Description Group-Mounted Feeder Sections Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Features, Benets and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Standards and Certications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Integrated Facility Switchboards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Compartmentalized Feeder Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Instant Service Switchboards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Roll-up Generator Termination Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 15-2 15-2 15-2 15-2 15-4 15-5 15-6 15-7 15-10

15

Pow-R-Line C Group-Mounted Distribution Switchboard

CA08101001E

For more information visit: www.eaton.com

15-2

Switchboards Pow-R-Line C Switchboards


February 2007

Group-Mounted Feeder Sections

Product Description
Eatons Cutler-Hammer Pow-R-Line C Distribution Switchboards combine a space-saving design with modular construction and increased systems rating to provide economical and dependable electrical system distribution and protection.

Features, Benets and Functions


Standards and Certications

Pow-R-Line C Group-Mounted Distribution Switchboard

Application Description

15

Refer to the Cutler-Hammer Consulting Application Guide, 13th Edition.

6000 amperes maximum main bus rating. 600 Vac and below. Front or rear accessible. Type 1 or Type 3R enclosures. ANSI-61 gray powder coat paint nish. The IQ family of microprocessorbased metering and monitoring devices. Utility metering provisions. Transient Voltage Surge Suppression (TVSS). Ground Fault protection on mains and distribution devices. Busway and transformer connections. Complete protective device accessory capability. 65 kAIC standard bus bracing; optional 100 or 200 kAIC. Standard tin-plated aluminum bus; optional copper- or silver-plated copper bus. Standard bus ampacities based on UL heat test ratings. Optional density rated bus systems are also available.

Meets NEMA Standard PB-2 and UL 891. Seismically qualied.

Main Devices

DS/DSL air power circuit breakers, 800 4000 amperes, xed or drawout. Magnum DS power circuit breakers, 800 5000 amperes, xed or drawout. Molded case circuit breakers, 400 2500 amperes, xed mounted. Bolted pressure switches, 800 5000 amperes. FDPW fusible switches, 400 1200 amperes.

Group-Mounted Distribution Devices


Molded case circuit breakers, 15 1200 amperes. FDPW fusible switches, 30 1200 amperes.

For complete application and pricing information, contact your local Eaton sales ofce. For more information visit: www.eaton.com CA08101001E

Switchboards Pow-R-Line C Switchboards


February 2007

15-3

Group-Mounted Feeder Sections

Product Description
Eatons Cutler-Hammer commercial metering switchboards provide electrical system distribution and metering for shopping centers, ofce buildings and other commercial multimetering applications. Using standard Pow-R-Line C construction and features, these switchboards incorporate metering sections with tenant feeder circuits using meter sockets to meet local utility or customer requirements. All meter sockets and associated feeder devices are completely factory prewired and shipped ready for the installation of the meters.

Service
120/240 volt, 1-phase, 3-wire. 240/120, 208Y/120 or 480Y/277 volt, 3-phase, 4-wire.

Application Description

Type WWCMS

Main Bus Rating

400 4000 amperes.

For EUSERC serviced areas. The selfcontained meter sockets include a test bypass/disconnect block per EUSERC requirements, and are arranged, typically, for hot sequence metering.

Service Section
Main circuit breaker, 400 4000 amperes. Main fusible switch, 400 4000 amperes. Main lugs only, 400 4000 amperes.

Metering Sections

Tenant Main Disconnects and Meter Sockets (200 amperes maximum self-contained metered circuits). Hot sequence metering circuits. Cold sequence metering circuits (WCMS only). Optional rear barriered wireways or load side pull sections for cable exit requirements. Sections for metered circuits larger than 200 amperes available with 400 amperes continuous rated self-contained sockets or with CT compartment and transformer rated socket in combination with disconnect.

Socket and Test Block Assembly

Type WCMS

For other than EUSERC serviced areas. Self-contained meter sockets are provided with manual lever bypass and can be arranged for either hot or cold sequence metering.

15

WWCMS

Socket with Manual Lever Bypass

Refer to the Cutler-Hammer Consulting Application Guide, 13th Edition.

Standards and Certications


UL 891. NEMA PB-2. Seismically qualied.

WCMS

CA08101001E

For more information visit: www.eaton.com

15-4

Switchboards Pow-R-Line C Switchboards


February 2007

Group-Mounted Feeder Sections

Product Specications
Pow-R-Line designates a family of distribution switchboards incorporating new design concepts that t the ever-increasing need for applications on high short-circuit systems, while retaining maximum standardization, safety and convenience throughout the line.

Space Only for Future Devices Group Mounted Construction


Where space only for future circuit protective devices is required, the proper space and a blank ller plate will be supplied. Connections and mounting hardware are not included.

Provision for Busway Entrance and Exit


Busway connections to switchboard sections include cutout and drilling in the top of the switchboard with riser connections from the switchboard device or bus, up to the point where the bus duct enters the switchboard. No connections are furnished external to the switchboard. In all transactions involving busway attached to switchboards, it is essential that information regarding orientation of the busway with respect to the front of the switchboard be supplied to the coordinating assembly plant. On Pow-R-Line switchboards, solid bus bar is used to connect the bus duct to the individually mounted main device, main or sub-main switchboard bus, or vertical main bus of panel mounted circuit protective device panels. Busway fed by group mounted branch devices are cable connected. Aluminum riser connections are standard. Copper- or silver-plated copper is available as a modication.

Provision for Future Devices


Where provisions for future circuit protective devices are required, space for the device, corresponding vertical bus, device connectors and the necessary mounting hardware will be supplied.

Front Accessibility
Front accessibility switchboards align at the rear, enabling them to be placed against a wall (Cutler-Hammer Type Pow-R-Line C front accessible). If the main section is deeper than others, due to physical size of the main device, the necessary off-set in line-up will occur in front, and the main section will be accessible from the side as well as from the front. Standard front accessible switchboards will align at the front and rear.

Bus Bar System


Standard bus in the switchboards is tin-plated aluminum. Copper and silver-plated copper are also available. Main bus and sub-main buses meet UL and NEMA standards for temperature rise on all Pow-R-Line switchboards. Special bus densities are available.

Rear Accessibility
Rear accessible switchboards align at the front and the rear. Bus maintenance and cable entry and exit require rear access. There are two types of rear accessible switchboards. Both types utilize the same incoming utility and/or main structures. The rst type utilizes group mounted feeder devices with panel construction (CutlerHammer Type Pow-R-Line C rear accessible). The second type utilizes individually compartmentalized feeder devices with load side insulated bus bar extensions (Cutler-Hammer Type Pow-R-Line i).

Overcurrent Devices
To properly select and size overcurrent devices for use in a switchboard, the allowable temperature rise must be taken into account as to its effect on the tripping characteristics of the devices in question. Accordingly, Article 220-4(a) of the NEC requires overcurrent devices to be rated not less than 125% of the continuous load they are protecting. To comply with this, an 80% derating factor must be used with all overcurrent devices such as molded case breakers and FDPW fusible switches unless they are tested and approved for application at 100% of the rating.

Transitions
Transition structures are required for connecting switchboards to the secondary of power center transformer (dry or uid lled), motor control centers, and for other special switchboard congurations such as L or U shaped lineups. In some application, an extra structure complete with connections is required; in others, where switchboard depth and space permit, only the connection conductors are required. (Refer to factory for these applications.)

15

Standard Switchboard Height


Standard Pow-R-Line switchboard height is 90 inches (2286 mm).

Group Mounting
Group mounted circuit protective devices are an assembly of units mounted on a panelboard type base (panelboard construction). Units may be molded case breakers, or FDPW fusible switches. Circuit protective devices are accessible from the front. A main molded case breaker or main FDPW fusible switch, within the sizes listed for panelboard design, can be included in the panel-mounted assembly in lieu of a separate, individually mounted unit.

Short Circuit Rating


Standard bus and connectors on all switchboards are rated for use on systems capable of producing up to 65,000 amperes rms symmetrical short circuit current at the incoming terminals. Increased bus short circuit ratings equal to that of connected switchboard devices, up to 200,000 amperes rms symmetrical, are available in most Pow-R-Line switchboards when approved main devices are installed. Contact Eaton for more information. UL labeled switchboard sections are marked with their applicable short-circuit rating.
For complete application and pricing information, contact your local Eaton sales ofce. For more information visit: www.eaton.com CA08101001E

Switchboards Integrated Facility Switchboards


February 2007

15-5

Product Description

Product Description
Cutler-Hammer Integrated Facility Switchboards by Eaton Corporation utilize the modular Pow-R-Line C group mounted switchboard design to integrate traditionally separate electrical distribution and control equipment into a single space-saving factory assembled and connected package. The service entrance equipment can be integrated with multiple lighting and appliance branch panelboards into a compact front accessible group mounted switchboard. Where multiple panelboards are utilized in the same electrical room as a conventional distribution switchboard or power panelboards, the integrated design will signicantly reduce equipment space requirements, as well as, reducing installation time and costs. Other associated equipment can also be integrated into the assembly, including dry type distribution transformers, time clock space, lighting control, electronic controls, surge suppression, metering and energy monitoring devices. Depending upon the application, other user-dened equipment such as a subsystem control package may also be incorporated.

