Documentos de Académico
Documentos de Profesional
Documentos de Cultura
Ssdc5100-Dossier Tecnico Manual Servicio - 1 To em
Ssdc5100-Dossier Tecnico Manual Servicio - 1 To em
24-sep-2014
REVISIONES
DISEÑÓ: CHLORIDE REVISIÓ: CIICS
ELABORÓ: EMERSON APROBÓ:
PROYECTO:
FABRICACION Y SUMINISTRO DE UPS CHLORIDE Y BATERIAS ENERSYS PARA EL
PROYECTO PMSI ENERGIA & VAPOR
ORDEN DE COMPRA No:
1346-01-30-E0-4270-001
TITULO:
Manual de servicio SSDC5100 (Libro técnico)
CODIGO DEL DOCUMENTO
SSDC5100-DOSSIER TECNICO
No. DE HOJAS: REVISIÓN:
116 01
2
Tabla de contenido
DOCUMENTOS DE DISEÑO
SSDC5100-HJD-01 Hojas de datos ........................................................................................ 3
SSDC5100-PLN-01 Diag. unifilar general planos de detalle con identificacion de partes.... 7
LISTA DE REPUESTOS
REVISIONES
DISEÑÓ: CHLORIDE REVISIÓ: CIICS
ELABORÓ: EMERSON APROBÓ:
PROYECTO:
FABRICACION Y SUMINISTRO DE RECTIFIACADOR CHLORIDE Y BATERIAS ENERSYS
PARA EL PROYECTO PMSI ENERGIA & VAPOR
ORDEN DE COMPRA No:
1346-01-30-E0-4270-001
TITULO:
HOJAS DE DATOS
CODIGO DEL DOCUMENTO
SSDC5100-HJD-01
No. DE HOJAS: REVISIÓN:
04 03
4
No cliente: GRB-MA0011889-12001-ID-ELE-ET-015
HOJA DE DATOS SISTEMA DE CORRIENTE CONTINUA SUBESTACIÓN ET-220
5 ELE-ET-015
De acuerdo con el numeral 5 de esta especificación De acuerdo con el numeral 5 de esta
Doc. No. GRB-MA0011889-12001-ID-ELE-ET-015 especificación
Empaques Doc. No. GRB-MA0011889-12001-ID- 1
6 ELE-ET-015
De acuerdo con el numeral 7.10 De acuerdo con el numeral 7.10
Documentación Requerida 1
7 ECP-VIN-P-ELE-ET-018 ECP-VIN-P-ELE-ET-018
De acuerdo con el numeral 7.11 De acuerdo con el numeral 7.11
Planos y Esquemas 1
8 ECP-VIN-P-ELE-ET-018 ECP-VIN-P-ELE-ET-018
De acuerdo con el numeral 7.12 De acuerdo con el numeral 7.12
Garantías 1
9 ECP-VIN-P-ELE-ET-018 ECP-VIN-P-ELE-ET-018
11 Repuestos de arranque SI SI 1
14 Asistencia técnica
15 Al montaje SI SI
16 A la puesta en servicio SI SI
35 Intercambiabilidad
Todos los componentes électricamente iguales son intercambiables SI SI
36
mecánicamente
REQUERIMIENTOS TÉCNICOS
37 Equipo paquete
38 Rectificador SI SI
SI
39 Cargador de batería (instalado en la parte inferior del gabinete) SI
40 Equipo de medida SI SI
41 Dispositivo de protección SI SI
42 Tablero de distribución SI SI
43 Banco de baterías SI SI
5
No cliente: GRB-MA0011889-12001-ID-ELE-ET-015
HOJA DE DATOS SISTEMA DE CORRIENTE CONTINUA SUBESTACIÓN ET-220
BATERIAS
44 Fabricante (1) ENERSYS Nota 3.
45 Modelo (1) ES 29
46 Tropicalización SI SI
47 Tipo de batería Plomo-Acido tipo abierta Plomo-Calcio abierta
48 Tiempo de vida esperado a 40° C 10 Años 20 años @ 25°C
49 Condiciones de tensión Baterías
50 Tensión nominal 125 Vcc 125
51 Tensión de flote nominal 135 ± 0,5% Vcc 135 ± 0,5%
52 Tensión de ecualización nominal 140 ± 0,5% Vcc 140 ± 0,5%
53 Tensión minima 100 Vcc 100
54 Condiciones de tensión Celdas
55 Tensión por celda (1) V 2
56 Tensión maxima (1) V 2,35
57 Tension minima (1) V 1,67
58 Tensión de flote nominal (1) V 2,25
59 Tensión de ecualización nominal (1) V 2,28
60 Tensión minima (1) V 1,67
61 Cargada (1) Vcc 2,25
62 75% de carga (1) Vcc 2.2 -- 2.25
Dos bancos de baterias de 60 celdas En total 120 celdas por
63 Numero de celdas Dos bancos de baterias de 60 celdas cada uno. / (1) 1
cada uno. / (1) los dos bancos.
64 Capacidad por celda 900 A-h 900 1
Por cada banco de
65 Capacidad del banco 900 A-h 900 1 baterias
66 Autonomia del banco de baterias para los A-h requeridos 24 Horas 24
67 Aumento de carga de corriente (1) A 90
Condicion de 0 - 95%
68 Tiempo de recarga luego de la descarga 12 HORAS 12 1 de descarga.
69 Celdas modulares SI SI
70 Dimensiones por celda
71 Largo (1) mm 257
72 Ancho (1) mm 274
73 Alto (1) mm 475
74 Peso por celda (1) kg 79,9
75 Dimensiones del Rack (Se incluye en el alcance)
76 Largo (1) mm 4267,2 Frente
90 Frecuencia nominal ±5 % ±5
No cliente: GRB-MA0011889-12001-ID-ELE-ET-015
HOJA DE DATOS SISTEMA DE CORRIENTE CONTINUA SUBESTACIÓN ET-220
PUERTO DE COMUNICACIONES
107 Puerto de Comunicaciones RJ-45 RJ-45
108 Protocolo de Comunicaciones ETHERNET TCP/IP ETHERNET TCP/IP
109 Puerto de Interfaz Adicional RS-232 RS-232
RECTIFICADOR
110 Equipo paquete Rectificador Autosoportado Rectificador Autosoportado 1
111 Transformador de aislamiento SI SI
116 Tropizalización SI SI
118 Calibre 12 12
REVISIONES
DISEÑÓ: CHLORIDE REVISIÓ: CIICS
ELABORÓ: EMERSON APROBÓ:
PROYECTO:
FABRICACION Y SUMINISTRO DE RECTIFICADOR CHLORIDE Y BATERIAS ENERSYS
PARA EL PROYECTO PMSI ENERGIA & VAPOR
ORDEN DE COMPRA No:
1346-01-30-E0-4270-001
TITULO:
DIAGRAMA UNIFILAR GENERAL, PLANOS DE DETALLE CON IDENTIFICACION DE PARTES Y LISTA DE
MATERIALES, DIAGRAMAS DE CONTROL Y CABLEADO, ARREGLOS PRELIMINARES CON PESOS Y DIMENSIONES
CODIGO DEL DOCUMENTO
SSDC5100-PLN-01, SSDC5100-PLN-02, SSDC5100-PLN-03,
SSDC5100-PLN-04
No. DE HOJAS: REVISIÓN:
33 06
Page Titre/Title 00 01 02 03 04 05 06 07 08 09 10 11 12 13
0 8
SUMMARY XX XX XX XX XX XX
1 CHARGER A AND B - AC SUPPLY XX XX XX XX
2 CHARGER A AND B - AC/DC CONVERTER XX XX XX XX XX
3 CHARGER A AND B - DC OUTPUT XX XX XX XX XX
4 CHARGER A AND B - VENTILATION XX XX
5 CHARGER A AND B - AUXILIARIES INPUT XX XX
6 CHARGER A AND B - DISPLAY & COMMUNIC XX XX
7 CHARGER A AND B - CANO XX XX
8 CHARGER A AND B - ALARMS XX XX
90 CHARGER A AND B - PLATE DETAILS (CHA XX XX
91
100
CHARGER A AND
CHARGER A AND
B
B
-
-
SCHEMATIC LEGEND
CUSTOMER TERMINALS
XX
XX XX
XX
XX XX
CUSTOMER : EMERSON ELECTRIC DE COLOMBIA
200 CHARGER A AND B - ELEVATION AND BASE XX XX XX XX XX
201
202
CHARGER A AND
CHARGER A AND
B
B
-
-
NAMEPLATE SCHEDULE
NAMEPLATE SCHEDULE
XX
XX
XX
XX
XX
XX
PROJECT : PMSI E&V ECOPETROL BARRANCABERMEJA
203 CHARGER A AND B - DISPLAY DETAILS-EN XX XX
204 CHARGER A AND B - DISPLAY DETAILS-SP XX XX XX EQUIPMENT : SSDC5100 125VDC DUAL BATTERY CHARGERS
500 CHARGER A AND B - SINGLE LINE DIAGRA XX XX XX XX XX
600 CHARGER A AND B - SPECIFICATION XX XX XX
B
-CB3 -T10
250A
-TB1
TO TRANSFORMER
1
1 1 2 4 P1 P2 4 (/2.03)
C
S1 S2
2
2 3 4 5 5 (/2.03)
D
-T30
3
3 5 6 6 P1 P2 6 (/2.03)
14
E
S1 S2
11 1553
1555 12
6
T10
H T30
SK3 (L1)
SK3 (L2)
SK3 (L3)
SK4 (N)
-XT
1
2
3
4
J FRT
-A90
SK5 (PE)
1000
(/2.12)
L
200
201
204
205
2A
N
(/2.11)
1500
1501
X2 81 80 77 76
(/3.03)
O (/5.08) -A20 T30 T10
I MEASURE
(/6.03) ESA F40
2A
1501
L1 L2 L3
P
INCA &
ALIN SUPPLY -S50 DOOR SWITCH
E
Q
-LIGHT50
1500 1502
R
CABINET LIGHT
07/30/2014 THL
Date Creat.
RAM
Verif.
DNG
App.
AS BUILT
DESCRIPTION
=CH1 +A1
DESIGNATION
9217-01 5 1
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
10
A
CHARGER OUTPUT
100KVA x 2 -F11 1004 P1
+
(/1.27) 4 1002 1003 P2 ~A1 + 22 22
(/3.03)
CHARGER INPUT
A a2
C
S1 S2
125VDC
5 1005 1006 1007 ~B1 -C01+ -R01
(/1.27)
B b2 -L02
D F13 -V01_1
-
- 1009 1008 1008 1008 23
-T90_1 (/3.03)
1504
E
S1 S2
-V01_2
1503
1008 23
1506
T90_1
1002
1005
1010
(Gr)
(Bl)
(Or)
(Ye)
(Br)
(Re)
(Bl)
(Gr)
(Ye)
(Or)
(Re)
(Bl)
(Gr)
(Ye)
(Or)
(Re)
(Br)
1505
T80_1
F -V01_3
1008 23
5 6 3 4 1 2 6 5 4 3 2 1 6 5 4 3 2 1
SK4 SK1 SK3
SK5.5
A301 CGCH3
1008
1008
SK5.6
1013
22
22
(/4.28)
G -XV9 Pulses Generator Board
SK2.2 6P
SK5.4 -V01_4
1014 1 1000 1008 23
(FUSE)
SK5.3
SK6.1
SK6.2
SK6.3
(FAN)
SK6.4
SK5.1
SK5.2
-A02
(T°)
SEC 1015 2 1001
1507
H (/4.28) 26 -B01 (/2.21)
1508
P.prim (Or) (Re)
>70kVA (/2.14)
1000
(/1.19) (/2.21)
1001
I (/1.19) (/2.17) (/2.17)
1018 1019 ~B
K b1 -L03
F14 1020
-
-T90_2
1021 1022 ~C
L
P1 P2
c1
1511
S1 S2
1510
(/5.20)
1513
M T90_2
(Gr)
(Bl)
(Or)
(Ye)
(Br)
(Re)
(Bl)
(Gr)
(Ye)
(Or)
(Re)
(Bl)
(Gr)
(Ye)
(Or)
(Re)
(Br)
1512
T80_2
5 6 3 4 1 2 6 5 4 3 2 1 6 5 4 3 2 1
SK4 SK1 SK3
SK5.5
N SK5.6 A302 CGCH3
Pulses Generator Board
SK2.2 6P
SK5.4
(FUSE)
SK5.3
SK6.1
SK6.2
SK6.3
(FAN)
SK6.4
SK5.1
SK5.2
(T°)
O
(/2.21)
(/2.17) (/2.17)
26
1509
(/2.21)
P -B02
(/2.15)
Q 26
(/1.09) X2 82 83
SK20.4
SK4
SK3
SK20.3
SK20.1
SK20.2
-A20 + -
R 6P 6P DC REGUL
+15V
-15V
S
0V
ESA Yd/Dy Dd/Yy
A204 A204
INCA INCA
S TO PULSES GENERATOR Idc MEASURE
05/12/2014 THL
Date Creat.
RAM
Verif.
DNG
App.
AS BUILT
DESCRIPTION DESIGNATION
=CH1 +A1 9217-01 5 2
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
11
A
B
-CB6
700A -TB2
FROM CHARGER
22 22 1 2 29
TO BATTERY
(/2.27) 1
C
+
-
D 23 23 3 4 30 -TB2
(/2.27) 2
14
11 1530
1532 12 (/5.16)
E -CB6
-V02 (/3.23)
1514
G -CB7
700A -TB7
TO BACK-UP
22 1 2 1023 1
BATTERY
H
23 3 4 1024 -TB7
I 2
22
23
(/3.25)
J
-CB7
-V03 (/3.23)
1515
K
L
C3 (Ye)-TB31 1 -B92
C3 (Gr) 2
M
(/1.09) X2 54 55 X2 78 79
SK22.4
SK22.3
SK22.2
SK22.1
SK5.1
SK5.2
SK5.3
SK5.4
+24V 0V F30
O DC EARTH 4A
DC OUTPUT FAULT + -
MEASUREMENT DC SUPPLY BAT. CURRENT BATT. AMB.
(ALIN) MEASURE TEMP. TEMP.
P -A20 A204 A204
ESA INCA INCA
05/12/2014 THL
Date Creat.
RAM
Verif.
DNG
App.
