Data sheet

SONOMETERTM1100 Ultrasonic compact energy meter

Description/Application

The SONOMETER1100 is an ultrasonic static compact energy meter especially designed for heating, cooling or combined heating/cooling application in local and district energy systems. The SONOMETER1100 as a compact energy meter consists of the following components: - Ultrasonic flow sensor; - Calculator with integral hardware and software for measuring flow rate, temperature and energy consumption; - Pair of temperature sensors.

MID examination certificate no. : DE-10-MI004-PTB003

Features - 1st. approval in Europe for ultrasonic energy meter with dynamic range of qi/qp 1 : 250 in class 2 (qp 1.5 / 2.5 / 6 / 10 / 15 / 25 / 40 / 60 m/h) - Complete dynamic range: 1 : 1500 - Lithium battery, 230 V AC or 24 V AC mains unit - Battery lifetime 11 years (16 years optional) - Unique free- beam principle - Improved service-friendly energy meter design - Housings with thread and flange (PN 16 / 25) - Can be configured for heating, cooling or combined heating/cooling application - Temperature range: 5 - 130 / 150 C - Overload temperature up to 150 C (qp= 0.6 - 2.5 m3/h) - Swirl-free flow around reflector - Lower pressure loss - Robust stainless steel reflector - Insensitive to dirt - Available in nominal sizes - Measuring accuracy meets the requirements of EN 1434 ( MID) class 2 and 3 - No calming sections necessary in the inlet and/or outlet (standard installation)
qp 0.6 / 1.0 / 1.5 / 2.5 / 3.5 / 6 / 10 / 15 / 25 / 40 / 60 m/h

Special Features - Power save mode - NOWA test capability - Remote reading via M-Bus, L-Bus, RS 232, RS 485, Radio or optical interface - Integrated Radio (868 or 434 Hz), Real Data or Open Metering Standard (OMS) - Individual remote reading (Automatic Meter Reading) with add on modules Plug&Play - 2 communication ports (e.g. M-Bus + M-Bus) - Improved radio performance - Individual tariff functions - History memory for 24 months - Extensive diagnostic displays - IZAR@SET parameterization software on Windows basis guarantees optimum adaptation to the users specific needs

DEN-SMT/PL

VD.SH.J4.02 Danfoss 11/2011

Data Sheet

SONOMETERTM1100 Ultrasonic energy meter

Ordering: The ordering code no. consists of both dummy code and ordering code. Dummy code: 087G6011 Ordering code: AAA BB - C D E F G H P AAA - application energy meter for heating energy meter for cooling 1,2 energy meter for heating/cooling 1
1

L M - NN O 0 1 4 00 AT BA BG CN DK CZ DE GB HR IE IT KZ LV MD PL RO RU CS SK SI TR UA 0 1 2 3 4 O - verification without approval mark, no test reports compliant according to national regulations PTB K 7.2 for cooling compliant to MID. With letter of conformity 1
1

1HE 1CO 1HC

includes potting and special temperature sensors for cooling or heating/cooling application 2 meter without type approval

test reports on request

BB - flow sensor qp 0.6 m/h / 110 mm thread / DN 15 / GB qp 0.6 m/h / 130 mm thread / DN 20 / G1B qp 0.6 m/h / 190 mm thread / DN 20 / G1B qp 1.0 m/h / 110 mm thread / DN 15 / GB qp 1.0 m/h / 130 mm thread / DN 20 / G1B qp 1.0 m/h / 190 mm thread / DN 20 / G1B qp 1.5 m/h / 110 mm thread / DN 15 / GB qp 1.5 m/h / 130 mm thread / DN 20 / G1B qp 1.5 m/h / 190 mm thread / DN 20 / G1B qp 2.5 m/h / 130 mm thread / DN 20 / G1B qp 2.5 m/h / 190 mm thread / DN 20 / G1B qp 3.5 m/h / 260 mm thread / DN 25 / G11/4B qp 6 m/h / 260 mm thread / DN 25 / G11/4B qp 10 m/h / 300 mm thread / DN 40 / G2B qp 0.6 m/h / 190 mm flange DN 201 qp 1.0 m/h / 190 mm flange DN 201 qp 1.5 m/h / 190 mm flange DN 201 qp 2.5 m/h / 190 mm flange DN 201 qp 3.5 m/h / 260 mm flange DN 251 qp 3.5 m/h / 260 mm flange DN 321 qp 6 m/h / 260 mm flange DN 251 qp 6 m/h / 260 mm flange DN 321 qp 10 m/h / 300 mm flange DN 401 qp 15 m/h / 270 mm flange DN 501 qp 25 m/h / 300 mm flange DN 651 qp 40 m/h / 300 mm flange DN 801 qp 60 m/h / 360 mm flange DN 1001
1

