Documentos de Académico
Documentos de Profesional
Documentos de Cultura
Module 1/5
Objectives:
To define:
a) Ventilation
b) Air Conditioning
To look generally at the systems and
their components used for each of
the above
INTRODUCTION TO MODULE
The Commissioning of air systems
requires a basic knowledge of
ventilation and air conditioning and
when and why they are used. In this
module we will define ventilation and
air conditioning, look at the different
types of systems that you will see and
discuss the equipment used in them.
1. VENTILATIONS
Whenever people are present in an enclosed space, there is a natural
build-up of carbon dioxide, body odour, water vapour and heat.
Imagine being shut in a sealed room on a hot day with twenty other
people. In a short time, the air in the room will begin to feel stale. The
temperature of the room will begin to rise. There will be a distinct smell
of perspiration. If some of the people are smoking, the room air will feel
even staler. Ventilation is used to prevent a situation like this
happening.
Ventilation is normally a legal requirement whenever people are
gathered in public buildings, or in industrial processes where dust,
fumes and smoke may be present. With any ventilation system, the air
in the room containing contaminants is replaced by fresh air. This
creates air movement, which in turn creates a feeling of freshness.
Note:
The performance of ventilation systems is often based on "air
change rates" expressed in air changes per hour. This is the
amount of times the ventilation system will completely replace
all room air with fresh outside air in one hour.
There are two methods of ventilation, natural and mechanical. Let us
look at each in turn.
Natural Ventilation
Natural ventilation is provided by wind pressure, "stack effect" or
a combination of both.
Wind will cause a positive pressure on the windward side of a
building and a negative pressure on the leeward side. If windows
are open on both the windward and leeward side of the building,
there will be a natural air movement within the building from
windward to leeward side. This is due to air movement from the
positive to the negative pressure side.
Whenever the air temperature in a room is higher than outside,
the warm room air will always rise, drawing in cold air to replace
it. This principle is known as "Stack Effect". It follows that the
higher the room is, the further the "stack" of warm air can rise
and the more cold outside air will be drawn in.
These two forms of natural ventilation are best used by installing
fixed inlet openings at low level on the windward side of a
building and outlet openings at high level on the leeward side.
It can be seen that whenever it is either cold outside, windy or a
mixture of both, natural ventilation can be used to its' full
advantage.
Mechanical Ventilation
2.
3.
Mechanical Ventilation
1. Natural inlet, mechanical extract
With this type of system a fan is used to extract air from a
room space.
This causes a negative pressure in the room, having the
effect of drawing air in from surrounding areas through
natural openings such as gaps around doors.
These systems are normally used in kitchens, toilet areas
and workshops.
Schematic diagram below shows a typical extract system,
consisting of a fan, ductwork and extract grilles.
Mechanical Ventilation
2. Mechanical inlet, natural extract
With this type of system a fan is used to supply air to a room
space.
This causes a positive pressure in the room, having the effect
of forcing room air out to surrounding areas, again through
natural openings.
These systems are normally used to provide fresh air to
areas such as offices.
Schematic diagram below shows a supply system consisting
of a supply air handling unit, ductwork and supply grilles. The
air handling unit is made up of a filter, heater and fan.
Schematic Diagram (a)
Mechanical inlet, natural
extract system:
Mechanical Ventilation
1. Mechanical inlet and extract
With this type of system fans are used to both supply and extract
air.
The quantities of supply and extract air are often not matched. In
areas where it is necessary to prevent smells or fumes escaping to
other areas, more air is extracted than supplied, thereby causing a
negative pressure in the area.
Where it is important to prevent dust entering an area, more air is
supplied to the area than extracted, thereby causing a positive
pressure in the area.
This type of system is used to serve many different areas, including
those already described above.
Schematic diagram below shows a mechanical inlet and extract
system consisting of a supply air handling unit ductwork and grilles
and an extract fan, ductwork and grilles. The supply air handling
unit is again made up of a filter, heater battery and fan.
Schematic Diagram (a)
Mechanical inlet and
extract system:
Mechanical Ventilation
Note:
2. AIR CONDITIONING
Definition
Air conditioning can be defined as control of the
environmental conditions of an area within preset
limits. This control may be required for the comfort
of people (or animals) or for the correct
performance of an industrial or scientific process.
Large computer installations, for example, need to
be maintained at a temperature of approximately
21C and a relative humidity of 50%. A ventilation
system will not normally provide this type of
control.
Air conditioning can be split into two main
classifications; close control and comfort. Let us
look at each in turn.
Passing the air over an open pan of water that has an electric element
heating the water to boiling point.
2.
3.
Heating the air then passing it over a water spray. This method is
losing favour as it may be susceptible to developing the bacteria that
cause Legionnaires Disease.
Moisture is removed by cooling the air stream to below its' dewpoint
temperature. (Dewpoint being the temperature to which air can be
cooled without condensing the moisture it holds). This is known as
latent cooling and is again achieved by using a cooling coil; coils
served by refrigerant are more efficient in this instance.
3. ENERGY CONSERVATION
The Need for Energy Conservation
All of the systems that we have looked at in this module
have in one form or another removed air from a room
area and replaced it with fresh air from outside. Room
air that has been heated or cooled is thrown away to be
replaced with more air that needs to be heated or
cooled. This is very uneconomical from an energy
viewpoint. To prevent this type of energy wastage,
various methods of energy conservation are employed
in ventilation and air conditioning systems.
