Compressor Air Requirement PROPOSED COMPRESSOR SIZEPressure OPTION 1 Assume Pipe Size Pipe Length Equivalent length of 90 bends Total Pipe Length Maximum Allowable pressure Drop 40 mm 70 m 4no x 6.2 24.8m 70+24.8 =94.8m 1psi 143.29cfm (As per Annexure 1) 228 cfm
Above Pipe Size is not sufficient for this Application so considering next Pipe Size 63mm. OPTION 2 Assume Pipe Size Pipe Length Equivalent length of 90 bends Total Pipe Length 63 mm 70 m 4no x 6.2 24.8m 70+24.8 =94.8m 462.50cfm 1psi (As per Annexure 2)
Maximum Allowable CFM for 63mm PipePressure loss for 63mm pipe at 462.50cfm ) PROPOSED Air PIPING SIZE
Project: Intel. CONSIDERING COOLING WATER PIPE SIZE= 25 mm FRICTIONAL LOSS (Per Meter Length of Pipe in bars) Pf = 6.05 x (10)5 x (Q) 1.85 1.85 x (D) 4.87 Q C D Pf = 60 Lpm = 120(Constant for GI Pipe) = Mean bore of the Pipe in mm = 6.05 x (10)5 x (60)1.85 (120)1.85 x (25)4.87 = 0.02611 bar/m Total Length of the Pipe - 24m 24 x 0.02611 .6267 bar CONSIDERING COOLING WATER PIPE SIZE= 32 mm FRICTIONAL LOSS (Per Meter Length of Pipe in bars) Pf = 6.05 x (10)5 x (Q) 1.85 1.85 x (D) 4.87 Q C D Pf = 60 Lpm = 120(Constant for GI Pipe) = Mean bore of the Pipe in mm = 6.05 x (10)5 x (60)1.85 (120)1.85 x (32)4.87 = 0.007848 bar/m Total Length of the Pipe - 24m 24 x 0.007848 .188bar PROPOSED COOLING WATER PIPING SIZE = 32mm Last Modified: 29.09.10 Rev: R0 2 POTENTIALSERVICE CONSULTANTS (P) Ltd.,
V = V =