Document Title: Data Sheet for Distribution Transformer

ENGINEERING & DEVELOPMENT ORGANIZATION of TEHRAN Client Doc. No.: Contractor Doc No.:

Date:7/30/2011
Rev.: 0

Page 1 of 5

MUNICIPALITY OF TEHRAN

NIAYESH TUNNEL
Document Title:

Data Sheet for Distribution Transformer


Client Doc. No.: XXXXXXXXXXXXXX Contractor Doc No.: XXXXXXXXXXXXXXXXX

0 Rev

7/30/2011 Date dd.mm.yy

A.Ghafouri TABLIEH Prepared

S.BAYANI TABLIEH Checked P.O.R

For review

Purpose of Issue
Approved

To

Set

Distributed

File Name: xxxxxxxxxxxxxxxxxxxxxxxxx

Contractor J.V.

Client

Consultant J.V.

Document Title: Data Sheet for Distribution Transformer

ENGINEERING & DEVELOPMENT ORGANIZATION of TEHRAN Client Doc. No.: Contractor Doc No.:

Date:7/30/2011
Rev.: 0

Page 2 of 5

Tabulation of Revised Pages


Page 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 00 X X X X X 01 02 03 04 05 06 07 Page 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 00 01 02 03 04 05 06 07

File Name: xxxxxxxxxxxxxxxxxxxxxxxxx

Contractor J.V.

Client

Consultant J.V.

Document Title: Data Sheet for Distribution Transformer

ENGINEERING & DEVELOPMENT ORGANIZATION of TEHRAN Client Doc. No.: Contractor Doc No.:

Date:7/30/2011
Rev.: 0

Page 3 of 5

No.
1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2..2 2.3 2.4 2.5 2.6 2.7

Description
GENERAL Application Type Rated output Quantity required Installation No load transformer ratio Number of phases Rated frequency Type of cooling WINDING Type of transformer Material of conductor Method of connection Method of connection Vector group LV Neutral Insulation of Windings H.V and L.V. One minute power Frequency withstand voltage (dry and wet) 1.2/50 micro second full wave impulse withstand TAP CHANGER Tap changer Tapping on winding HV/LV Type of Tap Changer Tap range Tap step SYSTEM DATA Nominal System Voltage On HV Side Highest System Voltage on HV side Nominal System Voltage on LV side Highest System Voltage On LV Side Fault level on HV side Fault level on LV side System Neutral on HV side

Unit

Technical Particulars Specification


Distribution Transformer Cast Resin 250 KVA Two Indoor 30/0.420 Three 50 AN 2 winding Electrolytic Cu conductor Delta Star Dyn 11 Solidly earthed H.V L.V Xx 2.5 75

Bidders configuration

Insulation KVA Nos. Indoor/Outdoor kV/kV Nos. Hz AN 2-wdg/ 3-wdg/ Auto

HV winding LV winding

kV (r.m.s)

2.8 3.0 3.1 3.2 3.3 3.4 3.5 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7

kV (Peak)

OLTC/ OCTC/ Off-Circuit link % 2.5% kV kV kV kV kA kA

By means of links HV Off Circuit links +5% t o - 5 % 2.5% 30 33 0.420 0.5 25 kA for l sec 50 kA for lsec -

File Name: xxxxxxxxxxxxxxxxxxxxxxxxx

Contractor J.V.

Client

Consultant J.V.

Document Title: Data Sheet for Distribution Transformer

ENGINEERING & DEVELOPMENT ORGANIZATION of TEHRAN Client Doc. No.: Contractor Doc No.:

Date:7/30/2011
Rev.: 0

Page 4 of 5

No.
4.8 5.0 5.1 5.2 5.3

Description
System Neutral on LV side TERMINATIONS Terminal connection HV termination Entry Termination size

Unit

Technical Particulars Specification


Solidly Earthed

Bidders configuration

Busduct/Cable Box Top/Bottom

In-built cable box Bottom Suitable for 30 kV (E) grade cable, 3x1Cx 95 sq.mm busduct Top Suitable for 1.1 kV (E) Grade busduct Solidly Earthed

5.4 5.5 5.6 6.0 6.1 6.2 6.3 6.3.1 6.3.2 7.0 7.1 7.2 8.0 8.1 8.2 9.0 9.1 9.2 9.3 10.0 10. l 10.2 10.3 10.4 11.0

LV termination Entry Termination size NEUTRAL Transformer Neutral on HV Side Transformer Neutral on LV side EARTH BUS Material Size TEMPERATURE RISE Ambient temperature End Temperature after rise PAINTING Paint type Paint Shade MOVEMENT Type of Wheels Wheel gauge Direction of Wheels Miscellaneous Accessories Spares Configuration of HV/LV Routine tests to be carried out No Load Loss

Busduct/Cable Box Top/ Bottom

Electrolytic Cu 2 no 50x6 mm strip Deg C Deg C 40 90 Deg C Class F. Epoxy Siemens grey RAL 7032 Plain/ Flanged Unidirectional/ Bidirectional Reqd/ Not Reqd Reqd/ Not Reqd degrees Yes/No KW Plain As per site requirement Bidirectional

Epoxy/ Synthetic enamel

Required Required As per site requirement Yes BY bidder

File Name: xxxxxxxxxxxxxxxxxxxxxxxxx

Contractor J.V.

Client

Consultant J.V.

Document Title: Data Sheet for Distribution Transformer

ENGINEERING & DEVELOPMENT ORGANIZATION of TEHRAN Client Doc. No.: Contractor Doc No.:

Date:7/30/2011
Rev.: 0

Page 5 of 5

No.
11.1 12.0 13.0

Description
Full Load Loss % impedance Degree of protection for enclosure

Unit
KW As per IS

Technical Particulars Specification


By Bidder 5 % at 75 deg C IP23

Bidders configuration

File Name: xxxxxxxxxxxxxxxxxxxxxxxxx