Está en la página 1de 1

MEMORIA DE CLCULO CAIDA DE TENSION

PIP: CONSTRUCCION DE LOCAL MULTIUSOS DE LA JUNTA VECINAL LOS LIRIOS


CONDUCTORES
A) POR CAIDA DE TENSIN
PARMETROS PRELIMINARES
* Temperatura de trabajo =
* Tipo de conductor =
* Frecuencia de la red =
* Factor de potencia =
* Sistema trifsico =
Siendo Fd : Factor de Demanda

45 C
de cobre NYY
60 Hz
0.90
380/220 V
0.9

CUADRO DE CARGAS
DESCRIPCION DE CARGAS
C 1 ALUMBRADO (A1)
C 2 TOMACORRIENTES (A1)
RESERVA
C 1 ALUMBRADO 1ER PISO (A2)

C 2 TOMACORRIENTES 1ER PISO (A2)


C 3 ALUMBRADO 2DO PISO (A2)

TG

C 4 TOMACORRIENTES 2DO PISO (A3)


C 5 TOMACORRIENTES 2DO PISO (A3)
RESERVA
C 1 ALUMBRADO (A3)
C 2 ALUMBRADO (A3)
C 3 TOMACORRIENTES (A3)
C 4 TOMACORRIENTES (A3)
C 5 TOMACORRIENTES (A3)
C 6 ALUMBRADO DE EMERGERGENCIA
RESERVA
C 1 ALUMBRADO (A)
C 2 TOMACORRIENTES (A)
RESERVA

CANT.
(U)

POT. UNIT.
(W/U)

POT. INST.
(W)

Fd

M.D.
(KW)

6
8

80.00
160.00

4
8
2
8
6
2
1
6
8

120.00
35.00
22.00
160.00
120.00
80.00
22.00
160.00
160.00

10
2
7
2
8
4
6
8

120.00
80.00
80.00
35.00
160.00
160.00
160.00
140.00

8
1
1

22.00
35.00
160.00

480.00
1,280.00
500.00
480.00
280.00
44.00
1,280.00
720.00
160.00
22.00
960.00
1,280.00
500.00
1,200.00
160.00
560.00
70.00
1,280.00
640.00
960.00
1,120.00
500.00
176.00
35.00
160.00
200
TOTAL M.D.:

1.0
0.6
1.0
1.0
1.0
1.0
0.6
1.0
1.0
1.0
0.6
0.6
1.0
1.0
1.0
1.0
1.0
0.6
0.6
0.6
1.0
1.0
1.0
1.0
0.6
1.0

Id(A)

AV%

0.48
0.77
0.50
0.48
0.28
0.04
0.77
0.72
0.16
0.02
0.58
0.77
0.50
1.20
0.16
0.56
0.07
0.77
0.38
0.58
1.12
0.50
0.18
0.04
0.10
0.20
11.91

1. CAIDA DE TENSION
PUNTO

POT (W)

SUMA POT (W)

L (M)

S (MM2)

11.91

11.91

20.000

25.16

0.6691

0.6691

TG

11.91

11.91

6.000

25.16

0.2007

0.8698

12.000
23.000
26.000

4
6
6

11.04
27.26
11.28

0.2633
0.8312
0.3893

1.1331
1.7010
1.2591

1.7010

A1 (TD 1)
A2 (TD 2)
A3 (TD 3)

1.75
4.32
5.34

1.75
4.32
5.34

La cada de tensin ms crtica es la del circuito A2 (TD 2) monofasico


valor por debajo de lo establecido 2.5 %

AV%

1.75

4.32

5.34

0.51

También podría gustarte