4.53
54 x 4.13
45 x 4.65
54 x 4.25
45 x 4.77
54 x 4.36

1 x 4.25
1 x 4.77
1 x 1.78
7 x 2.00
7 x 2.12
7 x 2.54
7 x 2.25
7 x 2.69
7 x 2.44
7 x 2.92
7 x 2.68
7 x 3.20
7 x 3.28
7 x 2.89
7 x 3.46
7 x 2.69
7 x 3.09
19 x 2.22
7 x 2.75
7 x 2.82
7 x 2.82
7 x 3.27
19 x 2.35
7 x 2.92
7 x 3.47
19 x 2.48
7 x 2.25
7 x 3.08
7 x 3.23
7 x 3.28
7x 2.46
7 x 3.37
7 x 2.57
7 x 3.51
7 x 2.66
19 x 2.19
7 x 2.75
19 x 2.26
7 x 2.84
19 x 2.34
7 x 2.92
19 x 2.41
7 x 3.02
19 x 2.48
7 x 3.10
19 x 2.55
7 x 3.18
19 x 2.61

12.75
14.30
16.05
16.31
17.27
17.78
18.31
18.82
19.89
20.47
21.79
22.43
22.96
23.54
24.20
24.20
25.14
25.88
24.81
25.40
25.40
26.69
27.46
26.31
28.14
28.95
27.00
27.76
29.11
29.51
29.59
30.37
30.81
31.65
31.98
32.84
33.07
33.86
34.16
35.10
35.20
36.17
36.24
37.21
37.24
38.25
38.15
39.24

rea nominal
del aluminio

Calibre equivalente
cobre duro

Numero de Dimetro
de Alambres

Peso
Nominal
kg/km
341.7
430.3
509.6
543.6
610.8
696.4
683.3
780.1
809.4
921.7
972.4
1105.6
1162.2
1133.7
1290.6
1159.3
1295.0
1462.2
1217.0
1271.3
1276.0
1457.8
1644.3
1372.0
1619.1
1827.8
1326.1
1515.5
1677.0
1715.3
1591.0
1818.9
1724.2
1969.9
1857.4
2117.9
1983.2
2268.9
2122.3
2419.8
2252.6
2570.8
2387.3
2723.2
2519.0
2874.2
2652.2
3025.2

CABLES
Desnudos de Aluminio
ACSR
Reactancia a 60 HZ 305 mm
de esparcimiento
Cdigo
Mundial
Turkey
Swan
Swanate
Sparrow
Sparate
Robin
Raven
Quail
Pigeon
Penguin

Calibre
AWG
6
4
4
2
2
1
1/0
2/0
3/0
4/0

Cableado
AL/Acero
6/1
6/1
7/1
6/1
7/1
6/1
6/1
6/1
6/1
6/1

Sol
No Viento
60
85
85
115
115
130
150
175
205
240

Ampacidad
(Amperes)
No Viento
Sol
No sol
Viento
70
95
95
130
130
150
175
205
240
275

105
140
140
185
185
210
240
275
315
365

Resistencia
Ohms / km

Inductiva
Ohms / km

Viento
No sol

DC20C

CA 25C

25C

75C

110
145
145
195
195
220
255
295
340
390

2.1135
1.3278
1.3136
0.8343
0.8251
0.6621
0.5243
0.4160
0.3304
0.2618

2.1489
1.3550
1.3386
0.8530
0.8432
0.6759
0.5381
0.4265
0.3379
0.2697

0.3937
0.3740
0.3773
0.3576
0.3609
0.3510
0.3412
0.3346
0.3228
0.3156

0.4823
0.4495
0.4626
0.4167
0.4232
0.4003
0.3871
0.3740
0.3609
0.3445

Capacidad
Megohms
Por Km
2.4639
2.3458
2.3327
2.2244
2.2113
2.1654
2.1063
2.0472
1.9882
1.9291

Reactancia a 60 HZ 305 mm
de esparcimiento
Cdigo
Mundial

Calibre
AWG

Cableado
AL / Acero

Sol
No Viento

Ampacidad
(Amperes)
No Viento
Sol
No sol
Viento

Viento
No sol

DC20C

CA 25C

Inductiva
Ohms / km
Megohms
por / km

RESISTENCIA
Ohms / km

Capacidad
Megohms
Por Km

Waxwing
Partidge

266,800
266,800

18/1
26/7

300
305

345
355

445
455

480
490

0.2119
0.2098

0.2169
0.2146

0.2559
0.2890

1.8898
1.8602

Ostrich
Merlin
LInnet
Oriole
Chickadee
Ibis
Lark
Pelican
Flicker
Hawk
Hen

300,000
336,400
336,400
336,400
397,500
397,500
397,500
477,000
477,000
477,000
477,000

26/7
18/1
26/7
30/7
18/1
26/7
30/7
18/1
24/7
26/7
30/7

330
350
360
365
390
405
410
440
450
460
460

390
405
420
425
460
470
475
520
530
540
540

495
515
530
530
575
590
590
640
670
660
660

530
560
570
575
620
640
640
700
710
720
720

0.1867
0.1679
0.1666
0.1653
0.1421
0.1409
0.1399
0.1184
0.1178
0.1174
0.1166

0.1906
0.1719
0.1699
0.1690
0.1457
0.1444
0.1434
0.1217
0.1207
0.1201
0.1191

0.2844
0.2871
0.2802
0.2766
0.2808
3.2739
0.2700
0.2739
0.2684
0.2676
0.2634

1.8307
1.8274
1.8012
1.7881
1.7848
1.7585
1.7454
1.7388
1.7192
1.7126
1.6962

Osprey
Parakeet
Dove
Eagle
Peacock
Squab

556,500
556,500
556,500
556,500
605,000
605,000

18/1
24/7
26/7
30/7
24/7
26/7

490
500
510
510
530
540

580
590
600
600
630
630

710
720
730
730
760
760

770
790
790
800
830
830

0.1015
0.1010
.01006
0.0999
0.0929
0.0926

0.1043
0.1037
0.1033
0.1027
0.0955
0.0951

0.2684
0.2628
0.2708
0.2579
0.2598
0.2579

1.6995
1.6798
1.6732
1.6568
1.6568
1.6503

Teal
Rook
Grosbeak
Egret

605,000
636,000
636,000
636,000

30/19
24/7
26/7
30/19

540
550
560
560

640
650
660
660

770
780
790
790

840
860
860
870

0.0920
0.0884
0.0880
0.0875

0.0942
0.0906
0.0902
0.0899

0.2549
0.2579
0.2559
0.2523

1.6339
1.6470
1.6371
1.6240

CABLES
Desnudos de Aluminio
ACSR
Cdigo
Mundial
Flamingo
Crow
Starling
Redwing
Tern
Condor
Drake
Mallard
Crane
Canary
Rail
Cardinal
Ortolan
Curlew
Bluejay
Finch
Bunting
Grackle
Bittern
Pheasant
Dipper
Martin
Bobolink
Plover
Nuthatch
Parrot
Lapwing
Falcon
Chukar
Bluebird
Kiwi

Reactancia a 60 HZ 305 mm
de esparcimiento
Calibre
AWG
666,600
715,500
715,500
715,500
795,000
795000
795000
795000
874500
900000
954000
954000
1,033.500
1,033.500
1,113,000
1,113,000
1,192,500
1,192,500
1,272,000
1,272,000
1,351,500
1,351,500
1,431,000
1,431,000
1,510,500
1,510,500
1,590,000
1,590,000
1,780,000
2,156,000
2,167,000

Cableado
AL/Acero
24/7
54/7
26/7
30/19
45/7
54/7
26/7
30/19
54/7
54/7
45/7
54/7
45/7
54/7
45/7
54/19
45/7
54/19
45/7
54/19
45/7
54/19
45/7
54/19
45/7
54/19
45/7
54/19
84/19
84/19
72/7

Sol
No Viento
570
600
610
610
630
640
650
660
690
700
720
730
760
770
790
810
830
850
870
890
900
920
940
950
970
990
1010
1030
1090
1230
1220

Ampacidad
(Amperes)
No Viento
Sol
No sol
Viento
670
700
710
720
750
760
770
780
810
830
850
870
900
910
940
960
990
1010
1030
1050
1080
1100
1120
1140
1160
1180
1200
1230
1300
1480
1460

810
840
850
860
890
900
910
910
960
950
970
990
1020
1040
1070
1090
1120
1130
1160
1180
1210
1230
1250
1270
1300
1320
1340
1360
1440
1610
1600

Resistencia
Ohms / km

Viento
No sol

DC20C

CA 25C

880
920
930
940
970
990
990
1000
1050
1050
1070
1090
1130
1150
1190
1210
1240
1260
1290
1320
1340
1370
1390
1420
1440
1470
1490
1520
1600
1810
1790

0.0843
0.0786
0.0782
0.0778
0.0713
0.0708
0.0704
0.0700
0.0642
0.625
0.0594
0.0584
0.0574
0.0568
0.0535
0.0531
0.0502
0.0495
0.0472
0.0466
0.0449
0.0440
0.0427
0.0417
0.0404
0.0400
0.0387
0.0381
0.0348
0.0295
0.0299

0.0869
0.0810
0.0804
0.0801
0.0738
0.0728
0.0728
0.0722
0.0666
0.0646
0.0620
0.0614
0.0574
0.0568
0.0535
0.0531
0.0502
0.0495
0.0472
0.0466
0.0449
0.0440
0.0427
0.0417
0.0404
0.0400
0.0387
0.0381
0.0348
0.0295
0.0299

69
KV

85
KV

118
KV

X
X
X
X
X

Inductiva
Ohms / km
25C

75C

0.2559
0.2529
0.2516
0.2480
0.2523
0.2487
0.2480
0.2441
0.2454
0.2441
0.2454
0.2425
0.2425
0.2392
0.2398
0.2362
0.2372
0.2336
0.2349
0.2313
0.2323
0.2287
0.2306
0.2267
0.2280
0.2251
0.2260
0.2224
0.2205
0.2139
0.2162

Capacidad
Megohms
Por Km
1.6339
1.6142
1.6437
1.5945
1.6010
1.5879
1.5814
1.5650
1.5617
1.5551
1.5551
1.5420
1.5322
1.5190
1.5125
1.4993
1.4961
1.4829
1.4797
1.4665
1.4665
1.4501
1.4501
1.4337
1.4370
1.4206
1.4239
1.4108
1.3911
1.3451
1.3550

MANEJO DE CABLE DESNUDO A.C.S.R. EN SUS CALIBRES USUALES


Calibre
AWG
KCM
1X
1/0
3/0
266.8
336.4
477.0
795.0
900.0
113.0

B.T.

6
KV

13.2
KV

23
KV

34.5
KV

X
X

X
X

X
X
X
X
X

X
X
X
X
X

X
X
X
X
X

X
X
X
X

230
KV

400
KV

X
X
X

X
X

ESPECIFICACIN
ALCANCE: Esta especificacin cubre la construccin del cable de aluminio con refuerzo de acero (A.C.S.R.) , el cual est formado por un ncleo de
alambre (s) de acero galvanizado, sobre el cual se cablean una o ms capas de alambre de aluminio duro, dispuestos helicoidalmente.
NORMAS: Las siguientes normas y especificaciones forman parte de esta especificaciones: NOM-J-58, NOM - J-27, CFE E-0000-12.
CONSTRUCCIN: El conductor deber ser formado por alambres de aluminio puro temple duro, cableados sobre el ncleo de alambre o alambres de
acero galvanizados.
PRUEBAS: Las pruebas de los conductores en sus propiedades mecnicas y elctricas debern ser efectuadas de acuerdo a las normas de referencia:
NOM -J-27 Y NOM-J-58.

ALAMBRES y CABLES
Desnudos de Cobre

Cable de cobre con cableado concntrico

APLICACIN:
Estos conductores se utilizan en lneas areas para conduccin de energa elctrica en
alta y baja tensin o como componente principal de conductores aislados ms elaborados.
CARACTERSTICAS:
Alambre y cables de cobre en temple
a) Duro b) Semiduro c) Suave
*Resistividad a 20c (ohms-mm2/m)
a) 0.017745 b) 0.017654 c) 0.017241
*Coeficiente de Correccin por temperatura a 20C
a) 0.00382 b) 0.00378 c) 0.00393

Calibre
AWG

4/0
3/0
2/0
1/0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

Dimetro
nominal
mm

pulg

11.684
10.404
9.266
8.252
7.348
6.543
5.827
5.189
4.620
4.115
3.665
3.264
2.906
2.588
2.304
2.052
1.829
1.628
1.450
1.290
1.151
1.024

0.4600
0.4096
0.3648
0.3248
0.2893
0.2575
0.2294
0.2043
0.1818
0.1620
0.1143
0.1285
0.1144
0.1019
0.09070
0.08078
0.07200
0.6408
0.5707
0.05082
0.04526
0.04030

rea de la seccin
nominal
circular
mils
mm2
107.200
85.001
67.430
53.480
42.410
33.620
26.670
21.150
16.760
13.300
10.550
8.367
6.633
5.260
4.169
3.307
2.627
2.082
1.651
1.307
10.040
0.8235

211,600
167,800
133,100
105,600
83,690
66,360
52,620
41,740
33,090
26,240
20,820
16,510
13,090
10,380
8,230
6,530
5,180
4,110
3,260
2,580
2,050
1,620

Peso
kg/km

953.0
756.0
599.0
475.0
377.0
299.0
237.1
188.0
149.0
118.0
93.8
61.01
59.0
46.8
37.1
29.4
23.3
18.5
14.7
11.6
9.23
7.23

Duro
Resistencia
Ruptura a
elctrica
la tensin
20C en C.
mnima
ohms/km
kg
0.16552
0.20870
0.26317
0.33530
0.42292
0.53316
0.67227
0.84781
1.0689
1.3478
1.6998
2.1434
2.7028
3.4089
4.2981
5.4202
6.8343
8.6159
10.8666
13.7014
17.2777
21.7858

3.693.665
3049.009
2503.418
2048.911
1672.876
1362.160
1106.330
893.592
721.677
580.608
467.208
374.673
299.920
240.045
191.827
152.863
121.565
96.844
77.021
61.281
48.762
38.769

Semi-duro
Resistencia Ruptura a
elctrica
la tensin
20C en C.
mnima
ohms/km
kg
0.16467
0.20765
0.36182
0.33006
0.42062
0.53053
0.66866
0.84321
1.0633
1.3409
1.6910
2.1323
2.6887
3.3892
4.2751
5.3906
6.7982
8.57332
10.8108
13.6292
17.1891
21.6742

3166.128
2570.551
2086.106
1691.928
1371.686
111.320
899.942
718.502
573.350
458.138
365.873
292.073
233.241
186.157
148.599
118.661
94.711
75.569
60.328
48.172
38.424
30.667

