Está en la página 1de 54

TEMPERATURA

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-1

TEMPERATURA
INTRODUCCION A LA VARIABLE
CONCEPTO UNIDADES PRINCIPIOS DE MEDICION

TRANSMISORES ROSEMOUNT:
3144/3244

PRACTICAS DE LABORATORIO CON EQUIPO ROSEMOUNT

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-2

OBJETIVO:
AL TERMINO DE ESTA SESION, SE TENDRA AMPLIO CONOCIMIENTO DE: -CONCEPTO DE TEMPERATURA

- LAS PRINCIPALES FORMAS DE MEDICION - UNIDADES -HABILIDAD EN EL MANEJO DE INSTRUMENTACION ROSEMOUNT. -HABILIDAD EN SELECCIN DE EQUIPO.

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-3

TEMPERATURA
SIN SER UNA VARIABLE FACIL DE DEFINIR, SE DICE QUE LA TEMPERATURA ES LA ENERGIA MEDIA DE LAS MOLECULAS DE UN CUERPO. EN FORMA COLOQUIAL DIRIAMOS QUE ES EL GRADO DE CALOR O FRIO MEDIDO EN UNA ESCALA DEFINIDA.

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-4

CONCEPTOS RELATIVOS

TEMPERATURA AMBIENTE: TEMPERATURA QUE PREVALECE DEBIDO AL CLIMA (20C SIU). TEMPERATURA DE ALMACENAMIENTO:TEMPERATURA EN LA QUE SE ESPERA ALMACENAR EL INSTRUMENTO SIN QUE SUFRA DAO. TEMPERATURA DE SERVICIO: CAMPO DE TEMPERATURAS EN LAS CUALES SE ESPERA TRABAJE EL INSTRUMENTO DENTRO DE LIMITES DE ERROR POR ESPECIFICACION. TEMPERATURA DE CERO ABSOLUTO: ES LA TEMPERATURA A LA CUAL LA ENERGIA CINETICA DE LOS GASES SE VUELVE CERO.

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-5

UNIDADES Escalas ms comunes: ESCALA KELVIN Y CELCIUS ESCALA RANKINE Y FAHRENHEIT ESCALA REAUMUR CONVERSIONES:
K = C + 273 . 15 R = F + 459 . 67 F 32 C = 1 .8 F = ( 1 . 8 C ) + 32

R = 1 .8 K ( R ) K = 1 .8

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-6

RELACIN DE ESCALAS DE TEMPERATURA


F
1340 1800

K
1000

C
727

1000

538

Rea
500 960 533 260 208

EBULLICIN DEL AGUA 212 TEMPERATURA AMBIENTE 70 CONGELACIN DEL AGUA 32


0 -40 460 273

100 21 0 -40

80 17 0

C=F

TEMPERATURA DEL CERO ABSOLUTO


-460 FAHRENHEIT 0 RANKINE 0 KELVIN -273 CELSIUS -218 REAUMUR

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-7

PRINCIPIOS DE MEDICION DE TEMPERATURA


BIMETALICOS TERMOMETRO DE BULBO PIROMETRO DE RADIACION TERMISTORES TERMOPARES RTD
EMERSON Process Management Educational Services Course 2051 Copyrighted Material / Duplication Prohibited

5-8

BIMETALICOS
ESTE TIPO DE TERMOMETRO ESTA BASADO EN EL PRINCIPO DE QUE EL COEFICIENTE DE EXPANSION TERMICA ES DIFERENTE EN DOS METALES, POR LO QUE SI UNIMOS DOS LAMINAS DE DIFERENTE METAL, AL SOMETERSE A UNA TEMPERATURA DIFERENTE A LA DE FABRICACION ESTAS TENDRAN UNA DEFLEXION PROPORCIONAL AL CAMBIO EN TEMPERATURA, CURVEANDOSE Y CON ELLO UN EFECTO MECANICO QUE SE PUEDE TRANSMITIR A UNA ESCALA.

