Está en la página 1de 24

Dear Participants WELCOME To a discussion on FSSS/ Boiler Protection System Basic Concepts and Standards

24 December 2013

PMI Revision 00

CONTENT Basic concept Function of BMS Furnace purge procedure STANDARDS / NFPA

24 December 2013

PMI Revision 00

Main Functions Furnace purge before boiler light-up Oil firing: Permissives, Sequences and Protections Coal firing: Permissives, Sequences and Protections Master Fuel Trip (MFT) or Boiler Trip

Post-Trip Purge Fans Trip Runback: Graded Mill Tripping Runback: Graded Mill Tripping

24 December 2013

PMI Revision 00

SG (Steam Generator) CONTROLS


BURNER MANAGEMENT SYSTEM BOILER PROTECTIONS MILLING SYSTEM FUEL OIL SYSTEM UNIT PURGE

SEC. AIR DAMPER AUX. PRDS CONTROL CONTROL SOOT BLOWER CONTROL HP-BYPASS CONTROL

24 December 2013

BACK

PMI Revision 00

Some Definitions
Boiler Control System: Deals with Regulating Control Burner Management System (BMS): Deals with Furnace Safety and Start/Stop of Fuel Preparation and Burning Equipment BMS Logic:

Deals with Control System which would give output based on external inputs and internal logic
24 December 2013 PMI Revision 00 5

Burner management system


Burner management system is designed to ensure the execution of a safe ,orderly operating sequence in the startup and shutdown of fuel firing equipments and to prevent errors of omission safe operating procedure.
24 December 2013 6

Function of BMS
TO PROVIDE SAFETY TO BOILER.

TO PROVIDE ORDERLY SEQUENCE IN THE S/U & S/D OF FUEL FIRING EQUIPMENTS. PREVENT S/U OF FUEL FIRING EQUIPMENTS UNLESS CERTAIN PERMISSIVE INTERLOCKS HAVE BEEN SATISFIED. CONTINUOUS FLAME MONITORING. FAULT DETECTION AND ASSOCIATE S/D. INITIATE MFT UNDER CERTAIN CONDITION OF LOAD COMBINATION.
24 December 2013 7

Basic Concepts of BMS


BMS is an independent and discreet logic system specially designed for safety and protection during starting , shutdown, low load and emergency conditions. BMS system has been designed to provide increased safety, reliability, flexibility and over all performance of the boiler. The system is intended to protect against malfunction of fuel firing equipment and associated systems. In some phases of operation, the BMS shall provide permissive interlocks only to ensure safe startup of equipment.
24 December 2013 PMI Revision 00 8

The Burner Management system monitors the presence or absence of the forced draft fan running and verifies air flow is being produced, ensures the water level in the boiler drum is satisfactory, and verifies that there is at least one flame in the furnace. The Burner Management alarm system provides for a first out cause of trip allowing operators to readily identify the reason for an unexpected boiler trip condition. The Burner Management System controls the air registers, igniters and fuel oil valves for each burner, as well as monitoring of the flame signals for each burner in service.

24 December 2013

PMI Revision 00

If the flame quality degrades to 60% of maximum signal strength a poor flame alarm is issued to the alarm system. When a flame quality signal is below 40% for 4 seconds the burner will trip. The Burner Management System lights off the initial burner and cuts out burners automatically based on an operator selected sequence. It determines when burners need to be cutout based on the steam pressure signal from the ACC (Automatic Combustion Control) system. It also provides an interface to the ACC system to tell it when there is a state of change that can affect how the ACC will respond or perform.

24 December 2013

PMI Revision 00

10

Function of BMS
Controls boiler purge, fuel headers, and burner field devices, allowing sequential control of the start-up and shutdown of any burners. Continuous monitoring of supervisory interlocks, fuel valve positions, flame status and field devices. The control strategy normally utilize de energize to trip method. Smart alarms provide fail to open, fail to start, fail to close, and fail to stop information. Flame monitoring equipment provides the logic controller with flame status of burners and/or igniters. Prevent firing unless a satisfactory furnace purge has first been completed.

24 December 2013

PMI Revision 00

11

Prohibit start-up of the equipment unless certain permissive interlocks have first been completed. Monitor and control the correct component sequencing during startup and shut-down of the equipment. Conditionally allow the continued operation of the equipment only while certain safety interlocks remaining satisfied. Provide automatic supervision when the equipment is in service and provide means to make a Master Fuel Trip (MFT) should certain unacceptable firing conditions occur.