The three major types of energy conservation systems
are:
Economy Control
Plate Heat Exchangers
Run Round Coils
Economy Control
With economy control, a variable proportion of the air extracted
from a room area is mixed with the incoming fresh air to the
room area.
This is achieved by connecting a re-circulation duct between the
fresh air input and exhaust ducts and installing motorised
dampers in all three ducts. A schematic diagram is given below:
Economy Control
Ventilation System:
In Winter, the room air will be hot and the outside air will be
cold. By mixing as much hot extract air with fresh air as
possible, the air mixture will need only a small amount of
additional heating to raise it to the required supply
temperature. If you compare this against exhausting all of the
room air and then having to heat a corresponding amount of
fresh air to replace it, you can see that considerable savings in
heating costs can be made.
To achieve this pre-heating effect the dampers will need to be in
the following positions:
The fresh air inlet damper will be at its' minimum fresh air
position
The exhaust air damper will be at its' minimum exhaust position
The re-circulation air damper will be at its' maximum recirculation position.
Economy Control
Ventilation System:
In Summer, it is desirable to provide as much fresh air as
possible to the room area. This will provide cooling to the room
area whenever outside temperature is less than the room
temperature. This principle is known as free cooling.
To achieve this free cooling effect the dampers will need to be in
the following positions:
The fresh air inlet damper will be at its' maximum fresh air
position
The exhaust air damper will be at its' maximum exhaust position
The re-circulation air damper will be at its' minimum re-circulation
position (possibly even fully closed)
Note:
Whenever a ventilation system (or an air conditioning
system) supplies an area that is occupied by people, a
minimum amount of fresh air must be supplied to the area.
Table B24 of Book B of the CIBSE Guide gives fresh air
requirements for various applications.
Economy Control
Air Conditioning System:
If this arrangement is used with an air conditioning system, the
sequence of events is slightly different.
In both Winter and Summer, it is advantageous to have the
dampers in the same position as they would be for winter with a
mechanical ventilation system. This is because in the same way as
mixing fresh and re-circulation air in winter will provide a preheated air mixture, mixing fresh and re-circulation air in summer
will provide a pre-cooled air mixture.
In Spring and Autumn, it is advantageous to have the dampers
in the same position as they would be for summer with a
mechanical ventilation system. This is because an air conditioned
area will normally still require cooling even during these seasons.
By supplying fresh air that is colder than the room area,
advantage will be taken of the "free cooling" principle already
described. This means that the mechanical refrigeration system
may not have to be used and can give considerable energy
savings.
EXERCISES
1. Name 4 situations in which you use a
comfort cooling system as opposed to a
full air conditioning system? and explain
your reasons.
2. In the previous module (on water
systems) you investigated Legionnaires
Disease. What effect does this have on
the use of spray type humidifiers in air
conditioning systems?
ANSWERS TO EXERCISES
1. Comfort cooling would be used as
opposed to Air Conditioning system:
Shops
Offices
Factories
Hotels
Restaurants Theatres
ANSWERS TO EXERCISES
2. Spray type Humidifiers / Legionnaires Disease
i.
ANSWERS TO EXERCISES
ii.
ANSWERS TO EXERCISES
iii. Outbreak of Legionnaires disease in Glasgow Royal
Infirmary, Microbiological aspects. Timbury: M.C. et al.,
(J. Hygiene), December 1986, Vol. 97, No.3, 393-403,
18 refs.
A report on the bacteriological and epidemiological
investigations leading to the rapid diagnosis and
containment of an outbreak of Legionnaires disease at
Glasgow Royal Infirmary in November 1985. Most of
the 15 patients affected had been treated in highdependency areas on two floors of the hospital
supplied by the same two air-conditioned ventilation
systems. The source of infection was traced to
contamination of a cooling tower from which a plune of
spray discharged into the intake vents of the two
ventilation systems. Rubber grommets within the
cooling tower remained persistently positive for
Legionella over a period of 18 days despite thorough
cleaning and repeated chlorination of the system.
ANSWERS TO EXERCISES
iv. Monitoring and controlling the source of Legionnaires'
disease in cooling water McGlone: K. (Hospital Engng.)
September 1985, Vol. 39, No.8, 8.
Notes Legionnaires' disease is a relatively common
illness, mistaken for pneumonia before 1976. The
bacterium, which is ubiquitous in nature in low
concentrations, can become dangerous when left to
develop in man-made water systems. Industrial cooling
systems, humidifiers, domestic water supplies and
shower heads have all been found to contain traces of
the bacterium. Research has shown the only means of
infection is by inhalation of fine water spray containing
the bacterium. Explains how the application of the
correct waterside chemicals can help in both the
elimination and prevention of the bacterium. If this is
also coupled with the correct engineering practice, the
possibility of a Legionnaires' disease outbreak is
greatly reduced.
ANSWERS TO EXERCISES
v. Air conditioning fever. Anon. (Heat. Air Condit. J.)
September 1979, Vol. 49, No. 571, 12-15, 3 figs.
Contends it seems established that cases of
Legionnaires' disease and `humidifier fever' can
be traced directly to air conditioning equipment.
Only ducted systems probably with a spray type
humidifier are likely to propagate disease.
Prevention by good housekeeping practice is
simple and inexpensive. Swiss research shows
absenteeism with lung and bronchial infections is
20% higher among those working in air
conditioned areas. Examines air conditioningrelated diseases. Notes multiplication of microbes
in water reservoirs, and duct contamination.
Recommends preventive measures.