T1 T1 = / T2
EMERSON Process Management Educational Services Course 2051

T2
Copyrighted Material / Duplication Prohibited

5-9

BIMETALICO
PUNTERO BALERO

ELEMENTO HELICOIDAL BIMETALICO FLECHA


EMERSON Process Management Educational Services Course 2051 Copyrighted Material / Duplication Prohibited

5-10

TERMOMETRO DE BULBO
ESTA BASADO EN LA PROPIEDAD DE LOS LIQUIDOS A EXPANDERSE AL INCREMENTO DE TEMPERATURA. EL LIQUIDO SE ENCUENTRA CAPTURADO EN UN TUBO CONECTA A UN BOURDON, DE TAL FORMA QUE AL EXPANDERSE EL LIQUIDO EL BOURDON SUFRE UN MOVIMIENTO MECNICO PROPORCIONAL AL INCREMENTO DE TEMPERATURA
PUNTERO

BOURDON

BULBO CON LIQUIDO VOLATIL

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-11

PIROMETRO DE RADIACION
SE BASAN EN LA LEY DE STEFAN-BOLTZMAN, QUE DICE QUE LA INTENSIDAD DE ENERGIA EMITIDA POR LA SUPERFICIE DE UN CUERPO AUMENTA PROPORCIONALMENTE A LA CUARTA POTENCIA DE LA TEMPERATURA BSOLUTA DEL CUERPO, ES DECIR, W=KT4

OBJETO CALIENTE

LECTURA

VENTANA O APERTUIRA
EMERSON Process Management Educational Services

SISTEMA DE AMPLIFICACION

LENTE
Course 2051

FILTRO
Copyrighted Material / Duplication Prohibited

5-12

TERMISTOR ES EL ELEMENTO RESISTIVO CON PROPIEDADES DE COEFICIENTE DE TEMPERATURA -RESISTENCIA NEGATIVO, ES DECIR AL INCREMENTARSE LA TEMPERATURA LA RESISTENCIA DISMINUYE.

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-13

TERMOPAR
Es el elemento formado por la unin de dos metales diferentes, los cuales presentan una fuerza electromotriz al encontrarse en presencia de una temperatura, ya que sus uniones se mantienen a distintas temperaturas estableciendo con los metales la unin de medida (caliente) y la unin de referencia (fra).

CALOR

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-14

RTD
Son aquellos elementos conductores que tienen la caracterstica de cambiar su resistencia en funcin de la variacin de temperatura . El cambio de resistencia en ohms por cada grado est determinado por el coeficiente de temperatura de resistencia del material del elemento.
2 1 4 3

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-15

OPCIONES DE SENSOR
RTDs de Platino 2-, 3-, or 4-hilos Pt 100, Pt 200, Pt 500: a = 0.00385 * diferencial Pt 100, Pt 200, Pt 500: a = 0.00385 Ni 120 2-, 3-, or 4- hilos * diferencial Ni 120 Cu 10 2-, 3-, or 4- hilos Type B, E, J, K, N, R, S, T * Termopares diferencial 10 to 100 Millivolts * Millivolts diferencial 2-, 3-, or 4- hilos 0 to 2000 ohms * Ohms diferencial Especial RTD o T/C con hojas de calibracin NIST, Termopares Tipo C

RTDs de Nquel

RTDs de cobre Termopares Millivolts Ohms

Custom Inputs * Diferencial solo es viable en el 3244

Si los RTDs diferenciales son usados, la temperatura diferencial es determinada (Sensor 1Sensor 2). Sensor 1 y Sensor 2 son inicialmente independientes, y no necesariamente ser del mismo tipo. Cuando los RTDs son usados en mediciones diferenciales, solo 2- o 3- hilos de las conexiones del sensor RTD pueden ser usados.
Course 2051 Copyrighted Material / Duplication Prohibited

EMERSON Process Management Educational Services

5-16

Especificaciones
Opciones De sensor 2-,3-,4-Hilos de RTDs Pt100 Ni 120 Cu 10 Thermocoples NIST Type B NIST Type J NIST Type K NIST Type S Entrada en Milivolts 2-,3-,4-Hilos de entrada en Ohms 2-Hilos Diferenciales en Ohms (Modelo 3244MV) Rangos de Entrada C F -200 to 850 328 to 1562 -70 to 300 94 to 572 -50 to 250 58 to 482 Span Mnimo Recomendado C F 10 18 10 18 10 18 Precisin Digital C F +0.14 +0.25 +0.14 +0.25 +1.00 +1.80 C +0.75 +0.25 +0.50 +0.50 Precisin D/A +0.02% of Span +0.02% of Span +0.02% of Span

F C 100 to 1820 212 to 3308 25 -180 to 760 -292 to 1400 25 -180 to 1372 -292 to 2502 25 0 to 1768 32 to 3214 25 -10 to 100mV 0 to 2000 Ohm -2000 to 2000 Ohm 3 mV

F 45 45 45 45

F +1.35 +0.45 +0.90 +0.90

+0.02% of Span +0.02% of Span +0.02% of Span +0.02% of Span

+0.015 mV +0.02% of Span 20 Ohm 20 Ohm +0.35 Ohm +0.02% of Span +0.52 Ohm +0.02% of Span

Son algunos ejemplos, que pueden verse en las paginas 5-1 y 5-2 del manual 3144/3244 para completar la lista.

