Magnitude Magnetic Bearing Chiller

2014 Daikin Applied People and ideas you can trust.TM


Daikin Magnitude Chillers

Two models, from 100 to 700 tons


Magnetic bearing compressor system eliminates the
efficiency losses inherent with traditional compressors
First in the chiller industry to utilize magnetic bearing
technology, in 2004

Magnitude WMC Magnitude WME


100 to 400 tons 400 to 700 tons

Page 2
Magnitude Product Line Chart

Page 3
Innovative Compressor Design

Magnetic bearings
No contact = No friction = Greater efficiency
Oil-free design
No contact surfaces = No oil or oil handling equipment
Integrated variable frequency drive VFD

VFD

Magnitude WME Compressor Magnitude WMC Compressor


Page 4
WMC Compressor Design

Integral VFD Discharge Port

Magnetic bearings
and sensors

Permanent magnet
Inlet Guide
brushless DC motor
Vanes

Heat exchanger
for motor cooling
(refrigerant cooled Suction gas
motor/VFD)

Compressor
control module Shaft & impeller

Page 5
R-134a Refrigerant

No phase-out schedule, no ozone depletion potential


Positive pressure refrigerant = reduced contaminant risk
On-board refrigerant containment
Simpler, more cost-effective solution
No purge system required
Units ship with refrigerant
No recovery system required
Many Magnitude units earn 2 LEED points for Category
EAC 4, Enhanced Refrigerant Management

Page 6
The Simplicity of Being Oil-Free

Standard Centrifugal Magnetic Bearing


Centrifugal
Oil YES NO

+ Oil Heater YES NO

+ Oil Cooler YES NO

+ Oil Pump/Starter YES NO

+ Oil Reservoir YES NO

+ Oil Filter YES NO

+ Oil Piping/Valving YES NO

+ Oil Sensors/Controls YES NO

= More things to break, No concerns, no cost


more maintenance,
more $
Page 7
Oil-Free Magnitude Chiller Offers Sustainable Performance

Positive pressure, oil-free


design eliminates the
performance degradation due
to non-condensables and oil
contamination of the refrigerant

Source: The News, 04/15/04, by Jack Sine

Page 8
Industry-Leading Performance

Model Capacity Full load, IPLV


tons kW/ton
WME700S 700 0.532 0.306
14% Energy
WME500S 570 0.570 0.335 Savings Over
WME500S 500 0.532 0.312 Comparable
Standard
WMC400D 390 0.604 0.329 Centrifugal
Chiller w/ VFD
WMC400D 360 0.571 0.327
WMC290D 290 0.545 0.326 39% Energy
Savings Over
WMC250D 250 0.614 0.350 Fixed Speed
WMC150D 150 0.611 0.355 Centrifugal
Chiller
WMC145D 145 0.629 0.367
WMC145S 145 0.661 0.360

Page 9
Industry-Leading Performance

Up to 40% more energy


efficient than standard
centrifugal chillers

Saving more than


$2 million
over the life of the chiller!

Page 10
Industry-Leading Performance

What this means for owners...


Energy savings at non-peak loads
LEED Energy and Atmosphere Credit 1 (EAc1), Optimize Energy
Efficiency, for 1 to 19 possible points
Potential qualification for rebate programs

Page 11
Real Savings in Real Jobs

One Crawford Condominiums


Portsmouth, Virginia

We saved 3,000 a month in electrical costs after replacing our old


chillers with two Daikin magnetic bearing chillers. And the units are so
quiet, the residents living directly below the chillers cannot hear them
operate.
Charles Twine, Vice President of the Crawford Residents Association

Page 12
Real Savings in Real Jobs

Florida Community College,


North Campus
Jacksonville, Florida

We installed a 300-ton Daikin magnetic bearing centrifugal chillers as part


of an upgrade to our campus chiller plant and BAS system. The North
Campus reduced its electrical usage by 519,514 kWh in the first six
months. This chiller contributes 30 to 40% of our energy savings for the
entire system upgrade.
Mark Gandy, North Campus HVAC Facilities Manager

