CR4 - Thread: Polarity Checking Of 6 Lead 3Ph Induction Motor

Guru Join Date: Oct 2009 Posts : 1505 Good Answers : 110 08/21/2011 8:30 AM

Page 2

1. Question: How to find out Motor Terminal? Answer: i) With a multimeter or continuity tester, you can segregate three sets of windings . Can't you ? ii) Now, assume one set of windings to be, say, winding " U" and also, designate its terminals as assumed " U1 & U2". iii) Take a 9V Cell ; Connect + ve of Battery to the assumed "U1" preferably thro a push- switch and - ve to the assumed " U2". iv) Connect a zero centred galvanometer, to another set of winding , say winding "V" such that the assumed " V1" is connected to the + ve terminal of the galvanometer and the assumed " V2" to the - ve terminal of the meter. v) Now, when the switch is pressed, the zero centred galvanometer would deflect in the positive direction, if the assumed "U1, U2, V1 & V2" are correct. vi) Else, if the deflection is on the negative side in the galvanometer , change your assumptions for either one of the winding (That is may be the assumed U1 can be U2 and the assumed U2 is U1 . Or keep the assumptions for U winding as it is and reverse it for the V winding (that is assumed V1 is V2 and assumed V2 is V1). vii) Repeat this test for applying voltage to other windings and confirm your terminal assumptions. But, in many cases, in star- delta starters, it is not the motor internal winding connections, that would cause stalling, but the external connections. I have authored an article on this, but as it contains diagrams, I am unable to copy & paste here. If you can send me your mail ID thro this forum 's mailbox, I shall send you the article.

Go to Next Good Answer

kvsridhar manindra

Re: Polarity checking of 6 lead 3 ph induction motor


08 /21/2011 11 :27 PM

#4 In reply to #3

Re: Polarity checking of 6 lead 3 ph induction motor


08 /23/2011 7 :51 AM

#7 In reply to #3

electricalexpert65 manindra Raj123


Participant Join Date: Sep 2011 Posts : 1

Re: Polarity checking of 6 lead 3ph induction motor


08/23/2011 8:46 AM

#8 In reply to #7

Re: Polarity checking of 6 lead 3 ph induction motor


08 /24/2011 4 :30 AM

#9 In reply to #8

Re: Polarity checking of 6 lead 3ph induction motor


09 /14/2011 12 :59 PM

# 10 In reply to #3

sir, can u send me CR4 Admin - email address removed From the CR4 Rules: Do not post phone numbers or email addresses. The CR4 Admin will delete all phone numbers and email addresses posted in threads or comments. You can share this information via the CR4 internal messaging system.

Lspraba
Commentator

Re: Polarity Checking Of 6 Lead 3Ph Induction Motor


08 /22/2011 1 :58 AM

#6

Hi , I will give you one more method. First confirm U, V and W windings , by doing continuity test. Then follow the procedure given below.
Join Date: Sep 2008 Location : India Posts : 93 Good Answers : 6

1.Connect V and W windings in series . 2.Connect 110V/230V AC to U winding. In this case let us consider 230V is applied to U winding terminals . 3. Measure the voltage between V and W series circuit. If the meter reads about 460V, then opposite polarities are connected at the junction of V and W winding ( V2 and W 1 or V1 and W 2) 4. If the meter reads about 0V. Then same polarities are connected at the juction of V and W winding (V 1 and W 1 or V2 and W2)