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-17

TRANSMISOR DE TEMPERATURA Modelo 3144/3244

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-18

BLOQUE DE TERMINALES

Hacia Electrnica
2 1 3 4 5 T

+
T

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-19

CABLEADO (SOLO MODELO 3144) Dcada de Resistencia


2 1 3 4 5 2 HILOS 4 HILOS 4 5 3 HILOS
2 1 3 4 5 T

2 1

3 4 5

T/C Simulador - Fuente de mV


1

1 +

3 4 5

TC y mV Fuente de Alimentacin

+ 250 Ohms

4.00 mA

Miliampermetro

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-20

CABLEADO (SOLO MODELO 3244)


2 1 3 4 5 1 2 3 4 5 1 2 3 4 5 1 + 2 3 4 5

2 HILOS

3 HILOS

4 HILOS
1

TC & mV
2 S1 3 4 S2 5 1 + _ 2 3 4 5

Dcada de Resistencia
2 1 3 4 5 T

T/C Simulador - Fuente de mV

2 RTDs
2 3 4 5

2 TCs
2 3 4 S2 5

+ 4.00 mA

S1 _ S2 +

1 + S1 _

RTD/TC

TC/RTD

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-21

RESPALDO DEL SENSOR


2 1 S1 S2 3 4 5 1 + S1 _ S2 2 3 4 5 + 1 2 3 4 5 1 + S1 _ 2 3 4 S2 5

S1_ S2 +

2 RTDs

2 TCs

RTD/TC

TC/RTD

S1 Es la entrada del sensor primario S2 Es redundante o la entrada del sensor de resistencia en caliente 3244 Puede tener tambin entrada doble para lectura diferencial

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-22

MENUS DEL 3144


1 PROCESS VARIABLES
1 PV Engineering Units 2 PV Percent Range 3 PV Analog Output 4 SV 5 Variable Mapping 6 VARIABLE RE-MAP 1 TEST DEVICE 2 LOOP TEST 3 CALIBRATION 4 Smart Calibration 1 Tag 2 PV Unit 3 Range Values 4 SENSOR 1 CONN 5 PV Damp 6 Sensor 1 Sensor s/n 1 SENSORS 1 PV 2 SV 1 Status 2 Self Test 3 Master Test 1 Terminal Temp 2 Sensor 1 1 Apply Values 2 RANGE VALUES 3 SENSOR TRIM 4 Digital-to-Analog Trim 5 Scaled D/A Trim 6 CJC Calibration Value 7 RTD Current Number of Wires

MENUS (Parciales) 3144


1 DEVICE SETUP 2 PV 3 AO 4 LRV 5 URV

2 DIAGNOSTICS
AND SERVICE

3 BASIC SETUP

Select Sensor Type 1 PROCESS SENSOR 2 TERM TEMP SENSOR 3 A/D Conversion Info 1 PV Lower Range Value 2 PV Upper Range Value 3 PV Percent Range 4 PV Damp 1 ANALOG OUTPUT

4 DETAILED SETUP

2 SIGNAL CONDITION

3 OUTPUT CONDITION 4 DEVICE INFORMATION

2 HART OUTPUT 3 METER OPTIONS

5 REVIEW
EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-23

MENUS DEL 3244


MENUS (Parciales) 3244MV 1 PROCESS VARIABLES 1 PV Engineering Units 2 PV Percent Range 3 PV Analog Output 4 SV 5 (TV) 6 (QV) 7 Mapping 1 Variable TEST DEVICE 8 RE-MAP 2 VARIABLE LOOP TEST 3 CALIBRATION 4 1 Smart Tag Calibration 2 PV Unit 3 Range Values 4 SENSOR 1 CONN 5 SENSOR 2 CONN 6 PV Damp 7 1 Sensor s/n 1 Sensor SENSORS 8 Sensor 2 Sensor s/n 2 SIGNAL CONDITION 1 Differential Temp 2 Terminal Temp 3 Sensor 1 4 Sensor 2 1 Apply Values 2 RANGE VALUES 3 SENSOR TRIM 4 Digital-to-Analog Trim 5 Scaled D/A Trim 6 CJC Calibration Value 7 RTD Current Select Sensor Type Number of Wires 1 PROCESS SENSOR 2 TERM TEMP SENSOR 3 A/D Conversion Info 1 PV Lower Range Value 2 PV Upper Range Value 3 PV Percent Range 4 PV Damp 1 ANALOG OUTPUT 2 HART OUTPUT 3 METER OPTIONS 4 DEVICE INFORMATION 1 PV 2 SV 3 TV 4 QV 1 Status 2 Self Test 3 Master Test