Page 13
Among the quietest Chiller in its Size Range

Sound pressure levels as low as 76 dBA per ARI


Standard 575
Ideal for schools, condos, libraries and healthcare
facilities

Page 14
Daikin Magnitude Chiller

Seismic compliant option


California Office of Statewide Health Planning and
Development (OSHPD) pre-approved
International Building Code (IBC) certified

Daikin Chiller label

Page 15
Daikin Magnitude Chiller

Advantages of seismic pre-approval


Lower costs to achieve seismic certification
Faster approvals
Faster building occupancy
Increased protection for your building investment

Page 16
More Magnitude Chiller Benefits

Feature Benefit
Multiple vessel and tubing options Design flexibility to meet specific performance
requirements

Open Choices feature for communication with Easy integration without expensive gateway
your choice of BAS using BACnet, LonTalk or panels
Modbus protocols

Intelligent controls system with touch screen Intuitive, easy to use for enhanced operator
interface productivity

AHRI certification and factory functional testing Verified performance

Certified and witness test options Customer confidence that the chiller performs as
specified

Comprehensive factory support after installation, Customer satisfaction through the life of the chiller
including operator training

Page 17
Magnitude Rapid Restore

Quickly restores cooling capacity in mission


critical facilities!

RideThrough - Beyond quick start


Compressor rotor never stops and re-
synchronizes during short duration power
failures

Maximum Fast Loading Minimum


Compressor Time to 80% RideThrough
Start Time* Load* Time
WMC 43 sec 120 sec NA
WME 500-700 60 sec 75 sec 5 sec**
* Time after power is restored after a power failure
** Power Loss Duration
Times may vary slightly based on system conditions at the time of power failure and at the time of power
restoration.
WME requires separate controls UPS for Rapid Restore and Fast Loading
Page
Magnitude Chillersa Great Choice for

Areas with high electric rates


Immediate savings and quick payback
Sound-sensitive environments
Its the quietest chiller in its size range
Buildings with high lease rates
Small footprint means smaller equipment rooms
and more space available for leasing
Limited space for moving or install units
WMC models fit through standard 4 wide doors

Page 19
Ideal for Retrofit
Compact size of the Magnitude chiller makes it
ideal for retrofit and replacement
Stacked Shells = Smaller Footprint!

H = 84.0
(2137 mm)

L = 170.6
(4333 mm)
W= 45.5
(1158 mm)

Magnitude WMC-290D, C-vintage unit shown


Page 20
Reliable

Magnitude chillers have proven their reliability


in 2,900+ installations around the world

Page 21
A Favorite Choice of Green Buildings

Child Development Centre, University of Calgary Johnson County Office Building, Kansas
LEED Platinum LEED Gold

Harford Board of Education Office Building, Maryland Northbrook Junior High School, Illinois
LEED Gold Energy Star rated

Page 22
Top 6 Reasons To Specify and Buy a
Daikin Magnitude Chiller

1. Significant energy savings


2. World-class, sustainable, and reliable performance
3. Environmental commitment
4. LEED points and potential rebate qualifications
5. Great value with fast payback opportunity
6. Seismic certified

Page 23
What a Magnitude Chiller Means for the Facility Owner

+ + =
High Reduced Sustainability Lowest
Efficiency Maintenance Total Cost
(no oil, no purge) of Ownership

Page 24
Make it a Complete Daikin System

Magnitude Chiller
100 to 700 tons

Vision Indoor Air Handler Skyline Outdoor Air Handler Destiny Air Handler
900 - 100,000 cfm 900 - 65,000 cfm 600 - 15,000 cfm

Unit Ventilator Fan Coil units


RoofPak Outdoor Air Handler 600 - 3,000 cfm
750 - 2,000 cfm
900 - 65,000 cfm
Page 25
Questions?

e
2014 Daikin Applied People and ideas you can trust.TM
Thank You!

e
2014 Daikin Applied People and ideas you can trust.TM

También podría gustarte