1A 1B 1C 1D 1E 1F 1G 1H 1I 1J 1K 1L 1M 1N 2A 2B 2C 2D 2E 2F 2G 2H 2I 2J 2K 2L 2M
only PN 25 possible!

NN - country code Neutral code with docs in English (standard) Austria Bosnia Bulgaria China Denmark Czech Republic Germany United Kingdom Croatia Ireland Italy Kazakhstan Latvia Moldova Poland Romania Russia Serbia Slovak Republic Slovenia Turkey Ukraine

M - connections (sets) without screwing set R x G B screwing set R x G 1 B screwing set R 1 x G 11/4 B screwing set R 1 x G 2 B

screwing sets are packaged in an extra box

C - nominal pressure PN 16 PN 251


1

C D
flange versions must be PN 25

D - cable length between calculator and flow sensor 1.5 m (standard) 3m 5m1 0.2 m 2
1

A B C D

not possible for qp 3.5 m/h and qp to 6 m/h versions 2 max. 90C possible. Only for qp 0.6 - 2.5 versions

L - accessories / pocket 0 without for 5.2 mm temperature sensors (pair1) F brass-pockets, 35 mm, MID 2 G brass-pockets, 52 mm, MID H brass-pockets, 85 mm, MID I brass-pockets, 120 mm, MID 3 stainless steel-pockets, 85 mm, MID 4 stainless steel-pockets, 120 mm, MID 5 stainless steel-pockets, 155 mm, MID 6 stainless steel-pockets, 210 mm, MID

E - installation low temperature high temperature F - power supply battery 3.6 V DC (A-cell) (standard) battery 3.6 V DC (D-cell) 1 mains unit 230 V AC mains unit 24 V AC
1

L H 1 2 3 4
Standard for integrated radio

1 versions with one sensor pocket on request 2 max temperature: 105C temperature sensor pockets are packaged in an extra box

DN 15-32 DN 40-65 DN 80-125 DN 150-200 DN 80-125 DN 150-200 DN 200-250 DN 300

for 6.0 mm temperature sensors (pair) V brass-pockets, 40 mm MID W brass-pockets, 85 mm MID X brass-pockets, 120 mm MID Y stainless steel-pockets, 85 mm MID Z stainless steel-pockets, 120 mm MID 1 stainless steel-pockets, 155 mm MID 2 stainless steel-pockets, 210 mm MID

GH - interface modules modules slot 1 no module in slot 1 Analogue output module (4-20mA)1 Combined module (2 pulse inputs / 1 pulse output) Pulse input module (2 inputs) M-Bus module L-Bus module (use for external radio) RS232 module RS485 module modules slot 2 no module in slot 2 Pulse output module2 Combined module (2 pulse inputs / 1 pulse output)2 Pulse input module (2 inputs)2 M-Bus module2 L-Bus module (use for external radio)2 RS232 module 2 RS485 module 2 P - version of communication without integrated radio (standard) Radio 868 MHz Real Data Radio 434 MHz Real Data Radio 868 MHz Open Metering Standard Radio 434 MHz Open Metering Standard

0 A B C D E F G 0 A B C D E F G

Accessories (1 piece) 3 R ball valve DN 15 - for direct sensor S ball valve DN 20 - for direct sensor T ball valve DN 25 - 1 for direct sensor U adapter for mounting direct sensor R M 10x1

temperature sensor pockets are packaged in an extra box

DN 25-65 DN 80-125 DN 150-200 DN 80-125 DN 150-200 DN 200-250 DN 300

3 not possible for 6.0 mm sensors ball valves packaged in an extra box

1 2 3 4

K - temperature sensor mounting Direct sensor mounting (qp 0.6 - qp 2.5) 1 (standard) Direct sensor mounting (qp 3.5 - qp 15) 1 Pocket sensor mounting (2 free sensors) (qp 0.6 - qp 2.5)2 Pocket sensor mounting (2 free sensors) (qp 3.5 - qp 60) (standard)
2