Suave
Resistencia
Ruptura a
elctrica
la tensin
20C en C.
mnima
ohms/km
kg
0.16080
0.20276
0.25568
0.32242
0.40651
0.51282
0.64635
0.81532
1.0279
1.2963
1.6345
2.0611
2.5988
3.2773
4.1340
5.2102
6.5718
8.2845
10.4467
13.1764
16.6149
20.9491

2713.888
2152.332
1706.897
1353.542
1103.155
874.994
694.008
550.216
436.317
346.051
274.428
217.637
172.595
139.430
112.946
89.586
71.033
56.337
44.670
35.426
28.091
22.280

ALAMBRES y CABLES
Desnudos de Cobre

Cable de cobre con cableado concntrico

rea
Calibre
de la
KCM
seccin
O
transversal
AWG
mm2
5000
3000
2500
2000
1750
1500
1250
1000
900
800
750
700
600
500
400
350
300
250
4/0
3/0
2/0
1/0
1
2
3
4
5
6
8
10
12
14
16
18
20

2534.0
1520.00
1267.00
1013.00
886.70
760.10
633.30
506.77
456.00
405.40
380.00
354.70
304.00
253.40
202.74
177.35
152.00
126.70
107.20
85.00
67.43
53.48
42.41
33.62
26.67
21.15
16.76
13.30
8.367
5.260
3.307
2.082
1.307
0.8235
0.5191

Clase AA
Clase A
Nmero
Dimetro Nmero Dimetro
de
de
de
de
Alambres
Alambres cada
cada
alambre
alambre

37
37
37
37
37
37
19
19
12
12
12
7
7
7
7
3
3
3
3

4.176
3.961
3.735
3.616
3.494
3.234
4.121
3.686
4.337
4.016
3.667
4.416
3.932
3.502
3.119
4.243
3.777
3.364
2.996

169
127
91
91
91
61
61
61
61
61
61
61
37
37
19
19
19
19
7
7
7
7
7
7
7
7

4.369
3.904
4.210
3.765
3.522
3.983
3.636
3.252
3.085
2.909
2.816
2.721
3.234
2.953
3.686
3.447
3.192
2.914
4.416
3.932
3.502
3.119
2.777
2.473
2.203
1.961

Clase B
Nmero
Dimetro
de
de
Alambres
cada
alambre
217
169
127
127
127
91
91
61
61
61
61
61
61
37
37
37
37
37
19
19
19
19
19
19
7
7
7
7
7
7
7
7
7
7
7

3.856
3.384
3.560
3.187
2.982
3.261
2.977
3.252
3.085
2.909
2.816
2.721
2.519
2.953
2.641
2.470
2.287
2.088
2.680
2.387
2.126
1.893
1.686
2.473
2.203
1.961
1.746
1.555
1.234
0.978
0.776
0.615
0.488
0.387
0.307

Nmero
de
Alambres

Dimetro
de
cada
alambre

271
217
169
169
169
127
127
91
91
91
91
91
91
61
61
61
61
61
37
37
37
37
37
19
19
19
19
19
19
19
19
19
19
19
19

3.450
2.986
3.090
2.763
2.585
2.761
2.520
2.663
2.526
2.382
2.306
2.228
2.062
2.300
2.057
1.924
1.781
1.626
1.921
1.709
1.523
1.357
1.208
1.501
1.337
1.191
1.060
0.944
0.749
0.594
0.471
0.374
0.296
0.235
0.187

Clase D
Nmero
Dimetro
de
de
Alambres
cada
alambre
271
271
217
217
217
169
169
127
127
127
127
127
127
91
91
91
91
91
61
61
61
61
61
37
37
37
37
37
37
37
37
37

3.450
2.672
2.727
2.438
2.281
2.393
2.184
2.254
2.138
2.016
1.952
1.886
1.746
1.883
1.684
1.575
1.458
1.331
1.496
1.331
1.186
1.057
0.941
1.076
0.958
0.853
0.759
0.677
0.537
0.425
0.337
0.268

ALAMBRES y CABLES
Desnudos de Cobre
Calibre Cableado
KCM O
Clase
AWG
5000
5000
3000
3000
2500
2500
2000
2000
1750
1750
1500
1500
1250
1250
1000
1000
900
900
800
800
750
750
700
700
600
600
500
500
400
400
350
350
350
300
300
300
250
250
250
4/0
4/0
3/0
3/0
2/0
2/0
1/0
1/0

A
B
A
B
A
B
A
B
A
B
A
B
A
B
B-A
AA
B-A
AA
B-A
AA
B-A
AA
B-A
AA
B
A-AA
B-A
AA
A-AA
B
A
AA
B
A
AA
B
A
AA
B
A-AA
B
A-AA
B
A-AA
B
A-AA

Duro
rea
Resistencia
Carga
Nmero
de la
Peso
Dimetro
elctrica
ruptura
de
seccin
exterior Ampacidad
aproximado
20C y C.D.
kg
alambres transversal
aproximado
kg/km
mm2
mm
ohm/km
169
217
127
169
91
127
91
127
91
127
61
91
61
91
61
37
61
37
61
37
61
37
61
37
61
37
37
19
37
19
37
19
12
37
19
12
37
19
12
19
7
19
7
19
7
19
7

2534.00
2534.00
1520.40
1520.40
1267.00
1267.00
1013.60
1013.60
886.80
886.80
760.10
760.10
633.30
633.30
506.70
506.70
456.00
456.00
405.40
405.40
380.00
380.00
354.70
354.70
304.00
304.00
253.40
253.40
202.70
202.70
177.30
177.30
177.30
152.00
152.00
152.00
126.70
126.70
126.70
107.20
107.20
85.00
85.00
67.43
67.43
53.48
53.48

23653.60
23653.60
13921.80
13921.80
11601.50
11601.50
9190.00
9190.00
8041.30
8041.30
6892.40
6892.40
5742.60
5742.60
4590.00
4590.00
4140.00
4140.00
3676.3
3676.3
3445.8
3445.8
3216.3
3216.3
2757.5
2757.5
2296.9
2296.9
1838.0
1838.0
1609.0
1609.0
1609.0
1379.0
1379.0
1379.0
1149.0
1149.0
1149.0
1149.0
972.10
972.10
770.80
770.80
611.20
485.10
485.10

65.54
65.55
50.75
50.76
46.31
46.33
41.42
41.43
38.74
38.77
35.85
35.87
32.72
32.75
29.27
29.23
27.77
27.73
26.18
26.15
25.34
25.31
24.49
24.46
22.67
22.64
20.67
20.61
18.49
18.43
17.29
17.24
18.02
16.01
15.96
16.69
14.62
14.57
15.24
13.40
13.25
11.94
11.80
10.63
10.51
9.47
9.36

2000
2000
1860
1860
1715
1715
1540
1540
1300
1300
1220
1220
1130
1130
1090
1090
1040
1040
940
940
840
840
730
730
670
670
670
610
610
610
540
540
540
480
480
420
420
360
360
310
310

0.0074
0.0075
0.0121
0.0121
0.0146
0.0146
0.0181
0.0181
0.0206
0.0206
0.0241
0.0241
0.0289
0.0289
0.0361
0.0361
0.0401
0.0401
0.0451
0.0451
0.0481
0.0481
0.0516
0.0516
0.0602
0.0602
0.0722
0.0722
0.0903
0.0903
0.1030
0.1030
0.1030
0.1200
0.1200
0.1200
0.1440
0.01440
0.1440
0.1710
0.1710
0.2150
0.2150
0.2710
0.2170
0.3420
0.3420

21788
19880
19731
19226
17605
15930
15693
15150
14745
14139
12447
12256
10211
9957
8310
8079
7285
7072
6868
6291
6128
5974
5244
5153
5049
4362
4152
3492
3341
2791
2688
2222
2155

Semiduro
Suave
Resistencia Carga Resistencia Carga
elctrica
ruptura
elctrica
ruptura
20C y C.D.
kg
20C y C.D.
kg
ohm/km
ohm/km
0.0074
0.0074
0.0121
0.0121
0.0145
0.0145
0.0180
0.0180
0.0205
0.0205
0.0239
0.0239
0.0287
0.0287
0.0359
0.0359
0.0399
0.0399
0.0449
0.0449
0.0479
0.0478
0.0513
0.0513
0.0599
0.0599
0.0718
0.0718
0.0898
0.0898
0.1030
0.1030
0.1030
0.1120
0.1120
0.1120
0.1440
0.1440
0.1440
0.1700
0.1700
0.2140
0.2140
0.2700
0.2700
0.3400
0.3400

15898
15600
14376
14183
12812
12569
12021
11862
11278
11072
10788
9553
7961
7856
6414
6328
5647
5334
5461
4872
4776
4713
4061
4008
3954
3392
3297
2708
2636
2162
2105
1725
1680

0.00714
0.00714
0.0117
0.0117
0.0140
0.0140
0.0174
0.0174
0.0198
0.0198
0.0231
0.0231
0.0278
0.0278
0.0347
0.0347
0.0386
0.0386
0.0434
0.0434
0.0463
0.0463
0.0496
0.0496
0.0579
0.0579
0.0694
0.0694
0.0868
0.0868
0.0992
0.0992
0.0992
0.1160
0.1160
0.1160
0.1390
0.1390
0.1390
0.1640
0.1640
0.2070
0.2070
0.2670
0.2610
0.3290
0.3290

13256
13180
12630
11866
10866
10546
9942
9879
9333
9226
8080
7911
6591
6591
5271
5271
4799
4613
4613
4115
3954
3954
3429
3295
3295
2989
2789
2301
2212
1625
1755
1447
1391

ALCANCE:
Esta especificacin cubre la fabricacin de conductores slidos o cableados de cobre, temples duro,semi-duro o suave para usos elctricos
NORMAS:
Las siguientes normas forman parte de la presente especificacin: NOM-J-2, NOM-J-35, NOM-J-36, NOM-J-12, NOM-J-215, NOM-J-66, NOM-J-129 NOM-J-212, NOM-J312, ASTM B1, B2 Y B3.
CONDUCTOR:
La materia prima para la elaboracin de estos conductores debe ser alambrn de cobre segn NOM-J-215, donde se obtiene alambre de cobre en temple duro, semiduro o
suave para formacin slida o cableada, segn se requiera y de acuerdo a las normas correspondientes. No deber tener defectos tales como grietas. melladuras,
incisiones, astilladuras, etc. Los conductores de seccin circular cableados con una o ms capas de alambre dispuestos helicoidalmente, stos pueden ser de cobre duro,
semi-duro o suave. Los conductores cableados se clasifican de acuerdo al nmero de alambres como se indica a continuacin: Clase AA, Clase B, Clase C y Clase D.
PRUEBAS:
Las pruebas a que deben someterse estos conductores desnudos son las siguientes: Determinacin de los dimetros, Determinacin de resistencia elctrica,
Determinacin del rea de la seccin tranversal, Determinacin del esfuerzo de ruptura por tensin y alargamiento.

CABLE
THW, THHW/LS
APLICACIN:
La excelente caracterstica de flexibilidad que posee el Cable THW-THHW / LS permite su rpida y fcil instalacin en conduits, ductos o
charolas, tanto en ambiente seco o hmedo. La formulacin especial del aislamiento le proporciona excelentes caractersticas en condiciones
de incienso de manera que bajo condiciones del mismo, presenta baja emisin de humos oscuros y gases txicos, permitiendo as su
instalacin en interior de locales en donde hay gran influencia de personas tales como: hospitales, cines, teatros, almacenes, hoteles, sistemas
de transporte masivos como el metro y ferrocarril, as como en instalaciones industriales, o en aquellos lugares en donde se requiere mxima
seguridad.
CARACTERSTICAS
600 volts.
Conductor slido o cableado flexible clases C B
THHW/THW-LS Segn clasificacin NOM-J-10 y NEC 1990
Temperatura de operacin 90 C en ambiente seco y 75 C en ambiente hmedo.
Aislamiento de PVC resistente a la propagacin de incendio y bajo condiciones del mismo, tiene:
Baja emisin de humos oscuros y
Reducida emisin de gases txicos.

Aislamiento de P.V.C. Baja emisin de humos y gases txicos

Conductor de cobre slido o cableado

CONDUCTOR DESNUDO
Calibre
AWG o
KCM

Numero
de
hilos

Dimetro
de cada
hilos

Dimetro
total
mm

rea
mm2

20
18
16
14
12
10
8
6
4
2
1/0
2/0
3/0
4/0
250
300
350
400
500
750
1000

19
19
19
19
19
19
19
19
19
19
19
19
19
19
37
37
37
37
37
61
61

0.187
0.235
0.296
0.374
0.471
0.594
0.749
0.944
1.191
1.501
1.89
2.12
2.39
2.68
2.09
2.29
2.47
2.64
2.95
2.81
3.25

0.94
1.18
1.48
1.87
2.36
2.97
3.75
4.72
5.38
7.42
9.45
10.64
11.94
13.41
14.60
16.00
17.30
18.49
20.65
25.30
29.30

0.52
0.82
1.31
2.08
3.3
5.26
8.37
13.3
21.1
33.6
53.4
67.4
85.1
107
127
152
177
203
253
380
506

Espesor
nominal del
aislamiento
mm

Dimetro
exterior
Nominal
mm

Peso
aproximado
Kg/100m

Corriente
Admisible
en Conduit
A

0.76
0.76
0.76
0.76
0.76
0.76
1.14
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.41
2.41
2.41
2.41
2.41
2.79
2.79

2.46
2.70
3.00
3.39
3.88
4.49
6.03
7.76
8.43
10.46
13.51
14.7
16.00
17.47
19.42
20.82
22.12
23.31
25.47
30.88
34.88

1.1
1.3
1.8
2.8
4.2
6.1
10.2
116.5
24.5
36.5
58.5
72.0
89.5
115.5
132.5
157.5
181.5
205.5
254.0
386.5
520

7
10
14
20
25
35
50
65
85
115
150
175
200
230
255
285
310
335
380
475
545

ALCANCE:
Esta especificacin cubre la construccin de cables THHW / LS con conductor de cobre, slido o cableado, con aislamiento de PVC, no propagador de incendio y bajo
condiciones del mismo presenta baja emisin de humos oscuros y gases txicos y corrosivos. Para tensiones de operacin hasta de 600 volts. y temperatura de operacin en
el conductor de 90 C en ambiente seco 75 C en ambiente hmedo, clasificado segn NOM-J-10 y NEC-90 como THHW/THW-LS.
NORMAS:
Las siguientes normas forman parte de esta especificacin: NOM-J-10; NOM-J-93; NOM-J-472; NOM-J-474; ASTM E-662; IEC 754-1; NFC 32-0-070.
CONDUCTOR:
El conductor es de cobre suave, slido o cableado concntrico clase B o C de acuerdo con las especificaciones ASTM-NB-3 O B-8, dependiendo de la aplicacin.
AISLAMIENTO:
El aislamiento es de policloruro de vinilo (PVC) no propagador de incendio y baja emisin de humos oscuros y gases txicos y corrosivos.
COLORES:
Los colores de lnea son, para cables (20 a 8 AWG) y para alambres: negro, blanco, rojo, azul, amarillo, verde, caf y gris. Para cables en calibres del 6 al 1000 KCM en color
negro. Bajo pedido especial se podrn surtir en cualquier color.
EMPAQUE:
Cajas de cartn con 100mts. para calibres del 20 al 8 AWG. Rollos de 100 m para calibres de 6 al 4/0 AWG: Carretes con 500m para calibres de 1/0 al 1000 KCM.
PRUEBAS:
Las pruebas al conductor como producto terminado en sus propiedades fsicas y elctricas se realizan de acuerdo con las normas mencionadas anteriormente.

