Está en la página 1de 2

As simultaneous heating and cooling operation with one outdoor unit, your environment is ensured of optimum conditions regardless

of season or space.

Heating & Cooling Synchronous Operation


MULTI V SYNC II is an advanced system that allows a single outdoor unit to perform cooling & heating simultaneously. With MULTI V SYNC II, flexible air conditioning design according to the needs of each space can be achieved without a hitch.

Heating

Cooling

Heating

Cooling

Room

Gym

Office

Kitchen Heat Recovery unit

High Energy Efficiency

With the heat recovery system, MULTI V SYNC II achieves global top level of energy efficiency(COP 5.68) and 30% of power consumption can be saved when it operates as 40% of cooling and 60% of heating compared with heat pump type.

Power Consumption Comparison


Energy Consummation Ratio(COP)

COP Max. COP (5.68)

100 Power consumption rate

30%
Saving

70

40% cooling

60% heating

Heat Pump (5HPx2)

(10HP)

Heating Operation Ratio(%)

* Outdoor temperature : 7C DB / 6C WB * Indoor temperature Heating: 20C DB/ 15C WB Cooling: 27C DB/ 19C WB

Auto Changeover

Auto Changeover function automatically changes operating mode(cooling & heating) to maintain optimum room temperature according to the outdoor and indoor temperature without any manual control.

Change Point (Heating>Cooling)


Temp

Cooling

Heating

Change Point (Cooling>Heating) +T -T


Time Setting Temp.

Heating

Cooling

Heating

Outdoor Temp. 27C / Setting Temp. 25C

Outdoor Temp. 23C / Setting Temp. 25C

* Indoor unit Line up R410A


Wall Mounted ARTCOOL Gallery ARTCOOL Mirror 4 Way Cassette
(570x570)

4 Way Cassette
(840x840)

2 Way Cassette

1 Way Cassette

Ceiling Concealed Duct

Ceiling & Floor

Ceiling Suspended

Floor Standing With Case

Floor Standing Without Case

(Low Static)

(Built-in)

(High Static)

* Outdoor unit line up


8,10,12,14,16 HP

R410A
18,20,22,24,26,28,30,32 HP 34,36,38,40,42,44,46,48 HP

* Specifications for outdoor units


Unit System(HP) Model Power supply Cooling capacity Heating capacity Dimension (WxHxD) Machine weight Unit System(HP) Model Combination unit Independent unit , V, Hz kW kW mm kg Combination unit Independent unit , V, Hz kW kW mm kg

R410A
1 Outdoor Unit

8
ARUB80LT2 ARUB80LT2
3, 380~415, 50 3, 380, 60 22.4 25.2 1280x1607x730 240

10
ARUB100LT2 ARUB100LT2
3, 380~415, 50 3, 380, 60 28.0 31.5 1280x1607x730 285

12
ARUB120LT2 ARUB120LT2
3, 380~415, 50 3, 380, 60 33.6 37.8 1280x1607x730 285 2 Outdoor Units

14
ARUB140LT2 ARUB140LT2
3, 380~415, 50 3, 380, 60 39.2 44.1 1280x1607x730 285

16
ARUB160LT2 ARUB140LT2
3, 380~415, 50 3, 380, 60 44.8 50.4 1280x1607x730 285

18

20

22

24

26

28

30

32

ARUB180LT2 ARUB200LT2 ARUB220LT2 ARUB240LT2 ARUB260LT2 ARUB280LT2 ARUB300LT2 ARUN320LT2 ARUB80LT2 ARUB80LT2 ARUB80LT2 ARUB80LT2 ARUB120LT2 ARUB140LT2 ARUB140LT2 ARUN160LT2 ARUB100LT2 ARUB120LT2 ARUB140LT2 ARUB160LT2 ARUB140LT2 ARUB140LT2 ARUB160LT2 ARUN160LT2
3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 50.4 56.0 61.6 67.2 72.8 78.4 84.0 89.6 56.7 63.0 69.3 75.6 81.9 88.2 94.5 100.8 2560x1607x730 2560x1607x730 2560x1607x730 2560x1607x730 2560x1607x730 2560x1607x730 2560x1607x730 2560x1607x730 240+285 240+285 240+285 240+285 285x2 285x2 285x2 285x2 3 Outdoor Units

Power supply Cooling capacity Heating capacity Dimension (WxHxD) Machine weight Unit System(HP) Model

34
Combination unit Independent unit

36

38

40

42

44

46

48
ARUB480LT2 ARUB160LT2 ARUB160LT2 ARUB160LT2

ARUB340LT2 ARUB360LT2 ARUB380LT2 ARUB400LT2 ARUB420LT2 ARUB440LT2 ARUB460LT2 ARUB80LT2 ARUB80LT2 ARUB80LT2 ARUB80LT2 ARUB100LT2 ARUB140LT2 ARUB140LT2 ARUB120LT2 ARUB140LT2 ARUB140LT2 ARUB160LT2 ARUB160LT2 ARUB140LT2 ARUB160LT2 ARUB140LT2 ARUB140LT2 ARUB160LT2 ARUB160LT2 ARUB160LT2 ARUB160LT2 ARUB160LT2

Power supply Cooling capacity Heating capacity Dimension (WxHxD) Machine weight
Note :

, V, Hz kW kW mm kg

3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 3, 380, 60 95.2 100.8 106.4 112.0 117.6 123.2 128.8 134.4 107.1 113.4 119.7 126.0 132.3 138.6 144.9 151.2 3840x1607x730 3840x1607x730 3840x1607x730 3840x1607x730 3840x1607x730 3840x1607x730 3840x1607x730 3840x1607x730 285x2+240 285x2+240 285x2+240 285x2+240 285x3 285x3 285x3 285x3

1. Capacities are based on the following conditions Cooling-Indoor temp. 27C[80.6F]DB / 19C[66.2F]WB Outdoor temp. 35C[95F]DB / 24C[75.2F]WB Interconnecting Piping Length 7.5m Level Difference of Zero

Heating-Indoor temp. 20C[68F]DB / 15C[59F]WB Outdoor temp. 7C[44.6F]DB / 6C[42.8F]WB Interconnecting Piping Length 7.5m Level Difference of Zero

2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. When the calculated refrigerant charge is over 95kg, multiple outdoor system must be divided into smaller independent systems. So, each system contains less than 95kg refrigerant charge.

Distributed by Air Conditioner

20 Yeouido-dong, Yeongdeungpo-gu, Yeouido P.O.Box 335 Seoul, 150-721, Korea. Phone : +82-2-3777 -7985 Fax : +82-2-3777- 5136

http://www.lgeaircon.com