1 one temperature sensor mounted in the body 2 free sensors, temperature sensor drill in the body closed

1 only one module possible 2 integrated radio is not available

N O P Q T U V W 0 1 2 3 4

J - temperature sensors (pair) Pt 500 / 5.2 mm / 2 m cable, MID and 22.77/08.04 (standard) Pt 500 / 5.2 mm / 3 m cable, MID and 22.77/08.04 Pt 500 / 5.2 mm / 5 m cable, MID and 22.77/08.04 Pt 500 / 5.2 mm / 10 m cable, MID and 22.77/08.04 1 Pt 500 / 6.0 mm / 2 m cable, MID 2 Pt 500 / 6.0 mm / 3 m cable, MID 2 Pt 500 / 6.0 mm / 5 m cable, MID 2 Pt 500 / 6.0 mm / 10 m cable, MID 1, 2
2

1 only available as an accessory not available for Heating/Cooling and Cooling

A B C D E F G H I J K L M

I - energy units kWh (without digit after comma) MWh (with 1 digit after comma) MWh (with 2 digit after comma) MWh (with 3 digit after comma) GJ (with 1 digit after comma) GJ (with 2 digit after comma) GJ (with 3 digit after comma) Gcal (with 1 digit after comma) 1 Gcal (with 2 digit after comma) 1 Gcal (with 3 digit after comma) 1 MBtu (with 1 digit after comma) 1 MBtu (with 2 digit after comma) 1 MBtu (with 3 digit after comma) 1
1

not applicable for MID approved meters

DEN-SMT/PL

VD.SH.J4.02 Danfoss 11/2011

Data Sheet
Ordering continued

SONOMETERTM1100 Ultrasonic energy meter


Modules
Communication Designation M-Bus module L-Bus module (use for external radio) RS232 module RS485 module Analogue output module (4-20mA) Combined module (2 pulse inputs/ 1 pulse output) Pulse input module (2 inputs) Pulse output module (2 outputs) battery 3.6 V DC (A-cell) battery 3.6 V DC (D-cell) mains unit 230 V AC mains unit 24 V AC Code No. 087G6027 087G6035 087G6029 087G6032 087G6034 087G6041 087G6037 087G6039 087G6020 087G6022 087G6024 087G6025

Function

Supply voltage

Accessories Temperature sensors


Temperature sensors (pair) Pt 500 / 5.2 mm / 10 m cable, MID Pt 500 / 6.0 mm / 10 m cable, MID Dimension (IG) G G G 1

pair

Code No. 087G6048 087G6052 Code No. 087G6068 087G6069 087G6070

1
1 Set 12 pcs 12 pcs 12 pcs

Ball valves

Adapter for mounting temperature sensors

Coupling thread

Sensor thread

Set

Code No.

M 10 x 1

32 pcs

087G6076

Tailpieces

Threaded

Dimension (AGR x IG) R x G B R x G 1 B R 1 x G 11/4 B R 1 x G 2 B

Set 1 pc 1 pc 1 pc 1 pc

Code No. 087G6071 087G6072 087G6073 087G6074

Software

The IZAR@SET parameterization software on windows basis is a convenient tool for handling the energy meter. The IZAR@SET software is available on web site www.hydrometer.de.

It is used for: - commissioning - reading out measured values - printing out energy meter logs - energy meter configuration - application analysis - print the meter protocol

VD.SH.J4.02 Danfoss 11/2011

DEN-SMT/PL

Data Sheet
Technical data
Nominal Flow rate ranges Maximum Minimum Starting Nominal Diameter Connection Tailpiece Operating Maximum pressure
Flow sensor heating Temp. range

SONOMETERTM1100 Ultrasonic energy meter

qp m3/h qs m3/h qi l/h l/h DN mm AGZ AGV PN bar C 15 G B R

0.6 1.2 6 1 20 G 1B R 16 / 25 FL 25 15 G B R

1.0 / 1.5 2/3 10 / 6 2.5 20 G 1B R 16 / 25 5...130 5...50 5...105 FL 25

2.5 5 10 4 20 G 1B R 16 / 25 FL 25 25 G 11/4B R1 16 / 25

3.5 7 35 7 32 FL 25 25 G 11/4B R1 16 / 25

6 12 24 7 32 FL 25

10 20 401) / 100 20 40 G 2B R 1 25 5...150 5...50 5...105 FL -

15 30 601) / 150 40 50 FL 25

25 50 1001) / 150 50 65 FL 25

40 80 160 80 80 FL 25

60 120 2401) /6002)/ 1200 120 100 FL 25

cooling heat. /cool.