AS BUILT
DESCRIPTION
=CH1 +A1
DESIGNATION
9217-01 5 3
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
12
A
TB1:10
TB1:3
TB1:4
TB1:5
TB1:6
TB1:7
TB1:8
TB1:9
D
1517
1518
1519
1520
1521
1525
1526
1516
E
TB1:10
TB1:3
TB1:4
TB1:5
TB1:6
TB1:7
TB1:8
TB1:9
I
1524
1527
1528
1529
1530
1531
1532
1533
J -XV1 -XV1
4
1534
1535
1536
1537
1538
1539
1540
1541
K
-M05 -M06 -M07 -M08
L
CABINET FANS CABINET FANS
02/20/2014 THL
Date Creat.
RAM
Verif.
DNG
App.
AS BUILT
DESCRIPTION
=CH1 +A1
DESIGNATION
9217-01 5 4
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
13
A
14
14
-CB3 -CB6
H (/1.08) (/3.23)
1544 11
1545 11
1542
1543
1546
I (/1.09) X2 68 69 X2 70 71 X2 72 73 74 75
REMOTE INPUT BATTERY DC EARTH
ON/OFF PROTECTION PROTECTION FAULT
J -A20
PREDEFINED INPUT (RECTIFIER)
ESA
SPARE INPUT
K
TRANSFORMER
SPARE1 SPARE2 SPARE3 SPARE4 THERMOSTAT SPARE6
X2 56 57 X2 58 59 X2 60 61 62 63 64 65 66 67
L
1549
1550
3 1547
-T01
M -A501 (/2.08)
1548
(/4.04)
3 1551 2
N -A504
(/4.15)
2
02/20/2014 THL
Date Creat.
RAM
Verif.
DNG
App.
AS BUILT
DESCRIPTION
=CH1 +A1
DESIGNATION
9217-01 5 5
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
14
A
E
(/1.09)
-A20
F
ESA
SK2.2
SK2.1
SK2 SK27 SK1
RJ45
1552
J
1553
K
-A03 -A04
DC SUPPLY
+V SK6.3 19 +24V
SK1
Rx-
Rx+
Tx+
Tx-
GND
input
0V
T-
T+
R-
R+
RS232
SK2
SK6 SK7
SK4 1 2 3 4 5 6 SK3 RJ45 1 2 3 4 8
M
1555
1556
1558
1557
1554
RJ45 1555
RJ45 1556 RJ45
N 1558
1557
1554
O (/7.02) (/7.02)
(/7.03)
02/20/2014 THL
Date Creat.
RAM
Verif.
DNG
App.
AS BUILT
DESCRIPTION
=CH1 +A1
DESIGNATION
9217-01 5 6
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
15
A
EN
OP
B
R
KE
EA
BR
UT
S
C
TP
LT
S
E
LT
OU
UR
VO
VO
(/6.03)
(/6.06)
IL
R
DC
GE
FA
DC
AR
GH
N
W
CH
FA
HI
LO
D
14 14 14 14
11 11 11 11
12 (/8.04) 12 (/8.10) 12 (/8.23) 12 (/8.13)
E RLY913
24
K917
24
K919
24
K920
24
21 21 21 21
22 (/8.04) 22 (/8.10) 22 (/8.23) 22 (/8.13)
F RJ45 RJ45
-RLY913 A1(+) -K917 A1(+) -K919 A1(+) -K920 A1(+)
(Re)
(Bk)
(Re)
(Bk)
(Re)
(Bk)
(Re)
(Bk)
N13 N17 N19 N20
H 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
SK8.1
SK8.2
SK8.3
SK8.4
SK8.5
SK8.6
SK1.1
SK1.2
SK1.3
SK4
(MODBUS) SK16
SK12 SK13
+ - + - + - + - + - + - + - + -
1 2 3 13 14 15 16 17 18 19 20
TO LISA
24V 0V
I
SPARE INPUT OUTPUTS
BUSCAN
J -A221
CANO
OUTPUTS
K
1 2 3 4 5 6 7 8 9 10 11 12
+ - + - SK9 + - + - + - + - SK10 + - + - + - + - SK11 + - + -
SK5
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
L
N1 N4 N8 N11
(Re)
(Bk)
(Re)
(Bk)
(Re)
(Bk)
(Re)
(Bk)
M
-RLY901 A1(+) -RLY904 A1(+) -K908 A1(+) -K911 A1(+)
RJ45
14 14 14 14
11 11 11 11
O 12 (/8.04) 12 (/8.10) 12 (/8.16) 12 (/8.23)
RLY901 RLY904 K908 K911
24 24 24 24
21 21 21 21
22 (/8.04) 22 (/8.10) 22 (/8.16) 22 (/8.23)
P
M
ON
AR
UL
UR
TI
AL
FA
IL
A
FA
ER
Q
AL
R
GE
OP
R
T
NE
AR
PU
IN
GE
CH
IN
RY
ON
AC
E
MM
TT
R
CO
BA
S
02/17/2014 THL
Date Creat.
RAM
Verif.
DNG
App.
AS BUILT
DESCRIPTION
=CH1 +A1
DESIGNATION
9217-01 5 7
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
16
A
E
(/7.04) (/7.10) (/7.19) (/7.25)
-RLY901 -RLY904 -K908 -K911
F
G
X41 12 11
* 14 *22 21
* 24 * X41 12 11
* 14 *22 21
* 24 * X41 12 11
* 14 *22 21
* 24 * X41 12 11
* 14 *22 21
* 24 *
COMMON GENERAL ALARM CHARGER FAULT AC INPUT FAILURE BATTERY IN OPERATION
H
X41 12 11
* 14 22 21
* 24 X41 12 11
* 14 22 21
* 24 X41 12 11
* 14 22 21
* 24 X41 12 11
* 14 22 21
* 24
N
CHARGER OUTPUT BREAKER OPEN FAN FAILURE HIGH DC VOLTS LOW DC VOLTS
02/17/2014 THL
Date Creat.
RAM
Verif.
DNG
App.
AS BUILT
DESCRIPTION
=CH1 +A1
DESIGNATION
9217-01 5 8
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
17
A
TO A3 (CGCH3A SK10)
TO A3 (CGCH3B SK10)
TO BATTERY SENSOR
NOT USED
TO TEMPERATURE
TO TEMPERATURE
F
SENSOR N°1
SENSOR N°2
EARTH FAULT
AC SUPPLY DC SUPPLY MEASUREMENT
G L1 L2 L3 + + - -X2 +- -X2 +-
78
79
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
80
81
82
83
-F40 -F30
2A (/91.27) 4A 4 26 26
78
H
204
205
206
207
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
80
81
82
83
79
(/90.05)
204
SK16.1
SK16.2
SK16.3
SK16.4
SK16.5
SK16.6
SK17.1
SK17.2
SK17.3
SK17.4
SK17.5
SK17.6
SK18.1
SK18.2
SK18.5
SK18.6
SK19.3
SK19.4
SK19.5
SK19.6
SK23.1
SK23.2
SK23.4
SK23.5
SK25.1
U batterie SK25.3
SK5.1
SK5.2
SK5.3
SK5.4
SK4
SK3
SK24.1 L1
205
SK24.3 L2
206
I
6 pulses
6 pulses
SK24.5 L3
Yd/Dy
Dd/Yy
Spare 1
Spare 2
Spare 3
Spare 4
Spare 5
Spare 6
Remote On/Off
Input protection
Battery protection
DC earth fault
Temperature
Temperature
T10
T30
-X2 52
Battery
Ambiant
52 78
+24VI SK2.2 SK7 + SK1.1
53 53 79
J 0VI SK2.1 - SK1.2
-A202 E -X2
+24V 54 54
SK3.2 ALIN + SK1.3
207
SK26
-A204
SK1.5
SK1.4
34
55 55 INCA
K 0V SK3.1 SK4 SK28
SK30 SK31
202
203
SK2
OR
-T202
L A B C D E F G
H I
24V 24V 80V 80V 300V
M
0V 115V 230V 415V 480V 0V 115V 230V 415V 480V
NOT USED
N
SK41.1
SK41.3
SK36.1
SK36.2
SK36.3
SK36.4
SK36.5
SK36.6
205
204
TO A200-SK1 (CANDIS)
84
85
86
87
88
89
90
91
RJ45
O
84
85
86
87
88
89
90
91
92
93
P
-X2
+- NOT USED
02/11/2014 THL
Date Creat.
RAM
Verif.
DNG
App.
AS BUILT
DESCRIPTION
=CH1 +A1
DESIGNATION
9217-01 5 90
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
18
A
SYMBOL DESIGNATION SYMBOL DESIGNATION SYMBOL DESIGNATION AUXILLARIES
B TRANSFORMER SWITCHING & PROTECTING DEVICES POWER SEMICONDUCTORS
NORMALLY OPEN CONTACT
SW**: LOAD
INTERRUPTER SWITCH D**: DIODE
C
NORMALLY CLOSE CONTACT
XF**:3 PHASE FSW**: FUSED LOAD
TRANSFORMER INTERRUPTER SWITCH V**: THYRISTOR
D
SPDT CONTACT
CB**: CIRCUIT BREAKER
E V*: TRANSISTOR
PB**: PUSH BUTTON
F**: FUSE ELECTRICAL ELEMENTS
F H**: LED
XF**: SINGLE PHASE + BATTERY
G
TRANSFORMER K**: CONTACTOR - H**: LIGHT
K
T**: HALL EFFECT
DC CURRENT L
<--------- MEASURE DEVICE LIGHTNING ARRESTER
T
L
+15V -15V S 0V
XF**: SINGLE PHASE (1) (2) (3) (4)
AUTOTRANSFORMER
R**: RESISTOR
M
R**: SHUNT
T**: CURRENT FN**: FAN
TRANSFORMER
N
V P**:AC VOLTMETER
CHOKE ~
A**: ELECTRONIC DEVICE
O
L**: CHOKE A P**:AC AMMETER
OR SUB-ASSEMBLY
~
P
L**: SATURABLE CHOKE Hz P**:FREQUENCY METER
~
CONNECTION RULES (physical)
Q LEFT TO RIGHT:
kW P**:WATTMETER AC DEVICE : Earth/Neutral/phase 1/2/3
L**: MIXING CHOKE ~ DC DEVICE : + / -
R
+ V- P**:DC VOLTMETER
L**: FERRITE CHOKE =
STANDARD
S
+ A- P**:DC AMMETER
SYMBOLS ROTATION
=
02/07/2014 THL
Date Creat.
RAM
Verif.
DNG
App.
AS BUILT
DESCRIPTION
=CH1 +A1
DESIGNATION
9217-01 5 91
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
19
A
(/1.02)
(/1.02)
(/1.02)
(/3.26)
(/3.26)
(/3.26)
(/3.26)
(/3.26)
(/3.26)
=CH1 +A1
=CH1 +A1
=CH1 +A1
=CH1 +A1
-TB31
-TB1
-TB2
-TB7
D 1 2 3 1 2 1 2 1 2
E
1
2
3
29
30
1017
1018
C3 (Ye)
C3 (Gr)
F
G
CHARGER INPUT DC OUTPUT TO BATTERY BATTERY TEMP.
480VAC/3PH/60Hz 125VDC 125VDC PROBE
(Re)
(Bk)
(Re)
(Bk)
(Re)
(Bk)
(Re)
(Bk)
(Re)
(Bk)
(Re)
(Bk)
(Re)
(Bk)
(Re)
(Bk)
J
A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2
K
(/7.04)
(/7.10)
(/7.19)
(/7.25)
(/7.13)
(/7.22)
(/7.26)
(/7.28)
RLY901
RLY904
RLY913
=CH1 +A1
K908
K911
K917
K919
K920
-X41
14 24 14 24 14 24 14 24 14 24 14 24 14 24 14 24
M 11 21 11 21 11 21 11 21 11 21 11 21 11 21 11 21
12 22 12 22 12 22 12 22 12 22 12 22 12 22 12 22
MIN MAX
N TERMINALS cable cable NOMINAL
TYPE size size CURRENT
AWG/KCMIL AWG/KCMIL
P6 22 10 35A
P8 24 8 50A
O P10 20 6 65A
P16 16 4 85A
M
ON
EN
RE
S
AR
UL
UR
LT
LT
TI
OP
U
P32 16 1/0 150A
AL
FA
IL
IL
VO
VO
A
ER
FA
AL
KE
DC
DC
P46 2/0 500 380A
GE
OP
R
EA
N
P53 1/0 (4) 500 840A
NE
AR
PU
FA
GH
W
IN
BR
LO
GE
CH
IN
HI
Q RELAYS TERMINALS
Y
T
N
AC
U
MO
TE
TP
OU
CO
BA
ER
11 Common
R
G
CONTACT 1 12 NC
AR
14 NO
CH
21 Common
S CONTACT 2 22 NC
24 NO
The Customer shall be responsible for providing latest and most accurate technical information about the Apparatus. The Customer shall notify Emerson Network Power in writing of any change in any Apparatus. In no way shall Emerson Network Power be held liable for any inaccurate,
wrong or non notified information provided by the Customer about the Apparatus. Apparatus: Any and all equipment, machinery, materials, accessories and supplies not provided by Chloride but which are directly or indirectly linked to the Chloride equipment and its operational performance.
CHARGER A AND B - CUSTOMER TERMINALS Ind/Rev Page
05/12/2014 THL
Date Creat.
RAM
Verif.
DNG
App.
AS BUILT
DESCRIPTION
=TERMINALS +
DESIGNATION
9217-01 5 100
20
21
22
23
24
25
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
26
A
CHARGER / RECTIFIER
B INSPECTION
X BURN-IN 1HR 4HR X 8HR 36HR 72HR 200HR
HEATRUN TEST 4HR 8HR 36HR 72HR 200HR
X RIPPLE W/OUT BATTERY 2% X 1% 100mV 30mV
C
X 1% REGULATION (STD) 0.5% REGULATION
X 100% CURRENT LIMIT (NOTE 1) 115% CURRENT LIMIT 125% CURRENT LIMIT
NEMA PE5 TESTING
D X PCB TROPICALIZATION AND FUNGUS PROOFING
3/4 OZ TOUCH-UP PAINT ANSI 61 GRAY
E *NOTE1 - CURRENT LIMIT IS LISTED AS 100% OF RATED 700A OUTPUT.
700A OUTPUT RATING ALREADY CONSIDERS CUSTOMER
REQUIREMENT OF 115% CURRENT LIMIT INTO CALCULATION.
F
03/10/2014 THL
Date Creat.
RAM
Verif.
DNG
App.
