Está en la página 1de 11

IMPLEMENTATION OF

NGT ISOLATOR OPEN/CLOSE


FEEDBACK IN DCS

TEAM MEMBERS

SIBA

NARAYAN HOTA
AMIT KUMAR
V K SRIVASTAVA
SULEMAN BAIG

CONTENT

APPLICATION

OF NGT
PROBLEM STATEMENT
SCHEME IMPLEMENTATION
ADVANTAGE OF SCHEME
CHANGE

APPLICATION OF NGT

APPLICATION OF NGT
THE

GENERATOR NEUTRAL STAR POINT IS


GROUNDED
THROUGH
NEUTRAL
GROUNDING TRANSFOMER.

NGT

IS USED TO LIMIT THE FAULT


CURRENT IN CASE OF ANY GROUND FAULT
IN GENERATOR AND BUSDUCT.

NGT

IS USED FOR IMPLEMENTATION OF


GROUND FAULT AND OTHER MAJOR
PROTECTIONS OF GENERATOR.

PROBLEM STATEMENT
NGT

ISOLATOR OPEN/CLSOE FEEDBACK


IS NOT AVAILABLE IN DCS.

IF

NGT ISOLATOR IS OPEN, GROUND


FAULT PROTECTION IS BYPASSED.

WHILE

OPERATION OF GENERATOR IF
ANY FALUTS OCCUR IT MAY LEAD TO
DAMAGE OF GENERATOR WINDING.

UNBALANCE

OPERATION OF GENERATOR
AS NEUTRAL IS FLOATING.

SCHEME IMPLEMENTATION
AFTER

BEFORE

LIMIT
SWITCH

GEN
GEN

GEN
ISOLATOR

NGT

L.S
d

DCSC
S

SCHEME IMPLEMENTATION
BEFORE

SCHEME IMPLEMENTATION
AFTER

OPEN FEEDBACK

CLOSE FEEDBACK

ADVANTAGES

DCS OPERATOR NOW KNOWS NGT IS


CONNECTED TO GENRATOR NEUTRAL
STAR POINT.

RELIABILITY OF GENERATOR GROUND


FAULT PROTECTION.

PROLONG GENERATION LOSS CAN BE


AVOIDED BY PROTECTING THE
GENERATOR.

THANKYOU