Control & Instrumentation

Instrumentation and control


Instrumentation and control system is designed for minimum local manning and operator attention. The basic need of the instrumentation us for safe operation and efficient functioning of the plant. This can be achieved by installing optimum number measurement, indicating, transmitting and controlling instruments for all required parameters of the plants (e.g. pressure, level, temperature, flow etc.)

BASIC COMPONENTS OF A CONTROL SYSTEM


 Sensor Also often called as Primary Element. Acquires information about the status of the process variables. Typical examples: RTD/thermocouples (for temperature measurements), Capacitance type cells (for liquid level /draft /pressure measurements), etc. Controller The Brain or Heart Of the control system (the decision maker). It is the hardware element with Built-in capacity for performing the only task requiring some forms of Intelligence. Typical examples: Electronic controllers, digital computers used as controller.
3

BASIC COMPONENTS OF A CONTROL SYSTEM


 Transmitter Secondary Element. Responsible of passing the information acquired by the sensor to controller and sending the controller decision to the final control element. Measurement and control signals may be transmitted or as electrical signals. Typical examples: Electrical transmitters. Final control element Have the task of actually implementing the control command issued by the controller on the process. Typical examples: Control valve, variable speed motors, electric motors etc.
4

BASIC COMPONENTS OF A CONTROL SYSTEM


The importance of these components is that they perform the three basic operations that must be present in every control system: 1. Measurement: Measuring the variable to be controlled is usually done by the combination of sensor and transmitter. 2. Decision: Based on the measurements and the set point, the controller must then decide what to do to maintain the variable at its desired value. 3. Action: As the result of the controller's decision, the system must then take an action. This is usually accomplished by the final control element.
5

CONTROL SYSTEM
ENGG OPERATOR STATIONS STATION

PROCESSOR

I/O CARDS I/O CARDS

Basic Parameters
Measurement & Control of following Parameters are essential for Instrumentation

Pressure Temperature Flow Level

TAPPING POINTS
GASES

STEAM GASES

LIQUIDS

Pressure
Pressure measurements are one of the most common measurements required in the boiler .These range from very low -1500mmwc Draft to very high steam pressure 150 kg/cm2 .That include different type of media like steam ,water, fuel oil, air, gas each with varying degree of accuracy and reliability. Pressure varies depending on altitude above sea level, weather pressure fronts and other conditions. The measure of pressure is, therefore, relative and pressure measurements are stated as either gauge or absolute. A gauge pressure device will indicate zero pressure when bled down to atmospheric pressure (i.e., gauge pressure is referenced to atmospheric pressure). Gauge pressure is denoted by a (g) at the end of the pressure unit [e.g., kPa (g)]. Absolute pressure includes the effect of atmospheric pressure with the gauge pressure. It is denoted by an (a) at the end of the pressure unit [e.g., kPa (a)]. An absolute pressure indicator would indicate atmospheric pressure when completely vented down to atmosphere - it would not indicate scale zero. Absolute Pressure = Gauge Pressure + Atmospheric Pressure The majority of pressure measurements in a plant are gauge.
9

Pressure

10

Pressure
Pressure measuring devices The common pressure measuring devices used in IJT boilers are Diaphragm, capsule gauges for low pressure measurement Bourdon tube gauges for medium and high pressure Smart type Pressure Transmitter with required range
11

Pressure

12

Pressure
Installation: Pressure Gauges are installed on site using accessories as follows: Syphons Sunbber Seal 2 way manifold These are protective devices for pressure measuring instrument from surges & pulsations. These devices used as per application requirement 13

Pressure Gauges (Normal Installation)

14

Pressure Gauges along with Syphon

15

Pressure Gauges along with Sunbber:

16

Pressure Transmitter
(Normal Installation)

17

Temperature Measurement
1. 2. 3. 1. 2. Temperature is measured by following: Temperature Gauge: Mercury in Steel type Bi-Metallic Gas Filled Temperature Sensors: RTD Thermocouple
18

Temperature Measurement
Installation: Temperature Gauges / Sensors are installed on site using thermowell. It is a protective devices for temperature measuring instrument from damages.