2 DIAGNOSTICS AND SERVICE 1 DEVICE SETUP 2 PV 3 AO 4 LRV 5 URV 3 BASIC SETUP

4 DETAILED SETUP

3 OUTPUT CONDITION

5 REVIEW

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-24

Secuencias Rpidas del 3144/3244


Funcin/Variable Analog Output Analog Output Alarm Type Apply Values Basic Setup Burst Mode Control Burst Operation Calibration CJC Calibration Value Configure Hot Backup (3244) D/A Trim Damping Values (3144) Damping Values (3244) Date Description Detailed Setup Device Info Diagnostic and Service Disable Hot Backup (3244) Enable Hot Backup (3244) Filter 50/60 Hz Hardware Rev HART Output Loop Test LRV Lower Range Value LSL Lower Sensor Limit Message Meter Configuration Number of Requested Preambles Percent Range Poll Address Secuencia rpida 1,4,3,1,1 1,4,3,1,2 1,2,3,1 1,3 1,4,3,2,3 1,4,3,2,4 1,2,3 1,2,3,6 1,4,1,1,3,3 1,4,3,1,4 1,3,5 1,3,6 1,4,4,1 1,4,4,2 1,4 1,4,4 1,2 1,4,1,1,3,3,2 1,4,1,1,3,3,1 1,4,1,3 1,5 1,4,3,2 1,2,2 1,2,3,2,1 1,2,3,2,4 1,4,4,3 1,4,3,3 1,4,3,2,2 1,1,2 1,4,3,2,1 Funcin/Variable Process Temperature Process Variables PV Unit Range Values Review RTD Current Scaled D/A Trim (4-20 mA Output) Secondary Variable Sensor 1 Configuration Sensor 2 Configuration (3244) Sensor 1 Connection Sensor 2 Connection (3244) Sensor Information Sensor Serial Number (3144) Sensor 1 Serial Number (3244) Sensor 2 Serial Number (3244) Sensor Setup Sensor Trim Sensor Type Signal Condition Software Revision Special Constants Special Sensor Status Tag Terminal Temperature Test Device URV (Upper Range Value) USL (Upper Sensor Limit) Variable Remap Wires Secuencia rpida 1,1 1,1 1,3,2 1,3,3 1,5 1,2,3,7 1,4,3,1,5 1,1,4 1,4,1,1,3,1 1,4,1,1,3,2 1,3,4 1,3,5 1,4,1,1,4 1,3,6 1,3,7 1,3,8 1,4,1,1,3 1,2,3,3 1,3,4 1,4,2 1,5 1,4,1,1,3,1,4 1,4,1,1,3,1,4 1,2,1,1 1,3,1 1,4,1,2 1,2,1 1,2,3,2,2 1,2,3,2,5 1,1,6 1,3,4

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-25

TAREAS COMUNES
Esta seccin cubre las tareas comunes usadas con el Comunicador HART . Despus de esta seccin usted podr:

Seleccionar la entrada de un sensor. Cambiar las unidades de PV. Rangear el valor alto y bajo del rango. Configurar fuera de lnea. Revisar el dispositivo. Realizar una prueba del lazo.
Course 2051 Copyrighted Material / Duplication Prohibited

EMERSON Process Management Educational Services

5-26

SELECCIONANDO EL SENSOR
Secuencia Rpida : 1, 3, 4
3144 Temp:TT-5621 Online 1 Device Setup 2 PV 0.00 deg C 3 PV AO 4.00 mA 4 PV LRV 0.00 deg C 5 PV URV 100.00 deg C F1 F2 F3 F4 3144 Temp:TT-5621 Device Setup 1 Process variables 2 Diag/Service 3 Basic Setup 4 Detailed Setup 5 Review HELP HOME F1 F2 F3 F4 3144 Temp:TT-5621 Basic Setup 1 Tag 2 PV Unit 3 Range Values 4 Snsr 1 Conn 5 PV SAVE Damp HOME HELP F1 F2 F3

