Documentos de Académico
Documentos de Profesional
Documentos de Cultura
RIESGOELECTRICO
RIESGOELECTRICO
PREVENCIN DE RIESGOS
BRIGADA CONTRAINCENDIOS
Ao 2006
OQC
1
RIESGO ELCTRICO
TODO RIESGO PARA EL SER HUMANO GENERADO POR LA
ELECTRICIDAD
ARCO ELCTRICO
c) TIEMPO DE EXPOSICIN
e) TRAYECTORIA DE LA CORRIENTE
IIN T E N S ID A D E F E C T O P R O D U C ID O E N E L O R G A N IS M O
C .A . (m A )
1 U M B R A L D E P E R C E P C IO N
7 U M B R A L D E S E N S A C IO N D O L O R O S A
10 V A L O R L IM IT E D E IN T E N S ID A D
11 T E T A N IZ A C IO N M U S C U L A R D E L A M A N O Y E L
BRAZO
25 U M B R A L D E T E T A N IZ A C IO N D E L A C A J A
T O R A C IC A
H A S T A A Q U L O S E F E C T O S S O N R E V E R S IB L E S
30 U M B R A L D E F IB R IL A C IO N
V E N T R IC U L A R
4
b) TENSIN Y FRECUENCIA DE LNEA
FRECUENCIA 50 - 60 HZ.
A ALTAS FRECUENCIAS LA C.A. SE COMPORTA COMO C.C.
1 10 4,5 UMBRAL DE
PERCEPCION
10 76 76 VALOR LIMITE DE
INTENSIDAD
TENSIN DE SEGURIDAD
7
d) RESISTENCIA DEL CUERPO HUMANO
VARA CON:
TENSIN APLICADA
EDAD
SEXO
TIPO DE PIEL
ESTADO DE LA PIEL
8
TABLA COMPARATIVA
9
e) TRAYECTORIA DE LA CORRIENTE
AFECTA LA ESTRUCTURA MUSCULAR
10
CONCLUSIONES
Intensidad (mA)
1000
Z ZONA DE RIESGO
O
N
A
CURVA DE SEGURIDAD
30
DE SEGURIDAD
Tiempo
0,03 3 (seg) 11
CONTACTO DIRECTO
CONTACTO DIRECTO
T E N S IO N D E C O N T A C T O ( V n ) : 2 2 0 V / 5 0 H z .
R E S IS T E N C IA D E L C U E R P O H U M A N O ( R c ) : 2 0 0 0 W
R E S IS T E N C IA D E T IE R R A ( R u ) : 2 0 W
R E S IS T E N C IA D E L E L E M E N T O B A J O T E N S IO N ( R i) : 3 0 W
C O R R IE N T E D E D E F E C T O ( Id ) : ?
Vn 220 V
Id = - - - - - - - - - - - - - - - - - = - - - - - - - - - - - - - - - - - - - - - - = 4 ,4 A
Ru + Ri 20 W + 30 W
15
T E N S I N D E C O N T A C T O P A R A E L S E R H U M A N O (V c ):
V c = R u x Id = 2 0 W x 4 ,4 A = 8 8 V
IN T E N S ID A D D E L A C O R R IE N T E E L C T R IC A QUE
C IR C U L A P O R E L C U E R P O H U M A N O (Ic ):
Vc 88 V
Ic = ------------------ = ------------------------- = 0 ,0 4 4 A = 4 4 m A
Rc + Ru 2000 W + 20 W
R A T IF IC A E L P R IN C IP IO D E L A P R O T E C C IO N
D IF E R E N C IA L
16
PREVENCIN DE CONTACTOS DIRECTOS
17
PREVENCIN DE CONTACTOS INDIRECTOS
18
DISYUNTOR DIFERENCIAL
SEGURIDAD EN INSTALACIONES ELCTRICAS
PROTECCION TERMOMAGNTICA
PROTECCIN DIFERENCIAL
20
CINCO REGLAS DE ORO
21
RIESGO DE INCENDIO Y/O EXPLOSIN
22
ELEMENTOS DE EXTINCIN UTILIZADOS EN
RIESGOS ELCTRICOS
NO UTILIZAR AGUA
23
TRABAJOS CON TENSIN
24