CABLE TRIFSICO
THW/LS
APLICACIN:
Cable multiconductor especialmente indicado para instalarse en charolas, ductos metlicos, tubera conduit, o en ductos subterrneos
de asbestocemento. Temperatura mxima de operacin en el conductor de 90C en ambiente seco y 75C en ambiente hmedo.
CARACTERSTICAS:
Conductor de cobre en cableado Clase B
Aislamiento termoplstico.
No propagador de incendio.
Tipo MTW
Indicado para conexiones a maquinas herramientas, con alimentacin trifsica.
Relleno de PVC negro antiflama

Conductor de cobre

Cubierta exterior PVC Coloreado antiflama

TABLA DE DIMENSIONES Y CORRIENTES ADMISIBLES


Calibre
AWG
KCM

Nmero
de
Conductores

Alambre
por
conducto

Espesor
de
aislamiento
mm

Espesor de
la cubierta
exterior
mm

Dimetro
total
aproximado
mm

6
4
2
1/0
2/0
3/0
4/0
250
300
350
400
500
750
1000

3
3
3
3
3
3
3
3
3
3
3
3
3
3

7
7
7
19
19
19
19
37
37
37
37
37
61
61

1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.41
2.41
2.41
2.41
2.41
2.79
2.79

1.52
2.03
2.03
2.03
2.03
2.03
2.03
2.79
2.79
2.79
2.79
2.79
3.56
3.56

19.91
23.54
26.86
32.98
35.44
38.24
41.47
47.34
50.36
53.16
55.75
60.49
73.62
82.24

*Corriente
Admisible en
aire
(A)

130
170
195
225
260
290
320
350
380
430
535
615

Peso
aproximado
Kg / Km
691.6
1029.5
1476.7
2284.2
2770.4
3374.9
4128.8
5081.9
5949.1
6808.6
7659.0
9345.2
15070.0
19546.0

ALCANCE:
La presente especificacin cubre la construccin de los cables trifsicos, formados por tres conductores de cobre suave cableado clase B y
aislados con policloruro de vinilo (PVC) para 90C no propagador de incendio, trenzados entre s y con un relleno de PVC negro no propagador
de incendio, para darle forma circular al conjunto. Sobre el relleno se aplica una capa de PVC no propagador de incendio para proporcionar
proteccin mecnica al conjunto. Estos cables son capaces de operar a una temperatura mxima en el conductor de 90C en ambientes secos y
de 75C en hmedos, y en contacto con aceites y grasas, para una tensin mxima de operacin de 600 volts.
NORMAS:
Las siguientes especificaciones y normas forman parte de la presente especificacin: ASTM: B-8; NOM-J-12; ICEA S-61-402; UL-83; IEEE-383;
NF-C-32-070 Y NFPA Standard No. 79 en las partes que corresponda.
CONDUCTOR:
El conductor es de cobre temple suave con cableado concntrico clase B y deber cumplir en general con lo indicado en la norma ASTM: B-8.
AISLAMIENTO:
El aislamiento es de PVC-90C no propagador de incendio aplicado sobre el conductor de acuerdo a las dimensiones indicadas en la tabla y de
colores Negro, Blanco y Rojo para identificacin de las fases. Cumpliendo en general con lo indicado en las normas de referencias.
RELLENO:
Despus de cablear los conductores monopolares se aplica sobre stos en relleno de PVC flexible no propagador de incendio para darle forma
circular al conjunto, cumpliendo con lo indicado en las normas de referencias.
CUBIERTA EXTERIOR:
Sobre el relleno de PVC se aplica una cubierta exterior de PVC no propagador de incendio color negro para proteccin mecnica del conjunto y
su espesor estar de acuerdo con lo indicado en la tabla de dimensiones. Cumpliendo en general con lo indicado en las normas de referencia.

CABLE ANTIFLAMA
THHW/LS
APLICACIN:
Conductor sencillo con aislamiento de policloruro de vinilo (PVC). Uso general para instalaciones en interior de locales, con ambiente seco o
hmedo, pudindose alojar en conduit, ductos o charolas.
CARACTERSTICAS:
Alambre o cable de cobre suave.
Aislamiento termoplstico no propagador de incendio.
Resistente a la humedad.
Temperatura de operacin 60 C
Aislamiento de PVC antiflama

Conductor de Cobre

TABLA DE DIMENSIONES Y CORRIENTES ADMISIBLES


Calibre
AWG
20
18
16
14
14
12
12
10
10
8
8
6
6
4
2
1/0
2/0
3/0
4/0

Conductor desnudo
Hilos
Dimetro
Dimetro
Nmero
mm
mm
1
1
1
1
7
1
7
1
7
1
7
1
7
7
7
19
19
19
19

0.81
1.02
1.29
1.63
0.61
2.05
0.77
2.59
0.98
3.26
1.23
4.11
1.55
1.96
2.47
1.89
2.12
3.39
2.68

0.81
1.02
1.29
1.63
1.84
2.05
2.32
2.59
2.95
3.26
3.71
4.11
4.67
5.89
7.42
9.45
10.64
11.94
13.41

Dimetro
total
mm

Peso
aproximado
kg /100 m

2.39
2.60
2.87
3.21
3.42
3.63
3.90
4.17
4.53
5.64
6.03
7.27
7.83
9.05
10.58
13.51
14.70
16.00
17.47

0.9
1.2
1.7
2.7
2.8
2.9
4.2
5.8
6.1
9.9
10.2
15.8
16.5
24.5
36.5
58.5
72.0
89.5
111.5

Corriente admisible (A) *


en Conduit o Cableado
En
Nmero de Conductores
1a3
4a6
7 a 24
aire

15
20
20
25
25
30
30
40
40
55
55
70
95
125
145
165
195

12
16
16
20
20
24
24
32
32
44
44
56
76
100
116
132
156

10
14
14
17
17
21
21
28
28
38
38
49
66
87
101
115
136

25
25
30
30
40
40
60
60
80
80
105
140
195
225
260
300

Calibre
AWG
20
18
16
14
14
12
12
10
10
8
8
6
6
4
2
1/0
2/0
3/0
4/0

Datos aproximados y sujetos a tolerancias de manufactura.


*La corriente admisible est basada en una temperatura ambiente de 30C y temperatura en el conductor de 60C .
ALCANCE:
Esta especificacin cubre la construccin de conductores de cobre slido o cableados con aislamiento de policloruro de vinilo (PVC) antiflama tipo TW,
para tensin de operacin hasta 600V y temperatura de operacin en el conductor de 60 C.
NORMAS:
Las siguientes normas forman parte de esta especificacin: UL-83; ASTW: B3,B8; NOM-J-10;NOM-J-12; NOM-J-36; IEEE-383; NF-C-32--070.
CONDUCTOR:
El conductor es de cobre suave slido o cableado concntrico clase B
AISLAMIENTO:
El aislamiento es de policloruro de vinilo (PVC) antiflama.
COLORES:
Los colores de lnea son: negro, blanco, rojo, azul, amarillo, verde, caf y gris. Pudindose surtir cualquier color de acuerdo a las necesidades del
cliente.
EMPAQUE:
Se presenta en empaque de lnea en calibres del 20 AWG al 4/0 AWG, en rollos de 100m. Del 2 AWG al 4/0AWG, en tramos de 1000m, en carretes
de madera. Bajo pedido especial se podrn empacar de acuerdo a las necesidades del cliente.
PRUEBAS:
Las pruebas al conductor terminado en sus propiedades fsicas y elctricas, se realizan de acuerdo a lo indicado en UL-83, para la prueba de no
prolongacin de incendio deber cumplir con la norma NF-C-32-070:

CABLE DE NYLON
THHN
APLICACIN:
Uso general en industrias, edificios, hoteles, bodegas y en instalaciones donde ser requiere gran resistencia a los aceites y gasolinas.
CARACTERSTICAS:
Retardador de la flama.
Dimetro reducidos.
Indicado especialmente para instalaciones con sobre carga frecuentes.
Resistentes a la abrasin, y abuso mecnico, con bajo coeficiente de friccin debido a su cubierta de nylon.
Resistente a aceites, gasolina y solventes ligeros.
Cubierta de exterior de nylon

Conductor de cobre

Aislamiento de PC

TABLA DE DIMENSIONES Y CORRIENTES ADMISIBLES


Calibre
AWG
o kCM
14
14
12
12
10
10
8
8
6
6
4
2
1/0
2/0
3/0
4/0
250
300
350
400
500
750
1000

Conductor Desnudo
Dimetro
Hilos
Dimetro
Total
Nmero
mm
mm
1
7
1
7
1
7
1
7
1
7
7
7
19
19
19
19
37
37
37
37
37
61
61

1.63
0.61
2.05
0.77
2.59
0.98
3.26
1.23
4.11
1.55
1.96
2.47
1.89
2.12
2.39
2.68
2.09
2.29
2.47
2.64
2.95
2.81
3.25

1.63
1.84
2.05
2.32
2.59
2.95
3.26
3.71
4.11
4.67
5.88
7.42
9.45
10.64
11.94
13.41
14.60
16.00
17.30
18.49
20.65
25.60
29.31

Dimetro
Total
forrado
mm

Peso
Aproximado
kg/100m

2.59
2.80
3.01
3.28
3.79
4.15
5.04
5.49
5.89
6.45
8.22
9.74
12.35
13.54
14.84
16.31
18.04
19.44
20.74
21.93
24.09
29.36
33.37

2.3
2.5
3.5
3.7
5.5
5.9
9.0
9.07
13.8
14.8
23.6
36.2
57.7
71.6
89.2
111.3
132.9
158.1
183.2
208.3
258.5
3887.7
513.7

Corriente admisible*(AMPS)
En Conduits o Cableado
Nmero de Conductores

1a3

4a6

7 a 24

20
20
25
25
35
35
50
50
65
65
85
115
150
175
200
230
255
285
310
335
380
475
545

16
16
20
20
28
28
40
40
52
52
68
92
120
140
160
184
204
228
248
268
304
380
436

14
14
17
17
24
24
35
35
45
45
59
80
105
122
140
161
178
199
217
234
266
332
381

En
Aire

Calibre
AWG
o kCM

30
30
35
35
50
50
70
70
95
95
125
170
230
265
310
360
405
445
505
545
620
785
935

14
14
12
12
10
10
8
8
6
6
4
2
1/0
2/0
3/0
4/0
250
300
350
400
500
750
1000

Datos aproximados y sujetos a tolerancias de manufactura


*La corriente admisible esta basada en una temperatura ambiente de 30 C y temperatura de 75 C en el conductor.
ALCANCE:
Est especificacin cubre la construccin de los conductores de cobre, slidos y cableados, con aislamiento de PVC (Cloruro de Polivinilo(, para temperatura mxima de
operacin en el conductor de 75 C en ambientes hmedos (tipo THWN) y 90 C en ambientes secos Tipo (THHN), y una cubierta exterior de Nylon para tensiones de
operacin hasta 600 Volts.
NORMAS:
Las siguientes normas forman parte de seta especificacin: AST B3 B8; UL 83; ICEA-S-61 -402; NOM-J-10; NOM-J-38.
CONDUCTOR:
Conductor de cobre suave o recocido, slido o cableado clase B, de acuerdo con las normas de referencia, dependiendo de su aplicacin.
AISLAMIENTO:
Aislamiento de PVC (cloruro de Polivinilo), llevando como cubierta exterior un forro de Nylon, de acuerdo con NOM-J-10.
COLORES:
Los colores de lnea son: para alambres: negro, blanco, rojo, azul, amarillo, verde, caf, y gris. En calibres del 6 AWG al 100 kCM, en color negro.
EMPAQUE:
Se presenta en empaque de lnea, en calibres del 16 AWG al AWG, en rollos de 100m. Del 2 AWG al 4/0 AWG, en tramos de 500m. Bajo pedido especial se podrn empacar
de acuerdo a las necesidades del cliente.
PRUEBAS:
Las pruebas del conductor terminado en sus propiedades fsicas y elctricas debern ser efectuadas de acuerdo con lo indican las normas de referencia, para conductores
aislados con material termoplstico y cubierta protectora de Nylon.

CABLE
Portaelectrodos
APLICACIN:
Estos conductores se usan generalmente en mquinas soldadoras elctricas, como extensiones desde la mquina al electrodo. 60C
mximos de temperatura en el conductor y una tensin mxima de 600 volts.
CARACTERSTICAS:
Magnficas propiedades dialcticas y mecnicas, con retencin de las mismas, aun despus de uso prolongado.
Resistente a la intemperie, cidos, grasas y abrasin.
No propaga la flama.
Extraflexible, facilitando su manejo.
En colores negro y amarillo.

Conductor extraflexible de
cobre, tipo calabrote

Aislamiento de PVC flexible

TABLA DE DIMENSIONES Y AMPACIDADES

Calibre
AWG

Nmero de
hilos. Calibre
34 AWG

Dimetro
sobre el
conductor mm

6
4
2
1/0
2/0
3/0
4/0

665
1064
1666
2646
3325
4256
5320

5.400
6.830
8.560
10.700
12.900
14.600
16.400

Espesor de Aislamiento
mm
pulg
2.2
2.2
2.7
3.0
3.0
3.0
3.0

0.086
0.086
0.016
0.118
0.118
0.118
0.118

Dimetro Exterior
mm
pulg
9.91
11.4
14.0
16.8
18.9
20.6
22.4

0.390
0.448
0.551
0.661
0.744
0.811
0.881

Ampacidad*
amperes

peso
kg/km.

80
105
140
195
225
260
300

203.16
296.24
458.23
696.83
861.34
1067.42
1302.71

Datos aproximados y sujetos a tolerancias de manufactura.


* La ampacidad est basada a una temperatura ambiente de 30C.