TT-5621

F4

3144 Temp:TT-5621 Enter Sensor 1 type PT100, a=385 PT100, a=385 PT200, a=385 PT500, a=385 Ni 120 ABORT ENTER F1 F2 F3 F4

3144 Temp:TT-5621 Enter Sensor 1 connection 4 Wire 3 Wire 4 Wire Not Used ABORT ENTER F1 F2 F3 F4

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-27

CAMBIANDO UNIDADES
Secuencia Rpida : 1, 3, 2
3144 Temp:TT-5621 Online 1 Device Setup 2 PV 0.00 deg C 3 PV AO 4.00 mA 4 PV LRV 0.00 deg C 5 PV URV 100.00 deg C F1 F2 F3 F4 3144 Temp:TT-5621 Device Setup 1 Process variables 2 Diag/Service 3 Basic Setup 4 Detailed Setup 5 Review HELP HOME F1 F2 F3 F4 3144 Temp:TT-5621 Basic Setup 1 Tag TT-5621 2 PV Unit 3 Range Values 4 Snsr 1 Conn 5 PV Damp HOME HELP SAVE F1 F2 F3 F4

3144 Temp:TT-5621 Unit deg C deg C deg F deg R Kelvin ESC F1 F2 F3

3144 Temp:TT-5621 NOTICE - This Information must be sent to the transmitter to update dependent parameters. ENTER F4 F1 F2 ABORT F3 OK F4

3144 Temp:TT-5621 Online 1 Device Setup 2 PV 0.00 deg C 3 PV AO 4.00 mA 4 PV LRV 0.00 deg C 5 PV URV 100.00 deg C HELP SEND HOME F1 F2 F3 F4

Recuerde oprimir Send


EMERSON Process Management Educational Services Course 2051 Copyrighted Material / Duplication Prohibited

5-28

CAMBIO DE RANGO
3144 Temp:TT-5621 Online 1 Device Setup 2 PV 0.00 deg C 3 PV AO 4.00 mA 4 PV LRV 0.00 deg C 5 PV URV 100.00 deg C HELP F1 F2 F3 F4 3144 Temp:TT-5621 1 PV LRV 2 PV URV 0.00 deg C 100.00 deg C

HELP F1 F2

HOME F3 F4

3144 Temp:TT-5621 Term Upr Rng 100.00 deg C 150.00

3144 Temp:TT-5621 1 PV LRV 2 PV URV

0.00 deg C 150.00 deg C

HELP F1

DEL F2

ESC F3

ENTER F4

HELP F1

SEND F2

HOME F3 F4

Recuerde oprimir Send


EMERSON Process Management Educational Services Course 2051 Copyrighted Material / Duplication Prohibited

5-29

CONFIGURACION FUERA DE LINEA


HART Communicator 1 Offline 2 Online 3 Frequency Device 4 Utility HART Communicator Offline 1 New Configuration 2 Saved Configuration HART Communicator Manufacturer 1 Micro Motion 2 Rosemount 3 Rosemount Analytical

HELP F1 F2 F3 F4 F1 F2 F3 F4 F1 F2 F3 F4

HART Communicator Model 5 Mag HS 6 Magmeter 7 3144 Temperature 8 3244 Temperature 9 Vortex F1 F2 F3 F4

HART Communicator Fld Dev Rev 1 Dev v1, DD v2

Unnamed From Blank Template 1 Mark All 2 Unmark All 3 Edit Individually 4 Save As... HELP SAVE F2 F3 F4

F1

F2

F3

F4

F1

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-30

PRUEBA DEL DISPOSITIVO


Secuencia Rpida : 1, 2,1, 3
3144 Temp:TT-5621 Online 1 Device Setup 2 PV 0.00 deg C 3 Analog Out 4.00 mA 4 PV LRV 0.00 deg C 5 PV URV 100.00 deg C F1 F2 F3 F4 3144 Temp:TT-5621 Device Setup 1 Process variables 2 Diag/Service 3 Basic Setup 4 Detailed Setup 5 Review HELP HOME F1 F2 F3 F4 3144 Temp:TT-5621 Diag/Service 1 Test Device 2 Loop Test 3 Calibration 4 Smart Cal HELP HOME F1 F2 F3 F4