AS BUILT
DESCRIPTION
=SPIDER +
DESIGNATION
9217-01 5 600
27
28
29
30
31
NOTES
32
.375 DIA. CONSTRUCTION :SWITCHBOARD IS BUILT AND LABELED PER UL 891 IN EFFECT.
4.56 INCOMING :AMPERES: 800
SERVICE :SYSTEM VOLTAGE: 125 2W DC
3.00
3.00
3.00
3.00
26.00 26.00 2.19 INTERRUPTING :THE SHORT CIRCUIT INTERRUPTING CAPABILITY IS 30,000
RATING :RMS SYMMETRICAL AMPERES AT 125 VOLTS BASED ON THE LOWEST SHORT CIRCUIT
TYPICAL BOLTDOWN CURRENT RATING OF THE INDIVIDUAL OR SERIES RATED COMBINATION DEVICES INSTALLED
2.50 2.50 HOLE PROVISION FOR AT TIME OF MANUFACTURE OF BUSSING STRUCTURE. THE BUSSING STRUCTURE IS
CUBICLE BOTTOM EACH CONSTRUCTED TO WITHSTAND FAULTS OF 42,000 RMS SYMMETRICAL AMPERES.
17.00 17.00 SECTION ENCLOSURE :ENCLOSURE IS TYPE NEMA 2/1A FOR INDOOR DRIP PROOF APPLICATION WITH
20.00 15.00
12.00
RESTRICTED
12.00
RESTRICTED
15.00 20.00
IF PROVISIONS ALLOW, INCOMING
GASKETS ON ALL EXTERIOR COVERS.
AREA AREA LUGS EXTERIOR :SPECIAL RAL 7032 PAINT.
2.50 TOP & BOTTOM TOP & BOTTOM 2.50
REDUCED NUMBER OF TERMINATIONS :TERMINATIONS ARE ACCESSIBLE FROM THE FRONT.
LOAD LUGS
CONDUIT CONDUIT METERS WITH SELECTOR BARRIER
BUS BARS :SILVER PLATED COPPER BUS BARS SIZED ON BASIS OF 65°C MAXIMUM
TEMPERATURE RISE.
SWITCH WILL BE USED.
DC AMMETERS NEUTRAL
DISCONNECT
BUS BARS :THE SWITCHBOARD THROUGH BUS SHALL BE EXTENDED ON THE INCOMING SECTION
TO ALLOW FUTURE SECTION ADDITIONS.
LINK BUS BARS :THE GROUND BUS IN THIS SWITCHBOARD IS Copper SIZED PER UL 891 OR
GREATER.
Supply =800 Supply =800 BONDING STRAP
CUBICLE DEPTH
3.00
3.00
Section =800 Section =800
(NOMINAL) CONCEALED
SUSE UL SUSE UL SEE PLAN VIEW HINGES
KIT
40.00"
8.75 8.75
KIT
KIT
KIT
7.5 7.5
10.00" 75.0 2.5 75.0 2.5 'UL' INDICATES THAT THE MARKED SWITCHBOARD SECTION COMPLIES WITH ALL APPLICABLE
UNDERWRITERS LABORATORIES STANDARDS AND IS IDENTIFIED WITH A UL LABEL.
7.5 7.5 'SUSE' INDICATES THAT THE MARKED SWITCHBOARD SECTION IS SUITABLE ONLY FOR USE
0.00
AS SERVICE ENTRANCE EQUIPMENT.
SECTION# 1 SECTION# 2 (DRIPHOOD)
32.00 32.00 'UNUS. SPACE' INDICATES UNUSABLE SPACE NOT INTENDED FOR FUTURE USE.
'B' INDICATES A SERVICE BARRIER.
800 A CU 800 A CU
PER Ø PER Ø
800 A CU 800 A CU
PER Ø PER Ø
A A
600 A/2 LXD6 600 A/2 LXD6
A A
700 A/2 LM 700 A/2 LM
LMX2B LMX2B
700 A/2 LM 700 A/2 LM
JOB
LMX2B LMX2B
(3)500 (3)500
Job 9217 5-20-14
P.O. CUST.
- U P SYSTEMS INC
CONTR CONSLT
- -
TIE BY ENG. LOC. DESIGNATION
- andrcx
S.O. DATE E170 1000_1
- 6-4-2014
APP. MFG. LOC. DWG. NO.
1 0 julija 6-4-2014
E170
andrcx000_05201400_00_00_O00-21000-1
(1)#6-300 MCM
GRD LUG(s)
(1)#6-300 MCM
GRD LUG(s)
Siemens Industry, Inc. APP. DWG. FILE
REV.
SECTION DRAWN
BARRIER
NO. REVISIONS
BY:
DATE
Norcross, Georgia SHEET 1 OF 1 1
NOTES
33
.375 DIA. CONSTRUCTION :SWITCHBOARD IS BUILT AND LABELED PER UL 891 IN EFFECT.
4.56 INCOMING :AMPERES: 600
SERVICE :SYSTEM VOLTAGE: 125 2W DC
3.00
3.00
26.00 2.19 INTERRUPTING :THE SHORT CIRCUIT INTERRUPTING CAPABILITY IS 30,000
RATING :RMS SYMMETRICAL AMPERES AT 125 VOLTS BASED ON THE LOWEST SHORT CIRCUIT
TYPICAL BOLTDOWN CURRENT RATING OF THE INDIVIDUAL OR SERIES RATED COMBINATION DEVICES INSTALLED
2.50 HOLE PROVISION FOR AT TIME OF MANUFACTURE OF BUSSING STRUCTURE. THE BUSSING STRUCTURE IS
CUBICLE BOTTOM EACH CONSTRUCTED TO WITHSTAND FAULTS OF 42,000 RMS SYMMETRICAL AMPERES.
17.00 SECTION ENCLOSURE :ENCLOSURE IS TYPE NEMA 2/1A FOR INDOOR DRIP PROOF APPLICATION WITH
20.00 15.00
12.00 DC VOLTMETER TO BE MOUNTED AS GASKETS ON ALL EXTERIOR COVERS.
RESTRICTED INCOMING
AREA PERMITTED PER SPACE ALLOWANCE TO BE LUGS EXTERIOR :SPECIAL RAL 7032 PAINT.
2.50 TOP & BOTTOM DETERMINED DURING INSTALLATION. TERMINATIONS :TERMINATIONS ARE ACCESSIBLE FROM THE FRONT.
LOAD LUGS
CONDUIT BUS BARS :SILVER PLATED COPPER BUS BARS SIZED ON BASIS OF 65°C MAXIMUM
BARRIER TEMPERATURE RISE.
NEUTRAL BUS BARS :THE GROUND BUS IN THIS SWITCHBOARD IS Copper SIZED PER UL 891 OR
GREATER.
DISCONNECT
LINK
Supply =600 BONDING STRAP
CUBICLE DEPTH
3.00
3.00
Section =600
(NOMINAL) CONCEALED
SUSE UL SEE PLAN VIEW HINGES
5.0
40.00"
KIT
8.75
KIT
30.00"
8.75 ABBREVIATIONS
KIT
20.00"
8.75
5.0
10.00" 75.0 2.5 'UL' INDICATES THAT THE MARKED SWITCHBOARD SECTION COMPLIES WITH ALL APPLICABLE
UNDERWRITERS LABORATORIES STANDARDS AND IS IDENTIFIED WITH A UL LABEL.
7.5 'SUSE' INDICATES THAT THE MARKED SWITCHBOARD SECTION IS SUITABLE ONLY FOR USE
0.00
AS SERVICE ENTRANCE EQUIPMENT.
SECTION# 1 (DRIPHOOD)
32.00 'UNUS. SPACE' INDICATES UNUSABLE SPACE NOT INTENDED FOR FUTURE USE.
'B' INDICATES A SERVICE BARRIER.
600 A CU
PER Ø
1 0 andrcx 6-4-2014
E170
andrcx000_05201400_00_00_O00-23000-1
(1)#6-300 MCM
GRD LUG(s)
Siemens Industry, Inc. APP. DWG. FILE
REV.
DRAWN
NO. REVISIONS
BY:
DATE
Norcross, Georgia SHEET 1 OF 1 1
NOTES
34
.375 DIA. CONSTRUCTION :SWITCHBOARD IS BUILT AND LABELED PER UL 891 IN EFFECT.
4.56 INCOMING :AMPERES: 400
SERVICE :SYSTEM VOLTAGE: 125 2W DC
3.00
3.00
14.00 2.19 INTERRUPTING :THE SHORT CIRCUIT INTERRUPTING CAPABILITY IS 30,000
RATING :RMS SYMMETRICAL AMPERES AT 125 VOLTS BASED ON THE LOWEST SHORT CIRCUIT
TYPICAL BOLTDOWN CURRENT RATING OF THE INDIVIDUAL OR SERIES RATED COMBINATION DEVICES INSTALLED
2.50 HOLE PROVISION FOR AT TIME OF MANUFACTURE OF BUSSING STRUCTURE. THE BUSSING STRUCTURE IS
CUBICLE BOTTOM EACH CONSTRUCTED TO WITHSTAND FAULTS OF 42,000 RMS SYMMETRICAL AMPERES.
SECTION ENCLOSURE :ENCLOSURE IS TYPE NEMA 2/1A FOR INDOOR DRIP PROOF APPLICATION WITH
20.00 15.00 GASKETS ON ALL EXTERIOR COVERS.
INCOMING
LUGS EXTERIOR :SPECIAL RAL 7032 PAINT.
2.50
TOP & BOTTOM TERMINATIONS :TERMINATIONS ARE ACCESSIBLE FROM THE FRONT.
LOAD LUGS
CONDUIT BUS BARS :SILVER PLATED COPPER BUS BARS SIZED ON BASIS OF 65°C MAXIMUM
BARRIER TEMPERATURE RISE.
NEUTRAL BUS BARS :THE GROUND BUS IN THIS SWITCHBOARD IS Copper SIZED PER UL 891 OR
GREATER.
DISCONNECT
LINK
Supply =400 BONDING STRAP
CUBICLE DEPTH
3.00
3.00
Section =-
(NOMINAL) CONCEALED
UL SEE PLAN VIEW HINGES
60.00"
50.00"
90.00
40.00"
30.00"
ABBREVIATIONS
SIEMENS
20.00"
70.0
10.00" 'UL' INDICATES THAT THE MARKED SWITCHBOARD SECTION COMPLIES WITH ALL APPLICABLE
UNDERWRITERS LABORATORIES STANDARDS AND IS IDENTIFIED WITH A UL LABEL.
10.0 'SUSE' INDICATES THAT THE MARKED SWITCHBOARD SECTION IS SUITABLE ONLY FOR USE
0.00
AS SERVICE ENTRANCE EQUIPMENT.
SECTION# 1 (DRIPHOOD)
20.00
N JOB
1 0 andrcx 6-4-2014
-
andrcx000_05201400_00_00_O00-24000-1
(1)#6-300 MCM
GRD LUG(s)
Siemens Industry, Inc. APP. DWG. FILE
REV.
DRAWN
NO. REVISIONS
BY:
DATE
Norcross, Georgia SHEET 1 OF 1 1
PANELBOARD NOTES
35
DESIGNATION : SDC5100A
SECTION :1 OF 1
PANEL TYPE :P2
CATALOG NUMBER :P2N90BQ100FBS
ENCLOSURE :1 Indoor
SYSTEM VOLTAGE :125V DC 2 Pole Branches Only
IR RATING :10 K AIC
1 2 MAIN BUS :100 A
3 4
BUS MATERIAL :Copper Tin
5 6
1 2
FEED :Bottom
7 20A/2P 20A/2P 8
BQD BQD
9 3 4 10 MOUNTING :Surface
11 5 20A/2P 20A/2P 6 12 SE LABEL :No
KIT 6.0
BQD BQD
13 7 8 14 SERIES RATED :No
15 9 PROV PROV 10 16 CONDUIT AREA :NA
17 11 PROV PROV 12 18 *INDICATES POSITIONING NUMBERS TO HELP WITH THE
19 13 20A/2P 20A/2P 14 20 MANUAL PLACEMENT OF BREAKERS ON THE MECHANICAL VIEW
BQD BQD
21 15 16 22
23 17 20A/2P 20A/2P 18 24
KIT 6.0
BQD BQD
25 19 20 26
27 21 20A/2P 20A/2P 22 28
BQD BQD
29 23 24 30
31 25 20A/2P 20A/2P 26 32
BQD BQD
33 27 28 34
29
PANELBOARD COMPONENTS
35 20A/2P 20A/2P 30 36
KIT 6.0
BQD BQD
37 31 32 38
39 33 20A/2P 20A/2P 34 40
BQD BQD Main :
41 35 36 42 1 - 100A /2P-BQD MAIN BREAKER
43 37 20A/2P 20A/2P 38 44 1-(1)#8-#1 Cu / #6-#1/0 Al
BQD BQD
45.0 45 39 40 46
Branches :
47 41 20A/2P 20A/2P 42 48 12 - 15A /2P-BQD
KIT 6.0
BQD BQD
49 43 44 50 28 - 20A /2P-BQD
51 45 20A/2P 20A/2P 46 52 4 - BL/BQD PROVISION
BQD BQD
53 47 48 54
68.0 Options :
55 49 20A/2P 20A/2P 50 56
BQD BQD 1-Std Al/Cu Gnd Connector
57 51 52 58 1-Certification - UL
59 53 20A/2P 20A/2P 54 60 1-No Front
KIT 6.0
BQD BQD
73 67 68 74
75 69 15A/2P 15A/2P 70 76
BQD BQD
77 71 72 78
79 73 15A/2P 15A/2P 74 80
BQD BQD
81 75 76 82
83 77 15A/2P 15A/2P 78 84
KIT 6.0
BQD BQD
85 79 80 86
87 81 15A/2P 15A/2P 82 88
BQD BQD
89 83 84 90
MAIN
BQD
100A/2P
- andrcx
S.O. DATE - SDC5100A
- 5-30-2014
DWG. NO.
1 0 andrcx 5-30-2014
andrcx000_05201400_00_00_O00-24020
Siemens Industry, Inc. APP. MFG. LOC. REV.