ALCANCE:
Esta especificacin cubre la construccin del cable portaelectrodo, el cual deber estar formado por conductor extraflexible de cobre temple
suave y aislamiento de PVC flexible, que deber ser capaz de operar a una temperatura mxima en el conductor de 60C y una tensin
mxima de 600 volts. Para ser usado en mquinas soldadoras elctricas por arco, tanto en corriente continua como en corriente alterna.
NORMAS:
Las siguientes normas forman parte de la presente especificacin: NOM-J-14; NOM-J-37; ICEA-S-19-81.
CONDUCTOR:
El conductor deber ser de cobre extraflexible, temple suave, en cableado clase M, compuesto de alambre de calibre 34 AWG, cableados
entre s y en forma de calabrote, de acuerdo en lo indicado en la forma oficial mexicana NOM-J-14.
AISLAMIENTO:
El aislamiento debe ser de cloruro de polivinilo (PVC), especialmente formulado para ser flexible, y pigmentado en colores amarillo y negro.
Deber ser aplicado por extorsin y el acabado en forma estriada, para darle mayor resistencia a la abrasin. En general deber cumplir con
las dimensiones mostradas en la tabla.
EMPAQUE:
Se presentan en carretes de 500m, pudindose empacar segn necesidades del cliente y de comn acuerdo con el fabricante.

CABLE TERMAFLEX
Portaelectrodo
Conductor extraflexible de cobre suave.
Separador de papel o polister.
Aislamiento elastomrico.

Aplicacin:
Para soldadora elctrica por arco, tanto con corriente continua como alterna.
Conexin entre la fuente de potencia y electrodo.

Caractersticas
Por su cableado especial este cable es extremadamente flexible.
Alta resistencia a la mayora de aceites y agentes qumicos.
Resistente a la compresin, abrasin y al manejo rudo.

Especificacin:
NMX-J-37.
NOM-063.

Certificacin:
Sistema de Calidad certificado de acuerdo a normas ISO 9000.
ANCE.

Temperatura mxima de operacin:


Normal 90C

Calibre AWG

Dimetro nominal del


conductor mm

Espesor nominal del


aislamiento (cubierta) mm

Dimetro exterior
nominal mm

Peso kg/km

4
2
1
1/0
2/0
3/0
4/0

6.4
8
9.4
10.5
11.7
13.2
14.9

1.6
2.03
2.03
2.03
2.41
2.41
2.41

9.9
12.5
14
15.2
17
18.5
20.2

315
396
630
647
791
1009
1243

NOTA: Estos datos son aproximados y estn sujetos a tolerancias de manufactura

TERMAFLEX 105C
Cable salida motor 600 Volts
Conductor flexible de cobre suave.
Separador de papel o polister.
Aislamiento elastomrico.

Aplicacin:
En salidas de motores, balastras, generadores, tuberas o fuentes de calor, hornos, fundiciones y
cualquier instalacin que opere con altas temperaturas.

Caractersticas:
El cable TERMAFLEX M.R. 105 es resistente a la humedad, aceite y a la mayora de los agentes qumicos.
La gran flexibilidad de los cordones TERMAFLEX soportar movimientos y vibraciones del equipo.
Es resistente a altas temperaturas.
Es resistente a la flama (prueba VW-1-UL y FV-2-NMX-J-192).
Gran capacidad de conduccin de corriente.

Especificacin:
CONDUMEX P 13021-A3.

Certificacin:
Sistema de Calidad certificado de acuerdo a normas ISO 9000.

Temperatura de
Normal 105C

Cordn TERMAFLEX M.R. 105, 600 Volts


Calibre AWG

Nmero y dimetro de
los hilos mm

Dimetro nominal del


conductor mm

Espesor nominal del


aislamiento mm

Dimetro exterior
nominal mm

Peso Kg/ Km

18
16
14
12
10
8
6
4
2
1/0
2/0
3/0
4/0

16/0.254
26/0.254
41/0.254
65/0.254
104/0.254
133/0.282
133/0.356
133/0.450
133/0.566
259/0.513
342/0.511
418/0.511
532/0.511

1.2
1.5
1.9
2.4
3
4
5
6.3
7.9
10
11.9
13.2
14.9

1.14
1.14
1.14
1.14
1.14
1.57
1.57
1.57
1.57
1.98
1.98
1.98
1.98

3.9
4.2
4.6
5.1
5.7
7.5
8.6
10
11.1
14.5
16.5
17.2
19.7

25
30
40
55
75
130
187
274
396
644
802
990
1222

NOTA: Estos datos son aproximados y estn sujetos a tolerancias de manufactura

TERMAFLEX 200C
Cable salida motor 600 Volts
Conductores flexible de cobre suave estaado.
Aislamiento de hule silicn.
Malla trenzada de fibra de vidrio impregnada.

Aplicacin:
Gran capacidad de conduccin de corriente.
En salidas de motores, balastras, generadores, tuberas o fuentes de calor, hornos, fundiciones, y
cualquier instalacin que opere con altas temperaturas.

Caractersticas:
El cordn TERMAFLEXM.R. 200 es resistente a la humedad, aceite y a la mayora de los agentes qumicos.
La gran flexibilidad de los cordones TERMAFLEXM.R. 200 facilita sus instalaciones y les permite
soportar movimientos y vibraciones del equipo.
Es resistente a altas temperaturas.
Es resistente a la flama (prueba VW-1-UL y FV-2-NMX-J-192).

Especificacin:
CONDUMEX P 13031-1.

Certificacin:
Sistema de Calidad certificado de acuerdo a normas ISO 9000.

Temperatura de
Normal 200C

Cordn TERMAFLEX M.R. 200, salida de motores, 600 Volts


Calibre AWG

Conductor numero de
hilos

Dimetro nominal del


conductor mm

Espesor nominal del


aislamiento mm

Dimetro exterior
nominal mm

Peso Kg/ Km

18
16
14
12
10
8
6
4
2
1/0
2/0
3/0
4/0
250
300
400
500

16
26
41
65
104
133
133
133
189
259
342
418
532
637
735
980
1,225

1.20
1.50
1.90
2.40
3.00
4.00
5.00
6.20
7.90
9.90
11.90
13.20
14.80
17.00
18.10
21.10
23.60

0.76
0.76
1.14
1.14
1.14
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.41
2.41
2.41
2.41

3.40
3.70
4.90
5.20
6.00
7.90
8.90
10.20
11.80
15.00
16.70
17.90
19.60
22.60
23.70
26.50
29.00

20
26
42
57
78
128
183
267
395
629
773
950
1,192
1,434
1,670
2,178
2,675

NOTA: Estos datos son aproximados y estn sujetos a tolerancias de manufactura

FLEXANEL
Salida de motor 90C
Conductor flexible de cobre.
Aislamiento de PVC.

Aplicacin:
Alambrado interno de equipo elctrico y electrnico. Salida de las puntas de los transformadores y
motores. Puede ser utilizado para aplicaciones electrnicas con una tensin de 2500 V pico.
Nota: No aplicable en alambrado de tableros para la C.F.E.

Caractersticas:
Resistencia al maltrato mecnico.
Resistente a la humedad.
Flexibilidad.

Especificacin:
NMX-J-429.
UL Subject 758.
CONDUMEX EM-01-008.

Certificacin:
Sistema de Calidad certificado de acuerdo a normas ISO 9000.
ANCE.

Empaque:
En carretes de madera con una longitud nominal de 1000 m y rollos de 100 m en caja de cartn.

Temperatura de peracin:
Normal 90C

Cordn FlexanelM.R. con aislamiento de PVC 90 C, 600 V,


Calibre AWG

Construccin No. de
hilos/ AWG

Dimetro exterior mm

Peso kg/km

10
12
14
16
18
20

65/28
41/28
26/28
16/28
16/30
11232

4.6
4
3.5
3.1
2.8
2.6

60.41
41.07
28.47
20.12
14.65
11.05

Capacidad de conduccin de
corriente A
40
30
25
18
14
11

Estos datos son aproximados y estn sujetos a tolerancias de manufactura.


NOTA: La capacidad de conduccin de corriente est calculada a una Temperatura del conductor de 90 C y una temperatura ambiente de 30 C.

CABLE
SPT
APLICACIN:
Para usarse en extensiones de lmparas, estreos, ventiladores, TV y en general aparatos elctricos de poco consumo, as como en
extensiones mviles pueden instalarse en forma visible en conduit. Estos cables son capaces de operar a una temperatura de 60 C en
el conductor.
CARACTERSTICAS:
Excelentes propiedades dielctricas y mecnicas.
Resistente a la abrasin.
Resistente al calor y a la humedad.
Gran flexibilidad
Instalacin sencilla.

Conductor de cobre de multifilamentos


en temple suave.

Aislamiento de PVC flexible

TABLA DE DIMENSIONES Y CORRIENTES ADMISIBLES


Tipo

SPT-0
SPT-1
SPT-2
SPT-3

Designacin del Conductor


rea de la
Calibre
Seccin
AWG
Transversal
mm2
0.3247
0.5191 Y 0.8235
0.8235 A 2.082
0.8235 Y 1.307
2.082
3.307
5.260

22
20 Y 18
18 Y 14
18 Y 16
14
12
10

Espesor del
Aislamiento
Nominal
mm

No.
Conductores

Distancia Mnima
entre conductores
(mm)

Corriente
Admisibles*

0.64
0.76
1.14
1.52
2.03
2.41
2.79

2
2
2
2
2
2
2

0.96
1.14
2.03
2.79
2.79
2.79
2.79

3
7-10
10 a 20
18-13
20
25
30

ALCANCE:
Esta especificacin cubre la construccin del cable SPT (POT), el cual deber estar formado por dos conductores de cobre
extraflexibles, aislados con PVC especialmente flexible y unidos entre s por una membrana del mismo material aislante que permite la
separacin fcil de los conductores. Deber ser capaz de operar a 60 C mximos de temperatura en el conductor y a una tensin
mxima de 300 volts.
NORMAS:
Las siguientes normas forman parte de la presente especificacin: NOM-J-12, NOM-J-102, NOM-J-297; ASTM: B3,B8; UL 62, 1581.
CONDUCTOR:
El conductor deber ser de cobre temple suave, especial para uso elctricos, cableado clase K, formado por varios alambres, de
acuerdo a lo indicado en la tabla de dimensiones.
AISLAMIENTO:
El aislamiento del conductor deber ser un compuesto de policloruro de vinilo (PVC), especialmente formulado para ser flexible y
pigmentado en colores blanco, negro, caf, rojo y azul.
MARCADO:
El aislamiento de uno de los conductores debe estar marcado secuencialmente en toda su longitud con una distancia mxima de 30 cm,
indicando marca del fabricante, tipo de producto, calibre, voltaje de operacin, temperatura de operacin y el smbolo NOM.
EMPAQUE:
El cable deber empacarse en envases de cartn, conteniendo rollos de 100 m, o segn las necesidades del cliente y de comn
acuerdo con el fabricante.
PRUEBAS:
Las pruebas del conductor, debern ser efectuadas de acuerdo a lo indicado en las normas de referencias, en las partes que
correspondan.

CABLE
De uso rudo
ST 600 Volts y SJT 300 Volts
Conductores flexible de cobre suave.
Separador.
Aislamiento elastomrico.
Rellenos flexibles.
Cinta reunidora de polister.
Cubierta externa elastomrica.
Aplicacin:

Especificacion:

Alimentacin de equipo elctrico porttil o semiporttil,


en industrias ligeras y pesadas as como soldadoras,
taladros, etc.

NMX-J-436. UL-62.
NOM-063.

Temperatura de

Caracteristicas:

Normal 90C

Gran flexibilidad.
Gran resistencia mecnica.
Resistente a la abrasin, humedad, cidos y aceites.
La cubierta elastomrica proporciona resistencia al contacto
momentneo con objetos calientes.
No.
Cond.

Calibre
AWG

18
16
14
12
10
8
6
4
2
18
16
14
12
10
8
6
4
2
18
16
14
12
10
8
6
4
2

Dimetro nominal del


conductor
mm
TIPO SO
TIPO SJO
1.20
1.50
1.60
1.90
2.40
2.40
3.00
3.00
4.10
5.20
6.60
8.00
1.20
1.50
1.90
1.90
2.40
2.40
3.00
3.00
4.10
5.20
6.60
8.00
1.20
1.50
1.90
1.90
2.40
2.40
3.00
3.00
4.10
5.20
6.60
8.00

Espesor nominal del


aisalmiento
mm
TIPO SO
TIPO SJO
0.76
0.76
1.14
0.76
1.14
0.76
1.14
1.14
1.52
1.52
1.52
1.52
0.76
0.76
1.14
0.76
1.14
0.76
1.14
1.14
1.52
1.52
1.52
1.52
0.76
0.76
1.14
0.76
1.14
0.76
1.14
1.14
1.52
1.52
1.52
1.52

NOTA: Estos datos son aproximados y estn sujetos a tolerancias de manufactura

Dimetro exterior nominal


mm
TIPO SO

13.90
15.70
16.70
21.00
23.70
27.40
31.40

14.20
16.10
17.30
22.20
25.30
29.00
32.90

15.40
17.40
18.80
24.90
28.20
32.40
36.70

TIPO SJO
7.90
8.30
9.10
11.00
13.40

8.10
8.70
10.00
11.40
16.00

8.80
9.90
10.80
12.50
16.80

Peso Kg/Km
TIPO SO

238
312
377
584
730
1,028
1,410

284
374
459
711
925
1,295
1,820

337
444
552
918
1,192
1,595
2,228

TIPO SJO
80
90
115
190
265

100
120
174
240
330

120
162
183
300
453

CABLE
De uso rudo
SJO 300 Volts y SO 600 Volts
Conductores flexible de cobre suave.
Aislamiento de PVC.
Relleno flexible.
Cinta reunidora.
Cubierta de PVC lisa o estriada.
Aplicacin:
Alimentacin de aparatos estacionarios o porttiles para uso industrial, comercial o domstico
tales como refrigeradores, lavadoras, taladros, sierras mecnicas, calculadoras, etc.

Caractersticas:

Especificacin:
ANCE.

Gran flexibilidad.

Certificacin:
NMX-J-436. UL-62.

Temperatura de
Normal 60C

NOM-063.

Gran resistencia mecnica.


Resistente a la abrasin, humedad, cidos y aceites.

Cordn uso rudo, tipo SO de 600 Volts


Nmero de
conductores

Calibre
AWG

Dimetro nominal del


conductor
mm

2
2
2
2
2

18
16
14
12
10
18
16
14
12
10

1.22
1.55
1.96
2.46
3.1
1.19
1.55
1.96
2.46
3.1

3
3
3
3
3

Espesor nominal del


aislamiento
mm
0.76
0.76
0.76
0.76
1.14
0.76
0.76
0.76
0.76
1.14

Dimetro exterior
nominal
mm
7.9
8.6
9.4
11.2
14.7
8.4
9.1
10
11.8
15.6

Peso Kg/km
68
85
112
166
287
81
103
137
202
349

Cordn uso rudo, tipo SJO de 300 Volts


Nmero de
conductores

Calibre
AWG

Dimetro nominal del


conductor
mm

2
2
2
3
3
3
2
3
2
3

12
10
8
14
12
10
8
6
4
2

2.4
3
4.1
1.9
2.4
3
4.1
5.1
6.5
8

Espesor nominal del


aislamiento
mm

NOTA: Estos datos son aproximados y estn sujetos a tolerancias de manufactura.