24 December 2013

PMI Revision 00

12

SIMPLIFIED BLOCK DIAGRAM OF BURNER MANAGEMENT SYSTEM.


C.C.R

FUEL V/V AIR DAMPER FLAME DETECTOR IGNITER


24 December 2013

ABC LOCAL CONTROL BOX

B M S

DAS

MILL CONTROL BOILER PLANT 13

IGNITION CONTROL PANEL

BURNER GROUP-EACH STEAM GENERATOR HAS FOUR BURNER


GROUPS.EACH GROUP COMPRISES FOUR OIL BURNER WITH ASSOCIATE PF BURNER LOCATED ABOVE AND BELOW.

MILL GROUP- THERE ARE EIGHT MILL GROUPS PER STEAM


GENERATOR EACH GROUP COMPRISES A MILL ,ITS ASSOCIATED COAL FEEDER AND A SEAL AIR FAN.

AIR DAMPERAIR DAMPER ARE DIVIDED AS FOLLOWS1-FIVE ELEVATION OF FOUR SECONDARY AIR. 2- 4 ELEVATION OF 4 AIR TO OIL/S.A.D 3-8 ELEVATION OF 4 AIR TO P.F. BURNER. 4-TWO ELEVATION OF FOUR OVERFIRE AIR.
24 December 2013 14

BURNER GROUP NUMBER


4

RELATIONSHIP OF MILL GROUP, ELEVATION NUMBERS & GROUP NUMBERS.


NOZZLE ELEVATION NUMBER NOZZLE TYPE MILL GROUP GROUP

13---------------------------SECONDARY AIR 12---------------------------COAL--------------------------- -F 11---------------------------OIL AND S/A 10 --------------------------COAL-----------------------------E 9 --------------------------SECONDARY AIR 8---------------------------COAL------------------------------D 7-------------------------- OIL AND S/A 6---------------------------COAL------------------------------C 5---------------------------SECONDARY AIR 4---------------------------COAL------------------------------B 3---------------------------OIL AND S/A 2---------------------------COAL------------------------------A 1-------------------------- SECONDARY AIR

24 December 2013

15

24 December 2013

PMI Revision 00

16

STANDARDS AND CODES Prescriptive standards such as NFPA have done well at identifying what interlocks should be implemented based upon lessons learned from previous incidents and near misses. In todays microprocessor-based world, it is more important to know how to properly implement the prescriptive based interlocks. The logic solver was comprised of relays with simple and well-defined failure modes, it was very easy to understand what level of risk reduction the BMS provided.

24 December 2013

PMI Revision 00

17

NFPA Burner Management Systems (BMS) associated with fired devices in the power boilers are defined as Safety Instrumented Systems (SIS) if they contain sensors, a logic solver and a final control element according to NFPA. By actively embracing the concept that a BMS may in fact be a SIS, companies can ensure that these systems are designed, maintained, inspected and tested per both the applicable prescriptive standards (API, NFPA, etc.). A BMS can be designed that meets all requirements of the prescriptive standards such as NFPA.

24 December 2013

PMI Revision 00

18

Standard Followed
National Fire Protection Authority (NFPA) of USA Code 85 of 2001
This code is an amalgamation of earlier codes 8501 to 8506 applicable for various types of boilers and combustion

24 December 2013

PMI Revision 00

19

IBR Requirements
Fuel supply should be shut off when: Flame failure occurs Failure to ignite fuel within a pre-determined time Abnormal drum level Trip of Draft fans Increase in Boiler Pressure

24 December 2013

PMI Revision 00

20

BMS Logic Hardware


No specific stipulation regarding type of hardware NFPA stipulations are not retroactive Existing system if giving trouble free operation can continue to work even if not PLC/DCS based

24 December 2013

PMI Revision 00

21

Some Requirements of NFPA


Burner Management System (BMS) Logic shall: be such that single failure does not prevent shutdown evaluate and address failure of components diagnose improper logic functions have a direct operable device for MFT which would work irrespective of BMS logic be protected from unauthorised logic changes be provided with independent logic, I/O, power supply and hardware etc for each boiler separately

24 December 2013

PMI Revision 00

22

Interesting Insights to NFPA


NFPA recognises that: It is not possible to encompass all specific hardware applications The code should not be considered a cook book No standard can guarantee elimination of Furnace explosion or implosion Basic cause of Furnace Explosion is ignition of accumulated combustibles in the furnace

24 December 2013

PMI Revision 00

23

24 December 2013

PMI Revision 00

24

También podría gustarte