NO. REVISIONS DRAWN BY DATE -
Norcross, Georgia
APP. DWG. FILE SHEET 1 OF 2 1
PANELBOARD NOTES
36
DESIGNATION : SDC5100A
SECTION :1 OF 1
SWG5101+SK7 A
1 2 SWG5101+SK8 PANEL TYPE :P2
C
BQD 20A/2P 3 4 BQD 20A/2P CATALOG NUMBER :P2N90BQ100FBS
A
SWG5101+SK1 5 6 SWG5101+SK7 ENCLOSURE :1 Indoor
C
BQD 20A/2P 7 8 BQD 20A/2P
A SYSTEM VOLTAGE :125V DC 2 Pole Branches Only
PROV 9 10 PROV
C IR RATING :10 K AIC
PROV 11 A
12 PROV
SWG5101+SK10 13 14 SWG5102+H3 MAIN BUS :100 A
C
BQD 20A/2P 15 16 BQD 20A/2P BUS MATERIAL :Copper Tin
A
SWG5102+H4 17 18 SWG5102+H5 FEED :Bottom
C
BQD 20A/2P 19 20 BQD 20A/2P MOUNTING :Surface
A
SWG5102+H1 21 22 SWG5102+H7
C SE LABEL :No
BQD 20A/2P 23 24 BQD 20A/2P
A
SWG5103+M5 25 26 SWG5103+M7 SERIES RATED :No
C
BQD 20A/2P 27 28 BQD 20A/2P CONDUIT AREA :NA
A *INDICATES POSITIONING NUMBERS TO HELP WITH THE
SWG5103+M3 29 30 BQD 20A/2P
C MANUAL PLACEMENT OF BREAKERS ON THE MECHANICAL VIEW
BQD 20A/2P 31 32 BQD 20A/2P
A
SWG5103+M4 33 34 SWG5103+M10
C
BQD 20A/2P 35 36 BQD 20A/2P
A
SWG5103+M10 37 38 SPC5100+N3
C
BQD 20A/2P 39 40 BQD 20A/2P
A
SPC5100+N5 41 42 SPC5100+N5
C
BQD 20A/2P 43 44 BQD 20A/2P
A
STSG5100+N3 45 46 STSG5100+N4 ABBREVIATIONS
C
BQD 20A/2P 47 48 BQD 20A/2P
A
STSG5100+N5 49 50 RTU5100A
C 'DM' DIGITAL METER
BQD 20A/2P 51 52 BQD 20A/2P
A
RTU5100B 53 54 SPARE
C
BQD 20A/2P 55 56 BQD 20A/2P
A
SPARE 57 58 SPARE
C
BQD 20A/2P 59 60 BQD 20A/2P
A
TRF5100A 61 62 TRF5100B
C
BQD 15A/2P 63 64 BQD 15A/2P
A
TRF5100C 65 66 TRF5100D
C
BQD 15A/2P 67 68 BQD 15A/2P
A
TRF5100E 69 70 TRF5100F
C
BQD 15A/2P 71 72 BQD 15A/2P
A
CPTR5100 73 74 87L220
C
BQD 15A/2P 75 76 BQD 15A/2P
A
RTU-COM 77 78 SPARE
C
BQD 15A/2P 79 80 BQD 15A/2P
A
SPARE 81 82 SPARE
C
BQD 15A/2P 83 84 BQD 15A/2P
BQD
100A/2P
JOB
- andrcx
S.O. DATE - SDC5100A
- 5-30-2014
DWG. NO.
andrcx000_05201400_00_00_O00-24020
Siemens Industry, Inc. APP. MFG. LOC. REV.
-
Norcross, Georgia
APP. DWG. FILE SHEET 2 OF 2 1
37
DC OUTPUT
CB6 Breaker, 2 Pole, 700AT Siemens MD62B700 1
CBS-AUX/ST Breaker AUX, Form C Contact/Shunt Trip Siemens S11MN64A 1
CB7 Breaker, 2 Pole, 700AT Siemens MD62B700 1
CB7-AUX/ST Breaker AUX, Form C Contact/Shunt Trip Siemens S11MN64A 1
V02, V03 600V 6A Fast Recovery Diode SOLID STATE MR756 2
TB2 Power Stud Block, 600V, 840A, 2P, 3/8" STUD MARATHON 1442614 1
TB7 Power Stud Block, 600V, 840A, 2P, 3/8" STUD MARATHON 1442614 1
TB31 Terminal Blcok, 35A/600V, DR Mount, 26-10AWG, Beige Weidmuller 1020100000 2
TB31-ACC Terminal Block end plate, Weidmuller tb 1020100000 Weidmuller 1050000000 1
TB31-ACC Din Rail End Stop Entrelec 399903.02 2
B92 SMA-07 CTN SENSOR APODYS CIS 5904120007 1
B92-CBL HTA* SENSOR CABLE L=2500mm CIS 5011700016 1
VENTILATION
A501 PCB, FAN FAIL CIRCUIT CIS C500FFC-4C 1
A504 PCB, FAN FAIL CIRCUIT CIS C500FFS-2C 1
TS11 FAN THERMOSTAT, NO, 32 TO 140F STEG0 01141.9-00 1
M01, M02, M03, M04 FAN, 4 [in], 115VAC 110CFM, Pigtail wires ORION OA109AP-11-1WB 4
M05, M06, M07, M08 FAN, 10 [in], 115VAC 110CFM, Pigtail wires ORION OA254AP-11-1WB 4
M05, M06, M07, M08 Fan Guard 10 [in] ORION G25410P 2
DISPLAY AND COMMUNICATION
A200 PCB, CANDIS-10, TROPICALIZED CIS 6911110010 1
A200 PCB, CANDIS, KEYPAD, TROPICALIZED CIS 6911390000 1
A03 LISA-00 CARTE LIAISON ISOLEE SERIE APODYS CI1122 INDICE3, CIS 6911220000 1
TROPICALIZED
A04 Ethernet module(A82), XPRESS-DR-IAP CIS 5702600022 1
RJ-45 CABLE CAT.5E SHIELDED GRAY 2M Assmann Elect. A-MCSP-80020-R 1
RJ-45 CABLE CAT.5E SHIELDED GRAY 1M Assmann Elect. A-MCSP-80010-R 2
RJ-45 CABLE CAT.5E SHIELDED GRAY 3M Assmann Elect. A-MCSP-80030-R 2
39
REVISIONES
DISEÑÓ: CHLORIDE REVISIÓ: CIICS
ELABORÓ: EMERSON APROBÓ:
PROYECTO:
FABRICACION Y SUMINISTRO DE RECTIFICADOR CHLORIDE Y BATERIAS ENERSYS
PARA EL PROYECTO PMSI ENERGIA & VAPOR
ORDEN DE COMPRA No:
1346-01-30-E0-4270-001
TITULO:
DIAGRAMAS DE CONTROL Y CONEXIONADO
CODIGO DEL DOCUMENTO
SSDC5100-PLN-03
No. DE HOJAS: REVISIÓN:
06 02
41
42
43
44
45
46
04-07-2014
REVISIONES
DISEÑÓ: CHLORIDE REVISIÓ: CIICS
ELABORÓ: EMERSON APROBÓ:
PROYECTO:
FABRICACION Y SUMINISTRO DE RECTIFIACADOR CHLORIDE Y BATERIAS ENERSYS
PARA EL PROYECTO PMSI ENERGIA & VAPOR
ORDEN DE COMPRA No:
1346-01-30-E0-4270-001
TITULO:
ESPECIFICACIÓN DE PREPARACIÓN DE SUPERFICIES Y PINTURA
CODIGO DEL DOCUMENTO
SSDC5100-CER-02
No. DE HOJAS: REVISIÓN:
06 01
47
Work
Work Instruction
Electrostatic Painting Instruction QWI-7.4-14
Name:
ID:
Applicable Pages: 5 Issued Date: 02-03-13 Revision: 0
Management
Approved by: Representative Applicable Dept: Mechanical Date: 03/12/13
General Workflow
No
Remove heavy grease
Subassemblies Remove job number
Yes from parts with
and specs are Yes label and retain to Dry parts and stage
mineral spirits using a
received with De- place back on when for the painting
clean rag. Prime the
electrostatic burred? painting process is area.
parts as per paint
paint completed. specifications.
requirement
Ensure
proper If applicable,
ventilation Prepare Once setup is inspect air
and apply Paint RAL complete, filters (to be
Apply 2 coats or
by spraying 7032 Gray, thoroughly prep replaced
Texture (if final Hang parts
with Titan Sherwin the parts with biweekly or
required) finishing in the
Aircoat and Williams washes/ as needed).
End using HVLP shall be a painting
Stati-Kit POLANE primers. Ensure Otherwise,
without maximum area/painting
2000. If HS Plus, or parts are ensure proper
electrostatic of 2.5 mils booth.
texture as specified grounded with ventilation as
on. or as
needed, by clamps before per applicable
specified
apply a coat customer painting. safety
for project.
without guidelines
Stati-Kit.
1. Introduction / Purpose
The purpose of this Work Instruction is to control the method used for
electrostatic painting over galvannealed steel. This procedure is intended to
produce an end result closely similar to that of the standard Painting Work
Instruction (QWI-7.4-7).
CIS NA uses for all panels, doors, and rail structures Galvannealed carbon steel
sheet coated with a zinc coating on both sides by a continuous hot-dip process.
The galvannealed surface has a non-spangled matte finish, a finish very different
than the highly metallic appearance of the galvanized coating. One of the primary
attributes of the galvannealed coating is that the surface readily accepts paint.
Galvannealed surfaces can be painted without the application of a pretreatment.
In the case of electrostatic painting, a pretreatment will be applied when called by
the paint manufacturer’s specifications.
The zinc-iron alloy coating on galvannealed carbon steel behaves very differently
from the soft galvanized coating. Since galvannealed carbon steel is intended to
be painted, a thinner coating can be successfully applied to provide long product
life. Additionally, the coating is less reactive when exposed to the atmosphere,
and the dissolution that occurs during corrosion occurs more slowly than for a
galvanized coating. Thus, the coating does not have to be as thick as a
galvanized coating to provide the same level of protection. The synergy between
the lower overall corrosion rate of the galvannealed coating and the paint
provides excellent corrosion resistant characteristics.
Preparation for painting galvannealed steel is usually simple (as described is this
document), but for the purpose of electrostatic painting, manufacturer-
recommended practices shall be implemented in to remove all foreign
substances and contaminates typical of jobsites. Prime painting of Galvanneal
Steel prior to finish shall also be carried as/when recommended by the paint
manufacturer.
2. Scope
This Work Instruction applies to all panels, doors and structures being fabricated
with galvannealed carbon steel for every unit or job.
3. Instructions
WARNING
Flammable Products: Read all safety and warning labels before using
products. Keep away from high temperatures, sparks, and flames. Do not
ingest. In case of ingestion do not induce vomiting. Immediately seek
medical attention. Avoid contact with skin and eyes. Use this product with
adequate ventilation. Close container after each use. Contains solvents,
toxic substances, exposure to which by any means, including prolonged
inhalation, may cause serious health problems.
3.4 Painting:
• Hang panels in the painting area or booth.
• Whether painting in a booth or a general painting area, ensure that proper
ventilation exists. Always consult with supervisor when having difficulties
determining if sufficient ventilation is present.
• Wear protective face shield mask with organic vapor cartridge, painter’s
clothes (overalls), and latex gloves.
• Once the painting booth/area has been prepared, thoroughly spray the
parts with manufacturer-recommended washes/primers.
• If in a booth, ensure that primary doors are closed before the secondary
doors are opened. Exchange of air inside the painting booth should only
occur through the filters. If in a conditioned painting area, ensure that no
personnel is in painting area perimeter.
• Turn on ventilation fan if in a painting booth. If in a conditioned painting
area, verify again that ventilation is sufficient.
• Apply with Titan AirCoat and Stati-Kit , 2 even coats of RAL 7032 Gray,
Sherwin Williams POLANE HS Plus. Finishing shall be between 2 and 2.5
mils or as specified by customer. Texture finishing, required by the job,
with HVLP. For electrostatic painting, the texture is applied without the
electricity engaged (otherwise, appropriate texturing is impossible).
• When applying by electrostatic spray, use the manufacturer
recommended air pressure and volume to ensure proper atomization.
Also, ensure proper grounding, voltage, and electrostatic charge.
3.5 Completion:
After panels and frames have dried, label with work order number and stage
in panel holding area.
4. Records
For the implementation of this work instruction the following forms shall be used
weekly, by Fridays on a 10 parts sample from a randomized process.
Name
QF-8.31 Paint Thickness Measuring
Retention time and requirements for records shall be carried out as established
in Control of Records QP 4.2
5. Revision History
Revision history and details of changes are maintained in E2.
REVISIONES
DISEÑÓ: CHLORIDE REVISIÓ: CIICS
ELABORÓ: EMERSON APROBÓ:
PROYECTO:
FABRICACION Y SUMINISTRO DE 5(&7,),&$'25CHLORIDE Y BATERIAS ENERSYS PARA EL PROYECTO PMSI ENERGIA & VAPOR
ORDEN DE COMPRA No:
1346-01-30-E0-4270-001
TITULO:
LISTA DE REPUESTOS
CODIGO DEL DOCUMENTO
SSDC5100-SFO-01
No. DE HOJAS: REVISIÓN:
04 02
53
CUSTOMER CIISC
DESCRIPTION APD12-125-700-480
Date - 04/10/2013 SPARE PART LIST FOR 1COMMISSIONING
Revision - 0 SDC5100
Model No. APD12-125-700-480 ITEMS SUBJECT TO CHANGE
Parts List No. APD12-125-850-480_SP PER CUSTOMER SPECS.
Shop Job No.
PRICE SUBJECT CHANGE
Unit Quanity WITHOUT NOTICE.
TAG:
DWG ITEM DESCRIPTION VENDO MFG. PART NO. QTY Spare Type UNIT COST ea. EXT COST
R Com Sp $
F FUSE 2A, FAST ACTING, 600V AC/DC BUSSMANN KLM-2 10 X 10 EA $12,50 $125,00
F FUSE 4A, FAST ACTING, 600V AC/DC BUSSMANN KLM-4 10 X 10 EA $12,50 $125,00
CUSTOMER CIISC
DESCRIPTION APD12-125-700-480
Date - 04/10/2013 SPARE PART LIST FOR 1 YEAR
Revision - 0 SDC5100
Model No. APD12-125-700-480 ITEMS SUBJECT TO CHANGE
Parts List No. APD12-125-850-480_SP PER CUSTOMER SPECS.
Shop Job No.
PRICE SUBJECT CHANGE
Unit Quanity WITHOUT NOTICE.