Medium Pressure loss At qp p mbar mm 110 85 130 190 110 36 / 75 130 190 130 100 190

circulation water (pH-value: 7 - 10) 44 260 128 260 95 300 80 270 75 300 80 300 75 360

Overall length

Temperature Type sensors Sensor current Measuring cycle mA T s

Pt 500 with 2-wire leads Pt 500 peak < 2; rms < 0.012 Mains unit supply: 2 A-cell battery: 16; D-cell battery: 4 177

Max. max temperature K difference Input Min. min temperature K difference Starting temperature K difference Absolute temperature measuring C range Supply voltage Operating voltage Ambient class Protection class Basic features Storage and Transport temperature Type Measuring process Display Units Display indication Total values Values displayed
1) 2)

0.125

1...180

UN

3.6 V DC (Lithium-battery) / 230 V AC / 24 V AC EN 1434 class E1 + M1 calculator: IP 54 flow sensor: IP 54 (heating) / IP 68 (cooling) -40...+50 Static energy meter to EN 1434 (MID) Ultrasonic volume measurement LCD, 8-digit MWh - kWh - GJ - Gcal - MBtu - gal - GMP - C - F - m - m/h 99 999 999 - 9999 999.9 - 999 999.99 - 99 999.999 Power - energy - flow rate - temperature - volume

Only for horizontal installation Only in rising or falling pipes or tilted installation