Factory Interconnections
Most sub-panels are fed from the main distribution panel feeder circuit breakers utilizing copper cable sized per the NEC and UL.

Space Savings
The space-saving switchboard installation provides additional usable oor space. For example: Retail Stores. . . . . . Floor space for sales Ofces. . . . . . Additional storage, cubicle Health Care. . . . . . . Additional work area Retrots . . . .Ability to t existing rooms

Integrated Facility Switchboard

Features, Benets and Functions


Front Accessibility
Integrated Switchboards are front accessible and align at the rear, enabling them to be placed against a wall. Most switchboards align at the front and the rear. If the main section is deeper than others, due to physical size of the main device, the necessary off-set in line up will occur in front, and the main section will be accessible from the side as well as from the front.

Site Construction Savings


Timely installation of the electrical system is typically a key element on the critical path for any project. Along with the time to install the equipment, other expenses include the time to handle all of the loose pieces of equipment arriving on a job site and ensuring it reaches the proper trades person. With Eatons Cutler-Hammer Integrated Switchboards, one piece of equipment is typically shipped to a job site virtually eliminating these issues. The equipment may also be used for temporary power on job sites further reducing construction expenses and times.

Standard Switchboard Height


Switchboard height is 90 inches (2286 mm). A limited offering of 78 inch (1981.2 mm) high equipment is available. Consult the factory for specic applications.

15

Application Description
Cutler-Hammer Integrated Switchboards are designed to meet specic needs for:

Retail chain stores. Commercial ofces. High rise ofces. Correctional facilities. Agricultural facilities. Industrial facilities. Hospitals/healthcare facilities. Others.

Switchboard Shipping Splits


The sections can be shipped as specied by the customer to meet specic requirements. For retrot applications, single-piece switchboard structures can be shipped to facilitate movement through limited access doorways, etc.

Whether the application is a multisite prototype or single application, integrated switchboards offer time and space saving features. For complete application description, refer to the Cutler-Hammer Consulting Application Guide, 13th Edition.

Standards and Certications


Meets NEMA Standard PB-2 and UL 891. Panelboards mounted inside the sections meet NEMA PB-1 and UL 67. Other equipment is UL listed as applicable and appropriate.
CA08101001E

Traditionally Mounted Equipment

Figure 15-1. Construction Savings

For complete application and pricing information, contact your local Eaton sales ofce. For more information visit: www.eaton.com

15-6

Switchboards Compartmentalized Feeder Sections


February 2007

Pow-R-Line i

Product Description
Eatons Cutler-Hammer Pow-R-Line i Switchboards are engineered in a new compartmentalized design for applications where a greater degree of safety is required. A wide variety of congurations is possible including utility metering, customer metering, main devices, branch devices, accessories and enclosures. Signicant safety features include:

Space-Saving Ground Fault Test Panels


Pow-R-Line i Switchboards can accommodate either integral or zero sequence types of ground fault protection. Depending on the specic application, a test panel can be mounted in the circuit breaker compartment which may eliminate the need for an auxiliary structure.

Fusible Switches
Front View Fusible Units

Individual compartments for branch devices glass polyester for circuit breakers and steel for fusible switches. These compartments help eliminate possible contact with the main bus and reduce fault propagation. Three-section construction with each section barriered from the other. Device Section. Each device is mounted in its own compartment. Bus Bar Section. Contains both horizontal and vertical buses. Rear Cable Compartment. Completely isolated from the bus bars.

Features, Benets and Functions


Main devices are available from 400 to 4000 amperes and can include Molded Case Circuit Breakers, SPB Systems Pow-R-Breakers, DS or DSL Low Voltage Air Circuit Breakers, Magnum DS Circuit Breakers, FDPW fusible switches or bolted pressure switches. Main buses are rated up to 6000 amperes. Branch circuit breakers range from 150 to 1200 ampere frames. When Series C Circuit Breakers are used, higher ratings and increased series ratings will be achieved. Branch fusible switches are available from 100 to 1200 amperes. Interrupting capacities up to 200,000 amperes are UL listed and the bus bar system may be braced from a standard 65,000 amperes up to a maximum 200,000 amperes. Pow-R-Line i Switchboards are UL listed and meet all applicable requirements of NEMA and NEC. They are rear accessible and front and rear aligned. Both Type 1 and Type 3R enclosures are available.

Pow-R-Line i Switchboards have been designed to accommodate fusible switches. Safety is provided by steel compartments that insulate each horizontally mounted switch from the vertical and main buses. As with switchboards utilizing circuit breakers, insulated copper runbacks carry power into the spacious, glass polyester barriered rear cable compartment.

UL Listed Shunt Trip and Fusible Switches


Shunt trip attachments for use with ground fault protection devices can be installed on 400 to 1200 ampere Type FDPW fusible switches. Both are UL listed when the shunt trip is factory installed.

15

Insulated copper runback. Power is taken from the protective device by the insulated copper runback through a standard full height glass polyester barrier to the rear cable compartment. This design virtually eliminates the possibility of accidental contact with the main buses during installation or maintenance.

High Durability Finish


A baked-on polyester powder coating system protects all structural steel parts. It provides excellent mechanical strength and resistance to chalking normally caused by the suns ultraviolet rays and meets the salt spray requirements of ASTM B-117.

Pow-R-Line i Quality Assurance


Final testing helps ensure that each Pow-R-Line i Switchboard performs in accordance with UL standards and customer specications. Each assembly is shipped with a Switchboard Verication Report that documents completion of every inspection and test.

Integrated Monitoring Protection and Control Communications Systems


The capabilities of distribution and control assemblies can be expanded by tying together multiple devices in electrical distribution systems. From a central location (on-site or off-site), an operator uses a personal computer (master control unit) to monitor, control and communicate with compatible devices on a distribution system. These microprocessor-based devices, designed and built by Eaton, perform monitoring, protection and control functions.

Provisions for the Future


Future expansion provisions include line side connectors, load side runbacks, terminals, and glass polyester compartments and covers (for circuit breakers). Space only for both circuit breakers and fusible switches is also available.

Front View Circuit Breakers

Application Description

Refer to the Cutler-Hammer Consulting Application Guide, 13th Edition.

Standards and Certications

For complete application and pricing information, contact your local Eaton sales ofce.

Meets NEMA Standard PB-2 and UL 891. Seismically qualied.


For more information visit: www.eaton.com CA08101001E

Switchboards Instant Service Switchboards


February 2007

15-7

Product Description

Product Description
Eatons Cutler-Hammer Instant Service Switchboards are designed as stocked units to provide fast delivery to match the needs of the construction market. Suitable for use as service entrance equipment, they combine utility metering provisions with a fused main switch in a single compact section that can also include a distribution panel for feeder and branch circuit breakers. Typical applications for these versatile switchboards include small ofce buildings and factories, stores, supermarkets and shopping centers.

Application Description

120/240 Vac, 1-phase 3-wire. 208Y/120 volt or 240/120 Vac, 3-phase 4-wire. 480Y/277 Vac, 3-phase 4-wire.

Interrupting Ratings (Series Rating)

65,000 rms symmetrical amperes at 240 Vac, using Types BAB and ED branch circuit breakers. 65,000 rms symmetrical amperes at 480Y/277 Vac, using Types GHB and FD branch circuit breakers.

Distribution panels can be included for 240 Vac maximum (1-phase 3-wire or 3-phase 4-wire) or for 480Y/277 Vac (3-phase 4-wire). The 240 volt panels have provisions for four Type ED 225 ampere frame circuit breakers and 24 poles of Type BAB 100 ampere frame circuit breakers. The 480Y/277 volt panel has provisions for four Type FD 225 ampere frame circuit breakers and 24 poles of Type GHB 100 ampere frame circuit breakers. The bolt-on type circuit breakers are ordered separately. For applications that require the load circuit conductors to exit at the top, a loadside wireway compartment is available that bolts to the service section. Standard switchboards include two 15-inch (381.0 mm) high meter compartment doors, one with meter socket provisions and one blank. For other arrangements, accessory units are available. Check utility requirements.

Features, Benets and Functions


These switchboards are available in either indoor or outdoor enclosures manufactured of code-gauge steel with a durable light gray nish. All units are completely enclosed with front, rear and side covers. Outdoor units include a front hinged door. The service section includes:

Standards and Certications


Eatons Cutler-Hammer Instant Service Switchboards are listed by Underwriters Laboratories and comply with all applicable industry standards. These switchboards meet EUSERC standards as well as other local utility codes.