TAG:
DWG ITEM DESCRIPTION VENDO MFG. PART NO. QTY Spare Type UNIT COST ea. EXT COST
R 1 Year Sp $
FN FAN, 10 [in], 115VAC 110CFM, Pigtail wires ORION OA254AP-11-1WB 3 X 3 EA $221,04 $663,12
PC PCB, FAN FAIL CIRCUIT CIS C500FFCA-4C 1 X 1 EA $338,76 $338,76
PC PCB, FAN FAIL CIRCUIT CIS C500FFCA-3S 1 X 1 EA $433,01 $433,01
FN FAN, 4 [in], 115VAC 110CFM, Pigtail wires ORION OA109AP-11-1W 2 X 2 EA $58,40 $116,80
PC PCB, Charger SCR gate drive, CGCH3-00, 250V CIS 5911280000 2 X 2 EA $667,10 $1.334,20
SC SCR/SCR MODULE (1600V/500A) SEMIKRON SKKT570/16E 6 X 6 EA $461,92 $2.771,52
F FUSE 2A, FAST ACTING, 600V AC/DC BUSSMANN KLM-2 10 X 10 EA $12,50 $125,00
F FUSE 4A, FAST ACTING, 600V AC/DC BUSSMANN KLM-4 10 X 10 EA $12,50 $125,00
PC PCB, Charger power supp, ALIN-10 (80-300VDC) CIS 5911251000 1 X 1 EA $851,40 $851,40
CUSTOMER CIISC
DESCRIPTION APD12-125-700-480
Date - 04/10/2013 SPARE PART LIST FOR 2 YEAR
Revision - 0 SDC5100
Model No. APD12-125-700-480 ITEMS SUBJECT TO CHANGE
Parts List No. APD12-125-850-480_SP PER CUSTOMER SPECS.
Shop Job No.
PRICE SUBJECT CHANGE
Unit Quanity WITHOUT NOTICE.
TAG:
DWG ITEM DESCRIPTION VENDO MFG. PART NO. QTY Spare Type UNIT COST ea. EXT COST
R 2 Year Sp $
FN FAN, 10 [in], 115VAC 110CFM, Pigtail wires ORION OA254AP-11-1WB 3 X 3 EA $221,04 $663,12
PC PCB, FAN FAIL CIRCUIT CIS C500FFCA-4C 1 X 1 EA $338,76 $338,76
PC PCB, FAN FAIL CIRCUIT CIS C500FFCA-3S 1 X 1 EA $433,01 $433,01
FN FAN, 4 [in], 115VAC 110CFM, Pigtail wires ORION OA109AP-11-1W 2 X 2 EA $58,40 $116,80
PC PCB, Charger SCR gate drive, CGCH3-00, 250V CIS 5911280000 2 X 2 EA $667,10 $1.334,20
SC SCR/SCR MODULE (1600V/500A) SEMIKRON SKKT570/16E 6 X 6 EA $461,92 $2.771,52
F FUSE 2A, FAST ACTING, 600V AC/DC BUSSMANN KLM-2 10 X 10 EA $12,50 $125,00
F FUSE 4A, FAST ACTING, 600V AC/DC BUSSMANN KLM-4 10 X 10 EA $12,50 $125,00
PC PCB, Charger power supp, ALIN-10 (80-300VDC) CIS 5911251000 1 X 1 EA $851,40 $851,40
24-sep-2014
REVISIONES
DISEÑÓ: CHLORIDE REVISIÓ: CIICS
ELABORÓ: EMERSON APROBÓ:
PROYECTO:
FABRICACION Y SUMINISTRO DE RECTIFIACADOR CHLORIDE Y BATERIAS ENERSYS
PARA EL PROYECTO PMSI ENERGIA & VAPOR
ORDEN DE COMPRA No:
1346-01-30-E0-4270-001
TITULO:
MANUALES DE INSTALACIÓN OPERACIÓN Y MANTENIMIENTO
CODIGO DEL DOCUMENTO
SSDC5100-MAN-01
No. DE HOJAS: REVISIÓN:
50 03
57
2821 West 11th Street Houston, Texas 77008
T +1 713 880 0909 F +1 713 880 0952
http:/www.ChlorideIndustrialSystems.com
DEh>/E^dZh/KE^
OPERA/KE z DEdE/D/EdK
58
Custom Power, Ltd.
Tabla de Contenido
I. Información General
Garantía Limitada
1. SEGURIDAD
Título Página
1.1. GENERALIDADES
Nota: Se utiliza una nota de este tipo para subrayar un punto importante del texto
Utilizar únicamente herramientas aisladas, en particular para conectar una batería. Colocarse
en una alfombra de caucho. Se deben retirar los efectos personales metálicos tales como
anillos, pulseras, brazaletes y collares que pueden provocar un cortocircuito así como los
objetos metálicos (bolígrafos, herramientas, etc.) que pueden caerse de los bolsillos abiertos
cuando se trabaja en las baterías y cargadores.
Colocar el equipo en MODO MANTENIMIENTO (ver párrafo 5) antes de trabajar en él.
Si es necesario efectuar ajustes con el equipo conectado con la alimentación de corriente
alterna y/o la batería, retirar únicamente las tapas protectoras absolutamente necesarias para el
acceso.
Llevar siempre protecciones para los ojos y guantes de caucho para manipular las pilas.
Manipular las pilas con cuidado, cerciorándose de que permanecen en posición vertical.
61
Modo 2. El personal que manipula el electrólito derramado debe llevar ropa adecuada,
incluidas protecciones para los ojos y guantes. El electrólito ataca muchos
tejidos. En caso de derrame en la ropa, se debe retirar y lavar a fondo con
grandes cantidades de agua limpia o tirarse.
62
1.5. BATERIA
Tipo de peligro.
Los peligros son:
Riesgo de descarga eléctrica
Riesgo de quemaduras eléctricas
Riesgo de quemaduras químicas
Riesgo de envenenamiento
DESCARGA ELECTRICA
Una descarga eléctrica de corriente continua es más peligrosa que una descarga de corriente
alterna con la misma tensión porque la corriente continua tiene las características de “NO
DEJAR ESCAPAR” a causa de la contracción de los músculos sólo en el sentido del flujo de
corriente. Se ha limitado en este equipo el riesgo de descarga de corriente continua entre los
bornes de la batería y la tierra incorporando transformadores con aislamiento de doble
bobinado en el inversor así como en el rectificador para obtener una conexión de corriente
continua totalmente flotante. Una persona en contacto con este equipo recibirá únicamente la
descarga de compensación que no provoca herida. No obstante, esta protección puede
volverse ineficaz si, por ejemplo, una herramienta metálica cae entre un borne de la batería y
la tierra (por esta razón, se prefieren los soportes de batería de madera).
El sistema sigue funcionando normalmente pero la batería y la conexión de corriente continua
pueden ser peligrosas para las personas encargadas del mantenimiento que trabajan en él.
Si se ha instalado un detector de fallo de tierra, éste va a provocar una alarma. El principio de
operación es comprobar que los rieles negativos y positivos de corriente continua son
respectivamente de tensión simétricas en relación con la tierra. Cualquier corte anormal,
incluso de alta resistencia, romperá esta simetría.
QUEMADURAS ELECTRICAS
La corriente de un cortocircuito eventual de una batería es muy alta. Por consiguiente, incluso
una pequeña pila enviará más de mil amperios en un cortocircuito tal y como una pulsera
metálica, un anillo o una herramienta no aislada. El conjunto de la batería puede componerse
de más de cien pilas en serie en muchas aplicaciones y, por consiguiente, hay un riesgo de
herida grave.
El electrólito es hidróxido de potasio (potasa cáustica). Es corrosivo para la ropa y los tejidos
vivos. Incluso trazas ínfimas pueden provocar irritación y hacer huecos en la ropa.
Protegerse los ojos, la nariz y la boca con gafas y una máscara para el rostro o llevar una
visera para el conjunto del rostro.
Protegerse el cuerpo con un mono completo.
Protegerse las manos con guantes.
Protegerse los pies con botas con costuras herméticas. Las costuras simplemente cosidas
pueden permitir la filtración.
Un lavado para ojos debe ser disponible y cualquier salpicadura debe enjuagarse con
cantidades importantes de agua o de solución salina para diluir el electrólito. Consultar con un
médico.
Un agente neutralizante debe ser disponible. Verterlo en los derrames de electrólito.
ENVENENAMIENTO
Cuando el equipo alcance el fin de su vida útil, hay que deshacerse del él con el cuidado
adecuado. Contiene materia que puede ser muy peligrosa para el medio ambiente y los
organismos vivos si no se trata convenientemente. Contactar con un servicio de tratamiento
acreditado. Las información siguientes es una guía de los problemas de eliminación conocidos
en el momento de la fabricación.
64
ELECTROLITO DE BATERIA
Las baterías de níquel cadmio contienen electrólito corrosivo de hidróxido de potasio (potasa
cáustica). No se debe nunca vaciar en dispositivos de desagüe generales o públicos. En las
baterías herméticas, el electrólito es de forma no fluida al interior de una membrana.
PLACAS DE BATERIA
Las placas son de níquel, óxidos de níquel, cadmio y óxidos de cadmio o una mezcla de estas
materias según el tipo de batería. Las placas pueden ser porosas y estar impregnadas por
hidróxido de potasio.
SEMICONDUCTORES
Los tableros de circuito están constituidos por tableros de resina y de fibra de vidrio con
circuitos de cobre. Los componentes incluyen resistores de película metálica, transistores de
silicona, transformadores (a la vez bipolares y electrolíticos), diodos de silicona, microchips
de tipo CMOS, de alta velocidad CMOS y TTL.
PANEL DE SEÑALIZACION
HILOS Y CABLES
El cableado interno está constituido de barras y de hilos de cobre cubiertos con PVC de
combustión lenta.
TERMODISIPADORES
Son de aluminio.
PIEZAS METALICAS
Son de acero suave recubierto con una capa de pintura de resina de epoxi.
65
CONDENSADORES
SEMICONDUCTORES
Contienen silicona, cobre y otros metales y componentes metálicos incluido berilio. Están
cerrados herméticamente y no deben abrirse. Si la tapa de hermeticidad está quebrada, utilizar
guantes protectores para manipular los semiconductores y colocarlos en bolsas de plástico
herméticas antes de tirarlos.
Distribución Limitada
ADVERTENCIA:
La distribución de este producto está limitada a personas
informadas. Este producto puede ser manipulado sólo por
personal autorizado a penetrar en la zona de acceso limitado.
Restricciones de instalación o medidas suplementarias pueden ser
necesarias para evitar problemas.
66
2. DESCRIPCIÓN Y FUNCIONAMIENTO
Título Página
2.1. DESCRIPCION
2.2. TOPOLOGÍA
El equipo consta de cuatro partes principales, véase la Figura 2.1. Diagrama de Bloques, el
Rectificador/Cargador, la Batería, el Inversor y el Interruptor Estático. Estos elementos se
describen por separado.
B Y -P A S S
S u m in is t r o
R e s e rv a
In te rru p to r
C a rg a d o r In v e rs o r E s t a t ic o
S u m in is t r o
R e c t if ic a d o r
CARGA
B A T E R IA
VOLTAJE
Refuerzo
Cargador
Flotante
CORRIENTE
RECTIFICADOR/CARGADOR
BATERÍA
Almacena energía procedente del cargador para usarla durante un corte de suministro cuando
descargue para alimentar al inversor y a la carga.
La autonomía del sistema durante un fallo principal depende de la capacidad en amperios por
hora de la batería instalada.
INVERSOR
Convierte la energía CC en energía CA sinusoidal. Utiliza una técnica de accionamiento de
cadencia de alta frecuencia con modulación (PWM) para lograr energía de ondulación
sinusoidal de baja distorsión mientras que conserva una buena regulación de voltaje de
respuesta de oscilación momentánea. Funciona en los modos siguientes:
INTERRUPTOR ESTÁTICO
El interruptor estático es un interruptor automático, de estado sólido, de relevo que dispone de
acción de contacto de cortocircuito para que no se produzca ninguna interrupción en la carga.
Por tanto, el inversor estará permanentemente sincronizado con la reserva para evitar saltos de
fase o incluso inversiones de fase en la carga en el instante de transferencia. Monitoriza el
estado de funcionamiento de las diversas partes del UPS y la lógica seleccionará uno de los
dos modos: INVERSOR A CARGA o RESERVA A CARGA.
Modo 1. INVERSOR A CARGA. Es el modo normal para la unidad y se selecciona
automáticamente siempre que sea posible.
Modo 2. RESERVA A CARGA. La transferencia a reserva se produce automáticamente
cuando prevalecen ciertas condiciones específicas anormales. Vuelve a inversor 10
segundos después de que desaparezcan las condiciones de alarma.
No tiene partes móviles, los componentes activos son los tiristores de conmutación para
impedir los arcos eléctricos y los destellos durante el accionamiento para proporcionar una
fiabilidad a largo plazo. Observe que las transferencias pueden producirse en cualquier punto
del ciclo, no tienen por qué estar en el cruce cero.
69
BYPASS DE MANTENIMIENTO
Por motivos de seguridad durante el mantenimiento y la reparación, se incorpora un bypass
manual cruzado en el equipo. Sólo puede seleccionarlo el operario, no puede seleccionarse a
través de la lógica de control. Proporciona aislamiento seguro de las partes internas
importantes con el objetivo de realizar reparaciones y mantenimiento.
B Y -P A S S
S u m in is tr o
R e s e rv a
In te rr u p to r
S u m in is tr o C a rg a d o r In v e r s o r E s ta tic o
R e c tific a d o r
CARGA
B a te r ia
B Y -P A S S
S u m in is t r o
R e s e rv a
In te rru p to r
S u m in is t r o C a rg a d o r In v e rs o r E s t a t ic o
R e c t if ic a t o r
C a rg a
B A T E R IA
V o lta je flo ta n te
Apagador
im m in e n te
d e l in v e r s o r
A c tiv a tio n C C
B a ja
S u m in is tro
R e s e rv a
In te rru p to r
S u m in is tro C a rg a d o r In v e rs o r E s ta tic o
R e c tific a d o r
CARGA
B A T E R IA
La sobrecarga de salida es del 105% o superior que vuelve al inversor cuando cae por debajo
del 100%
El inversor se detiene
El interruptor de MANTENIMIENTO se acciona
Una vez en reserva, esperará diez segundos hasta que todas las alarmas hayan desaparecido
para volver al inversor.