Pressure loss graph

Measuring accuracy to EN 1434 Class 2

DEN-SMT/PL

VD.SH.J4.02 Danfoss 11/2011

Data Sheet
Design and function

SONOMETERTM1100 Ultrasonic energy meter


The SONOMETER1100 as a compact energy meter consists of the following components: - Ultrasonic flow sensor; - Calculator with integral hardware and software for measuring flow rate, temperature and energy consumption; - Pair of temperature sensors. The calculator contains all the necessary circuits for recording the flow rate and temperature and for calculating, logging and displaying the data. The calculator housing can be mounted directly on the flow sensor or on the wall. The energy meter can be conveniently read from a single-line 8-digit display with units and symbols. A push-button provides user-friendly control of the various display loops. All failures and faults are recorded automatically and shown on the LC display. To protect the reading data, all the relevant data are saved in a non-volatile memory (EEPROM). This memory saves the measured values, device parameters and types of error at regular intervals. Ultrasonic flow sensor The ultrasonic technology of the flow sensor permits very high measuring accuracy and can be used in the supply or return line. The flow sensor meets the requirements of EN 1434 / class 2 and 3. The standard cable length between the calculator and the flow sensor is 1.5 m (optional 5 m). Supply voltage: - Lithium battery 3.6 V DC A-cell (11 years typical lifetime) - Lithium battery 3.6 V DC D-cell (16 years typical lifetime) - Mains unit 230 V AC or 24 V AC with changeable backup battery Temperature Sensors Pairs of Pt 500 temperature sensors with 2-wire leads are used. Integrated Radio Integrated Radio is an interface for communication with radio receiver. - Frequency band: 868 or 434 MHz - Type of radio telegram: Real Data or Open Metering Standard (OMS) - Transmission data updating: Online - no time delay between value measurement and data transmission - Data transmission: Unidirectional - Sending interval: 12...20 s; depending on length of telegram (duty cycle) Interfaces - Optical: ZVEI interface as standard, for communication and testing, M-Bus protocol. - M-Bus: Configurable telegram, according to EN1434-3. Data reading and parametrization are via two wires with polarity reversal protection. - L-Bus: Adapter for external radio module; configurable telegram, according to EN1434-3. Data reading and parametrization are via two wires with polarity reversal protection. M-Bus protocol. - RS232: Serial interface for communication with external devices. A special data cable is required. M-Bus protocol. - RS485: Serial interface for communication with external devices. Power supply with 12V 5V. M-Bus protocol. - Pulse output: Module with 2 Open Collector pulse outputs (potential-free), 4 Hz (pulse width 125ms), 100 Hz (pulse width 5ms), ratio: pulse duration / pulse break ~ 1:1. Configurable via IZAR@SET software. Possible pulse output values are Energy, Volume, Tariff energy 1, Tariff energy 2, Tariff condition 1, Tariff condition 2, Energy error and Volume error. - Pulse input: Module with 2 pulse inputs, max. 20 Hz with minimum pulse duration of 10 msec, input resistance 2.2 M Ohms, terminal voltage 3V DC, cable length up to maximum 10m. The pulse value and the unit is configurable for energy, water, gas or electrical meter by IZAR@SET. Data can be transferred remotely. Also two accounting days are available for both inputs. - Combined pulse input / output: Module with 2 pulse inputs and 1 pulse output. Configurable via IZAR@SET software. - Analogue output: Module for 4...20 mA with 2 programmable passive outputs, programmable value in case of error. Output values can be power, flow rate, temperatures. Configurable via IZAR@SET software. Slot 1 - Analogue output module (4-20mA) - Combined module (2 pulse inputs / 1 pulse output) - Pulse input module (2 inputs) - M-Bus module - L-Bus module (use for external radio) - RS232 module - RS485 module Slot 2 - Pulse output module - Combined module (2 pulse inputs / 1 pulse output) - Pulse input module (2 inputs) - M-Bus module - L-Bus module (use for external radio) - RS232 module - RS485 module Event Memory Events such as changes and faults are stored in a nonvolatile memory with a capacity of up to 127 entries. The following events are recorded: - Checksum error - Temperature measurement error - Ultrasonic operating time measurement errors - Start and end of test mode - Changing of the main configuration Monthly Memory The SONOMETER1100 has a history memory of 24 months. The following values are stored in the EEPROM on the programmable interval (daily, weekly, monthly): - Date/ Time - Cumulated energy - Tariff energy 1 - Tariff energy 2 - Tariff definition 1 - Tariff definition 2 - Cumulated volume - Error hour counter - Value of max. flow - Time max. flow - Date max. flow - Value of max. power - Time max. power - Date max. power - Pulse input counter 1 - Pulse input counter 2 - Pulse 1 definition - Pulse 2 definition - Operating days - Max. forward temperature - Time max. forward temperature - Date max. forward temperature - Max. return temperature - Time max. return temperature - Date max. return temperature

VD.SH.J4.02 Danfoss 11/2011

DEN-SMT/PL

Data Sheet
Design and function, continued

SONOMETERTM1100 Ultrasonic energy meter


Log Memory The large two log memory blocks are used to store consumption values. The storage frequency can be selected from various storage intervals (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, 60 minutes or the default setting of 24 hours, Day in the month, Day of the week, (1024 seconds), 15th or end of month). Extract of possible log memory settings
Memory Storage Date block size Values block interval example area 1 1 hour Error status, overload time temperature, 16 byte 24 overload time flow rate, supply area 2 16 byte hours temperature, return temperature, date area 1 1 hour and time, energy, tariff energy 1, tariff 8 byte energy 2, tariff definition 1, tariff definition 24 area 2 2, volume, error day counter 8 byte hours Number of data records 556 299 1113 599 Recording period 23 days 299 days 46 days 599 days

The data saved in the log memory can be used for the following analyses: - Reading the calculator on a certain day. Example: If the day for reading is 01.10, the calculator reading is displayed for the period from 01.10 of the previous year to 30.09 of the current year. - Comparison of the last consumption period with the preceding period

Max. Actual Values Memories The calculator creates maximum values for power, flow rate and temperatures based on consumption time, which are stored in the EEPROM. The integration intervals are adjustable to 6, 15, 30 or 60 minutes, 24 hours (and 1024 seconds). Default setting is 60 minutes. Tariff Function The calculator offers four optional tariff memories for monitoring plant load states for limit tariffs. Extensive tariff conditions make it possible to adapt the energy meter individually to the required customer-specific applications. The following limit types are possible: (This example applies to the display with 3 decimal places)
Type T TR TF P Q Z LIMIT LIMIT resolution 1 ... 255 C 1 C 1 ... 255 C 1 C 1 ... 255 kW 1 kW 100 ... 25 500 l/h 100 l/h 15 minutes

Display Control The readings are displayed on the calculator by a 8-digit LCD with units and symbols. Loop Structure The SONOMETER1100 display has six loops. Some display windows consist of two (to maximum seven) displays that are shown alternately at 4-second intervals. Some pictures in loops or a complete loop can be deactivated separately.