1.14
1.14
1.52
1.14
1.14
1.14
1.52
1.52
1.52
1.52

Dimetro exterior
nominal
mm

Peso Kg/km

15.4
16.6
21.2
14.3
15.7
17
21.8
25.3
29.1
34.1

257
321
539
233
308
407
610
916
1288
1810

CABLE
Para bombas
Sumergibles 600 Volts
Conductor flexible de cobre suave.
Aislamiento de polietileno.*
Cubierta de PVC.
*Nota: Se puede ofrecer con aislamiento de etileno propileno (EP).

Aplicacin:
Uso general en la alimentacin de bombas sumergibles en crcamos de bombeo.

Caractersticas:
Gran resistencia a la humedad.
Facilidad de instalacin debido a su flexibilidad.
Resistente a la abrasin y al ozono.

Certificacin:
Sistema de Calidad certificado de acuerdo a normas ISO 9000.
ANCE.

Especificacin:
NMX-J-514.

Temperatura de Operacin:
Normal 75C

Cable para alimentacin de bombas sumergibles


Calibre AWG

Dimetro nominal del


conductor mm

Dimetro sobre
aislamiento mm

12
10
8
6
4
2
1/0
2/0
3/0
4/0

2.40
3.10
3.90
4.90
6.30
7.90
9.80
11.60
13.20
14.90

4.80
5.40
6.70
7.70
9.10
10.80
13.30
15.10
16.60
18.30

NOTA: Estos datos son aproximados y estn sujetos a tolerancias de manufactura.

Dimensiones nominales
Alto
Ancho
7.90
8.70
11.10
11.90
13.30
14.90
18.90
20.70
22.30
24.00

17.50
19.40
24.50
27.50
31.70
36.60
45.60
51.00
55.70
60.80

Peso Kg/Km
225
295
480
650
950
1,370
2,150
2,695
3,240
3,990

CABLES
XLP y XLPE
600 V TIPO XHHW
APLICACIN:
Estos conductores monopolares estn especificados para uso general hasta 600 Volts, en la distribucin de energa elctrica en
instalaciones areas en tubo conduit o ducto subterrneo. Temperatura de operacin normal de 90 C, 130 C en condiciones de
emergencia y 250 C en condiciones de corto circuito.
CARACTERSTICAS:
* Resistente a la mayora de aceites y grasas
* Alta resistencia a la penetracin de humedad
* Supera las propiedades trmicas del butilo y del polietileno
* Resistente a bajas temperaturas.
Aislamiento de polietileno
de cadena cruzada XLP

Conductor de Cobre
temple suave

TABLA DE DIMENSIONES Y CORRIENTES ADMISIBLES

Conductor

Desnudo

Calibre
AWG o
KCM

Nmero
de
alambres

Dimetro
mm

14
12
10
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
750
1000

7
7
7
7
7
7
7
19
19
19
19
19
37
37
37
37
37
61
61
61

1.85
2.34
2.94
3.69
4.65
5.88
7.41
4.18
9.45
10.65
11.95
13.40
14.63
16.03
17.30
18.48
20.65
22.68
25.35
29.25

Peso
Kg / Km

Espesor
del
aislamiento
mm

Dimetro
exterior
Aproximado
mm

Peso
Aproximado
Kg / 100m.

Corriente
Admisible
(A)*

18.9
30.1
47.8
75.9
121
192
305
384
485
612
771
972
1149
1379
1609
1838
2297
2757
3446
4595

0.76
0.76
0.76
1.14
1.14
1.14
1.14
1.40
1.40
1.40
1.40
1.40
1.65
1.65
1.65
1.65
1.65
2.03
2.03
2.03

3.70
4.16
4.77
6.27
7.21
8.38
9.85
11.61
12.62
13.73
12.23
16.43
18.26
19.56
20.86
21.96
24.06
26.82
29.42
33.22

26
38
58
96
145
220
340
445
512
670
837
1045
1246
1483
1720
1957
2430
2937
3646
4814

25
30
40
55
75
130
150
170
195
225
260
290
320
350
380
430
475
535
535
615

*La corriente admisible est basada en tres conductores aislados en charola y una temperatura ambiente de 30C.
Datos aproximados y sujetos a tolerancia de manufactura.
ALCANCE:
La presente especificacin cubre la construccin del cable XLP tipo XHHW con conductor de cobre, aislamiento de polietileno de cadena cruzada
XLP color negro para uso general, y operacin mxima de temperatura en el conductor de 90 C, 130 C en condiciones de sobre carga en
emergencias y 250 C en condiciones de corto circuito. Clasificados para ser empleados hasta tensin mxima de 600 volts.
NORMAS:
Las siguientes especificaciones y normas forman parte de la presente especificacin: ICEA S-66-524, NOM -J-12, UL 44.
CONDUCTOR:
El aislamiento es de polietileno de cadena cruzada (XLP) pigmentado con negro humo y debe cumplir en general con lo especificado en ICEA S-66524 y U.L.-44

CABLE PARA MEDIA TENSIN


Para 5, 15, 25 y 35 KV
EP, XLP
Conductor compacto cableado clase "B", de cobre suave.
Pantalla semiconductora extruda sobre el conductor.
Aislamiento de EP o XLP 100% N.A.
Pantalla semiconductora extruda sobre aislamiento.
Pantalla electrosttica a base de alambres de cobre suave.*
Cinta separadora.
Cubierta exterior de PVC.
Aplicacin
Sistemas trifsicos de distribucin. Es apropiado para instalaciones areas, en ducto, directamente enterrado y en
charolas, cuando se requiera de mxima seguridad en la instalacin.

Caractersticas:
Proceso de real triple extrusin y curado en seco que mejora notablemente las caractersticas elctricas.
El aislamiento de XLP (Polietileno de cadena cruzada) ofrece:
Resistencia excelente al calor y a la humedad.
Resistencia excepcional a las descargas parciales.
Alta rigidez dielctrica.
Baja absorcin de humedad.
Bajas prdidas dielctricas.
El aislamiento de EP (Etileno Propileno) ofrece:
Resistencia excelente al calor y a la humedad.
Resistencia excepcional a las descargas parciales.
Alta rigidez dielctrica.
Baja absorcin de humedad.
Gran resistencia a las arborescencias.
Bajas prdidas dielctricas.
La cubierta del cable ofrece:
Resistencia a la propagacin del incendio (IEEE-383).
Mnima emisin de humos densos y oscuros (NMX-J-474).
Mnima emisin de gases txicos y corrosivos (NMX-J-472).
Resistencia a la abrasin, calor, humedad, aceites, grasas y productos qumicos

Temperatura mxima de operacin:


Normal 90C
Sobrecarga 130C
Cortocircuito 250C

CABLE PARA MEDIA TENSIN


Para 5, 15, 25 y 35 KV
EP, XLP

Area
mm2
8.37
13.3
21.15
33.62
53.48
67.43
85.01
107.2
127.2
177.3
253.4
304
380
506.7

Dimetro
Dimetro nominal
Calibre nominal del
sobre aislamiento
AWG/kCM conductor 5kV 15kV 25kV 35kV
mm
mm mm mm mm
8
6
4
2
1/0
2/0
3/0
4/0
250
350
500
600
750
1000

3.4
4.3
5.4
6.8
8.5
9.6
10.7
12.1
13.2
15.7
18.7
20.7
23.1
26.9

9.4
10
11.1
12.5
14.2
15.3
16.5
17.8
19.2
21.7
24.7
26.9
29.4
33.1

16.8
18.6
19.6
20.8
22.1
23.5
26
29
31.2
33.7
37.5

22.9
23.9
25.1
26.4
27.8
30.3
33
35.5
38
41.8

27.2
28.2
29.4
30.7
32.1
34.6
37.6
39.8
42.3
46.1

Dimetro exterior
Peso aproximado
nominal
5kV 15kV 25kV 35kV 5kV 15kV 25kV 35kV 5kV 15kV 25kV 35kV
mm mm mm mm kg/km kg/km kg/km kg/km kg/km kg/km kg/km kg/km
14.9
16.3
17.4
18.8
20.5
21.5
23.8
25.1
26.5
29
32
34.7
37.2
41

24.3
26
27.2
28.2
29.5
30.9
33.9
36.9
39.1
41.6
46.9

30.3
31.3
33
34.3
35.7
38.2
41.2
44.9
47.9
51.7

35.2
36.2
37.4
38.7
40.1
42.6
47.6
49.8
52.3
56.1

255
335
430
510
790
940
1,175
1,410
1,630
2,155
2,925
3,485
4,250
5,510

770
1,000
1,155
1,355
1,600
1,825
2,395
3,190
3,740
4,520
5,935

1,185
1,345
1,580
1,835
2,075
2,630
3,445
4,145
4,990
6,300

1,340
1,665
1,820
2,200
2,330
2,900
3,920
4,505
5,325
6,660

270
350
450
600
815
965
1,205
1,440
1,665
2,195
2,970
3,545
4,310
5,570

Estos datos son aproximados y estn sujetos a tolerancias de manufactura.


NOTA 1 :
NOTA 2 :
NOTA 3 :
NOTA 4 :

Estos cables se fabrican tambin con un nivel de aislamiento del 133% (N.A.133%).
Estos cables se fabrican tambin en construcciones trifsicas (Cubierta comn).
Estos cables se pueden fabricar bajo la norma UL-1072 y su asignacin ser cable tipo MV-90 (con aprobacin UL).
Estos cables se fabrican tambin con conductores de Aluminio.

820
1,060
1,220
1,420
1,670
1,905
2,495
3,300
3,860
4,645
6,080

1,280
1,445
1,690
1,955
2,200
2,770
3,600
4,315
5,180
6,510

1,490
1,755
1,975
2,245
2,505
3,095
4,140
4,745
5,580
6,945

CABLE TRIPLEX MEDIA TENSIN


Para 5, 15, 25 y 35 KV
EP, XLP
Conductor compacto cableado clase "B", de cobre suave.
Pantalla semiconductora extruda sobre el conductor.
Aislamiento de EP o XLP 100% N.A.
Pantalla semiconductora extruda sobre aislamiento.
Pantalla electrosttica a base de alambres de cobre suave.*
Cinta separadora.
Cubierta exterior de PVC.
Aplicacin
Sistemas trifsicos de distribucin. Es apropiado para instalaciones areas, en ducto, directamente enterrado y en
charolas, cuando se requiera de mxima seguridad en la instalacin.

Caractersticas:
Proceso de real triple extrusin y curado en seco que mejora notablemente las caractersticas elctricas.
El aislamiento de XLP (Polietileno de cadena cruzada) ofrece:
Resistencia excelente al calor y a la humedad.
Resistencia excepcional a las descargas parciales.
Alta rigidez dielctrica.
Baja absorcin de humedad.
Bajas prdidas dielctricas.
El aislamiento de EP (Etileno Propileno) ofrece:
Resistencia excelente al calor y a la humedad.
Resistencia excepcional a las descargas parciales.
Alta rigidez dielctrica.
Baja absorcin de humedad.
Gran resistencia a las arborescencias.
Bajas prdidas dielctricas.
La cubierta del cable ofrece:
Resistencia a la propagacin del incendio (IEEE-383).
Mnima emisin de humos densos y oscuros (NMX-J-474).
Mnima emisin de gases txicos y corrosivos (NMX-J-472).
Resistencia a la abrasin, calor, humedad, aceites, grasas y productos qumicos

Temperatura mxima de operacin:


Normal 90C
Sobrecarga 130C
Cortocircuito 250C

CABLE TRIPLEX MEDIA TENSIN


Para 5, 15, 25 y 35 KV
EP, XLP

rea
mm2
8.37
13.3
21.15
33.62
53.48
67.43
85.01
107.2
127.2
177.3
253.4
304
380
506.7

Dimetro nominal
Dimetro
Calibre nominal del
sobre aislamiento
conductor
5kV
15kV 25kV 35kV
AWG/kCM
mm
mm mm mm mm
8
6
4
2
1/0
2/0
3/0
4/0
250
350
500
600
750
1000

3.4
4.3
5.4
6.8
8.5
9.6
10.7
12.1
13.2
15.7
18.7
20.7
23.1
26.9

9.4
10
11.1
12.5
14.2
15.3
16.5
17.8
19.2
21.7
24.7
26.9
29.4
33.1

------16.8
18.6
19.6
20.8
22.1
23.5
26
29
31.2
33.7
37.5

--------22.9
23.9
25.1
26.4
27.8
30.3
33
35.5
38
41.8

--------27.2
28.2
29.4
30.7
32.1
34.6
37.6
39.8
42.3
46.1

Dimetro exterior
Peso aproximado Triplex
nominal
5kV 15kV 25kV 35kV 5kV 15kV 25kV 35kV 5kV 15kV 25kV 35kV
mm mm mm mm kg/km kg/km kg/km kg/km kg/km kg/km kg/km kg/km
32.1 --35.1 --37.5 --40.5 52.4
44.2 56
46.3 58.6
51.3 60.8
54.1 63.6
57.1 66.6
62.5 73.1
69 79.5
74.8 84.3
80.2 89.6
88.4 101.1

--------65.3
67.5
71.1
73.9
76.9
82.3
88.8
96.8
103
111

--------75.9
78
80.6
83.4
86.4
91.8
102.6
107.3
112.7
120.9

780
1,025
1,315
1,560
2,420
2,880
3,600
4,315
4,990
6,595
8,950
10,665
13,000
16,860

Estos datos son aproximados y estn sujetos a tolerancias de manufactura.


NOTA 1 : Estos cables se fabrican tambin con un nivel de aislamiento del 133% (N.A.133%).