Type 1 Indoor

Main lugs mounted at the top (two #4 600 kcmil per phase) for overhead feed or for use with an underground pull section. A sealable metering and CT compartment with bussing for utility bar type CTs and two 15-inch (381.0 mm) high meter compartment doors one with provisions for meter socket and test block, one blank. (Meter socket is ordered separately.) A 400 or 600 ampere T-Type fused main switch with either load lugs (same as main lugs) or with connections to a factory installed distribution panel. Underground pull sections are available with lug landing kits providing studs for incoming cables per EUSERC standards and two #4 600 kcmil lugs per phase for cable connection to the service section.

15

Seismic Qualied
Cutler-Hammer Instant Service Switchboards are seismically tested, seismically qualied, and exceed requirements of both the Uniform Building Code (UBC) and the California Building Code (CBC) for all seismic zones. Table 15-1. Dimensions in Inches (mm)
Height Width 32 (812.8) 38 (965.2) Depth 14 (355.6) 26 (660.4)

Indoor
90 (2286.0)

Type 3R Outdoor

Outdoor
90 (2286.0)

CA08101001E

For more information visit: www.eaton.com

15-8

Switchboards Instant Service Switchboards


February 2007

Product Selection

Product Selection
Table 15-2. Main Fused Switch Only
Service Main Ampere Rating Type 1 Indoor Catalog Number MSB423 MSB623 MSB424 MSB624 MSB444 MSB644 Price U.S. $ Type 3R Outdoor Catalog Number RMSB423 RMSB623 RMSB424 RMSB624 800 400 600 RMSB444 RMSB644 Price U.S. $

Table 15-5. Lug Landing Kits for Underground Pull Sections


Maximum Service Ampere Rating 400 1-Phase 3-Wire 3-Phase 4-Wire 1-Phase 3-Wire 3-Phase 4-Wire Catalog Number LL4003 LL4004 LL8003 LL8004 Price U.S. $

240 Vac Maximum


1-Phase 3-Wire 3-Phase 4-Wire 400 600 400 600

480Y/277 Vac
3-Phase 4-Wire

Table 15-3. Main Fused Switch with Distribution Panel


Service Main Ampere Rating Type 1 Indoor Catalog Number MSBP423 MSBP623 MSBP424 MSBP624 MSBP444 MSBP644 Price U.S. $ Type 3R Outdoor Catalog Number RMSBP423 RMSBP623 RMSBP424 RMSBP624 RMSBP444 RMSBP644 Price U.S. $

Mounts in 30-inch (762.0 mm) wide section only.

240 Vac Maximum


1-Phase 3-Wire 3-Phase 4-Wire 400 600 400 600 400 600

Table 15-6. Load Side Wireway 12 Inches (304.8 mm) Wide Same Depth as Switchboard
Type Type 1 Indoor Type 3R Outdoor Catalog Number LSS12W RLSS12W Price U.S. $

480Y/277 Vac
3-Phase 4-Wire

240 volt distribution panels have double branch provisions for: four Type ED 225 ampere frame circuit breakers and 24 poles of Type BAB 100 ampere frame circuit breakers. 480Y/277 volt distribution panels have double branch provisions for: four Type FD 225 ampere frame circuit breakers and 24 poles of Type GHB 100 ampere frame circuit breakers.

15

Note: Circuit breakers for distribution panels are ordered separately.

Table 15-4. Underground Pull Sections Same Depth as Switchboard with Provisions for Lug Landing Kit
Section Width Inches 24 30 mm 609.6 762.0 Type 1 Indoor Catalog Number UG24W UG30W Price U.S. $ Type 3R Outdoor Catalog Number RUG24W RUG30W Price U.S. $

NEMA Type 1 pull section can be installed separate from service section. Add Side Closer Plate, Catalog Number UGCP, Price U.S. dollars $94.00. Check utility requirements most EUSERC utilities require 30-inch (762.0 mm) width.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . DE1 For more information visit: www.eaton.com CA08101001E

Switchboards Instant Service Switchboards


February 2007

15-9

Accessories and Circuit Breakers

Accessories
Table 15-7. Meter Compartment Doors (Meter Sockets Not Included)
Door Size Dimensions Inches 15 H x 32 W 30 H x 32 W mm 381.0 H x 812.8 W 762.0 H x 812.8 W Blank One socket Blank Two sockets Drilling Catalog Number MD150 MD151 MD300 MD302 Price U.S. $

Table 15-8. Meter Sockets For Field Installation


Number of Jaws 4 5 6 Catalog Price Number U.S. $ M4 M5 M6 Number of Jaws 8 13 15 Catalog Price Number U.S. $ M8 M13 M15

Fifth jaw at 9 oclock position. Basic four jaw socket with fth and sixth jaws at 3 and 9 oclock positions. Required for all SDG&E services rated at 3-phase 4-wire.

Circuit Breakers
Table 15-9. Circuit Breakers for Distribution Panels 240 Vac Maximum (1-Phase 3-Wire or 3-Phase 4-Wire)
Ampere Rating 1-Pole 120/240 Vac Catalog Number BAB1015I BAB1020I BAB1030I BAB1040I BAB1050I BAB1060I Price U.S. $ 2-Pole 120/240 Vac Catalog Number BAB2015I BAB2020I BAB2030I BAB2040I BAB2050I BAB2060I BAB2070I BAB2090I BAB2100I Price U.S. $ 2-Pole 240 Vac Catalog Number BAB2015HI BAB2020HI BAB2030HI BAB2040HI BAB2050HI BAB2060HI BAB2070HI BAB2090HI BAB2100HI ED2100I ED2125I ED2150I ED2175I ED2200I ED2225I Price U.S. $ 3-Pole 240 Vac Catalog Number BAB3015HI BAB3020HI BAB3030HI BAB3040HI BAB3050HI BAB3060HI BAB3070HI BAB3090HI BAB3100HI ED3100I ED3125I ED3150I ED3175I ED3200I ED3225I Price U.S. $

15 20 30 40 50 60 70 90 100 100 125 150 175 200 225

15

Table 15-10. Circuit Breakers for Distribution Panels 480Y/277 Vac (3-Phase 4-Wire)
Ampere Rating 1-Pole Catalog Number GHB1015I GHB1020I GHB1030I GHB1040I GHB1050I GHB1060I Price U.S. $ 2-Pole Catalog Number GHB2015I GHB2020I GHB2030I GHB2040I GHB2050I GHB2060I GHB2070I GHB2080I GHB2090I GHB2100I FD2100I FD2125I FD2150I FD2175I FD2200I FD2225I Price U.S. $ 3-Pole Catalog Number GHB3015I GHB3020I GHB3030I GHB3040I GHB3050I GHB3060I GHB3070I GHB3080I GHB3090I GHB3100I FD3100I FD3125I FD3150I FD3175I FD3200I FD3225I Price U.S. $

15 20 30 40 50 60 70 80 90 100 100 125 150 175 200 225

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . DE1 CA08101001E For more information visit: www.eaton.com

15-10

Switchboards Roll-up Generator Termination Box


February 2007

Product Description

Roll-up Generator Termination Box

Standards and Ratings


UL 1773 listed Termination Boxes. 600 Vac maximum. Amperage ratings: 800, 1200, 1600, 2000 and 2500. Assembly short circuit rating: 25,000 amperes rms symmetrical. Marked Suitable for use on the line side of service equipment per UL 1773.

The enclosure contains a sturdy, lockable, hinged door for access to the termination compartment by qualied personnel as described in NFPA 70E and the National Electrical Code. Feeder conductor entry is provided in the bottom of the enclosure for the line side (generator). A hinged bottom plate is provided on the line side for access to line terminations. The permanent load connections (feeding to the facility overcurrent device) exit the enclosure from the bottom.

Features
Enclosure
The enclosure is free-standing with feet on the bottom providing access to the cable connections for temporary roll-up generator terminations. The enclosure is made from code gauge steel and is suitable for either outdoor or indoor installation (Type 3R construction). The enclosure is powder coat painted ANSI 61 gray. Each enclosure houses line and load phase, neutral and ground connections. Access is provided at the bottom of the enclosure for both the temporary connections to the roll-up generator and permanent connections to the facility's generator overcurrent disconnecting means. The permanent connection section at the bottom of the enclosure contains a xed mounting plate. The temporary generator connection to the RUGTB contains a hinged cover that allows access to the enclosure for generator conductors. The enclosure utilizes feet that raise the termination compartment off nished grade by 18-inches (457.2 mm). Enclosure feet have provisions for anchoring the RUGTB. Anchor bolts are to secure the RUGTB and shall be encased in a concrete pad by the installer in a manner that is suitable as a permanent base for the unit. A template for anchor bolt installation is available from the manufacturer.

Terminations
All Roll-up Generator Termination Boxes contain a termination/lug landing for three phases and neutral plus ground. Line termination options include mechanical lugs, one-hole and two-hole compression lugs, one-hole and two-hole compression lug provisions and quick disconnect. Lug provisions are provided with bolt congurations as described in the catalog data on the following pages. Where lug provisions are ordered, lugs are supplied by others.

