Está en la página 1de 1

SINGLE-LINE DIAGRAM(SKELETON) STEP3

Messrs. :
Project : Maranta Bosques
Reference : Calculo de cortocircuito trifasico simetrico File name : MarantaT4.ms2
Engineer : CAMCh Created date : 22-11-2023
Changed : Changed date :
Comments : Para vo.bo.

23000V
CJM53090-CJM25X
465MVA
X/R=2
60Hz
23000V/440V
TN-S 440V,60Hz
T-T4 225kVA,295.2A G1 G TN-S
3.345%e 312kVA,409.4A
X/R=2.061644 17.42%e
I"k3direct=2.3495kA
400A
3Poles OFF
CB1 I"k3direct=8.6993kA CB0 400A
I"k1direct=8.6993kA 3Poles
I"k1direct(PE)=8.6993kA

Bpri I"k3=8.6993kA

50A
NF63-HW 3Poles
80A 20A 30A 40A 40A 40A 30A 40A 20A 200A
CB2 CB3 CB4 CB5 CB6 CB7 CB8 CB20 CB9 CB10 CB11 I"k3direct=8.6993kA
3Poles 3Poles 3Poles 3Poles 3Poles 3Poles 3Poles 3Poles 3Poles 3Poles
I"k1direct=8.6993kA
I"k1direct(PE)=8.6993kA

M1 M 22.38kW FILTROS L 1.63A M6 M 7.78kW


ELEVADOR 1 L 14.9A ELEVADOR 2 L 14.9A
MONTACARGAS L 19.6A TRANSFER L 11.2A M12 M 14.92kW M11 M 1.492kW 440V/220V
34.55A 12.01A 23.03A 2.303A TN-S 3Ph 16mm²x1
T-SG4 112.5kVA,295.2A N 16mm²x1
4.40%e W1 PE 16mm²x1
X/R=1.806667 0m,Cu
0.000=0.000+j0.000

400A
CB14 50A
3Poles
NF63-HW 3Poles
CB12 I"k3direct=8.6993kA
I"k1direct=8.6993kA
Bsg4 I"k3=4.8438kA I"k1direct(PE)=8.6993kA

440V/220V
TN-S
125A 40A 100A 50A
CB15 CB16 CB17 CB18 T-PTAR 30kVA,78.73A
3Poles 3Poles 3Poles 3Poles
5.010%e
X/R=1.131737

E1 L 81.3A J4 L 5.1A AA1 L 40.1A AEX L 3.9A 100A


NF125-CW 3Poles
CB13 I"k3direct=1.4453kA
I"k1direct=1.4453kA
I"k1direct(PE)=1.4453kA

Bptar I"k3=1.4453kA

M3 M 12.3kW M4 M 16.8kW
37.98A 51.87A