------2,355
3,060
3,535
4,145
4,895
5,585
7,330
9,760
11,445
13,830
18,160

--------3,625
4,115
4,835
5,615
6,350
8,047
10,540
12,685
15,270
19,280

--------4,100
5,095
5,570
6,730
7,130
8,875
11,995
13,785
16,295
20,380

825
1,070
1,375
1,835
2,495
2,955
3,685
4,405
5,095
6,715
9,090
10,850
13,190
17,045

------2,510
3,245
3,735
4,345
5,110
5,830
7,635
10,100
11,810
14,214
18,605

--------3,915
4,420
5,170
5,980
6,730
8,475
11,015
13,205
15,850
19,920

--------4,560
5,370
6,045
6,870
7,665
9,470
12,670
14,520
17,075
21,250

CABLE
Para 69 y 115 KV
EP, XLP
Conductor compacto cableado clase "B", de cobre suave o aluminio con conductor sellado.
Pantalla semiconductora extruida sobre el conductor.
Aislamiento de EP o XLP.
Pantalla semiconductora extruida sobre aislamiento.
Pantalla electrosttica a base de alambres de cobre suave, reunidos con una cinta de cobre.
Cinta separadora.
Cubierta exterior de PVC.
Aplicacin
Circuitos de subtransmisin y transmisin subterrnea. Es apropiado para
instalaciones en ductos directamente enterrados o en charolas; cuando se requiera

Caractersticas:
Proceso de real triple extrusin y curado en seco que mejora notablemente las caractersticas elctricas.
El aislamiento de XLP curado en seco ofrece:
Excelente resistencia a la humedad.

El aislamiento de EP (Etileno Propileno) ofrece:


Resistencia excelente al calor y a la humedad.
Resistencia excepcional a las descargas parciales.

Buena resistencia a aceites.

Alta rigidez dielctrica.

Propiedades elctricas estables.

Baja absorcin de la humedad.

Bajas prdidas dielctricas.

Gran resistencia a las arborescencias.


Bajas prdidas dielctricas.
La cubierta del cable ofrece:
Resistencia a la propagacin del incendio (IEEE-383).
Mnima emisin de humos densos y oscuros (ASTM E-662, NMX-J-474).
Mnima emisin de gases txicos y corrosivos (IEC-754-1, NMX-J-472).
Resistencia a la abrasin, al calor, humedad, ozono, aceites, grasas y productos qumicos.

Certificacin:

Especificacin:

Temperatura mxima de operacin:

Certificado de acuerdo a normas ISO 9000.

CFE-E0000-17

IEC 228

Normal 90C

Prototipos aprobados por la C.F.E

NMX-J-142

AEIC-CS-6

Sobrecarga 130C

AEIC-CS-7

Cortocircuito 250C

Cable de energa VULCANEL M.R. EP o XLP, tipo DS

rea

Calibre

Dimetro del

mm2

kCM

conductor
mm

253

Dimetro
nominal sobre
aislamiento
69kV 115kV

Dimetro
exterior
nominal
69kV 115kV

69kV

115kV

69kV

115kV

69kV

115kV

69kV

115kV

mm

mm

mm

mm

kg/km

kg/km

kg/km

kg/km

kg/km

kg/km

kg/km

kg/km

-----

4,460

-----

Peso EP
Cobre

Peso XLP

Aluminio

Cobre

500

18.8

57.30

-----

69.20

-----

6,788

-----

5,110

-----

5,950

Aluminio

380

750

23.1

59.78

65.30

74.10

80.00

9,215

-----

6,640

-----

8,115

8,795

5,670

6,355

506.7

1000

26.9

62.50

69.10

76.80

83.80

1,101

-----

7,560

-----

9,810

10,620

6,570

7,115

800

-----

*36.86

-----

86.03

-----

100.71

-----

-----

-----

-----

-----

Estos datos son aproximados y estn sujetos a tolerancias de manufactura.

CABLE
XLPE-Pb
APLICACIN:
Se utiliza en plantas de refinacin de petrleo, plantas petroqumicas o donde se requiera excelente hermeticidad en el cable. Se
puede instalar directamente enterrado, en ducto o charolas.
CARACTERSTICAS:
Conductor de Cobre cableado clase B compacto, pantalla semiconductora extruda sobre el conductor, aislamiento extrudo de
Polietileno de cadena cruzada (XLP), pantalla semiconductora extruda sobre el aislamiento fcilmente desprendible, pantalla
metlica a base de plomo y cubierta exterior de Policloruro de vinilo (PVC) antiflama. La pantalla de Plomo provee hermeticidad al
cable, adems de ser resistente a humedad, lcalis, cidos y agentes qumicos.

CABLE XLP-Pb, 5-35 KV, 90C


Dimetro Total
mm

Dimetro sobre aislamiento


mm

Conductor
Calibre
AWG
KCM

No. de
alambres

Dimetro
total
mm

rea
mm2

5KV

8KV

6
4
2
1/0
2/0
3/0
4/0
250
300
350
500
750
1000

7
7
7
19
19
19
19
37
37
37
37
61
61

4.30
5.40
6.90
8.53
9.55
10.74
12.06
13.21
14.48
15.65
18.69
23.10
26.90

13.3
21.1
33.6
53.5
67.4
85.0
107.0
127.0
152.0
177.0
253.0
380.0
507.0

10.40
11.50
12.90
14.55
15.57
16.76
18.08
19.49
20.76
21.93
24.97
29.68
33.48

11.60
12.70
14.10
15.92
16.94
18.13
19.45
20.86
22.13
23.30
26.34
31.05
34.85

*Datos aproximados sujetos a tolerancias de manufactura.

TABLAS DE PESOS (KG/KM)


Calibre
AWG
KCM

5KV

8KV

15KV

25 KV

35KV

6
4
2
1/0
2/0
3/0
4/0
250
300
350
500
750
1000

1357
1474
1642
2318
2542
2815
3142
3460
3812
4154
5627
7029
8375

1482
1599
1764
2465
2691
2966
3296
3617
3971
4315
5850
7300
8578

2484
2840
3071
3352
3688
4494
4909
5277
6401
7801
9094

4651
4989
5309
5688
6061
6463
6852
8165
9634
10982

3875
4163
4470
4835
5194
5659
6037
7113
8746
10067

*Datos aproximados sujetos a tolerancias de manufactura.

15KV

17.10
19.27
20.29
21.48
22.80
24.21
25.48
26.65
29.69
34.40
38.20

25 KV

24.02
25.04
26.23
27.55
28.96
30.23
31.40
34.44
39.15
42.95

35KV

5 KV

8KV

15KV

25KV

35KV

28.85
29.87
31.06
32.38
33.79
35.06
36.23
39.27
43.98
47.78

19.8
20.9
22.8
25.4
26.5
27.7
29.0
30.4
31.7
32.8
36.7
40.8
44.8

20.2
21.3
24.2
26.8
27.8
29.0
30.3
31.8
33.0
34.2
38.3
43.0
46.1

28.4
30.2
31.2
32.4
33.7
35.9
37.4
38.6
42.5
46.4
49.5

35.7
37.0
38.2
39.5
40.9
43.0
44.2
47.2
52.3
55.4

40.8
42.6
43.8
45.2
46.6
47.8
49.0
53.2
57.2
60.3

CABLE PARA MEDIA TENSIN


Para 5, 15, 25 y 35 KV (aluminio)
EP, XLP
Conductor comprimido o compacto cableado clase "B", de aluminio.
Pantalla semiconductora extruida sobre el conductor.
Aislamiento de EP o XLP.
Cubierta semiconductora extruida sobre aislamiento.
Conductor neutro formado por alambres de cobre suave estaado.
Cubierta opcional de polietileno.
TENSIN MXIMA DE OPERACIN:
8,660 (15,000/ 3 )
14,433 (25.000/ 3 )
20,207 (35.000/ 3 )

Volts al neutro
Volts al neutro
Volts al neutro

Aplicacin
En sistemas monofsicos de distribucin con 100% de nivel de aislamiento. Son apropiados para
instalaciones areas, en ductos o directamente enterrados.

Caractersticas:
La pantalla sobre el conductor, el aislamiento y la pantalla sobre aislamiento son aplicados por
extrusin simultnea (real triple extrusin).
El aislamiento de XLP (Polietileno de cadena cruzada ofrece:
Resistencia excelente al calor y a la humedad.

Temperatura mxima de operacin:


Normal 90C

Resistencia excepcional a las descargas parciales.

Sobrecarga 130C

Alta rigidez dielctrica.

Cortocircuito 250C

Baja absorcin de humedad.


Bajas prdidas dielctricas.

Especificacin:
El aislamiento de EP (Etileno Propileno) ofrece:
Resistencia excelente al calor y a la humedad.

ICEA S-66-524. AEIC-CS-5.


ICEA S-68-516. AEIC-CS-6.

Resistencia excepcional a las descargas parciales.


Alta rigidez dielctrica.

Certificacin:

Baja absorcin de humedad.

Certificado de acuerdo a normas ISO 9000.

Gran resistencia a las arborescencias.


Bajas prdidas dielctricas.
Ofrece facilidad de manejo.

Calibre Numero de
Hilos del
mm
conductor

2
1/0
2/0
3/0
4/0

7
19
19
19
19

rea
mm2

33.62
53.48
67.43
85.01
107.2

Dimetro nominal
Dimetro exterior
Dimetro
Neutro
sobre aislamiento
nominal
nominal del
conductor 15kV 25kV 35kV Calibre No. 15kV 25kV 35kV
mm
AWG Hilos
mm mm mm
mm mm
mm
6.8
8.5
9.6
10.7
12.1

17.1
18.8
19.9
21
22.4

23.2
24.3
25.4
27.1

27.6
28.7
29.8
31.6

14
14
12
12
10

10
16
13
16
13

22
23.7
25.6
26.7
29.1

28.1
30
32.1
34.6

33.5
35.4
36.5
37.9

Peso Kg/Km
15kV

EP
25kV

608
842
1012
1224
1440

1037
1248
1509
1776

35kV

XLP
15kV 25kV

35kV

1314
1562
1888
2222

584
808
972
1175
1383

1237
1471
1778
2092

983
1183
1430
1683

ALAMBRES y CABLES
Intemperie
APLICACIONES:
Estos conductores se usan generalmente en lneas areas para transmisin de energa elctrica, en sistemas de alumbrado, redes de distribucin
secundaria y acometidas areas.
CARACTERSTICAS :
Conductor de cobre cableado clase B para calibres de 10 AWG al 2 AWG y clase A para calibres del 1/0 AWG al 500 KCM en temples duros,
semiduros o suave.
Aislamiento de polietileno negro de alta densidad, resistente a la abrasin y a la intemperie.
Aislamiento de
Polietileno negro

Conductor de Cobre

TABLA DE DIMENSIONES Y CORRIENTES ADMISIBLES DE ALAMBRES Y CABLES INTEMPERIE WP


Calibre
AWG o
KCM

Nmero
de
alambres

Desnudo
Dimetro
de cada
alambre
mm

1
1
1
1
1
1
1
7
7
7
7
7
7
7
7
7

Aislado
Dimetro
Exterior
mm

Espesor
del
aislamiento
mm

Dimetro
exterior
mm

Corriente
Admisible
(A)

Resistencia
a la C.D. a 20C
Ohm / Km
cobre duro

Peso
Aproximado
Kg/100m

1.63
2.05
2.59
3.26
4.12
5.19
6.55

1.63
2.05
2.59
3.26
4.12
5.19
6.55

1.14
1.14
1.14
1.14
1.14
1.14
1.14

3.91
4.33
4.87
5.54
6.4
7.47
8.83

30
35
50
70
95
125
170

8.61
5.42
3.40
2.14
1.34
0.84
0.53

2.45
3.65
5.55
8.40
13.00
20.00
32.50

0.98
1.23
1.55
1.96
2.47
3.12
3.50
3.93
4.42

2.94
3.69
4.65
5.88
7.41
9.36
10.50
11.79
13.26

1.14
1.14
1.14
1.14
1.14
1.52
1.52
1.52
1.52

4.6
5.3
6.3
7.5
9.9
12.7
13.9
15.1
16.6

50
70
95
125
170
230
265
310
360

3.40
2.140
1.345
0.84
0.53
0.33
0.26
0.20
0.16

5.80
8.90
13.70
21.50
34.50
55.00
68.50
85.50
107.00

ALAMBRE
14
12
10
8
6
4
2

CABLE
10
8
6
4
2
1/0
2/0
3/0
4/0

Datos aproximados y sujetos a tolerancia de manufactura.


* La corriente admisible esta en una temperatura ambiente de 30C y temperatura mxima en el conductor de 75C

ALCANCE:
Esta especificacin cubre la construccin de los cables intemperie WP formados por un conductor de cobre slido o cableado concntrico cubierto con aislamiento
de polietileno resistente a la intemperie.
NORMAS:
Las siguientes normas y especificaciones forman parte de la presente especificacin: NOM-J-2, NOM-J12, NOM-J54, ICEA-S-61 -402; UL-83 ; C.L. y el clase A
para calibres de 1/ 0 AWG al 500 KCM.
CONDUCTOR :
El conductor podr ser slido o cableado, de cobre en temples duro, semiduro o suave. Para los conductores cableados, se deber emplear el cable B para calibres
del 10 AWG al 2 AWG y el clase A para calibres 1 / 0 AWG al 500 KCM.
AISLAMIENTO :
El aislamiento es de polietileno negro de alta densidad, formulado especialmente para aplicaciones de intemperie, alta resistencia a la abrasin y a la radiacin
solar.
USOS :
Estos conductores son usado en las redes de distribucin area secundaria, para acometidas dentro de las zonas urbanas, excelentes proteccin contra la
intemperie, a ramas de rboles por contactos producidos accidentalmente.
PRUEBAS:
Deber cumplir satisfactoriamente con las pruebas y mtodos de prueba indicados en la norma oficial mexicana NOM-J-54, en la norma ICEA-S-61 402 y la norma U L-83 en las partes correspondientes.

CABLES
Concntricos
APLICACIN:
Acometidas areas de baja tensin a medidores y salidas a los interruptores de los servicios. Alimentacin o interconexin de cajas derivadoras. El
conductor central se emplea como hilo de corriente. El conductor exterior se emplea como hilo neutro.
CARACTERSTICAS:
Mxima temperatura de operacin en el conductor de 60C
Alambre de cobre temple suave.
Alta resistencia a la abrasin, incluso en zonas arboladas.
Cubierta exterior de polietileno negro de baja densidad, resistente a la intemperie.
Cable concntrico trenzado (C.C.T)

Cubierta exterior de P.V.C. o PE

Alambre de Cobre Trenzado

Aislamiento de PVC

CABLE CONCNTRICO ESPIRAL- TABLA DE DIMENSIONES Y CORRIENTES ADMISIBLES


Calibre
AWG
4
6
8
10
12

Dimetro de
Conductor Desnudo
mm
pulg.

Espesor del
Aislamiento PVC
mm
pulg.

5.189
4.115
3.264
2.588
2.052

1.52
1.52
1.14
1.14
1.14

0.2043
0.1620
0.1285
1.1019
0.0808

0.0598
0.0598
0.0448
0.0448
0.0448

Espesor del
Cubierta de Polietileno
mm
pulg.
1.14
1.14
1.14
0.76
0.76

0.0448
0.0448
0.0448
0.0299
0.0299

Dimetro
Total
mm
pulg.
14.20
12.60
8.38
8.10
7.30

0.559
0.496
0.330
0.318
0.287

Peso
Aproximado
kg/km

Corriente
Admisible
(Amps.)