Roll-up Generator Termination Box

Product Description

15

Eaton's Cutler-Hammer Roll-up Generator Termination Boxes (RUGTB) are designed as an intermediate termination cabinet between a temporary, portable roll-up generator and the facility being served. The RUGTB is designed for permanent installation and is secured to a concrete pad with bolts. The RUGTB includes line terminations for the temporary connection of the portable generator and permanent connections on the load side to the secondary disconnect in the facility which is interlocked with the main overcurrent device in a manner that ensures that only one (either the service main or the generator main) can be energized at any one time. The conductors and conduits must be sized and suitable for carrying the load ratings marked on the equipment per the National Electrical Code.

For more information visit: www.eaton.com

CA08101001E

Switchboards Roll-up Generator Termination Box


February 2007

15-11

Dimensions

Dimensions

Figure 15-2. Enclosure Dimensions

15

Figure 15-3. Termination/Lug Landing

CA08101001E

For more information visit: www.eaton.com

15-12

Switchboards Roll-up Generator Termination Box


February 2007

Technical Data

Technical Data
Table 15-11. Roll-up Generator Termination Box with Line and Load Mechanical Box Lugs
Ampere Rating 800 Dimensions in Inches (mm) Mechanical Box Lugs Line HxWxD Termination Number, Range and Type 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (3) 4/0 500 kcmil Al/Cu (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu 1200 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (4) 4/0 500 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu 1600 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (5) 4/0 500 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu 2000 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (6) 4/0 500 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu 2500 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (8) 4/0 500 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu Mechanical Box Lugs Load Termination Number, Range and Type (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu Catalog Number GTB08MAMA GTB08MAMB GTB08MBMA GTB08MBMB GTB12MCMC GTB12MCMD GTB12MDMC GTB12MDMD GTB16MEME GTB16MEMF GTB16MFME GTB16MFMF GTB20MGMG GTB20MGMH GTB20MHMG GTB20MHMH GTB25MJMJ GTB25MJMK GTB25MKMJ GTB25MJMJ Price U.S. $

Note: Line and load mechanical lugs are factory selected and installed.

15

Table 15-12. Roll-up Generator Termination Box with Line Mechanical Box Lugs; Load 1-Hole Compression Lugs
Ampere Rating 800 Dimensions in Inches (mm) HxWxD 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) Mechanical Box Lugs Line Termination Number, Range and Type (3) 4/0 500 kcmil Al/Cu (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu 1200 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (4) 4/0 500 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu 1600 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (5) 4/0 500 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu 2000 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (6) 4/0 500 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu 2500 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (8) 4/0 500 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu 1-Hole Compression Load Termination Number, Range and Type (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu Catalog Number GTB08MACA GTB08MACB GTB08MBCA GTB08MBCB GTB12MCCC GTB12MCCD GTB12MDCC GTB12MDCD GTB16MECE GTB16MECF GTB16MFCE GTB16MFCF GTB20MGCG GTB20MGCH GTB20MHCG GTB20MHCH GTB25MJCJ GTB25MJCK GTB25MKCJ GTB25MJCJ Price U.S. $

Note: Line side mechanical lugs are factory selected and installed. Note: Load side Anderson, 1-hole compression lugs are factory selected and installed.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com CA08101001E

Switchboards Roll-up Generator Termination Box


February 2007

15-13

Technical Data
Table 15-13. Roll-up Generator Termination Box with Line Mechanical Box Lugs; Load 2-Hole Compression Lugs
Ampere Rating 800 Dimensions in Inches (mm) Mechanical Box Lugs Line HxWxD Termination Number, Range and Type 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (3) 4/0 500 kcmil Al/Cu (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu 1200 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (4) 4/0 500 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu 1600 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (5) 4/0 500 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu 2000 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (6) 4/0 500 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu 2500 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (8) 4/0 500 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu 2-Hole Compression Load Termination Cu ONLY Wire Size (3) 350 kcmil Cu ONLY (3) 400 kcmil Cu ONLY (3) 350 kcmil Cu ONLY (3) 400 kcmil Cu ONLY (4) 500 kcmil Cu ONLY (3) 600 kcmil Cu ONLY (3) 750 kcmil Cu ONLY (4) 500 kcmil Cu ONLY (3) 600 kcmil Cu ONLY (3) 750 kcmil Cu ONLY (5) 500 kcmil Cu ONLY (4) 600 kcmil Cu ONLY (4) 750 kcmil Cu ONLY (5) 500 kcmil Cu ONLY (4) 600 kcmil Cu ONLY (4) 750 kcmil Cu ONLY (6) 500 kcmil Cu ONLY (5) 600 kcmil Cu ONLY (5) 750 kcmil Cu ONLY (6) 500 kcmil Cu ONLY (5) 600 kcmil Cu ONLY (5) 750 kcmil Cu ONLY (7) 500 kcmil Cu ONLY (6) 600 kcmil Cu ONLY (6) 750 kcmil Cu ONLY (7) 500 kcmil Cu ONLY (6) 600 kcmil Cu ONLY (6) 750 kcmil Cu ONLY Catalog Number GTB08MACL GTB08MBCM GTB08MBCL GTB08MACL GTB12MCCN GTB12MCCP GTB12MCCQ GTB12MDCN GTB12MDCP GTB12MDCQ GTB16MECR GTB16MECS GTB16MECT GTB16MFCR GTB16MFCS GTB16MFCT GTB20MGCu GTB20MGCV GTB20MGCW GTB20MHCu GTB20MHCV GTB20MHCW GTB25MJCX GTB25MJCY GTB25MJCZ GTB25MKCX GTB25MKCY GTB25MKCZ Price U.S. $

15

Note: Line side mechanical lugs are factory selected and installed. Note: Load side factory installed Burndy, 2-hole, short barrel compression lugs suitable for COPPER WIRE ONLY requires 45-inches (1143.0 mm) wide enclosure.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E For more information visit: www.eaton.com

15-14

Switchboards Roll-up Generator Termination Box


February 2007

Technical Data
Table 15-14. Roll-up Generator Termination Box with Line Mechanical Box Lugs; Load PROVISIONS ONLY 1-Hole Compression Lugs
Ampere Rating 800 1200 1600 2000 2500 Dimensions in Inches (mm) Mechanical Box Lugs Line HxWxD Termination Number, Range and Type 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu 1-Hole Compression Load Provisions ONLY Number and Range (3) Provisions Per Phase (3) Provisions Per Phase (4) Provisions Per Phase (4) Provisions Per Phase (5) Provisions Per Phase (5) Provisions Per Phase (6) Provisions Per Phase (6) Provisions Per Phase (8) Provisions Per Phase (8) Provisions Per Phase Catalog Number GTB08MAP1 GTB08MBP1 GTB12MCP2 GTB12MDP2 GTB16MEP3 GTB16MFP3 GTB20MGP4 GTB20MHP4 GTB25MJP5 GTB25MKP5 Price U.S. $

Note: Line side mechanical lugs are factory selected and installed. Note: Load side factory installed 3/8" bolt provisions for 1-hole compression lugs (lugs furnished by others).

Table 15-15. Roll-up Generator Termination Box with Line Mechanical Box Lugs; Load PROVISIONS ONLY 2-Hole Compression Lugs
Ampere Rating 800 1200 1600 2000 Dimensions in Inches (mm) Mechanical Box Lugs Line HxWxD Termination Number, Range and Type 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu 2-Hole Compression Load Provisions ONLY Number and Range (3) Provisions Per Phase (3) Provisions Per Phase (4) Provisions Per Phase (4) Provisions Per Phase (5) Provisions Per Phase (5) Provisions Per Phase (6) Provisions Per Phase (6) Provisions Per Phase (8) Provisions Per Phase (8) Provisions Per Phase Catalog Number GTB08MAPA GTB08MBPA GTB12MCPB GTB12MDPB GTB16MEPC GTB16MFPC GTB20MGPD GTB20MHPD GTB25MJPE GTB25MKPE Price U.S. $

15
2500

Note: Line side mechanical lugs are factory selected and installed. Note: Load side factory installed 1/2" bolt provisions on 1 3/4" hole centers for 2-hole compression lugs (lugs furnished by others). Note: Requires 45-inch (1143.0 mm) wide enclosure.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com CA08101001E

Switchboards Roll-up Generator Termination Box


February 2007

15-15

Technical Data
Table 15-16. Roll-up Generator Termination Box with Line 1-Hole Compression Lugs and Load Mechanical Box Lugs
Ampere Rating 800 Dimensions in Inches (mm) 1-Hole Compression Line HxWxD Termination Number, Range and Type 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (3) 4/0 500 kcmil Al/Cu (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu 1200 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (4) 4/0 500 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu 1600 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (5) 4/0 500 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu 2000 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (6) 4/0 500 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu 2500 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (8) 4/0 500 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu Mechanical Box Lugs Load Termination Number, Range and Type (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu Catalog Number GTB08CAMA GTB08CAMB GTB08CBMA GTB08CBMB GTB12CCMC GTB12CCMD GTB12CDMC GTB12CDMD GTB16CEME GTB16CEMF GTB16CFME GTB16CFMF GTB20CGMG GTB20CGMH GTB20CHMG GTB20CHMH GTB25CJMJ GTB25CJMK GTB25CKMJ GTB25CJMK Price U.S. $

Note: Line side Anderson, 1-hole compression lugs are factory selected and installed. Note: Load side mechanical lugs are factory selected and installed.