71
B Y -P A S S
S um inistro
R eserva
Interruptor
S um inistro C argador Inversor E statico
R ectificador
C arga
B A TE R IA
Titulo Paginá
4. INSTALACIÓN
Título Página
Desempaque el equipo. No tome las terminales de las baterías al mismo tiempo, para evitar
un corto circuito. No tire las llaves, conectores de la batería o accesorios cuando se deshaga
de los materiales de embalaje. Las llaves de los gabinetes vienen en una bolsa en la puerta
del gabinete.
Revise los contenidos del paquete con las notas de embarque del equipo. El equipo tiene
una placa colocada en el interior normalmente panel de la puerta en el frente que
identificará el cubículo. Informe de inmediato al transportista y proveedor si algo falta o
está dañado. El retraso en la presentación de informes puede reclamos válidos para una
reparación gratuita o el reemplazo.
No arroje los equipos y las baterías manéjalas con cuidado, deben de ser colocadas en
posición como indica las marcas del embalaje.
La caja de transportación esta diseña nada para ser manejada con montacargas y/o grúas.
Tenga en cuenta que el centro de gravedad es a menudo compensados y las cajas pueden
ser demasiado pesados, así que tenga cuidado a la posición de las horquillas de elevación de
que están en forma segura.
El equipo debe de ser dejado con grúas, Será necesario para aprobar las eslingas por debajo
de la cabina. Las eslingas se deben colocar en los extremos de la cabina con las correas de
seguridad para evitar que se caigan hacia el centro cuando está bajo tensión vertical.
4.2. ALMACENAMIENTO
Los equipos deben de ser almacenados en ambientes limpios y secos. Los equipos están
diseñados para ser operados de 0° a 40°, sin embargo pueden ser almacenados a -20°C. si el
equipo será almacenado por un periodo largo de tiempo, será necesario colocar bolsas de
protección y absorvedores de humedad.
Al guardar o enviar las baterías a temperaturas bajo cero, el electrolito no se debe permitir
la congelación, de lo contrario Pueden ocurrió daños mecánicos a las placas. La
congelación se produce en alrededor de -20 C.
75
Las baterías deben mantenerse completamente cargada, ya que mantiene el bajo punto de
congelación. Siga las instrucciones del fabricante
Una vez colocados en posición adyacente los cubículos deben de ser sujetados uno con
otros con los pernos que vienen en bolsas dentro del embalaje, para sujetar al piso por
medio de agujeros, los cuales tendrán que ser taladrados de acuerdo a las especificaciones
del dibujo de los arreglos generales.
Coloque los tornillos por los agujeros de los montantes que pasar por el panel de
separación, habrá dos en el fondo y dos en la parte superior, coloque la tuerca y apriete.
Vea los diagramas y dibujos de de arreglos generales para la posición de entrada d los
cables. El tamaño de los cables de alimentación no vienen especificados en este manual,
serán proporcionados por el personal de instalación del proyecto. Antes de insta lar los
cables revise que los apagadores e interruptores estén en posición de apagado.
Los cables de entrada al equipo deben de ser asegurados por conectores o válvulas de alivio
de tensión a las entradas de conexiones del equipo. Es válvula no está formada de manera
76
estándar así que tendrá que adecuarse a cada tipo de cable. La válvula debe de ser retirad
del gabinete para ser manipulada para las terminaciones de los agujeros. Revisar que los
cales que se dirigen al equipo tengan la suficiente holgura para evitar tensión en la terminal.
El tendido del cable se debe de sujetar a cada ½ metro en el interior del cubículo.
La conexión de fase debe de conectarse de manera adecuada para una correcta operación.
Las terminales están en marcadas para la debida conexión del equipo.
4.5.2 Batería
4.5.3 Neutro.
Dentro de la UPS si hay relación de neutro a tierra, el neutro UPS adopta el mismo
potencial que la Reserva entrante Neutral. Por lo tanto, si la entrada de la Reserva no tiene
fijo neutral de la fase de salida del UPS y el neutro va a flotar.
Nota: no instale una línea neutral que tiene dos conexiones independientes a la tierra porque
esto va a crear un bucle de tierra que puede tener el efecto de la introducción de ruido en la
salida del SAI.
4.5.4 Tierra
La tierra (barra) del gabinete debe de ser conectado a un punto de tierra física. La tierra
proporciona tanto protección y seguridad al equipos, así como un dren del ruido espurio.
Existen fugas continuas de varias decenas de mA en operación normal del equipo, por lo
tanto las fugas de tierra ELT o RCCD en la entrada deben de ser tomadas en cuenta en el
conteo de estas pérdidas.
77
4.6 VENTILACIÓN.
El calor excedente del equipo puede ser removido por ventiladores de enfriamiento o un
equipos de acondicionamiento de aire.
Las perdida por calor se especifican en el apartado 3 del manual, el cual se refiera a
especificaciones técnicas y diagramas.
Las baterías con de tipo de recombinación de ácido plomo sellado. Este tipo de baterías a
diferencia de las plomo-acida ventiladas, están regulan por medio de válvulas los gases y
son reintegrados a la batería para una recombinación. Hay varios benéficos por este tipo de
arreglo:
Peligro. Remueva cualquier parte de metal mientras trabaje con las baterías, también utilice
equipo asilado
Para las baterías en los cubículos, los bloques individuales serán atados a los estantes y las
baterías en cada estante estarán interconectados
El instalador tendrá que conectar el cable de interconexión de las baterías como se muestra
en la sección 10 del manual o en su caso por el manual que vienen en las baterías.
5. INSTRUCCIONES DE
FUNCIONAMIENTO
Título Página
Carga en reserva o
verde
inversor funcionando
intermitente Cargas alimentadas con reserva o
en la batería.
inversor funcionando en la batería.
Naranja Advertencia del UPS. Un subconjunto o más subconjuntos
están afectados pero no se detienen.
5.2. PANTALLA
Se proporcionará una Pantalla de Cristal Líquido (LCD) gráfica (64 x 128 píxeles) e iluminada para
facilitar la monitorización de los parámetros de funcionamiento, todas las medidas y el esquema
sinóptico activo del UPS. Se accederá a los mensajes de la LCD a través de los botones pulsadores,
véase figura 2. El texto estará disponible en inglés, a menos que se mencione otra cosa.
6 1 2 3
STOP
C
UPS
O Charge Inverter
K r
Para iniciar el inversor, es necesario pulsar el mismo botón durante 1 segundo: se mostrará
temporalmente el mensaje "Inverter ON" ("Inversor encendido") en la LCD y desaparecerá el
pictograma OFF del bloque del inversor.
Observación: los botones pulsadores start (inicio)/ stop (parada) se mantienen activos de
forma permanente. La acción es válida cuando aparece un mensaje ON (encendido) u OFF
(apagado) en la pantalla. A continuación, la pantalla gráfica muestra la imagen sinóptica para
confirmar el nuevo estado del UPS. La imagen sinóptica de la LCD permite comprender el
estado real tanto del cargador como del inversor para saber inmediatamente si ambos bloques
estaban apagados o encendidos antes de pulsar los botones de control.
9 Cargador
9 Batería
9 Inversor
9 Reserva
9 Carga
9 Reinicio
9 Enlace Serie
9 Prueba LED
9 Idioma
9 Contacto
9 Acerca de
5.11. ENCABEZADO
El encabezado mostrará el esquema sinóptico activo del
sistema UPS (véanse Figura 2 y Figura 3 a
continuación). Pulsando los botones “OK”, “UP”
(arriba) o “DOWN” (abajo), el usuario accederá al
menú general. Si el usuario navega por los menús,
volverá al esquema sinóptico activo pulsando el botón
“C”.
87
NOTA: si el usuario no solicita ninguna acción (como pulsar un botón) durante 5 minutos
mientras que se muestran los menús, el sistema volverá automáticamente a la pantalla del
esquema sinóptico activo del encabezado.
UPS en funcionamiento
Carga CA suministrada
Inversor no sincronizado en reserva
88
Indicaciones de fallos.
Fallo memorizado de prueba de batería. Indicaciones de medidas.
Fin de descarga. Voltaje de batería.
Protección de batería abierta. Corriente de batería.
Mensaje de fallo 1 de batería adaptada. Temperatura de batería.
Mensaje de fallo 2 de batería adaptada. Autonomía de batería.
Mensaje de fallo 3 de batería adaptada. Tiempo de autonomía de batería.
89
1
5
9
10
11 2 3 4
Lista de pictogramas:
Bloque cargador:
Bloque batería:
Batería OK
Detección de advertencias de la batería
Detección de fallos de batería
Problema de comunicación con la batería
Añadir a los pictogramas de la batería – estado de la batería:
Batería cargando
Batería descargando
90
Bloque inversor
Inversor ON y OK
Inversor ON pero con advertencias
Inversor parado a causa de la detección de fallos
Apagado voluntario del inversor
Problema de comunicación con el inversor
Bloque interruptor estático
WZ/DZWh^dEDZ,
Para un cargador Sencillo:
1. Situacion Inicial. Todos los switches, breakers y aisladores debe estar en “OFF”.
2. Cambie Alimentacion Primaria a ON. Cerrar el interruptor de entrada de AC o un Breaker
3. La pantalla LCD se enciende y comienza una secuencia de inicializacion de 10 segundos.
4. Pulse el boton “1” durante un segundo para iniciar el cargador en el display de la puerta frontal
si el bloque del cargador muestra “OFF state”.
5. Tension de salida del cargador se incrementara a la normalidad.
6. Utilice un medidor de prueba de mano para comprobar:
a. Tension del Cargardor
b. Voltaje de la Bateria
7. Si ambas Tensiones anteriores son correctas en amplitud y polaridad, Cambia el aislador de la bateria a ON.
El sistema esta ahora encendido.
Apagado de Emergencia .
Para ser utilizado en caso de una emergencia,como incendio o accidentes
PRECAUCION: Este procedimiento interrumpe la carga.
Para un Cargador Sencillo:
1. Cambie los aisladores de la Bateria a OFF.
2. Presione el boton de control “0” durante 2 segundos para detener el cargador sobre
el display de la puerta frontal.
3. Cambie aisladores Primarios a OFF.
92
6. MANTENIMIENTO DE RUTINA
Título Página
6.1. GENERALIDADES
En condiciones normales de funcionamiento, sólo se requiere mantenimiento preventivo. Los
intervalos entre las acciones de mantenimiento variarán conforme al nivel de monitorización
remota y a las normas de limpieza del cuarto del equipo.
6.5. ANUALMENTE
Lleve a cabo una descarga de prueba de la batería para comprobar la autonomía especificada.
6.6. VENTILADORES
Se considera que los ventiladores tienen una duración de 5 años. Es recomendable renovarlos
a los cuatro años de uso para evitar fallos.
94
7. DIAGNÓSTICO DE FALLOS
Título Página
En esta parte, pueden detectarse otros 3 mensajes de fallo específicos del cargador debido a la adaptación del
equipo. Compruebe estos mensajes en el dibujo de Distribución General (PA).
En esta parte, pueden detectarse otros 3 mensajes de fallo específicos de la batería debido a la
adaptación del equipo. Compruebe estos mensajes opcionales en el dibujo de Distribución
General (PA).
Qualified Personnel
For the purpose of this document a qualified person is someone who has specific knowledge
and s kills r elative t o t he oper ating o f the r espective el ectrical equi pment and t he i nstallation.
This i ndividual s hall hav e c ompleted safety t raining sufficient to r ecognize and av oid t he
hazards involved in the use and installation of the respective equipment. The qualified individual
shall also have the following qualifications:
• Proper training and authorization to energize, de-energize, clear, ground and tag circuits
and equipment in accordance with established safety practices
• Training regarding the proper use and care protective equi pment including but no t
limited to rubber gloves, safety glasses, face shields, flash clothing, etc., in accordance
with ENP/Chloride Industrial Power and end customer established safety procedures
• Properly trained in rendering first aid
• Working knowledge of applicable safety standards, building codes, laws and standards
Markings
The following markings may be i ncluded, where utilized the following terms are defined. These
terms are used to define the degree, severity, or risk of a haz ard that may be encountered by
the user.
• Danger – A “Danger” indication relates to a i mminent hazardous situation, which, if not
avoided, will result in death or serious injury
• Warning – A Warning” indication relates to a potential hazardous situation which, if n ot
avoided, could result in death or serious injury
• Caution – A “Caution” indication denotes a potentially hazardous situation which, if not
avoided may result in minor or moderate injury.
Hazardous Procedures
All users shall adhere to the following warnings:
• Danger! High Voltage. This shall be accessed by qualified personnel only! All power to
this distribution panel and equipment must be powered off before working inside. Always
work on de-energized equipment; Always de-energize all equipment before performing
any repair, maintenance, or tests.
• Warning! Always perform maintenance on the interrupting device after the closing
mechanism(s) are discharged.
• Caution! Do not defeat or force any interlock device or safety mechanism.
102
All parts, conductors, and insulation materials have been designed and constructed (commercial
3rd party) to s uit t he v oltage class o f the equi pment and a re enclosed within grounded m etal
enclosures.
The equipment furnished has been des igned to operate in a system having the circuit capacity
specified in the purchase order or from conversation between the customer and sales. Any
equipment used outside of the intended application, a different system or application, or if the
short-circuit capacity of the system is increased; the momentary rating of the switchboards, the
interrupting capacity of the protective devices and the bus capacity may not be suitable. Should
the s ervice be c hanged, the equi pment m ust be c hecked to as sure t hat t he s hort circuit
capacity, amperage and voltage class of the equipment meets or exceeds the requirement of
the new system.
The power distribution switch is a f ree-standing unit rated for the specified ampacity or less at
600 volts AC or less. The typical switchboard may contain a service entrance section with main
devices and distribution sections with branch devices. Sections may contain disconnect devices,
protective dev ices, aux iliary equi pment, an d any c urrent transformers for m etering, c ontrol, or
ground fault protection.
Field Servicing
Any filed service shall be performed ONLY by qualified service personnel:
Electrical Connections
All el ectrical c onnections s hall be c ompliant t o el ectrical di agrams pr ovided. A dditionally, al l
electrical c onnections s hall be i n ac cordance with s tate, l ocal, federal and nat ional l aws and
codes.
103
Initial Usage
Pre-Energizing
Prior to any equipment being energized, it must be thoroughly inspected and tested. Any
deviations must be c orrected first and a r e-inspection i nitiated pr ior t o energizing. Emerson
Network Power /Chloride Industrial (ENP) offers a commissioning service and can be contracted
to assure proper start up occurs.
