Documentos de Académico
Documentos de Profesional
Documentos de Cultura
Client
Consultant J.V.
ENGINEERING & DEVELOPMENT ORGANIZATION of TEHRAN Client Doc. No.: Contractor Doc No.:
Date:7/30/2011
Rev.: 0
Page 1 of 5
MUNICIPALITY OF TEHRAN
NIAYESH TUNNEL
Document Title:
0 Rev
For review
Purpose of Issue
Approved
To
Set
Distributed
Contractor J.V.
Client
Consultant J.V.
ENGINEERING & DEVELOPMENT ORGANIZATION of TEHRAN Client Doc. No.: Contractor Doc No.:
Date:7/30/2011
Rev.: 0
Page 2 of 5
Contractor J.V.
Client
Consultant J.V.
ENGINEERING & DEVELOPMENT ORGANIZATION of TEHRAN Client Doc. No.: Contractor Doc No.:
Date:7/30/2011
Rev.: 0
Page 3 of 5
No.
1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2..2 2.3 2.4 2.5 2.6 2.7
Description
GENERAL Application Type Rated output Quantity required Installation No load transformer ratio Number of phases Rated frequency Type of cooling WINDING Type of transformer Material of conductor Method of connection Method of connection Vector group LV Neutral Insulation of Windings H.V and L.V. One minute power Frequency withstand voltage (dry and wet) 1.2/50 micro second full wave impulse withstand TAP CHANGER Tap changer Tapping on winding HV/LV Type of Tap Changer Tap range Tap step SYSTEM DATA Nominal System Voltage On HV Side Highest System Voltage on HV side Nominal System Voltage on LV side Highest System Voltage On LV Side Fault level on HV side Fault level on LV side System Neutral on HV side
Unit
Bidders configuration
HV winding LV winding
kV (r.m.s)
2.8 3.0 3.1 3.2 3.3 3.4 3.5 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7
kV (Peak)
By means of links HV Off Circuit links +5% t o - 5 % 2.5% 30 33 0.420 0.5 25 kA for l sec 50 kA for lsec -
Contractor J.V.
Client
Consultant J.V.
ENGINEERING & DEVELOPMENT ORGANIZATION of TEHRAN Client Doc. No.: Contractor Doc No.:
Date:7/30/2011
Rev.: 0
Page 4 of 5
No.
4.8 5.0 5.1 5.2 5.3
Description
System Neutral on LV side TERMINATIONS Terminal connection HV termination Entry Termination size
Unit
Bidders configuration
In-built cable box Bottom Suitable for 30 kV (E) grade cable, 3x1Cx 95 sq.mm busduct Top Suitable for 1.1 kV (E) Grade busduct Solidly Earthed
5.4 5.5 5.6 6.0 6.1 6.2 6.3 6.3.1 6.3.2 7.0 7.1 7.2 8.0 8.1 8.2 9.0 9.1 9.2 9.3 10.0 10. l 10.2 10.3 10.4 11.0
LV termination Entry Termination size NEUTRAL Transformer Neutral on HV Side Transformer Neutral on LV side EARTH BUS Material Size TEMPERATURE RISE Ambient temperature End Temperature after rise PAINTING Paint type Paint Shade MOVEMENT Type of Wheels Wheel gauge Direction of Wheels Miscellaneous Accessories Spares Configuration of HV/LV Routine tests to be carried out No Load Loss
Electrolytic Cu 2 no 50x6 mm strip Deg C Deg C 40 90 Deg C Class F. Epoxy Siemens grey RAL 7032 Plain/ Flanged Unidirectional/ Bidirectional Reqd/ Not Reqd Reqd/ Not Reqd degrees Yes/No KW Plain As per site requirement Bidirectional
Contractor J.V.
Client
Consultant J.V.
ENGINEERING & DEVELOPMENT ORGANIZATION of TEHRAN Client Doc. No.: Contractor Doc No.:
Date:7/30/2011
Rev.: 0
Page 5 of 5
No.
11.1 12.0 13.0
Description
Full Load Loss % impedance Degree of protection for enclosure
Unit
KW As per IS
Bidders configuration