Table 15-17. Roll-up Generator Termination Box with Line and Load 1-Hole Compression Lugs
Ampere Rating 800 Dimensions in Inches (mm) HxWxD 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 1-Hole Compression Line Termination Number, Range and Type (3) 4/0 500 kcmil Al/Cu (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu 1200 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (4) 4/0 500 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu 1600 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (5) 4/0 500 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu 2000 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (6) 4/0 500 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu 2500 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) (8) 4/0 500 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu 1-Hole Compression Load Termination Number, Range and Type (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu Catalog Number GTB08CACA GTB08CACB GTB08CBCA GTB08CBCB GTB12CCCC GTB12CCCD GTB12CDCC GTB12CDCD GTB16CECE GTB16CECF GTB16CFCE GTB16CFCF GTB20CGCG GTB20CGCH GTB20CHCG GTB20CHCH GTB25CJCJ GTB25CJCK GTB25CKCJ GTB25CJCK Price U.S. $

15

Note: Line side and load Anderson, 1-hole compression lugs are factory selected and installed.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E For more information visit: www.eaton.com

15-16

Switchboards Roll-up Generator Termination Box


February 2007

Technical Data
Table 15-18. Roll-up Generator Termination Box with Line 1-Hole Compression Lugs; Load 2-Hole Compression Lugs
Ampere Rating 800 Dimensions in Inches (mm) HxWxD 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 1-Hole Compression Line Termination Number, Range and Type (3) 4/0 500 kcmil Al/Cu (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu 1200 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (4) 4/0 500 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu 1600 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (5) 4/0 500 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu 2000 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (6) 4/0 500 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu 2500 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (8) 4/0 500 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu 2-Hole Compression Load Termination Cu ONLY Wire Size (3) 350 kcmil Cu ONLY (3) 400 kcmil Cu ONLY (3) 350 kcmil Cu ONLY (3) 400 kcmil Cu ONLY (4) 500 kcmil Cu ONLY (3) 600 kcmil Cu ONLY (3) 750 kcmil Cu ONLY (4) 500 kcmil Cu ONLY (3) 600 kcmil Cu ONLY (3) 750 kcmil Cu ONLY (5) 500 kcmil Cu ONLY (4) 600 kcmil Cu ONLY (4) 750 kcmil Cu ONLY (5) 500 kcmil Cu ONLY (4) 600 kcmil Cu ONLY (4) 750 kcmil Cu ONLY (6) 500 kcmil Cu ONLY (5) 600 kcmil Cu ONLY (5) 750 kcmil Cu ONLY (6) 500 kcmil Cu ONLY (5) 600 kcmil Cu ONLY (5) 750 kcmil Cu ONLY (7) 500 kcmil Cu ONLY (6) 600 kcmil Cu ONLY (6) 750 kcmil Cu ONLY (7) 500 kcmil Cu ONLY (6) 600 kcmil Cu ONLY (6) 750 kcmil Cu ONLY Catalog Number GTB08CACL GTB08CACM GTB08CBCL GTB08CBCM GTB12CCCN GTB12CCCP GTB12CCCQ GTB12CDCN GTB12CDCP GTB12CDCQ GTB16CECR GTB16CECS GTB16CECT GTB16CFCR GTB16CFCS GTB16CFCT GTB20CGCu GTB20CGCV GTB20CGCW GTB20CHCu GTB20CHCV GTB20CHCW GTB25CJCX GTB25CJCY GTB25CJCZ GTB25CKCX GTB25CKCY GTB25CKCZ Price U.S. $

15

Note: Line side Anderson, 1-hole compression lugs are factory selected and installed. Note: Load side factory installed Burndy, 2-hole, short barrel compression lugs suitable for COPPER WIRE ONLY. Note: Requires 45-inch (1143.0 mm) wide enclosure.

Table 15-19. Roll-up Generator Termination Box with Line 1-Hole Compression Lugs; Load PROVISIONS ONLY 1-Hole Compression Lugs
Ampere Rating 800 1200 1600 2000 2500 Dimensions in Inches (mm) HxWxD 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 1-Hole Compression Line Termination Number, Range and Type (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu 1-Hole Compression Load Provisions ONLY Number and Range (3) Provisions Per Phase (3) Provisions Per Phase (4) Provisions Per Phase (4) Provisions Per Phase (5) Provisions Per Phase (5) Provisions Per Phase (6) Provisions Per Phase (6) Provisions Per Phase (8) Provisions Per Phase (8) Provisions Per Phase Catalog Number GTB08CAP1 GTB08CBP1 GTB12CCP2 GTB12CDP2 GTB16CEP3 GTB16CFP3 GTB20CGP4 GTB20CHP4 GTB25CJP5 GTB25CKP5 Price U.S. $

Note: Line side Anderson, 1-hole compression lugs are factory selected and installed. Note: Load side factory installed 3/8" bolt provisions for 1-hole compression lugs (lugs furnished by others).

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com CA08101001E

Switchboards Roll-up Generator Termination Box


February 2007

15-17

Technical Data
Table 15-20. Roll-up Generator Termination Box with 1-Hole Compression Lugs; Load PROVISIONS ONLY 2-Hole Compression Lugs
Ampere Rating 800 1200 1600 2000 2500 Dimensions in Inches (mm) HxWxD 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 1-Hole Compression Line Termination Number, Range and Type (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu 2-Hole Compression Load Provisions ONLY Number and Range (3) Provisions Per Phase (3) Provisions Per Phase (4) Provisions Per Phase (4) Provisions Per Phase (5) Provisions Per Phase (5) Provisions Per Phase (6) Provisions Per Phase (6) Provisions Per Phase (8) Provisions Per Phase (8) Provisions Per Phase Catalog Number GTB08CAPA GTB08CBPA GTB12CCPB GTB12CDPB GTB16CEPC GTB16CGPC GTB20CGPD GTB20CHPD GTB25CJPE GTB25CKPE Price U.S. $

Note: Line side Anderson, 1-hole compression lugs are factory selected and installed. Note: Load side factory installed 1/2" bolt provisions on 1 3/4" hole centers for 2-hole compression lugs (lugs furnished by others). Note: Requires 45-inch (1143.0 mm) wide enclosure.

Table 15-21. Roll-up Generator Termination Box with Line 2-Hole Compression Lugs and Load Mechanical Box Lugs
Ampere Rating 800 Dimensions in Inches (mm) HxWxD 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 2-Hole Compression Line Termination Cu ONLY Wire Size (3) 350 kcmil Cu ONLY (3) 350 kcmil Cu ONLY (3) 400 kcmil Cu ONLY (3) 400 kcmil Cu ONLY 1200 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (4) 500 kcmil Cu ONLY (4) 500 kcmil Cu ONLY (3) 600 kcmil Cu ONLY (3) 600 kcmil Cu ONLY (3) 750 kcmil Cu ONLY (3) 750 kcmil Cu ONLY 1600 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (5) 500 kcmil Cu ONLY (5) 500 kcmil Cu ONLY (4) 600 kcmil Cu ONLY (4) 600 kcmil Cu ONLY (4) 750 kcmil Cu ONLY (4) 750 kcmil Cu ONLY 2000 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (6) 500 kcmil Cu ONLY (6) 500 kcmil Cu ONLY (5) 600 kcmil Cu ONLY (5) 600 kcmil Cu ONLY (5) 750 kcmil Cu ONLY (5) 750 kcmil Cu ONLY 2500 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (7) 500 kcmil Cu ONLY (7) 500 kcmil Cu ONLY (6) 600 kcmil Cu ONLY (6) 600 kcmil Cu ONLY (6) 750 kcmil Cu ONLY (6) 750 kcmil Cu ONLY Mechanical Box Lugs Load Termination Number, Range and Type (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu Catalog Number GTB08CLMA GTB08CLMB GTB08CMMA GTB08CMMB GTB12CNMC GTB12CNMD GTB12CPMC GTB12CPMD GTB12CQMC GTB12CQMD GTB16CRME GTB16CRMF GTB16CSME GTB16CSMF GTB16CTME GTB16CTMF GTB20CuMG GTB20CuMH GTB20CVMG GTB20CVMH GTB20CWMG GTB20CWMH GTB25CXMJ GTB25CXMK GTB25CYMJ GTB25CYMK GTB25CZMJ GTB25CZMK Price U.S. $