Inspection
The following point shall be evaluated and confirmed correct prior to energizing your units:
• Visually inspect your panel switch for any damage that may have affected the bus bar,
bus bar s upports, and device m ountings or r educed el ectrical c learances anywhere
within the switchboard.
• All proper fuses are correctly installed.
• Manually operate all devices (circuit breakers, switches, etc.) Check for alignment and
proper operation.
• Operate all electrically operated devices (circuit breakers, switches, meters, relays, etc.).
An auxiliary power source may be required.
• Confirm all temporary wiring jumpers (if applicable) are removed
• All ground connections properly made.
• Incoming primary and secondary connections are properly made and checked for shorts
or undesired grounds.
• Inspect and remove any tools or objects left inside the equipment.
Testing
A simple test should be performed to ensure that all connections made in the field are properly
insulated. Test from phase to phase, phase to ground, phase to neutral, and neutral to ground
with t he neut ral i solated from g round and al l ov er current dev ices i n t he open position. S ee
NEMA P B2.1, S ection 7 .6. R esistance readings o f 1 M egohm or gr eater ar e pr eferred. If l ow
readings ar e obs erved and an i nvestigation f or pos sible corrections d oes not c orrect t est
readings, then contact your ENP Service representative.
Where possible a dielectric test should be performed by a qualified individual. This should be
performed in accordance with ANSI C37.20.02 Clause 5.5, Field Dielectric Tests.
Operation
WARNING: HAZARDOUS VOLTAGES IN ELECTRICAL EQUIPMENT CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ENERGIZING A PANEL SWITCH FOR THE FIRST TIME
AFTER INITIAL INSTALLATION OR MAINTENANCE IS POTENTIALLY DANGEROUS.
Only qualified individuals familiar with the operation and construction of the power distribution
panel shall perform the work described in this set of instructions. No work shall be performed
until this document has been read and the operator/user is familiar with this product.
a) Check all interrupting devices. Set all devices to their open position. Check and open all
control circuits.
b) Energize primary incoming power source to the equipment. (the primary incoming power
source shall not exceed the normal rating of equipment).
c) Close the control c ircuit t o c heck al l i nstruments, r elays, meters, e tc. (if ap plicable),
Note: There should be no load on switchboard when it is energized.
104
d) Energize in sequence starting at the source and work towards the load. Close the main
device, t hen any feeder dev ices, t hen any branch dev ices t o s ource l oad. A s the
smallest br anch l oad i s added, obs erve i nstruments. A llow s everal m inutes t o pas s
before connecting additional loads.
e) Slowly connect additional loads to equipment. Carefully observe the instruments and
allow several minutes before adding additional loads. Follow this procedure until the full
load is connected.
f) Once all mains and branch devices have been closed, any downstream loads (as
intended) may be turned on.
g) Verify and check primary and secondary circuits for any overheating.
Switchboard loading
Note: Do not use your distribution panel above the specified ampere rating.
Contacto/Servicio de Informacion
Chloride Industrial Systems, NA
Emerson Network Power
2821 West 11th Street
Houston, Texas 77008
T +1 713 880 0909
F +1 713 880 0952
http://www.ChlorideIndustrialSystems.com
ŽŶƚĂĐƚŽͬServicŝŽĚĞ InformaĐŝŽŶ
+1 800 442 7489 / +571 7058011
service-chlorideindustrial@emerson.com /
callcenter.colombia@emerson.com
Contact Information
106
This manual provides instructions regarding safety, storage, installation, operation and
maintenance. Failure to observe the precautions as presented may result in injury or loss of life.
193
108
Other warning symbols may appear along with the Danger, Warning, and Caution symbol and
are used to specify special hazards. These warnings describe particular areas where special
care and/or procedures are required in order to prevent serious injury and possible death:
DANGER
A battery can present a risk of electrical shock and high short circuit current.
1. Verify that the Charging Power Supply to the battery is off and that all power is
disconnected from the power source.
9. Vented lead-acid (VLA) batteries can contain an explosive mixture of hydrogen gas. Do
not smoke, cause a flame or spark in the immediate area of the batteries. This includes
static electricity from the body and other items that may come in contact with the battery.
10. Use proper lifting means when moving batteries and wear all appropriate safety clothing
and equipment.
11. Do not dispose of lead acid batteries except through channels in accordance with local,
state and federal regulations.
This manual contains important instructions for Flooded Lead-Acid Battery Systems that should
be followed during the installation and maintenance of the battery system.
Only a qualified EnerSys service representative who is knowledgeable in batteries and the
required precautions should perform servicing of the batteries. Keep unauthorized personnel
away from batteries.
Misuse of this equipment could result in human injury and
equipment damage. In no event will EnerSys be responsible or
Caution liable for either indirect or consequential damage or injury that may
result from the use of this equipment.
TABLE OF CONTENTS
1.2 Precautions
BEFORE UNPACKING, STORING, HANDLING, INSTALLING, OPERATING OR
PERFORMING MAINTENANCE ON THE FLOODED LEAD-ACID STATIONARY BATTERY
SYSTEM
READ
THE FOLLOWING
INFORMATION THOROUGHLY!
It is important to read, understand and strictly follow the instructions in this manual.
If the following precautions are not fully understood, or if local conditions are not covered,
contact your nearest EnerSys sales/service representative for clarification, or call the corporate
office number listed on the back of this manual and ask for EnerSys Reserve Power Service.
Also, refer to all applicable federal, state and local regulations and industry standards.
1.3 Service
Should you require installation supervision, service, parts, accessories or maintenance,
EnerSys has a nationwide service organization to assist with your new battery purchase.
Please call your nearest EnerSys sales/service representative for more information, or, call the
corporate office number listed on the back of this manual and ask for EnerSys Reserve Power
Service.
2.0 SAFETY
2.1 General
All flooded, lead-acid batteries, may leak, release hydrogen gas or cause acid misting. Always
follow the generally accepted safety procedures for handling batteries. In addition, it is vitally
important that you observe the precautions recommended in this manual.
YOU SHOULD BE TRAINED IN HANDLING, INSTALLING, OPERATING AND
MAINTAINING BATTERIES BEFORE YOU WORK ON ANY BATTERY SYSTEM.
You MUST understand the risk of working with batteries and BE PREPARED and
EQUIPPED to take the necessary safety precautions. If not, contact EnerSys Reserve
Power Service.
ALWAYS:
• remove all jewelry (i.e., rings, watches, chains, etc.)
• keep sparks, flames and smoking materials away from the battery
Using the correct tools and wearing proper safety equipment will help prevent injury should an
accident occur.
Batteries are safe when operated and handled properly. However, they do contain sulfuric acid,
which can cause burns and other serious injuries.
Always wear protective clothing AND use the correct safety tools.
In case of SKIN CONTACT with sulfuric acid, IMMEDIATELY
3. Apply the solution until bubbling stops, then rinse with clean
water.
NOTE: In case of a sulfuric acid SPILL, bicarbonate of soda or an emergency spill kit
should be within the battery room in accordance with OSHA regulation
1910.178g2.
Batteries can generate gases which, when released, can explode, causing blindness and other
serious personal injury.
• Always wear protective clothing and use the correct safety tools.
• Eliminate any potential of sparks, flames or arcing.
• Provide adequate ventilation. See Appendix.
IN CASE OF FIRE: To extinguish a fire in a battery room containing lead acid batteries, use
CO2, foam, or dry chemical extinguishing media. Do NOT discharge the extinguisher directly
onto the battery. The resulting thermal shock may cause cracking of the battery case/cover.
SPECIAL PROCEDURES:
If batteries are on charge, shut off power. Use positive pressure, self-contained breathing
apparatus. Water applied to electrolyte generates heat and causes it to splatter. Wear acid-
resistant clothing.
TOXIC FUMES:
Burning plastic may cause toxic fumes. Leave area as soon as possible if toxic fumes are
present. Wear breathing apparatus if required to remain in the area.
1. Disconnect ALL loads and power sources to the battery. Use appropriate lockout/tagout
procedures.
3. Check the battery system grounding. Grounding of the battery system is NOT
recommended. However, grounding of the rack is recommended.
Therefore, should you be required to work on a grounded battery system, make absolutely sure
you use the correct safety precautions, equipment and clothing.
IMPORTANT!!
If you have ANY question concerning safety when working with the battery system, contact your
local EnerSys sales/service representative to clarify any of the noted safety precautions, or, call
the corporate office number listed on the back of this manual and ask for EnerSys Reserve
Power Service.
WARNING
Check material quantities received against the Bill of Lading, including the number of battery
pallets and the number of accessory boxes.
Note any:
• damage to packing material.
• wetness or stains, indicating electrolyte leakage.
If damage is noted:
Examine the electrolyte level to ensure that none has been spilled. If electrolyte has been lost in
transit and the level is less than 1/2 inch (12 mm) below the top of the plates, add Battery Grade
sulfuric acid electrolyte of the nominal operating specific gravity indicated on the cell nameplate,
and bring to the low level line on open circuit.
If the electrolyte level is more than 1/2 inch (12 mm) below the top of the plates, request an
inspection by a representative of the carrier and file a claim for concealed damage.
NOTE: For export, cells are usually shipped assembled, moist charged with
separate electrolyte. Fill when ready to place in service, not before.
Refer to Section 12.6, “Filling and Charging Moist-Charged Cells”.
Check the received materials against the detailed packing list to verify receipt of all materials in
the quantities specified.
If you have questions concerning potential damages, contact your local EnerSys sales/service
representative, or, call the corporate office number listed on the back of this manual and ask for
EnerSys Reserve Power Service.
Store batteries indoors in a clean, dry and cool location. Storage at higher temperatures will
result in accelerated rates of self-discharge and possible deterioration of battery performance
and life.
Do NOT stack pallets. DAMAGE MAY OCCUR AND THE WARRANTY WILL BE VOIDED.
Give the battery a freshening charge before the end of the recommended storage interval. See
Section 8 for charging information.
Repeat the freshening charge for each additional storage interval until the battery is installed.
Maximum total storage time before installation is two years from date of shipment from the
factory to the customer. Freshening charges are required a minimum of every three to six
months during the storage time period, as noted above.
If freshening time interval is likely to be exceeded in storage, make advance preparation to have
an adequate charger available and adjacent to an appropriate AC supply voltage. Positioning of
the cells to accept the temporary intercell connectors is another consideration of advance
planning. Keep cells on styrofoam pads until they are installed on the rack.
Make every effort to get the battery installed and connected to the charger before the expiration
of the storage period, thereby avoiding the additional labor cost of preliminary freshening
charges.
WARNING
BEFORE INSTALLATION
READ THIS SECTION THOROUGHLY.
When planning the system space requirements for the EnerSys flooded stationary batteries,
consider the following:
• space • ventilation
• environment • battery system configuration
• temperature • floor loading
• distance from operating equipment • floor anchoring
Use Table 5.1 to ensure that all requirements for installation location are considered.
TABLE 5.1
CONSIDERATION RECOMMENDATION
Space It is recommended that the aisle space provided in front of all racks be a
minimum of 36 inches (915 mm). The designer must verify the
requirements for aisle space in all applicable local codes or regulations.
A minimum of 9 inches (230 mm) is desirable above the tops of the cell
posts of the top row of cells to permit access for maintenance or cell
removal.
Each cell should be accessible for the addition of water and for taking
individual cell voltage and hydrometer readings.
Environment Clean, cool and dry. The location should be selected to keep water, oil, and
dirt away from all cells.
Temperature Ambient temperature between 72o - 78o F (23o - 26o C).
Elevated temperatures reduce operating life. Lower temperatures reduce
battery performance.
Minimize temperature variations between the cells.
• To avoid temperature variation between the cells, do NOT locate
the battery near HVAC ducts or exhausts, heat sources
(i.e., equipment that generates heat) or direct sunlight.
Codes Building codes and fire codes may require a spill containment system
for battery installations. Please consult local building codes. EnerSys
offers spill containment systems. Contact your EnerSys sales/ service
representative for more information.
Floor Reasonably level. Shim up to 1/4 inch (6 mm) maximum to level battery
rack or cabinet front to rear and side to side. Capable of supporting the
weight of the battery as well as any auxiliary equipment.
Anchoring Anchoring should meet all local, state, and federal codes and all
industry standards.
Floor anchoring and its design are the responsibility of the user.
• between the battery and its load are the shortest routing possible to the terminal,
allowing sufficient additional cable (about 6 inches/15 cm) for connect/disconnect.
• are the proper size to minimize the voltage drop between the battery output terminals
and the load.
To select the proper cable size:
2. Calculate the voltage drop of the cable between the battery terminal plate and the
operating equipment.
Cable selection should create no greater voltage drop than allowed between the battery system
and the operating equipment as determined by the equipment/system supplier. Excessive
voltage drop will reduce the desired support time of the battery system.
All accessories for installation and use are supplied as optional prepackaged kits. Cells may be
packed in wooden boxes, which must be opened completely and carefully. The cells are then
handled as described in Section 6.3.
TABLE 6.1
CHECK IF
EQUIPMENT REQUIRED ON HAND
Forklift or Portable Lift Crane
Chalk Line
Torpedo Level (Plastic)
Torque Wrench (10-200 in-lbs)
Torque Wrench (50-100 ft-lbs)
Drift Pins
Floor Anchors (User-supplied per battery system and attached stress analysis)
Floor Shims (User-supplied)
Insulated 3/8 inch Drive Ratchet Wrench with Minimum 3" Extension
With 3/8 inch thru 11/16 inch Sockets
Insulated Box Wrenches (3/8 inch to 11/16 inch)
Screwdrivers
Wipes, Paper or Cloth
Plastic Bristle Brush or Nonmetallic Cleaning Pad
Tape Measure (Nonmetallic)
Safety Equipment and Clothing
Small Paint Brush
Standard Allen Wrench Set
NO-OX-ID Grease
Be sure you have all the proper protective clothing and safety tools
and equipment on hand before starting the installation.
DO NOT lift any cell by the terminal posts as this will void the warranty. When lifting large
cells/units with crane, hoist or similar device, use the lifting belt(s) and protective styrofoam
shipping cover(s) provided.
DO NOT tamper with the seal nuts on the cell posts as this will void the warranty.
2. Position hands under the bottom of the cell/jar to lift it, and place the cell/unit in the
desired location.
Never lift a cell by the posts. Lifting the cell by the post can damage the seals and will void the
warranty. When lifting medium-size cells, use the lifting belt and protective styrofoam shipping
cover provided.