For quick visual guidance, the loops in the display are numbered from 1 to 6. The main loop with the current data, e.g. for energy, volume and flow rate is programmed as default setting.

According to above table the energy or the time (in hours) how long the tariff condition is fulfilled will be stored in the tariff memories.

DEN-SMT/PL

VD.SH.J4.02 Danfoss 11/2011

Data Sheet
Overview of Loops

SONOMETERTM1100 Ultrasonic energy meter

VD.SH.J4.02 Danfoss 11/2011

DEN-SMT/PL

Data Sheet
Informative Displays (Standard)
Loop Sequence 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.9 1.10 Sequence 2.1 2.2 2.3 2 Accounting date loop 2.4 2.5 2.6 2.7 Loop 2.8 Sequence 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 3.10 Loop 4 Pulse input loop [off] = not active Sequence 4.1 4.2

SONOMETERTM1100 Ultrasonic energy meter

1 Main loop

Loop

Window 1 Accumulated energy Volume Flow Power Forward / - return temperature Difference temperature Operating days Error status Display test Window 1 Accounting date 1 date Next accounting date 1 date Previous accounting date 1 date ,Accd 1' Accounting date 2 date Next accounting date 2 date Previous accounting date 2 date ,Accd 2' Window 1 Current date ,SEC_Adr' ,Pri_Adr 1' ,Pri_Adr 2' Installation position ,Port 1' ,Port 2' Status integrated radio No. of error hours ,F01-001' (software version) Window 1 ,In1' ,In2'

Window 2

Window 3

Window 4

Window 2 Accounting date 1 energy Next accounting date 1 energy Previous accounting date 1 energy Date of next accounting date 1 Accounting date 2 energy Next accounting date 2 energy Previous accounting date 2 energy Date of next accounting date 2 Window 2 Secondary address Primary address 1 Primary address 2 No. of the mounted module at port 1 No. of the mounted module at port 2 (Sequence will be shown only in meters with integrated radio) Checksum Window 2 Accumulated values pulse input 1 Accumulated values pulse input 2

Window 3 [off] Accounting date 1 volume Next accounting date 1 volume Previous accounting date 1 volume Accounting date 2 volume Next accounting date 2 volume Previous accounting date 2 volume Window 3

Window 4 ,Accd 1A' ,Accd 1L' ,Accd 1' ,Accd 2A' ,Accd 2L' ,Accd 2' Window 4

3 Info loop

Window 3 ,PPI' pulse value 1 ,PPI' pulse value 2

Window 4

DEN-SMT/PL

VD.SH.J4.02 Danfoss 11/2011

Data Sheet
Loop 5 Tariff loop Loop Sequence

SONOMETERTM1100 Ultrasonic energy meter


Window 1 Window 2 Window 3 Window 4 Window 5 Window 6 Window 7

The tariff loop is switched off as a standard at the heat meter or meter for cooling. Sequence 6.1 6.2 6.3 ... 6.24 Window 1 ,LOG ,LOG ,LOG ,LOG Window 2 date last month date month - 1 date month - 2 ... date month - 23 energy volume Window 3 [off] Window 4 [off] Window 5 energy energy energy Window 6 volume volume volume Window 7

6 Monthly value loop [off] = not active

Simple operation A push-button mounted on the front of the calculator is used to switch to the various displays. The button can be pressed for a short or long time. A short press of the button ( < 3 seconds) switches to the next display within a loop and a long press ( > 3 seconds) switches to the next display loop. The Energy window (sequence 1.1) in the main loop is the basic display.

The calculator switches automatically to power save mode if the button is not pressed for approx. 4 minutes and returns to the basic display when the button is pressed again. The loop settings can be programmed to suit the customers individual requirements using the IZAR@SET software.