15

Note: Line side factory installed Burndy, 2-hole, short barrel compression lugs suitable for COPPER WIRE ONLY. Note: Load side mechanical lugs are factory selected and installed. Note: Requires 45-inch (1143.0 mm) wide enclosure.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E For more information visit: www.eaton.com

15-18

Switchboards Roll-up Generator Termination Box


February 2007

Technical Data
Table 15-22. Roll-up Generator Termination Box with Line 2-Hole Compression Lugs and Load 1-Hole Compression Lugs
Ampere Rating 800 Dimensions in Inches (mm) HxWxD 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 2-Hole Compression Line Termination Cu ONLY Wire Size (3) 350 kcmil Cu ONLY (3) 350 kcmil Cu ONLY (3) 400 kcmil Cu ONLY (3) 400 kcmil Cu ONLY 1200 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (4) 500 kcmil Cu ONLY (4) 500 kcmil Cu ONLY (3) 600 kcmil Cu ONLY (3) 600 kcmil Cu ONLY (3) 750 kcmil Cu ONLY (3) 750 kcmil Cu ONLY 1600 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (5) 500 kcmil Cu ONLY (5) 500 kcmil Cu ONLY (4) 600 kcmil Cu ONLY (4) 600 kcmil Cu ONLY (4) 750 kcmil Cu ONLY (4) 750 kcmil Cu ONLY 2000 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (6) 500 kcmil Cu ONLY (6) 500 kcmil Cu ONLY (5) 600 kcmil Cu ONLY (5) 600 kcmil Cu ONLY (5) 750 kcmil Cu ONLY (5) 750 kcmil Cu ONLY 2500 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (7) 500 kcmil Cu ONLY (7) 500 kcmil Cu ONLY (6) 600 kcmil Cu ONLY (6) 600 kcmil Cu ONLY (6) 750 kcmil Cu ONLY (6) 750 kcmil Cu ONLY 1-Hole Compression Load Termination Number, Range and Type (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu Catalog Number GTB08CLCA GTB08CLCB GTB08CMCA GTB08CMCB GTB12CNCC GTB12CNCD GTB12CPCC GTB12CPCD GTB12CQCC GTB12CQCD GTB16CRCE GTB16CRCF GTB16CSCE GTB16CSCF GTB16CTCE GTB16CTCF GTB20CuCG GTB20CuCH GTB20CVCG GTB20CVCH GTB20CWCG GTB20CWCH GTB25CXCJ GTB25CXCK GTB25CYCJ GTB25CYCK GTB25CZCJ GTB25CZCK Price U.S. $

15

Note: Line side factory installed Burndy, 2-hole, short barrel compression lugs suitable for COPPER WIRE ONLY. Note: Load side Anderson, 1-hole compression lugs are factory selected and installed. Note: Requires 45-inch (1143.0 mm) wide enclosure.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com CA08101001E

Switchboards Roll-up Generator Termination Box


February 2007

15-19

Technical Data
Table 15-23. Roll-up Generator Termination Box with Line 2-Hole Compression Lugs; Load 2-Hole Compression Lugs
Ampere Rating 800 Dimensions in Inches (mm) HxWxD 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 2-Hole Compression Line Termination Cu ONLY Wire Size (3) 350 kcmil Cu ONLY (3) 350 kcmil Cu ONLY (3) 400 kcmil Cu ONLY (3) 400 kcmil Cu ONLY 1200 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (4) 500 kcmil Cu ONLY (4) 500 kcmil Cu ONLY (4) 500 kcmil Cu ONLY (3) 600 kcmil Cu ONLY (3) 600 kcmil Cu ONLY (3) 600 kcmil Cu ONLY (3) 750 kcmil Cu ONLY (3) 750 kcmil Cu ONLY (3) 750 kcmil Cu ONLY 1600 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (5) 500 kcmil Cu ONLY (5) 500 kcmil Cu ONLY (5) 500 kcmil Cu ONLY (4) 600 kcmil Cu ONLY (4) 600 kcmil Cu ONLY (4) 600 kcmil Cu ONLY (4) 750 kcmil Cu ONLY (4) 750 kcmil Cu ONLY (4) 750 kcmil Cu ONLY 2000 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (6) 500 kcmil Cu ONLY (6) 500 kcmil Cu ONLY (6) 500 kcmil Cu ONLY (5) 600 kcmil Cu ONLY (5) 600 kcmil Cu ONLY (5) 600 kcmil Cu ONLY (5) 750 kcmil Cu ONLY (5) 750 kcmil Cu ONLY (5) 750 kcmil Cu ONLY 2500 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (7) 500 kcmil Cu ONLY (7) 500 kcmil Cu ONLY (7) 500 kcmil Cu ONLY (6) 600 kcmil Cu ONLY (6) 600 kcmil Cu ONLY (6) 600 kcmil Cu ONLY (6) 750 kcmil Cu ONLY (6) 750 kcmil Cu ONLY (6) 750 kcmil Cu ONLY 2-Hole Compression Load Termination Cu ONLY Wire Size (3) 350 kcmil Cu ONLY (3) 400 kcmil Cu ONLY (3) 350 kcmil Cu ONLY (3) 400 kcmil Cu ONLY (4) 500 kcmil Cu ONLY (3) 600 kcmil Cu ONLY (3) 750 kcmil Cu ONLY (4) 500 kcmil Cu ONLY (3) 600 kcmil Cu ONLY (3) 750 kcmil Cu ONLY (4) 500 kcmil Cu ONLY (3) 600 kcmil Cu ONLY (3) 750 kcmil Cu ONLY (5) 500 kcmil Cu ONLY (4) 600 kcmil Cu ONLY (4) 750 kcmil Cu ONLY (5) 500 kcmil Cu ONLY (4) 600 kcmil Cu ONLY (4) 750 kcmil Cu ONLY (5) 500 kcmil Cu ONLY (4) 600 kcmil Cu ONLY (4) 750 kcmil Cu ONLY (6) 500 kcmil Cu ONLY (5) 600 kcmil Cu ONLY (5) 750 kcmil Cu ONLY (6) 500 kcmil Cu ONLY (5) 600 kcmil Cu ONLY (5) 750 kcmil Cu ONLY (6) 500 kcmil Cu ONLY (5) 600 kcmil Cu ONLY (5) 750 kcmil Cu ONLY (7) 500 kcmil Cu ONLY (6) 600 kcmil Cu ONLY (6) 750 kcmil Cu ONLY (7) 500 kcmil Cu ONLY (6) 600 kcmil Cu ONLY (6) 750 kcmil Cu ONLY (7) 500 kcmil Cu ONLY (6) 600 kcmil Cu ONLY (6) 750 kcmil Cu ONLY Catalog Number GTB08CLCL GTB08CLCM GTB08CMCL GTB08CMCM GTB12CNCN GTB12CNCP GTB12CNCQ GTB12CPCN GTB12CPCP GTB12CPCQ GTB12CQCN GTB12CQCP GTB12CQCQ GTB16CRCR GTB16CRCS GTB16CRCT GTB16CSCR GTB16CSCS GTB16CSCT GTB16CTCR GTB16CTCS GTB16CTCT GTB20CuCu GTB20CuCV GTB20CuCW GTB20CVCu GTB20CVCu GTB20CVCW GTB20CWCu GTB20CWCV GTB20CWCW GTB25CXCX GTB25CXCY GTB25CXCZ GTB25CYCX GTB25CYCY GTB25CYCZ GTB25CZCX GTB25CZCY GTB25CZCZ Price U.S. $

15

Note: Line and load side factory installed Burndy, 2-hole, short barrel compression lugs suitable for COPPER WIRE ONLY. Note: Requires 45-inch (1143.0 mm) wide enclosure.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E For more information visit: www.eaton.com

15-20

Switchboards Roll-up Generator Termination Box


February 2007

Technical Data
Table 15-24. Roll-up Generator Termination Box with Line 2-Hole Compression Lugs; Load PROVISIONS ONLY 1-Hole Compression Lugs
Ampere Rating 800 1200 Dimensions in Inches (mm) HxWxD 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 2-Hole Compression Line Termination Cu ONLY Wire Size (3) 350 kcmil Cu ONLY (3) 400 kcmil Cu ONLY (4) 500 kcmil Cu ONLY (3) 600 kcmil Cu ONLY (3) 750 kcmil Cu ONLY 2000 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (6) 500 kcmil Cu ONLY (5) 600 kcmil Cu ONLY (5) 750 kcmil Cu ONLY 2500 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (7) 500 kcmil Cu ONLY (6) 600 kcmil Cu ONLY (6) 750 kcmil Cu ONLY 1-Hole Compression Load Provisions ONLY Number and Range (3) Provisions Per Phase (3) Provisions Per Phase (4) Provisions Per Phase (4) Provisions Per Phase (4) Provisions Per Phase (6) Provisions Per Phase (6) Provisions Per Phase (6) Provisions Per Phase (8) Provisions Per Phase (8) Provisions Per Phase (8) Provisions Per Phase Catalog Number GTB08CLP1 GTB08CMP1 GTB12CNP2 GTB12CPP2 GTB12CQP2 GTB20CuP4 GTB20CVP4 GTB20CWP4 GTB25CXP5 GTB25CYP6 GTB25CZP6 Price U.S. $

Note: Line side factory installed Burndy, 2-hole, short barrel compression lugs suitable for COPPER WIRE ONLY. Note: Load side factory installed 3/8" bolt provisions for 1-hole compression lugs (lugs furnished by others). Note: Requires 45-inch (1143.0 mm) wide enclosure.