512
344
200
134
94

105
80
60
40
30

Peso
Aproximado
kg/km

Corriente
Admisible
(Amps.)

494
346
226
143
112

105
80
60
40
30

CABLE CONCNTRICO TRENZADO - TABLA DE DIMENSIONES Y CORRIENTES ADMISIBLES


Calibre
AWG
4
6
8
10
12

Dimetro de
Conductor Desnudo
mm
pulg.

Espesor del
Aislamiento PVC
mm
pulg.

5.189
4.115
3.264
2.588
2.052

1.52
1.52
1.14
1.14
1.14

0.2043
0.1620
0.1285
0.1019
0.0808

0.0598
0.0598
0.0448
0.0448
0.0448

Espesor del
Cubierta de Polietileno
mm
pulg.
1.14
1.14
1.14
0.76
0.76

0.0448
0.0448
0.0448
0.0299
0.0299

Dimetro
Total
mm
pulg.
13.20
12.02
10.00
8.20
7.40

0.519
0.480
0.393
0.322
0.291

Datos aproximados y sujetos a tolerancia de manufactura.


* La corriente admisibles est basada para un conductor en aire, con temperatura ambiente de 30C y temperatura mxima en el conductor de 60C segn 310-17 NEC 1987.

ALCANCE:
Esta especificacin cubre la construccin de los cables constituidos por dos conductores de cobre suave, con eje comn. El conductor central deber ser
slido, con aislamiento de PVC (cloruro de Polivinilo). El conductor exterior deber colocarse sobre el aislamiento del conductor central y estar constituido
por alambres trenzados en forma de malla o cableados heliocoidalmente. La cubierta exterior deber se de polietileno negro de baja densidad.
NORMAS:
Las siguientes normas forman parte de estas especificacin: NOM-J-12, NOM-J-36, NOM-J-28, CL. Y F.2. 1955-35, C.L. Y F.2.0216.
CONDUCTOR CENTRAL :
El conductor central deber ser de cobre, temple suave, slido y deber cumplir con las especificaciones NOM-J-12 Y NOM-J-36.
AISLAMIENTO:
El aislamiento deber ser de PVC (Cloruro de Polivinilo), para 600 volts y 60 C, en general deber cumplir con lo indicado en la norma Nom-J-28, C.L. y
F.2. 1955-35 y 2.1955-40.
CONDUCTOR EXTERIOR :
El conductor exterior es de cobre temple suave, aplicados en forma concntrica, en espiral o trenzados. Cuando se empleen en forma espiral el cableado
debe ser en sentido izquierdo.
CUBIERTA EXTERIOR :
La cubierta exterior debe ser de polietileno negro de baja densidad y resistente a la intemperie.
PRUEBAS :
Las pruebas del conductor terminado en sus propiedades mecnicas y elctricas debe efectuarse de acuerdo a lo indicado en las normas NOM-J-28
C.L. Y F.2. 1955-35 Y 2.1955-40 cuando as se requiera.
EMPAQUE:
Se presenta en empaque de lnea, en tramos de 100m o longitudes requeridas por el cliente y de comn acuerdo con el fabricante.
IDENTIFICACIN :
Sobre la cubierta exterior y a todo lo largo deber llevar una inscripcin repetida cada 30cms. con los siguientes datos: Nombre del fabricante, nombre tipo
de cable, ao de fabricacin. En general debe cumplir con lo indicado en la norma C.L. y F.2.0216.

CABLE
Para distribucin de rea
APLICACIN:
Conductores mltiples para distribucin y acometida area en baja tensin. El conductor desnudo se utiliza como neutro y mensajero.
CARACTERSTICAS:
Altamente resistente a la intemperie.
Dificulta posibles fraudes de energa.
La instalacin es ms econmica que si se utilizara desnudo.
Mxima temperatura de operacin en el conductor 75 C.
Neutro desnudo utilizable como mensajero.

Cables Forrados

Cable Mensajero

e
d
m
dc

D
Estras

Estras

Monopolar

Triples

Estras
Dimensiones de cable

Dplex

TABLA DE DIMENSIONES Y AMPACIDADES


Cable
mltiple de
cobre

No. de
Conductores
aislados

Designacin
AWG

rea de la
Seccin
mm2

No. de
Hilos

dc**
mm

e** Corriente
mm Admisible*
A

(1+1) 8s
(2+1) 8s
(3+1) 8s
(2+1) 4c
(3+1) 4c
(3+1) 1/0 -2c
(3+1) 3/0 -2/0c

1
2
3
2
3
3
3

8
8
8
4
4
1/0
3/0

8.37
8.37
8.37
21.15
21.15
53.5
85.5

1
1
1
7
7
19
19

3.26
3.26
3.26
5.89
5.89
9.415
11.94

1.14
1.14
1.14
1.14
1.14
1.52
1.52

70
64
64
114
114
207
207

CABLE MENSAJERO DE COBRE (TEMPLE SEMIDURO)


Cable
mltiple de
cobre

Designacin
AWG

rea de la
Seccin
mm2

No. de
Hilos

Resistencia
nominal
a 25C en C.D.
ohms / km

Carga
de
ruptura
kg.

(1+1) 8s
(2+1) 8s
(3+1) 8s
(2+1) 4C
(3+1) 4C
(3+1) 1/0 -2C
(3+1) 3/0 -2/0C

8
8
8
4
4
2
2/0

8.37
8.37
8.37
21.15
21.15
33.60
67.40

1
1
1
7
7
7
19

2.13
2.13
2.13
0.86
0.86
0.54
0.27

292
292
292
759
759
1189
2399

** Los datos de las tablas son aproximados y estn sujetos a las tolerancias de manufactura.
* Las ampacidades estn basadas en una temperatura ambiente de 30C y temperatura mxima en el conductor de 75C, para la instalacin de aire.

CABLE
Para distribucin de rea
TABLAS DE DIMENSIN Y AMPACIDAD
CABLES DE ALUMINIO FORRADOS (TEMPLE DURO)
Cable
mltiple de
aluminio

No. de
cables
aislados

Designacin
AWG

rea de la
Seccin
mm2

No. de
Hilos

Resistencia
nominal
a 20C en C.D.
ohms / km

dc**
mm

e** Corriente
mm Admisible*
A

(1+1) 6C
(2+1) 6C

1
2

6
6

13.3
13.3

7
7

2.167
2.167

4.65
4.65

1.14
1.14

75
67

(3+1) 6C
(2+1) 2C
(3+1) 2C
(2+1) 1/0 C

3
2
3
2

6
2
2
1/0

13.3
33.6
33.6
53.5

7
7
7
19

2.167
0.858
0.858
0.539

4.65
7.41
7.41
9.45

1.14
1.14
1.14
1.52

67
120
120
162

CABLES MENSAJERO DE ALUMINIO (TEMPLE DURO)


Cable
mltiple de
cobre

Designacin
AWG

rea de la
Seccin
mm2

No. de
Hilos

Resistencia
nominal
a 25C en C.D.
ohms / km

dm**
mm

Carga
de
ruptura
kg.

(1+1) 6C
(2+1) 6C
(3+1) 6C
(2+1) 2C
(3+1) 2C

6
6
6
2
2

13.3
13.3
13.3
33.6
33.6

7
7
7
7
7

2.167
2.167
2.167
0.858
0.858

4.65
4.65
4.65
7.41
7.41

252
252
252
605
605

(2+1) 1/0 C

1/0

53.5

19

0.858

9.45

1016

* Los datos de las tablas son aproximados y estn sujetos a las tolerancias de manufactura.
*Las especificaciones estn basadas en una temperatura ambiente de 30C y temperatura mxima en el conductor de 75 C para instalacin de aire.

ALCANCE:
Esta especificacin establece las caractersticas de los conductores de cobre templado suave o aluminio duro cableado clase B, con
aislamiento de polietileno negro, reunidos sobre un conductor de cobre desnudo temple semiduro o de aluminio duro, el cual sirve de
neutro del sistema y mensajero del conjunto, formado entre conductores aisladores y desnudos configuraciones monopolares, dplex o
triplex. Para forma de tensin de operacin de 600 volts mximos y 75 C de temperatura en el conductor.
NORMAS:
Las siguientes normas forman parte de esta especificacin: CFE-E-0000-09; CLYF 2.0096; CLY2.0104; NOM-J-12, NOM-J-32, NOM-J-35;
NOM-J-36, NOM-J-54, NOM-J-58, NOM-J-61; ICEA S-61-402.
CONDUCTOR DE FASE:
El conductor debe ser de cobre temple suave o de aluminio duro.
AISLAMIENTO:
El aislamiento es de polietileno alta densidad, color negro.
NEUTRO MENSAJERO:
El conductor neutro que se utiliza como mensajero est formado por alguna de las siguientes construcciones: Alambre o cable de cobre
semiduro o duro; alambre o cable de aluminio duro, cable tipo ACSR.
IDENTIFICACIN:
Los conductores aislados se identifican por medio de estras nmeros marcados en alto o bajo relieve segn el nmero de conductores
en el arreglo.
EMPAQUE:
Se presenta en empaques de lnea que depende del nmero de conductores y calibres de los mismos, o longitudes requeridas por el
cliente de comn acuerdo con la fbrica.
PRUEBAS:
Se efectan pruebas del conductor terminado de sus propiedades fsicas y elctricas, de acuerdo a las normas de referencia, adems de
cumplir con las caractersticas bsicas sealadas en las tablas de sta especificacin.

CABLE DE DISTRIBUCIN SECUNDARIA


XLP, XLPE tipo DRS 600V
PARA DISTRIBUCIN SUBTERRNEA
APLICACIN:
En circuitos secundarios de distribucin residencial subterrnea, pueden instalarse directamente enterrados o en ductos subterrneo.
Tiene una temperatura de operacin normal en el conductor de 90 C, de 130 C en condiciones de sobre carga en emergencia y de
250C en condiciones de corto circuito.
CARACTERSTICAS:
Se presentan en configuraciones unipolares, triples o cudruples, los cables utilizados como fases son de color blanco. Este cable
neutro podr tener reducida, de acuerdo a lo indicado en la tabla de caractersticas.

Costilla de
Identificacin

Conductor neutro de
seccin reducida

Conductor (es) de fase (s)


con aislamiento color negro

Costilla de
Identificacin

CARACTERSTICAS DE CABLE DE ALUMINIO XLP-DRS PARA 600 VOLTS EN CONFIGURACIN


TRIPLE Y CUDRUPLEX.
CONDUCTOR DESNUDO
Calibre
AWG o
KCM

Seccin
Transversal
mm2

Numero
de
Alambres

Dimetro
de cada
Alambre mm

Dimetro
de conductor
Desnudo mm

4
2
1/0
2/0
3/0
4/0
250
300
350
400
500

21.15
33.62
53.5
67.43
85.01
107.2
127
152
177
203
253

7
7
19
19
19
19
37
37
37
37
37

1.96
2.47
1.89
2.13
2.39
2.68
2.09
2.29
2.47
2.64
2.95

5.88
7.42
9.46
10.65
11.95
13.4
14.63
16.03
17.3
18.48
20.65

Datos aproximados y sujetos a tolerancias de manufactura.

CONDUCTOR AISLADO
Espesor del aislamiento
Resistencia
Dimetro
peso
hmica C.D.
exterior
kg/km
a 20C
pulg
mm
mm
ohms / km
1.58
1.58
1.98
1.98
1.98
1.98
2.39
2.39
2.39
2.39
2.39

0.062
0.062
0.078
0.078
0.078
0.094
0.094
0.094
0.094
0.094
0.094

9.02
10.56
13.42
14.56
15.86
17.36
19.38
20.78
22.08
23.28
25.48

110
150
240
290
360
440
520
670
700
820
940

1.363
0.8574
0.539
0.4275
0.3391
0.2689
0.2276
0.1897
0.1626
0.1422
0.1138

Conductor neutro
de seccin
reducida
correspondiente
AWG kCM
4
4
2
2
1/0
2/0
3/0
4/0
4/0
250
300

CABLE DE DISTRIBUCIN SECUNDARIA


XLP, XLPE tipo DRS 600V
CORRIENTE ADMISIBLE DE LOS CABLES XLP-DRS PARA 600V.
Calibre
AWG o kCM

No. de
Alambres

Triple
Amps.

Cudruple
Amps.

78

62

103

82

1/0

19

136

108

2/0

19

156

125

3/0

19

178

142

4/0

19

205

164

250

37

227

182

300

37

252

202

350

37

276

221

400

37

297

238

500

37

338

270

ALCANCE:
Esta especificacin cubre la construccin de los cables de energa con aislamiento de polietileno de cadena cruzada XLP-DRS, para
ser instalado directamente enterrado o en ductos subterrneos. S u configuracin puede ser unipolar, triple o cudruple.
NORMAS:
Las siguientes normas forman parte de esta especificacin : ICEA S-66524, CFE-E0000-02. ASTM B-23, NOM-J-32.
CONDUCTOR:
El conductor debe ser de aluminio cableado concntrico, de grado EC y clase B, y debe cumplir en general con las normas ASTM B231.
AISLAMIENTO:
El aislamiento es de polietileno de cadena cruzada (XLP), pigmentado de negro de humo. Deber operar satisfactoriamente en lugares
hmedos o secos y una temperatura mxima continua en el conductor de 90 C, a 130 C en condiciones de sobrecarga y 250 C en
condiciones de corto circuito.
CONFIGURACIN:
Unipolar, formada por un conductor con aislamiento color negro; triple, formada por tres cables unipolares reunidos entre si,
utilizndose dos de los cables como fase y el tercero cable como neutro de seccin reducida y Cudruple, formado por cuatro cables
unipolares reunidos entre s, utilizndose tres de los cables como fase y el cuarto cable como neutro de seccin reducida.
IDENTIFICACIN:
Los cables llevarn en toda su longitud una identificacin inscrita en la superficie exterior, ( 600 volts, XLP) calibre del conductor,
Aluminio (AL), ao de fabricacin y la leyenda CFE-E-0000-02 y deber repetirse a lo largo del cable, no excediendo de 30cm entre
cada marca.