19

Temperature Gauge / ELEMENT (Normal Installation)

20

Temperature Transmitter (Normal Installation)

21

Flow Measurement
The common flow measuring devices used in IJT boilers are Head Meter : (Restriction type flow meter )
Orifice Plate Flow nozzle Rotameter ( variable Area Type)

Positive Displacement meter


22

Flow Measurement
Installation: Flow sensors are installed in line of the fluid to create DP & hook-ed up with transmitter for measuring Differential Pressure, which corresponds to flow: Q = K1* (P/T ) * DP Where, DP = differential pressure across the flow element P = Main Steam Pressure T = Main steam temperature K1 = Constant Q = Compensated flow
23

Flow Transmitter (STEAM)

24

Flow Transmitter
(AIR)

25

Drum Level
H: Drum Center to Center Distance STEAM

WATER

Condensate Pot with constant Head as a wet Leg

h: Height of water inside pressurized drum

D1 = Water Density Inside Drum D2 = Water Density in Leg


HP LP

HP LP = (P+hD1g) (P+HD2g) Diff. Pr., P= hD1g HD2g = hD1 HD2 (Where P,h and H are measured in mm of water) (D1 & D2 are in gm/cc) Hence, h = P + HD2 D1

26

Drum Level
Drum Level Control Method
 Single Element  Three Element Shrink & Swell Effect Shrink : When Steam Flow Decreases Drum Level Decreases Swell : When Steam Flow Increases Drum Level Increases

Basic Elements
 Drum Level  Steam Flow  Feed Water Flow
27

Drum Level

28

Transmitter
Typical Basic Operation of Transmitter

SENSING ELEMENT

TRANSDUCER

INDICATION

Sensing Element + Transducer = Transmitter unit


29

Transmitter
Transmitters are generally use is of 2 wire type. This is the most widely used method for transmitter connections .There are three basic elements in this loop, namely Power Supply , transmitter and the receiving instrument .They are connected in series and the transmitter acts as a current regulator in the series circuit . The current in the series circuit changes with respect to change in process parameter. This simplifies cabling and reduces erection and cable cost.
30

Transmitter
Normal Pressure Transmitter

31

Transmitter
Differential Pressure Transmitter

32

TROUBLE SHOOTING OF TRANSMITTER I. POTENTIAL SOURCE LOOP WIRING

II . HIGH OUTPUT POTENTIAL SOURCE : 1.PRIMARY ELEMENT 2.IMPULSE PIPING 3.TRANSMITTER ELECTRONICS 4.SENSING ELEMENT
33

TROUBLE SHOOTING OF TRANSMITTER

III . LOW OUTPUT OR NO OUTPUT POTENTIAL SOURCE : 1. PRIMARY ELEMENT 2. LOOP WIRING 3. IMPULSE PIPING 4. SENSING ELEMENT

34

TROUBLE SHOOTING OF TRANSMITTER

IV .TRANSMITTER DOES NOT CHARACTERIZE PROPERLY POTENTIAL SOURCE : 1.PRESSURE SOURCE /CORRECTION 2.mA METER 3.POWER SUPPLY 4. TRANSMITTER ELECTRONICS 5. SENSING ELEMENT
35

Control Valve

Being the Final Control Element in a system is not an easy job. To start with, Control Valves are blamed for any and all problems that crop up in the process. Control Valve are subjected to corrosion, high velocity, cavitations, flashing liquids, cryogenic temperatures, abrasion, high temperatures and thermal shock. Control Valve are expected not only to throttle along through all this, but most likely, you are also being asked to act as a block valve and shut off tight.

36

Control Valve Classification


Linear Motion Globe Globe Single Seated Double Seated Diaphragm Pinch or Clamp Control Valve Angle 3-Way Split body

Rotary Motion

Butterfly Eccentric Plug

Swing Through Lined Eccentric

Ball

Segmented Full V-Notch

37

Control Valve Flow Characteristics

38

Control Valve Leakage Classifications


Class I: Identical to Class II, III, and IV in construction and design intent, but no actual shop test is made. Class II: Intended for double-port or balanced singe-port valves with a metal piston ring seal and metal-to-metal seats. Air or water at 45 to 60 psig is the test fluid. Allowable leakage is 0.5% of the rated full open capacity. Class III: Intended for the same types of valves as in Class II. Allowable leakage is limited to 0.1% of rated valve capacity. Class IV: Intended for single-port and balanced single-port valves with extra-tight piston seals and metal-to-metal seats. Leakage rate is limited to 0.01% of rated valve capacity.
39

Control Valve Leakage Classifications


Class V: Intended for the same types of valves as Class IV. The test fluid is water at 100 psig or operating pressure. Leakage allowed is limited to 5 X 10 ml per minute per inch of orifice diameter per psi differential. Class VI: Intended for resilient-seating valves. The test fluid is air or nitrogen. Pressure is the lesser of 50 psig or operating pressure. The leakage limit depends on valve size and ranges from 0.15 to 6.75 ml per minute for valve sizes 1 through 8 inches.
40

Basic Control Loops in BOILER


Pressure Control F W header pressure Furnace Draft Combustion Control (Main Stem Pressure) Soot Blower De-aerator Level control Drum Level Single Element Three Element De-aerator CBD

      o o  

Temperature Control  Super Heated Steam


41