Table 15-25. Roll-up Generator Termination Box with 2-Hole Compression Lugs; Load PROVISIONS ONLY 2-Hole Compression Lugs
Ampere Rating 800 1200 Dimensions in Inches (mm) HxWxD 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 2-Hole Compression Line Termination Cu ONLY Wire Size (3) 350 kcmil Cu ONLY (3) 400 kcmil Cu ONLY (4) 500 kcmil Cu ONLY (3) 600 kcmil Cu ONLY (3) 750 kcmil Cu ONLY 1600 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (5) 500 kcmil Cu ONLY (4) 600 kcmil Cu ONLY (4) 750 kcmil Cu ONLY 2000 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (6) 500 kcmil Cu ONLY (5) 600 kcmil Cu ONLY (5) 750 kcmil Cu ONLY 2500 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (7) 500 kcmil Cu ONLY (6) 600 kcmil Cu ONLY (6) 750 kcmil Cu ONLY 2-Hole Compression Load Provisions ONLY Number and Range (3) Provisions Per Phase (3) Provisions Per Phase (4) Provisions Per Phase (4) Provisions Per Phase (4) Provisions Per Phase (5) Provisions Per Phase (5) Provisions Per Phase (5) Provisions Per Phase (6) Provisions Per Phase (6) Provisions Per Phase (6) Provisions Per Phase (8) Provisions Per Phase (8) Provisions Per Phase (8) Provisions Per Phase Catalog Number GTB08CLPA GTB08CMPA GTB12CNPB GTB12CPPB GTB12CQPB GTB16CRPC GTB16CSPC GTB16CTPC GTB20CuPD GTB20CVPD GTB20CWPD GTB25CXPE GTB25CYPE GTB25CZPE Price U.S. $

15

Note: Line side factory installed Burndy, 2-hole, short barrel compression lugs suitable for COPPER WIRE ONLY. Note: Load side factory installed 1/2" bolt provisions on 1 3/4" hole centers for 2-hole compression lugs (lugs furnished by others). Note: Requires 45-inch (1143.0 mm) wide enclosure.

Table 15-26. Roll-up Generator Termination Box with Line 1-Hole Compression Lug PROVISIONS; Load Mechanical Box Lugs
Ampere Rating 800 1200 1600 2000 2500 Dimensions in Inches (mm) HxWxD 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 1-Hole Compression Line Provisions ONLY Number and Range (3) Provisions Per Phase (3) Provisions Per Phase (4) Provisions Per Phase (4) Provisions Per Phase (5) Provisions Per Phase (5) Provisions Per Phase (6) Provisions Per Phase (6) Provisions Per Phase (8) Provisions Per Phase (8) Provisions Per Phase Mechanical Box Lugs Load Termination Number, Range and Type (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu Catalog Number GTB08P1MA GTB08P1MB GTB12P2MC GTB12P2MD GTB16P3ME GTB16P3MF GTB20P4MG GTB20P4MH GTB25P5MJ GTB25P5MK Price U.S. $

Note: Line side factory installed 3/8" bolt provisions for 1-hole compression lugs (lugs furnished by others). Note: Load side mechanical lugs are factory selected and installed.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com CA08101001E

Switchboards Roll-up Generator Termination Box


February 2007

15-21

Technical Data
Table 15-27. Roll-up Generator Termination Box with Line 1-Hole Compression Lug PROVISIONS; Load 1-Hole Compression Lugs
Ampere Rating 800 1200 1600 2000 2500 Dimensions in Inches (mm) HxWxD 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 1-Hole Compression Line Provisions Only Number and Range (3) Provisions Per Phase (3) Provisions Per Phase (4) Provisions Per Phase (4) Provisions Per Phase (5) Provisions Per Phase (5) Provisions Per Phase (6) Provisions Per Phase (6) Provisions Per Phase (8) Provisions Per Phase (8) Provisions Per Phase 1-Hole Compression Load Termination Catalog Number, Range and Type Number (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu GTB08P1CA GTB08P1CB GTB12P2CC GTB12P2CD GTB16P3CE GTB16P3CF GTB20P4CG GTB20P4CH GTB25P5CJ GTB25P5CK Price U.S. $

Note: Line side factory installed 3/8" bolt provisions for 1-hole compression lugs (lugs furnished by others). Note: Load side Anderson, 1-hole compression lugs are factory selected and installed.

Table 15-28. Roll-up Generator Termination Box with Line 1-Hole Compression Lug PROVISIONS; Load 2-Hole Compression Lugs
Ampere Rating 800 1200 Dimensions in Inches (mm) HxWxD 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 1-Hole Compression Line Provisions 2-Hole Compression Load Termination ONLY Number and Range Cu ONLY Wire Size (3) 4/0 500 kcmil (3) 4/0 500 kcmil (4) 4/0 500 kcmil (4) 4/0 500 kcmil (4) 4/0 500 kcmil 1600 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (5) 4/0 500 kcmil (5) 4/0 500 kcmil (5) 4/0 500 kcmil 2000 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (6) 4/0 500 kcmil (6) 4/0 500 kcmil (6) 4/0 500 kcmil 2500 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (8) 4/0 500 kcmil (8) 4/0 500 kcmil (8) 4/0 500 kcmil (3) 350 kcmil Cu ONLY (3) 400 kcmil Cu ONLY (4) 500 kcmil Cu ONLY (3) 600 kcmil Cu ONLY (3) 750 kcmil Cu ONLY (5) 500 kcmil Cu ONLY (4) 600 kcmil Cu ONLY (4) 750 kcmil Cu ONLY (6) 500 kcmil Cu ONLY (5) 600 kcmil Cu ONLY (5) 750 kcmil Cu ONLY (7) 500 kcmil Cu ONLY (6) 600 kcmil Cu ONLY (6) 750 kcmil Cu ONLY Catalog Number GTB08P1CL GTB08P1CM GTB12P2CN GTB12P2CP GTB12P2CQ GTB16P3CR GTB16P3CS GTB16P3CT GTB20P4Cu GTB20P4Cu GTB20P4CW GTB25P5CX GTB25P5CY GTB25P5CZ Price U.S. $

15

Note: Line side factory installed 3/8" bolt provisions for 1-hole compression lugs (lugs furnished by others). Note: Load side factory installed Burndy, 2-hole, short barrel compression lugs suitable for COPPER WIRE ONLY. Note: Requires 45-inch (1143.0 mm) wide enclosure.

Table 15-29. Roll-up Generator Termination Box with Line 1-Hole Compression Lug PROVISIONS; Load 1-Hole Compression Lugs
Ampere Rating 800 1200 1600 2000 2500 Dimensions in Inches (mm) HxWxD 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00. (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 78.00 x 36.00 x 24.00 (1981.2 x 914.4 x 609.6) 1-Hole Compression Line Provisions 1-Hole Compression Load Provisions Only Number and Range Only Number and Range (3) Provisions Per Phase (4) Provisions Per Phase (5) Provisions Per Phase (6) Provisions Per Phase (8) Provisions Per Phase (3) Provisions Per Phase (4) Provisions Per Phase (5) Provisions Per Phase (6) Provisions Per Phase (8) Provisions Per Phase Catalog Number GTB08P1P1 GTB12P2P2 GTB16P3P3 GTB20P4P4 GTB25P5P5 Price U.S. $

Note: Line and load side factory installed 3/8" bolt provisions for 1-hole compression lugs (lugs furnished by others).