3144 Temp:TT-5621 Test Device 1 Status 2 Self Test 3 Master Test HELP F1 F2 HOME ENTER F3 F4

3144 Temp:TT-5621 WARN - Loop should be removed from automatic control ABORT F1 F2 F3 OK F4

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-31

Common Tasks

4-10

PRUEBA DE LAZOFast Key : 1, 2, 2


3144 Temp:TT-5621 Online 1 Device Setup 2 PV 0.00 deg C 3 Analog Out 4.00 mA 4 PV LRV 0.00 deg C 5 PV URV 100.00 deg C F1 F2 F3 F4 3144 Temp:TT-5621 Device Setup 1 Process variables 2 Diag/Service 3 Basic Setup 4 Detailed Setup 5 Review HELP HOME F1 F2 F3 F4 3144 Temp:TT-5621 Diag/Service 1 Test Device 2 Loop Test 3 Calibration 4 Smart Cal HELP F1 F2 HOME F3 F4

3144 Temp:TT-5621 WARN - Loop should be removed from automatic control

3144 Temp:TT-5621 Choose analog output 1 4 mA 2 20 mA 3 Other 4 End OK F4 F1 F2 ABORT F3 ENTER F4

ABORT F1 F2 F3

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-32

CALIBRACION

En esta seccin usted aprender como calibrar un 3144/3244MV. Despus de completar esta seccin, Usted podr:
Aprender la diferencia entre cambio de rango y calibracin Determinar la calibracin que sea necesaria. Ejecutar el ajuste fino del Sensor (Sensor Trim). Ejecutar el ajuste fino de la salida (Out put Trim).

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-33

QUE ES CALIBRACION?
Rango 0100 grados C

A/D

D/A

138.5 Ohms

19.98 mA

3144 Temp:TT-5677 Online 1 Device Setup 2 PV 99.70 deg C 3 PV AO 19.98 mA 4 PV LRV 0.00 deg C 5 PV URV 100.00 deg C
EMERSON Process Management Educational Services Course 2051 Copyrighted Material / Duplication Prohibited

5-34

SENSOR TRIM
Lectura de PV 100

- 50 Entrada de Temperatura - 50 100

Actual

Ideal

A/D

D/A Comunicaciones

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-35

CALIBRACION
SENSOR TRIM
Dos puntos de ajuste

SENSOR MATCHING
Callendar-Van Dusen 4 Constantes definen la presicin de Resistencia contra la curva de temperatura para un RTD especifico

Rt = Ro + Ro [ t - ( 0.01t - 1 )( 0.01t ) - ( 0.01t - 1 )( 0.01t3 ) ]


Donde: Rt = Resistencia a temperatura t C Ro = Resistencia a punto de congelacin del agua ( 0 oC) = Constante especifica del sensor

= Constante especifica del sensor = Constante especifica del sensor


Course 2051

EMERSON Process Management Educational Services

Copyrighted Material / Duplication Prohibited

5-36

Calibration

5-6

SENSOR TRIM
3144 Temp:TT-5621 Online 1 Device Setup 2 PV 0.00 deg C 3 Analog Out 4.00 mA 4 PV LRV 0.00 deg C 5 PV URV 100.00 deg C F1 F2 F3 F4

Fast Key : 1, 2, 3, 3, 1 3144 Temp:TT-5621 Device Setup 1 Process variables 2 Diag/Service 3 Basic Setup 4 Detailed Setup 5 Review SAVE HOME F1 F2 F3 F4

3144 Temp:TT-5621 Diag/Service 1 Test device 2 Loop Test 3 Calibration 4 Smart Cal SAVE F1 F2 HOME F3 F4

3144 Temp:TT-5621 Calibration 1 Apply values 2 Range values 3 Sensor trim 4 D/A trim 5 Scaled D/A trim SAVE HOME F1 F2 F3 F4

3144 Temp:TT-5621 Sensor trim 1 Snsr 1 inp trim 2 Snsr 1 trim-fact 3 Snsr 1 trim-select HELP F1 SAVE F2 HOME F3 F4

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-37

SENSOR TRIM DEL USUARIO


100

Inicio
0 0 100
Entrada de 100 Temperatura

Actual Ideal

Trim a bajo Valor Trim a alto Valor


EMERSON Process Management Educational Services

0 0 100
Entrada de Temperatura

100

0 0
Course 2051

Entrada de 100 Temperatura


Copyrighted Material / Duplication Prohibited

5-38

ACOPLAMIENTO DEL SENSOR


El acoplamiento del sensor incrementa el sistema de precisin (sensor y xmtr).