CABLE
Distribucin subterrnea
APLICACIN:
Se utiliza en sistemas trifsico de distribucin, se puede instalar directamente enterrado, en ducto o charolas.
CARACTERSTICAS:
Conductor de Cobre o Aluminio cableado clase B compacto, pantalla semiconductora extruida sobre el conductor, aislamiento extrudo de Propileno
(EP), pantalla metlica a base de hilos de Cobre, cubierta exterior de Policloruro de vinilo (PVC) antiflama. El aislamiento provee alta rigidez
dielctricas despreciables. Resistente a la humedad, aceites, cidos y a la abrasin

CABLE DS, 5-35 KV,90C


Dimetro Sobre
Aislamiento

Conductor

Dimetro Total
mm

Calibre
AWG/KCM

No. De
Alambres

Dimetro
total
mm

rea
mm2

5KV

15KV

25 KV

35KV

5 KV

15KV

25KV

35KV

2
1/0
2/0
3/0
4/0
250
300
350
500
750
1000

7
19
19
19
19
37
37
37
37
61
61

6.81
8.53
9.55
10.74
12.06
13.21
14.48
15.65
18.69
23.10
26.90

33.6
53.5
67.4
85.0
107.0
127.0
152.0
177.0
253.0
380.0
507.0

12.83
14.55
15.57
16.76
18.08
19.49
20.76
21.93
24.97
29.68
33.48

17.55
19.27
20.29
21.48
22.80
24.21
25.48
26.65
29.69
34.40
38.20

24.02
25.04
26.23
27.55
28.96
30.23
31.40
34.44
39.15
42.95

28.85
29.87
31.06
32.38
33.79
35.06
36.23
39.27
43.98
47.78

21.3
23.0
24.1
25.2
26.6
28.0
29.2
30.4
33.5
38.4
42.2

26.0
27.8
28.8
30
31.3
32.7
34.2
35.4
38.4
43.1
48.1

21.5
33.8
35.0
31.3
32.7
34.2
35.4
38.4
43.1
48.1

37.6
38.6
39.8
41.1
42.5
43.8
45.0
51.3
56.0
59.8

*Datos aproximados sujetos a tolerancias de manufactura.

CABLES CONTROL
600 y 1000 Volts
Conductores de cobre suave.
Aislamiento de PVC tipo THW-LS.
Cinta reunidora.
Cubierta exterior de PVC tipo THW-LS.
Nota: El cable puede construirse blindado o con armadura.

Aplicacin
Se utilizan para operacin y proteccin de equipo, aparatos elctricos y control en general. En centrales
elctricas e industriales donde se requieren mximas condiciones de seguridad.
Se puede instalar en ductos, tubos conduits, charolas e instalaciones areas.

Caractersticas:
No propaga el incendio. Prueba de norma NMX-J-93 (NFC 32-070).
Mnima emisin de humos densos y oscuros en caso de incendio, facilitando la salida de personas y las
labores de rescate y extincin del fuego.
Mnima generacin de gases txicos y corrosivos en caso de incendio, reduciendo el riesgo de intoxicacin
y los daos a bienes materiales.
Es deslizante, por lo que disminuye hasta 5 veces el esfuerzo de jalado en los cables en tubo conduit,
facilitando la instalacin y evitando daos al aislamiento.
Resistente al calor, humedad, aceites, grasas y productos qumicos.
Pasa la prueba de resistencia a baja temperatura (-25 C) (UL).
Fcil identificacin de conductores.

Voltaje de operacin:

Certificacin:

600 Volts

Temperatura mxima de operacin:

NMX-J-300.
ICEA S-73-532.
NOM-063.

Normal 75C

CABLE CONTROL 600 VOLTS


Calibre AWG

rea
mm2

16

1.307

14

2.082

Nmero de
conductores

Espesor de la
cubierta externa mm

Dimetro exterior
nominal mm

7
8
9
10
2
3
4
5
6
7
8
9
10
11
12
19
2
3
4
5
6

1.14
1.14
1.52
1.52
1.14
1.14
1.14
1.52
1.52
1.52
1.52
1.52
1.52
1.52
1.52
2.03
1.14
1.14
1.52
1.52
1.52

11.50
12.20
14.20
15.30
10.80
11.80
12.30
14.30
15.50
16.00
17.10
18.40
20.00
20.40
20.40
24.70
11.80
12.30
14.20
15.90
17.30

Peso nominal
kg/km
216
252
305
323
143
188
234
299
351
381
445
512
535
564
610
972
181
240
328
369
449

CABLES CONTROL
600 y 1000 Volts
CABLE CONTROL 600 VOLTS
Calibre AWG

Area
mm2

12

3.307

10

5.261

Nmero de
conductores
7
8
9
10
11
12
19
2
3
4
5
6
7
8
9
10
11
12
19

Espesor de la
cubierta externa mm
1.52
1.52
1.52
2.03
2.03
2.03
2.03
1.14
1.52
1.52
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03

Dimetro exterior
nominal mm

Peso nominal
kg/km

17.90
18.70
20.10
22.40
22.80
23.10
27.00
14.00
14.70
15.70
17.70
18.30
18.90
21.80
22.80
25.50
25.90
26.20
30.30

495
557
665
758
809
863
1208
242
339
433
509
584
665
802
893
1035
1067
1173
1731

Dimetro exterior
nominal mm

Peso nominal
kg/km

11.20
11.40
12.40
14.20
15.50
15.90
16.80
18.00
19.60
20.30
21.00
24.90
11.70
12.20
14.40
15.90
17.30
17.80
18.70
19.60
22.40
23.40
23.70
26.10
27.90
28.10
28.80
13.10
14.70
16.00
17.60
19.20
19.70
20.80
23.10
25.50
26.40
27.60
30.70

131
160
197
250
303
320
357
431
462
483
494
783
167
212
289
336
395
431
483
552
663
636
728
937
1060
1080
1110
242
307
387
433
528
590
727
803
883
960
1003
1514

CABLE CONTROL 1000 VOLTS


Calibre AWG

Area
mm2

14

2.082

12

3.307

10

5.261

Nmero de
conductores
2
3
4
5
6
7
8
9
10
11
12
19
2
3
4
5
6
7
8
9
10
11
12
16
19
20
21
2
3
4
5
6
7
8
9
10
11
12
19

Espesor de la
cubierta externa mm
1.14
1.14
1.14
1.52
1.52
1.52
1.52
1.52
1.52
1.52
1.52
2.03
1.14
1.14
1.52
1.52
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03
2.03
2.03
1.14
1.52
1.52
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03

NOTA: Estos datos son aproximados y estn sujetos a tolerancias de manufactura.

CABLES
Armados 600 Volts
Conductores de cobre suave cableado clase B.
Aislamiento de PVC en colores segn cdigo.
Conductor de tierra de cobre suave desnudo.
Cinta reunidora.
Armadura engargolada de acero galvanizado o aluminio.
Cubierta de PVC ANTILLAMAM.R. en colores (opcional).
Aplicacin:
Telecomando en equipo de medicin, proteccin y control en general, en centrales elctricas e
industriales donde se requiera un alto grado de resistencia a la flama y dentro de lugares
peligrosos (Clase I Divisin 2, Clase II Divisin 2 y Clase III Divisiones 1 y 2) de acuerdo a la NOM-

Caracteristicas:
Resistente a la propagacin de incendios segn norma IEEE-383.
Fcil identificacin de conductores.
Rapidez y facilidad de instalacin, ya que se elimina el uso de tubera conduit.
Gran flexibilidad de la armadura que permite librar fcilmente obstrucciones y cambios de direccin.
La estructura de la armadura metlica provee al cable de una mayor resistencia al impacto y a la abrasin.
Gran resistencia a efectos corrosivos en ambientes salinos. Cubierta de PVC ANTILLAMAM.R., no
propagador del incendio, con una mnima emisin de humos oscuros, txicos y corrosivos.
El conductor de tierra provee un buen medio para la conexin a tierra de los equipos.

Voltaje de operacion:

Temperatura maxima de operacin:

600 Volts

Ambiente seco 90C


Ambiente humedo 75C

Especificacion:
ICEA-S-61-402
Cdigo de colores
Nmero conductores

Color bsico

Color de traza

1
2
3
4
5
6
7
8
9
10
11
12

Negro
Blanco
Rojo
Verde
Naranja
Azul
Blanco
Rojo
Verde
Naranja
Azul
Negro

------------------------------Negro
Negro
Negro
Negro
Negro
Blanco

Calibre
AWG

Area
en
mm2

Diametro
nominal del
conductor

Nmero de
conductores

Espesor
nominal del
conductor

Calibre del
conductor de
tierra AWG

14
2.08
14
1.9
6
1.14
14
2.08
1.9
8
1.14
14
12
3.31
2.4
5
1.14
12
12
3.31
2.4
7
1.14
12
12
3.31
2.4
9
1.14
12
12
3.31
12
1.14
12
2.4
NOTA: Estos datos son aproximados y estn sujetos a tolerancias de manufactura.

Bajo Armadura

Diametro nominal
Sobre
armadura

total sobre
cubierta

13.1
15.6
14.5
15.9
18.1
21.2

20.5
23
21.9
23.3
26.5
27.6

23
25.6
24.5
25.9
29.1
30.2

Peso
Alumi Acero
kg/km kg/km
510
645
605
720
1005
1215

690
850
800
925
1250
1470

Cable ARMANEL 2000 M.R.


Control EP-FR+PVC 600 Volts
Conductores de cobre suave estaado cableado clase B.
Aislamiento de etileno propileno retardante a la flama (EP-FR) en colores segn cdigo.
Conductor de tierra de cobre suave desnudo.
Cinta reunidora.
Armadura engargolada de acero galvanizado o aluminio.
Cubierta de PVC ANTILLAMAM.R. en colores (opcional).
Aplicacin:
Telecomando en equipo de medicin, proteccin y control en general, en centrales donde se requiera un
alto grado de resistencia a la flama y dentro de lugares peligrosos; (Clase I Divisin 2, Clase II Divisin 2 y
Clase III Divisiones 1 y 2) de acuerdo a la NOM-001

Caracteristicas:
Resistente a la propagacin de incendios segn norma IEEE-383 y NMX-J-93.
Fcil identificacin de conductores.
Dimetros de los cables reducidos, lo cual provee ms capacidad de instalacin.
El aislamiento de EP-FR ofrece:
Excelentes propiedades elctricas, trmicas y fsicas.
Resistencia excelente a la humedad.
Resistencia excelente a la compresin y a la deformacin por calor.
Excelente resistencia a la flama.
Excelentes caractersticas de doblez en fro.
Rapidez y facilidad de instalacin, ya que se elimina el uso de tubera conduit.
Gran flexibilidad de la armadura que permite librar fcilmente obstrucciones y cambios de direccin.
La estructura de la armadura metlica provee al cable de una mayor resistencia al impacto y a la abrasin.
Gran resistencia a efectos corrosivos en ambientes salinos.
Cubierta de PVC ANTILLAMAM.R., no propagador del incendio, con una mnima emisin de humos
oscuros, txicos y corrosivos.
El conductor de tierra provee un buen medio para la conexin a tierra de los equipos.

Voltaje de operacion:

Temperatura maxima de operacin:

600 Volts

Normal 90C
Sobrecarga 130C

Especificacion:
UL-1569.
ICEA-S-61-402.

Cable ARMANEL 2000


Calibre
AWG

Area
en
mm2

ConstruccionN
o de hilos/mm

M.R.

Control EP-FR+PVC 600 Volts

Dimetro
nominal del
conductor

Nmero
de
conductores

Calibre del
conductor de
tierra AWG

1.9
7
14
2.08
7/0.61
12
3.31
7/0.77
2.3
5
12
3.31
7/0.77
2.3
7
10
5.26
7/0.98
2.9
3
2.9
4
10
5.26
7/0.98
10
5.26
7/0.98
2.9
5
10
5.26
7/0.98
2.9
7
Estos datos son aproximados y estn sujetos a tolerancias de manufactura

14
12
12
10
10
10
10

Diametro nominal mm
Bajo Armadura
Sobre
total sobre
armadura
cubierta
11.9
12.2
13.4
11.5
12.8
14.1
15.5

17.2
17.5
20.8
16.8
20.2
21.5
22.9

19.7
20.1
23.4
19.3
22.7
24.1
25.5

Peso
Alumi Acero
kg/km kg/km
455
490
600
470
575
665
795

610
650
780
620
750
855
1000

CABLES PARA TRANSMISIN


De voz y datos
NIVEL 3

Los cables de transmisin de voz y datos de nivel 3 estn formados por conductores de cobre suave, con aislamiento termoplstico
e identificadores por medio de color, torcidos en pares para cumplir los valores elctricos y sobre el conjunto se aplica una cubierta
termoplstico de PVC.

Aplicacin
Estos cables se utilizan en la interconexin de aparatos telefnicos y conmutadores
En la conexin de equipos computacionales de redes de datos con velocidades mximas de 16 mega bits por segundo.

Caractersticas:
Conductor formado por alambre de cobre suave en calibre 24 AWG (0.205 mm2)
Impedancia caracterstica de 100 Ohm.
Resistencia a la corriente directa es de 9.38 Ohm/100Mts
Atenuacin:

Frecuencia
MHz.
1
4
8
10
16

dB / 100 mts
2.6
5.6
8.5
9.7
13.1

El mismo cable puede ser usado para cableado de voz y datos indistintamente.
Cdigo de colores de aislamiento y bandas que facilitan su identificacin.

Nmero de
pares

Conductor
1

Conductor
2

1
2
3
4
5
6

Azul
Naranja
Verde
Caf
Gris
Azul

Blanco - Azul
Blanco - Amarillo
Blanco - Rojo
Blanco - Verde
Blanco - Naranja
Rojo - Azul

Calibre AWG

Numero de
pares

Dimetro exterior
nominal mm

Peso nominal
kg /100 Mts

24

2
3
4
6

3.8
4.5
4.9
5.3

1.5
2.1
2.7
3.7

CABLES PARA TRANSMISIN


De voz y datos
NIVEL 5

Los cables de transmisin de voz y datos de nivel 5 estn formados por conductores de cobre suave, con aislamiento termoplstico e
identificadores por medio de color, torcidos en pares para cumplir los valores elctricos y sobre el conjunto se aplica una cubierta
termoplstico de PVC.

Aplicacin
Estos cables se utilizan en la interconexion de aparatos telefonicos y conmutadores
En la conexin de equipos computacionales de redes de datos con velocidades maximas de 100 mega bits por Sg.

Caracteristicas:
Conductor formado por alambre de cobre suave en calibre 24 AWG (0.205 mm2)
Impedancia caracteristica de 100 Ohm.
Resistencia a la corriente directa es de 9.38 Ohm/100Mts
Atenuacion:
Frecuencia
MHz.
1
4
8
10
16
20
100

dB / 100 mts
2
4.1
5.8
6.5
8.2
9.3
22

El mismo cable puede ser usado para cableado de voz y datos indistintamente.
Codigo de colores de aislamiento y bandas que facilitan su identificacion.

Nmero de
pares

Conductor
1

Conductor
2

1
2
3
4

Azul
Amarillo
Rojo
Verde

Blanco - Azul
Blanco - Naranja
Blanco - Verde
Blanco - Caf

Calibre AWG

Nmero de
pares

Dimetro exterior
nominal mm

Peso nominal
kg /100 Mts

4.9

2.5

24