VD.SH.J4.02 Danfoss 11/2011

DEN-SMT/PL

Data Sheet
Mounting

SONOMETERTM1100 Ultrasonic energy meter


Depending on the design, the energy meter is installed either in the low temperature or high temperature line as indicated on the type plate. The energy meter is to be installed so that the direction of flow corresponds to the direction of the arrow on the flow sensor. Ensure that the flow sensor is always filled with liquid on completion of installation. Straight inlet/outlet pipes (calming sections) are not required for the flow sensor. The energy meter can be installed in both horizontal and vertical pipe sections, but every time so that air bubbles cannot collect in the flow sensor. For low flow we recommend to mount the flow sensor tilted 90 into the pipe. Make sure the energy meter is installed sufficiently far away from possible sources of electromagnetic interference (switches, electric motors, fluorescent lamps, etc.). For cooling application and for medium temperatures more than 90 C, the calculator must be mounted on the wall at a sufficient distance away from heat sources using the holder supplied. It is recommended that stop valves be fitted before and after the energy meter to simplify dismantling the energy meter. The energy meter should be installed in a convenient position for service and operating personnel.

For the further information pls. refer to the SONOMETER1100s instructions.

DEN-SMT/PL

VD.SH.J4.02 Danfoss 11/2011

10

Data Sheet
Dimensions

SONOMETERTM1100 Ultrasonic energy meter

L2

R
AGV AGZ

L L1

L1 L1

Nominal size L [mm] L1 [mm] L2 [mm] B [mm] R [mm] H [mm] h [mm] AGZ AGV D [mm] d [mm] F [mm] K [mm] Weight [kg] 82 14.5 GB DN 15 R 0.76 110 190

qp = 0.6 m/h 130 230 190 290 190 190

qp = 1.0 / 1.5 m/h 110 190 130 230 150 100 54 190 290 190 190

qp = 2.5 m/h 130 230 190 290 190 190

qp = 3.5 m/h 260 380 260 260 260 260 150 100 54

qp = 6 m/h 260 380 260 260 260 260

qp = 10 m/h qp = 15 m/h qp = 25 m/h qp = 40 m/h qp = 60 m/h 300 440 300 300 270 270 300 300 150 100 54 300 300 360 360

84 18 G1B DN 20 R 0.85

84 18 G1B DN 20 R -

84 47.5 FL DN 20 105 14 95 75

82 14.5 GB DN 15 R 0.76

84 18 G1B DN 20 R -

84 18 G1B DN 20 R -

84 47.5 FL DN 20 105 14 95 75

84 18

84 18

84 47.5

88.5 23

88.5 50 FL DN 25 114 14 100 85 3.5

88.5 62.5 FL DN 32 139 18 125 100 4.8

88.5 23 G11/4B DN 25 R1 1.5

88.5 50 FL DN 25 114 14 100 85 3.5

88.5 62.5 FL DN 32 139 18 125 100 4.8

94 33 G2B

94 39 FL DN 40 148 18 138 110 6.4

99 73.5 FL DN 50 163 18 147 125 7.0

106.5 85 FL DN 65 184 18 170 145 8.9

DN

K
d
114 92.5 FL DN 80 200 19 185 160 10.9 119 108 FL DN 100 235 22 216 190 16.4 G1B G1B DN DN 20 20 R R FL G11/4B DN DN 20 25 105 14 95 75 R1 1.5 R1 3.1 0.96 2.75 0.85 0.96 2.75 0.85 0.96 2.75

11

VD.SH.J4.02 Danfoss 11/2011

DEN-SMT/PL

Data Sheet
Dimensions, continued Temperature sensors

SONOMETERTM1100 Ultrasonic energy meter

Designation Direct mounted

Type Pt 500

Dimension D (mm) 5.2

L (mm) 45

5.2 Pocket sensor Pt 500 6.0

45

50

Sensor pockets
Type Sensor dimension Brass (mm) 5.2 6.0 Stainless steel 6.0

L1 (mm) Length L (mm)

47

60

93

128

47

92

128

98

133

168

223

35

52

85

120

40

85

120

85

120

155

210

12

VD.SH.J4.02

Produced by Danfoss A/S 11/2011