Precisin tpica =
Modelo 3144 = Estndar 68 RTD = Total = +0.18 C +1.05 C +1.23 C

Precisin del acoplamiento del sensor =


Modelo 3144 = Estndar 68 RTD = Total = +0.18 C +0.10 C (con carta) +0.28 C

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-39

ACOPLAMIENTO DEL SENSOR


Secuencia Rpida : 1, 4, 1, 1, 3, 1, 3
3144 Temp:TT-5621 Online 1 Device Setup 2 PV 0.00 deg C 3 Analog Out 4.00 mA 4 PV LRV 0.00 deg C 5 PV URV 100.00 deg C F1 F2 F3 F4 3144 Temp:TT-5621 Device Setup 1 Process variables 2 Diag/Service 3 Basic Setup 4 Detailed Setup 5 Review SAVE HOME F1 F2 F3 F4 3144 Temp:TT-5621 Detailed Setup 1 Sensors 2 Signal condition 3 Output condition 4 Device information HOME SAVE F1 F2 F3 F4

3144 Temp:TT-5621 Sensors 1 Process sensor 2 Term temp sensor 3 A/D Conv. Info SAVE F1 F2 HOME F3 F4

3144 Temp:TT - 5 621 Process sensor 1 PV 2 PV Unit 3 Sensor setup 4 Sensor info 5 Sensor trim

3144 Temp:TT-5621 Sensor setup 1 Snsr 1 config 2 Misc Config HOME F3 F4 F1 SAVE F2 HOME F3 F4

HELP

SAVE F2

F1

Continua
EMERSON Process Management Educational Services Course 2051 Copyrighted Material / Duplication Prohibited

5-40

ACOPLAMIENTO DEL SENSOR


Continuacin
3144 Temp:TT-5621 Snsr 1 config 1 Snsr 1 Conn 2 Snsr 1 damp 3 Snsr 1 Unit 4 Spec Snsr 1 Conn 5 Dis SAVE Spec Snsr 1 HOME HELP F1 F2 F3 F4 3144 Temp:TT-5621 - WARNING Pressing OK will Change device output. Put loop in manual. ABORT F1 F2 F3 OK F4

3144 Temp:TT-5621 Enter Special Sensor 1 connection 2 Wire 2 Wire 3 Wire 4 Wire ABORT F1 F2 F3

3144 Temp:TT-5621 Select Coeff type 1 alpha delta beta 2 A B C

ENTER F4 F1 F2

HOME F3

ENTER F4

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-41

AJUSTE DE LA SALIDA DE 420 mA

20 mA

Lectura del Medidor


4 mA
Actual Ideal

4 mA

20 mA

Salida del Microprocesador

A/D

D/A Comunicaciones

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-42

AJUSTE DE SALIDA
Secuencia Rpida : 1, 2, 3, 4
3144 Temp:TT-5621 Online 1 Device Setup 2 PV 0.00 deg C 3 Analog Out 4.00 mA 4 PV LRV 0.00 deg C 5 PV URV 100.00 deg C F2 F3 F4 F1 3144 Temp:TT-5621 Device Setup 1 Process variables 2 Diag/Service 3 Basic Setup 4 Detailed Setup 5 Review HELP HOME F1 F2 F3 F4

3144 Temp:TT-5621 Diag/Service 1 Test device 2 Loop Test 3 Calibration 4 Smart Cal HELP F1 F2 HOME F3 F4

3144 Temp:TT-5621 Calibration 1 Apply values 2 Range values 3 Sensor trim 4 D/A trim 5 Scaled D/A trim HOME HELP SAVE F1 F2 F3 F4

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-43

AJUSTE DE SALIDA
3244 Temp: TT-5561 WARN - Loop should be removed from automatic control 3244 Temp: TT-5561 Connect reference meter 3244 Temp: TT-5561 Setting fld dev output to 4 mA