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 CA08101001E For more information visit: www.eaton.com

15-22

Switchboards Roll-up Generator Termination Box


February 2007

Technical Data
Table 15-30. Roll-up Generator Termination Box with Line 1-Hole Compression Lug PROVISIONS; Load PROVISIONS ONLY 2-Hole Compression Lugs
Ampere Rating 800 1200 1600 2000 2500 Dimensions in Inches (mm) HxWxD 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 1-Hole Compression Line Provisions ONLY Number and Range (3) Provisions Per Phase (4) Provisions Per Phase (5) Provisions Per Phase (6) Provisions Per Phase (8) Provisions Per Phase 2-Hole Compression Load Provisions Catalog ONLY Number and Range Number (3) Provisions Per Phase (4) Provisions Per Phase (5) Provisions Per Phase (6) Provisions Per Phase (8) Provisions Per Phase GTB08P1PA GTB12P2PB GTB16P3PC GTB20P4PD GTB25P5PE Price U.S. $

Note: Line side factory installed 3/8" bolt provisions for 1-hole compression lugs (lugs furnished by others). Note: Load side factory installed 1/2" bolt provisions on 1 3/4" hole centers for 2-hole compression lugs (lugs furnished by others). Note: Requires 45-inch (1143.0 mm) wide enclosure.

Table 15-31. Roll-up Generator Termination Box with Line 1-Hole Compression Lug PROVISIONS; Load Mechanical Box Lugs
Ampere Rating 800 1200 1600 2000 2500 Dimensions in Inches (mm) HxWxD 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 2-Hole Compression Line Provisions ONLY Number and Range (3) Provisions Per Phase (3) Provisions Per Phase (4) Provisions Per Phase (4) Provisions Per Phase (5) Provisions Per Phase (5) Provisions Per Phase (6) Provisions Per Phase (6) Provisions Per Phase (8) Provisions Per Phase (8) Provisions Per Phase Mechanical Box Lugs Load Catalog Termination Number, Range and Type Number (3) 4/0 500 kcmil (2) 3/0 750 kcmil (4) 4/0 500 kcmil (3) 3/0 750 kcmil (5) 4/0 500 kcmil (4) 3/0 750 kcmil (6) 4/0 500 kcmil (5) 3/0 750 kcmil (8) 4/0 500 kcmil (7) 3/0 750 kcmil GTB08PAMA GTB08PAMB GTB12PBMC GTB12PBMD GTB16PCME GTB16PCMF GTB20PDMG GTB20PDMH GTB25PEMJ GTB25PEMK Price U.S. $

15

Note: Line side factory installed 1/2" bolt provisions on 1 3/4" hole centers for 2-hole compression lugs (lugs furnished by others). Note: Load side mechanical lugs are factory selected and installed. Note: Requires 45-inch (1143.0 mm) wide enclosure.

Table 15-32. Roll-up Generator Termination Box with Line 2-Hole Compression Lug PROVISIONS; Load 1-Hole Compression Lugs
Ampere Rating 800 1200 1600 2000 2500 Dimensions in Inches (mm) HxWxD 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 2-Hole Compression Line Provisions ONLY Number and Range (3) Provisions Per Phase (3) Provisions Per Phase (4) Provisions Per Phase (4) Provisions Per Phase (5) Provisions Per Phase (5) Provisions Per Phase (6) Provisions Per Phase (6) Provisions Per Phase (8) Provisions Per Phase (8) Provisions Per Phase 1-Hole Compression Load Catalog Termination Number, Range and Type Number (3) 4/0 500 kcmil Al/Cu (2) 3/0 750 kcmil Al/Cu (4) 4/0 500 kcmil Al/Cu (3) 3/0 750 kcmil Al/Cu (5) 4/0 500 kcmil Al/Cu (4) 3/0 750 kcmil Al/Cu (6) 4/0 500 kcmil Al/Cu (5) 3/0 750 kcmil Al/Cu (8) 4/0 500 kcmil Al/Cu (7) 3/0 750 kcmil Al/Cu GTB08PACA GTB08PACB GTB12PBCC GTB12PBCD GTB16PCCE GTB16PCCF GTB20PDCG GTB20PDCH GTB25PECJ GTB25PECK Price U.S. $

Note: Line side factory installed 1/2" bolt provisions on 1 3/4" hole centers for 2-hole compression lugs (lugs furnished by others). Note: Load side Anderson, 1-hole compression lugs are factory selected and installed. Note: Requires 45-inch (1143.0 mm) wide enclosure.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com CA08101001E

Switchboards Roll-up Generator Termination Box


February 2007

15-23

Technical Data
Table 15-33. Roll-up Generator Termination Box with Line 2-Hole Compression Lug PROVISIONS; Load 2-Hole Compression Lugs
Ampere Rating 800 1200 Dimensions in Inches (mm) HxWxD 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 2-Hole Compression Line Provisions ONLY Number and Range (3) Provisions Per Phase (3) Provisions Per Phase (4) Provisions Per Phase (4) Provisions Per Phase (4) Provisions Per Phase 1600 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (5) Provisions Per Phase (5) Provisions Per Phase (5) Provisions Per Phase 2000 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (6) Provisions Per Phase (6) Provisions Per Phase (6) Provisions Per Phase 2500 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) (8) Provisions Per Phase (8) Provisions Per Phase (8) Provisions Per Phase 2-Hole Compression Load Termination Cu ONLY Wire Size (3) 350 kcmil Cu ONLY (3) 400 kcmil Cu ONLY (4) 500 kcmil Cu ONLY (3) 600 kcmil Cu ONLY (3) 750 kcmil Cu ONLY (5) 500 kcmil Cu ONLY (4) 600 kcmil Cu ONLY (4) 750 kcmil Cu ONLY (6) 500 kcmil Cu ONLY (5) 600 kcmil Cu ONLY (5) 750 kcmil Cu ONLY (7) 500 kcmil Cu ONLY (6) 600 kcmil Cu ONLY (6) 750 kcmil Cu ONLY Catalog Number GTB08PACL GTB08PACM GTB12PBCN GTB12PBCP GTB12PBCQ GTB16PCCR GTB16PCCS GTB16PCCT GTB20PDCu GTB20PDCu GTB20PDCW GTB25PECX GTB25PECY GTB25PECZ Price U.S. $

Note: Line side factory installed 1/2" bolt provisions on 1 3/4" hole centers for 2-hole compression lugs (lugs furnished by others). Note: Load side factory installed Burndy, 2-hole, short barrel compression lugs suitable for COPPER WIRE ONLY. Note: Requires 45-inch (1143.0 mm) wide enclosure.

Table 15-34. Roll-up Generator Termination Box with Line 2-Hole Compression Lug PROVISIONS; Load 1-Hole Compression Lugs
Ampere Rating 800 1200 1600 2000 2500 Dimensions in Inches (mm) HxWxD 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 2-Hole Compression Line Provisions ONLY Number and Range (3) Provisions Per Phase (4) Provisions Per Phase (5) Provisions Per Phase (6) Provisions Per Phase (8) Provisions Per Phase 1-Hole Compression Load Provisions Catalog Only Number and Range Number (3) Provisions Per Phase (4) Provisions Per Phase (5) Provisions Per Phase (6) Provisions Per Phase (8) Provisions Per Phase GTB08PAP1 GTB12PBP2 GTB16PCP3 GTB20PDP4 GTB25PEP5 Price U.S. $

15

Note: Line side factory installed 1/2" bolt provisions on 1 3/4" hole centers for 2-hole compression lugs (lugs furnished by others). Note: Load side factory installed 3/8" bolt provisions for 1-hole compression lugs (lugs furnished by others). Note: Requires 45-inch (1143.0 mm) wide enclosure.

Table 15-35. Roll-up Generator Termination Box with Line 2-Hole Compression Lug PROVISIONS; Load 2-Hole Compression Lugs PROVISIONS
Ampere Rating 800 1200 1600 2000 2500 Dimensions in Inches (mm) HxWxD 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 78.00 x 45.00 x 24.00 (1981.2 x 1143.0 x 609.6) 2-Hole Compression Line Provisions ONLY Number and Range (3) Provisions Per Phase (4) Provisions Per Phase (5) Provisions Per Phase (6) Provisions Per Phase (8) Provisions Per Phase 2-Hole Compression Load Provisions Catalog ONLY Number and Range Number (3) Provisions Per Phase (4) Provisions Per Phase (5) Provisions Per Phase (6) Provisions Per Phase (8) Provisions Per Phase GTB08PAPA GTB12PBPB GTB16PCPC GTB20PDPD GTB25PEPE Price U.S. $

Note: Line and load side factory installed 1/2" bolt provisions on 1 3/4" hole centers for 2-hole compression lugs (lugs furnished by others). Note: Requires 45-inch (1143.0 mm) wide enclosure.
UL is a federally registered trademark of Underwriters Laboratories Inc. NEMA is the registered trademark and service mark of the National Electrical Manufacturers Association. National Electrical Code and NEC are registered trademarks of the National Fire Protection Association, Quincy, Mass. Uniform Building Code (UBC) is a trademark of the International Conference of Building Ofcials (ICBO). Cutler-Hammer is a federally registered trademark of Eaton Corporation.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9 For more information visit: www.eaton.com

CA08101001E

15-24

Switchboards
February 2007

This page intentionally left blank.

15

For more information visit: www.eaton.com

CA08101001E

También podría gustarte