DESARROLLO DE UNA MALLA A TIERRA PARA LA PUESTA A TIERRA EN
BAJA TENSIN CON UNA SUBESTACIN PARTICULAR.
2. MALLA A REALIZAR
SUPERFICIE MALLA:
LARGO DE LA MALLA (A):
ANCHO DE LA MALLA (B):
COND. PARAL. AL LARGO DE LA MALLA:
COND. PARAL. AL ANCHO DE LA MALLA:
PROFUNDIDAD DE LA MALLA (h):
LARGO DEL CONDUCTOR (L):
SECCIN CONDUCTOR DE MALLA (S):
36
6
6
4
4
0.6
48
41
[METROS^2]
[METROS]
[METROS]
[METROS]
[METROS]
[MM^2]
3. DATOS DE TERRENO
INSTALADOR:
EMPRESA INTERESADA:
DIRECCIN:
COMUNA:
FECHA:
EL MTODO UTILIZADO ES EL
CONFIGURACIN SCHLUMBERGER.
DE
LOS
ELECTRODOS
EN
LA
SOFTWARE TDT3_MESHES
Resistividad [OHM*MTR]
181.66
235.62
222.11
219.2
211.49
196.55
200.28
147.29
130.97
98.85
100.47
98.14
84.8
=
=
=
=
=
=
=
=
101.04 [OHM*MTR]
.14
[MTR]
252.6 [OHM*MTR]
2.14
[MTR]
101.04 [OHM*MTR]
INFINITO
[MTR]
----- [OHM*MTR]
----[MTR]
SOFTWARE TDT3_MESHES
CURVA TERRENO EN HOJA LOGARTMICA
SOFTWARE TDT3_MESHES
CURVA PATRN
SOFTWARE TDT3_MESHES
RhoEQUIV =
j =1
Fn
* ( F j F j 1 )
A = ANCHO =
6 [MTR]
L = LARGO =
6 [MTR]
COND. PARAL. AL LARGO DE LA MALLA: 4
COND. PARAL. AL ANCHO DE LA MALLA: 4
= UNIN ENTRE CONDUCTORES DE MALLA
SOFTWARE TDT3_MESHES
7. RESISTENCIA DE LA MALLA
USANDO EL MTODO DE SCHWARZ
2 * L K1 * L
RM =
* Ln
K 2
+
*L h*d
S
SUPERFICIE MALLA:
LARGO DE LA MALLA (A):
ANCHO DE LA MALLA (B):
PROFUNDIDAD DE LA MALLA (h):
LARGO DEL CONDUCTOR (L):
CONSTANTES:
36
6
6
0.6
48
[METROS^2]
[METROS]
[METROS]
[METROS]
[METROS]
K1 = 1.156
K2 = 4.75
8. CONCLUSIN
SEGN LA NORMA ELCTRICA CHILENA NCH. 4/2003
TEM 9.2.7.3 EMPLEO DE PROTECTORES DIFERENCIALES.
TEM 9.2.7.4 CON SUBESTACIN PARTICULAR MENOS DE 20 [OHM].
TEM 10.1.6.2 LA RESISTENCIA TOTAL ENTRE TODAS LAS PUESTAS
A TIERRA DESCRITAS EN 10.1.6.2 NO DEBE EXCEDER LOS 5 [OHM].
TEM 10.2.4. EMPLEO DE APARATO DE PROTECCIN, DEL CIRCUITO O
DEL EQUIPO PROTEGIDO POR LA PUESTA A TIERRA DE PROTECCIN.
ENTONCES OBSERVANDO LA RESISTENCIA DE LA PUESTA A TIERRA
DE 11,965[OHM], SI CUMPLE CON LA NORMATIVA.
TAMBIN CUMPLE CON DAR SEGURIDAD CONTRA CONTACTOS INDIRECTOS.
EL SISTEMA USADO ES DE NEUTRALIZACIN.