Whenever
transformer’s
Volts (P.U)
> Rated transformer’s
Volts (P.U)
Over Excitation
Hertz Hertz
1
Over Excitation protection:
Instantaneous tripping is undesirable for Over Excitation. As system
may get overexcited momentary due to some momentary disturbance.
2
Over Excitation protection: (Cont)
Over Excitation curve:
Every transformer possesses its own excitation curve.
It follows Inverse time characteristics and definite time characteristics.
70
60
50
40
(Sec)
Time
Danger zone
30
20
10
0
1 1.1 1.2 1.3 1.4 1.5 1.6
Percentage Over Excitation
3
Over Excitation: (Cont)
Basic concept:
ip(t) is(t)
+ +
Vp(t)= 132kV Vs(t)= 11kV
f= 50
35 Hz f= 50
35 Hz
- -
70
60
50
time(Sec)
40
30
20
10
0
1 1.1 1.2 1.3 1.4 1.5 1.6
Percentage Over Excitation
5
Over Excitation
Vp(t)= 132kV Vp(t)= 11kV
Solution: f= 50
35 Hz f= 35
50 Hz
Breaker Breaker
6
Over Excitation Solution: (Cont)
An Over flux relay tripping should be well coordinated with transformer’s
over excitation characteristics.
Over Excitation
70
60 Time from transformer curve
50 Relay Time to initiate Trip
Time(Sec)
40
30 Danger zone
20
10
0
1 1.1 1.2 1.3 1.4 1.5 1.6 1.7
Percentage Excitation