HELP
F1

SAVE
F2

ABORT
F3

OK
F4

HELP
F1

SAVE
F2

ABORT
F3

OK
F4

HELP
F1

SAVE
F2

ABORT
F3

OK
F4

3244 Temp: TT-5561 Enter meter value 4.00

3244 Temp: TT-5561 Fld dev output 4.00 mA equal to reference meter ? 1 Yes 2 No
OK
F4

3244 Temp: TT-5561 Setting fld dev output to 20 mA

HELP
F1

DEL
F2

ABORT
F3

HELP
F1

DEL
F2

ABORT
F3

OK
F4

HELP
F1

SAVE
F2

ABORT
F3

OK
F4

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-44

INSTALACION
En esta seccin aprender la apropiada instalacin de los modelos 3144/3244MV. Despus de completar la seccin usted podr:
Explicar la apropiada posicin de instalacin para 3144/3244MV. Describir el funcionamiento y locacin de los puentes HI/LO y de seguridad. Explicar como el 3144/3244MV debe ser cabledo, la mnima resistencia de carga, y el apropiado cable de tierra.

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-45

MENSULA DE MONTAJE

WARNING

Tubo de 2-pulgadas

B4 Mnsula de Montaje

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-46

MONTAJE DE SENSOR
Tuerca del Sensor Adaptador de Sensor Transmisor

THERMOPOZO

Unin o Acoplamiento

Conducto para cableado en campo Conducto sellado (Donde se requiera)

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-47

Consideraciones ambientales
oC oF

Incremento de temperatura de carcaza sobre la ambiente (oC)

60 50 40 30
22

108 90
815
54 0
o

(1 , 5

00

F) O

72 54
v en Te m p er
T em

20 10 3

C (1

000

F) O v en

atu

ra

36
E Longitud en pulgadas

pera

tura

18 9 0

250oC (482 F) Oven Temperatura


3.6

E Longitud de extensin en pulgadas Ejemplo: Si la temperatura de proceso es 540 o C con extensin de 3.6 resultar con un incremento de temperatura en la carcaza de 22 o C arriba de la temperatura ambiente

Incremento de temperatura de la carcaza del transmisor contra la longitud de extensin para prueba de instalacin.
EMERSON Process Management Educational Services Course 2051

Copyrighted Material / Duplication Prohibited

5-48

Conexin de tubera

Conducto sellado

Compuesto sellante
EMERSON Process Management Educational Services Course 2051 Copyrighted Material / Duplication Prohibited

5-49

Seleccin de puentes
Seguridad del transmisor On - Solo lectura OFF - Lectura y Escritura MODO DE FALLA HI = 21.50 mA de Salida LO = 3.70 mA de Salida

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-50

OPCIN CON MEDIDOR

MODO DE FALLA HI = 21.50 mA de Salida LO = 3.70 mA de Salida

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-51

CONFIGURACIN DEL MEDIDOR


Secuencia Rpida : 1, 4, 3, 3
3244 Temp: TT-5561 Online 1 Device setup 2 PV 75.00 deg C 3 AO 16.00 mA 4 LRV 0.00 deg C 5 URV 100.00 deg C

3244 Temp: TT-5561 Device Setup 1 Process variable 2 Diag/Service 3 Basic Setup 4 Detail Setup 5 Review
HELP
F1

BACK
F1

SAVE
F2

HOME
F3

ENTER
F4

SAVE
F2

HOME
F3

ENTER
F4

3244 Temp: TT-5561 Detail Setup 1 Sensors 2 Signal condition 3 Output condition 4 Device information 5 PV Damp

3244 Temp: TT-5561 Meter Options 1 Meter typ Eng unit 2 Meter decimal pt 3 Meter bar graph 4 Device information 5 PV Damp
ENTER
F4

3244 Temp: TT-5561 Meter typ Not Used Sensor 2 Eng Units Alt Snsr 1, Snsr 2 Diff Eng Units Alt Diff, S1, S2

HELP
F1

SAVE
F2

HOME
F3

HELP
F1

SAVE
F2

HOME
F3

ENTER
F4

HELP
F1

SAVE
F2

ESC
F3

ENTER
F4

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-52

SISTEMA DE CONEXIN ELECTRICA


2 1 3 4 5 T

RL =250 Max =1100

+
Power Supply

Terminal del Transmisor

Tierra
EMERSON Process Management Educational Services Course 2051

Terminal de la fuente

Copyrighted Material / Duplication Prohibited

5-53

CABLEADO DEL SENSOR

Mantenga la distancia entre el transmisor y RTD o TC lo mas corto posible. Use el tipo corresto de cable para la temperatura del dispositivo termopar. Use el cable de extensin para termopar en Millivolt (use cable de cobr)

EMERSON Process Management Educational Services

Course 2051

Copyrighted Material / Duplication Prohibited

5-54