1. Tilt the cell about 1 inch (25 mm) so as to position the lifting belt. See Figure 6.1.
3. Place the styrofoam cover on top of the cell, with the beveled ends up. See Figure 6.3.
4. Bring the end rings of the belt together over the cover and engage the hook of the lifting
device in both rings. Always lift vertically and balance the cell. See Figure 6.4.
Cells are shipped on a pallet, with each cell packaged in an individual styrofoam shipping base
and top.
Never lift a cell by the posts. Lifting the cell by the posts can damage the seals and will void the
warranty. When lifting large-size cells, use the lifting belt and protective styrofoam shipping
cover provided.
Each battery shipment includes one lifting belt, about 14 feet (4.3 meters) long x 1 inch
(25 mm) wide.
All cells are shipped with a molded styrofoam insert covering the posts and intercell connectors.
This insert should remain in place for lifting the cells. As the cell is lifted, the belts will tighten
against the shipping top. The belts will cut into the styrofoam. This is desirable, because the
indentations created will help to keep the belts positioned and the cell stable.
1. Remove the packaging from around the cells/units, and remove the wooden cleats from the
perimeter of the shipping pallet.
2. Leave the molded top insert in place. You will use it in lifting the cell.
3. Fold the lifting belt in half and push each loop end Down between the cells/units until the
loops touch the shipping pallet. See Figure 6.5.
LIFTING LARGE-SIZE
CELL
7. Place the loops on the two free ends of the belt over
the hook of the lifting device, and then place the middle
loop over the hook. See Figure 6.9.
Be sure the belt is not twisted. Straighten the belts down each
side and under the bottom of the cell/unit, so that they are
parallel with each other. The space between the belts should
be the same as the distance between the belt notches on the
edge of the styrofoam. Correct belt spacing is important
because it permits removal of the belt after the cell/unit has
been placed on the rack rails.
8. Lift cell into position and remove belt.
1. Locate the system position in the area designated as determined in Section 5.0.
3. Using the RACK ASSEMBLY DRAWING and instructions and rack components, locate the
position of the floor anchors.
Floor anchors are the responsibility of the owner. Follow the installation instructions of the
anchor manufacturer.
The floor must be level. Shimming up to 1/4 inch (6 mm) may be required to have the
Battery System fully level.
NOTE: The floor must be capable of supporting the weight of the Battery.
The Battery Rack must be securely anchored to the floor. Anchoring should meet all local,
state and/or federal codes and such compliance is the responsibility of the owner. Floor
anchoring and its design are the responsibility of the owner. Ensure seismic requirements
are considered.
4. Batteries should be kept in the original shipping containers until installed. However, if you
must remove the batteries before installation, see the procedures in Section 6.3, “Cell/Jar
Handling.”
1. Install the system in a well-ventilated location; allow at least 4 inches (10 cm) on all sides
for air ventilation and maintenance.
2. Install the unit in a stable, level and upright position which is free of vibration.
3. Install the unit where the ambient temperature is within the correct operating range.
4. Do not install the Battery System in areas that are subject to high humidity.
6. Do not install the Battery System in areas that are subject to contamination, such as high
levels of airborne dust, metal particles or flammable gasses.
7. Avoid installation near sources of electrical noise and always make sure that the unit
ground is intact to prevent electrical shock and to help reduce electrical noise.
8. Do not install where water, or any other foreign object or substances may get inside the
Battery System.
7.2.2 Arrangement
Arrange the cells so that the positive terminal of one cell/jar will be adjacent to the negative
terminal of the next cell/jar throughout the battery.
Cells/jars are usually positioned on rack rails with plates perpendicular to the rails. However, F
and large G cells are also positioned with plates parallel to the rails.
Take care when positioning cells to ensure that main battery terminals are not close together on
step or back-to-back racks.
7.2.3 Spacing
Maintain proper spacing between cells/jars on the rack to provide thermal management and
ensure proper fit of hardware connections. Position cells/jars such that a ¼ inch (6mm) is
maintained between the covers of adjoining units.
1. Install the rack according to the rack assembly information detailed in “Instructions for
Assembling and Maintaining Standard and Seismic Battery Racks” or “Instructions for
Assembling Seismic Racks” (included with the rack shipment).
2. Before lifting cells/jars, determine which two sides will be positioned across the rails.
WARNING
Exercise extreme caution when initially lifting cells and when lowering them into final
position on the rack. To prevent one end of the unit from “kicking out,” assign one person to
steady the unit on a level plane during the entire lifting procedure.
4. Position the first cell/jar on the bottom shelf, centered across the rails. After placement,
remove the lifting belt (if used) from the hook and pull the belt from under the module. Also
remove any remaining protective packing covers. See Figure 7.1.
WARNING
CELL/JAR PLACEMENT
Figure 7.1
To lubricate the rack rails for sliding cells into position, use only EnerSys
Pro-Slide or Dow Corning Silicon Compound #111.
When sliding the cells on the lubricated rails, Do NOT push on the center of the cell/unit.
Hold the cell by placing hands on the corners of the jar and then push to slide.
SPACER
(OPTIONAL)
CELL/JAR PLACEMENT
Figure 7.2
6. Lift the next cell/jar to be installed and place it next to
the previously installed unit. See Figure 7.3. Be certain
to allow proper spacing between cells/jars as outlined
in Section 7.2.2. Observe proper polarity orientation.
7. Remove the belt loops (if used) from the lifting hook and
pull the belt free from under the unit. Also remove any
remaining protective packing covers. See Figure 7.4.
Move cell into final position, observing spacing
requirements.
CELL/JAR PLACEMENT
Figure 7.4
8. Repeat Procedures 5 thru 7 until all units are installed on all tier/steps of the rack. See
Figure 7.5.
All terminal posts of the cells are greased at the factory to prevent oxidation.
2. Inspect each terminal post. If discoloration or tarnishing is noted, neutralize the post with
sodium bicarbonate and water solution (Section 12.1.2, Procedure 2). Dry thoroughly.
3. Clean the contact surface with a stiff-bristle nonmetallic brush/pad until a clean, bright
surface is obtained. Do NOT expose copper.
The connections are made by bolting the plated copper intercell connectors to the cell posts of
opposite polarity on adjacent cells. When more than one intercell connector for each cell is
furnished, bolt the connectors on opposite sides of the cell posts.
1. Clean the contact surface of the intercell connector using a stiff bristle nonmetallic
brush/pad. Use care so as NOT to remove the plating and expose any copper.
Note: Tin-plated connectors do not require plating material removal to provide an
adequate contact surface, only foreign material removal. Very light brushing and cleaning
with a cloth is generally sufficient.
2. With a small paintbrush, apply a light coat of heated NO-OX-ID grease to the contact
surface of the intercell connector.
3. Bolt all intercell connectors and assemble as shown in Figures 7.6a, 7.6b and the
details. Figure 7.6a is applicable to CA & CC models, Figure 7.6b is a representative
diagram for CX, DX, DXC, EA, EC, ES, FTA, FTC, GC, GT, GU.
Certain intercell connectors (such as those for all “G” cells) are furnished with the bolt
holes located off-center. Install these connectors so that the bottom edge of the
connector does not interfere with the post ledge (Figure 7.6b and the detail).
5. After all connections are completed, torque all stainless steel connector bolts according
to Table 7.1.
TABLE 7.1
1/4 - 20 70 – 75 60 – 65
(8.0 - 8.5) (7.0 - 7.5)
6. Apply a light coat of heated NO-OX-ID grease to the bolted connection with a small
paintbrush in the area of the terminal post only.
Terminal plates are supplied with the battery system to provide a system connection point
(except for “C” line). All system connections must be made to the terminal plate and NEVER to
the cell terminal post (except for “C” line).
1. Clean the electrical contact areas of the terminal plate, terminal connectors, and cell/jar
posts with a stiff-bristle nonmetallic brush/pad until the surface is bright. Be careful not to
remove the plating with excessive brushing. A typical terminal plate is illustrated in Figure
7.7.
2. With a small paintbrush, apply a light coating of heated NO-OX-ID grease to contact
areas.
3. Install the terminal connectors to cell posts. Tighten all connections according to the
torque values in Table 7.1.
TERMINAL PLATE
4. With a small paintbrush, apply a light coat of heated NO-OX-ID grease to the electrical
contact areas of the terminal plate.
5. Install the terminal plate to the terminal connectors using the torque values in Table 7.1.
6. Connect the positive lead from the charger to the positive terminal plate of the battery and
the negative lead from the charger to the negative terminal plate of the battery. (Some
seismic installations have interface connections.)
7. Connectors to battery terminal plates should be flexible since rigid terminal connectors
may transmit vibrations or strain to cell posts that could result in loose connections.
Support cables so that the cell post does not bear the load.
a. Inspect the cell connections of the system to ensure that all cells are connected
correctly, POSITIVE (+) to NEGATIVE (-),
b. Measure the voltage across the system terminals. Voltage of the battery should
equal approximately 2.06 times the number of cells in the string for 1.215
nominal specific gravity systems and 2.10 times the number of cells in the string
for 1.250 nominal specific gravity systems, and
Before switching on the charger, ensure that shipping vent plugs are removed and flame
arrestors are installed.
Do NOT attempt a freshening charge unless the electrolyte levels are near the low level
line on open circuit. When necessary, remove electrolyte to that level from cells with
high levels.
Most chargers of modern design utilize the principle of constant voltage (potential) charging.
The preferred charge method is to use a constant voltage of 2.50 volts per cell times the
number of cells. If this voltage is too high for the equipment (load) connected to the DC bus, the
use of lower voltage is accceptable. See Table 8.1. Should the charge current cause electrolyte
to flood out onto the cover, reduce the charge voltage at once.
Least desirable is to put the battery on at the float voltage - particularly for calcium alloy cells.
Equalize charging at 2.33 volts per cell is the minimum acceptable procedure for 1.215 calcium
alloy cells.
1. Determine the maximum voltage that may be applied to the system equipment (or
maximum charger voltage if load is not yet connected). Refer to the recommendations of
the manufacturer/supplier of system equipment, connected to DC bus.
2. Divide the maximum total system voltage by the number of cells (not units) connected in
series. This is the maximum volts per cell that may be used for the initial charge.
4. Connect battery positive (+) terminal to charger bus positive (+) terminal.
5. Connect battery negative (-) terminal to charger bus negative (-) terminal.
6. Raise the voltage to the maximum value permitted by the equipment as shown in Table
8.1.
Table 8.1 lists the hours of freshening charge to be given after charge current has
stabilized for 24 hours. Freshen charge must be given at a voltage high enough to
cause gassing/mixing of the electrolyte. Do not charge at voltages higher than in Table
8.1.
TABLE 8.1
MINIMUM HOURS OF CHARGE AFTER CURRENT STABILIZATION
Alloy Antimony Calcium
Sp. Gr. 1.215 1.250 1.215 1.250 1.300
V.P.C.
2.27 140 210 - - -
2.30 100 150 - - -
2.33 70 110 140 - -
2.36 50 78 100 160 -
2.39 35 56 70 110 -
2.42 25 - 50 80 125
2.45 24 - 40 55 85
2.50 22 - 36 50 60
2.60 - - 30 44 50
2.70 - - 24 36 44
Table 8.1 applies for cell temperatures between 60o to 90o F (16o to 32o C). For cell
temperatures 40o to 59o F (5o to 15o C), use twice the number of hours. For cell
temperatures 39o F (4o C) or below, use four times the number of hours.
On “C," “D,” “E,” “F,” and “G” cells, you may insert the thermometer in the funnel of the
pilot cell's flame arrestor and leave it there by adjusting the rubber washer to the correct
height and leaving off the dust cap. DO NOT LEAVE thermometers in place in
seismic regions.
7. When charging current has decreased and stabilized (i.e., no further reduction for 24
hours), charge for the hours shown in Table 8.1.
Monitor the battery temperature during the charge. If the battery exceeds
110o F (43o C), stop the charge immediately and allow the temperature to
decrease below 100o F ( 38o C). Failure to follow this warning may result
in severe overcharge and damage to the cell/battery.
9.0 OPERATION
9.1 Float Operation
In this type of operation, the battery and the critical load circuits are continuously connected in
parallel with a constant voltage charger. The charger must be capable of:
• charging the battery from the discharged condition while supplying the DC power to the
connected DC load,
Float voltage sustains the battery in a fully charged condition and makes it available to provide
the emergency power required in the event of an AC power interruption or charger failure.
The table below lists the recommended average float volts per cell for nominal specific gravities
used in stationary service.
TABLE 9.1
• the temperature corrected specific gravity has fallen more than 10 points (.010).
• one or more cells fall below the following critical voltages on float, corrected for
temperature. (Refer to Section 9.4 for equalizing charge.)
TABLE 9.2
MINIMUM TEMPERATURE – CORRECTED FLOAT VOLTAGES
Nominal Specific Gravity Cell Voltage
1.215 2.13
1.250 2.14
Specific gravity is a measurement of the density or weight of the electrolyte compared with
water (1.000). Specific gravity decreases on discharge and rises again on charge as a result of
the electrochemical reaction within the cell.
Because both the cell temperature and the electrolyte level affect the specific gravity reading,
they should be recorded at the same time as the gravity reading.
Do not take gravity readings immediately after adding water to the cells. Complete mixing
usually takes several days for antimony cells and several weeks for calcium cells. Because of
the low charging currents in float service, especially with lead calcium cells, mixing of the
electrolyte is a very slow process.
All calcium cells, except “C” size cells, are provided with an electrolyte withdrawal tube, located
in the corner of the cell cover adjacent to the positive post(s). Other corner holes are sealed off
with plugs. Keep these plugs tightly closed and do not open them to withdraw acid sample.
Antimony cells are not provided with an electrolyte withdrawal tube. To take a specific gravity
reading, use the flame arrestor's center funnel. Access this funnel by removing the dust cap of
the flame arrestor. (All the corner holes are sealed with plugs. Keep these plugs tightly
closed and do NOT open them to withdraw acid sample.)
Using the long-stemmed hydrometer (Cat. 81332) will result in sampling of the electrolyte at a
point one-third down from the top of the plate. The long stem of the hydrometer must be cut to
7 3/4 inches (200 mm) for "E" cells; to 9 inches (230 mm) for "D" and "F" cells; or 12 inches (300
mm) for "G" cells. At this level the electrolyte gives a reliable indication of the state of charge of
a cell.
When taking a hydrometer reading, insert the full length of the hydrometer stem into the
withdrawal tube hole, so that the base of the stem rests on top of the withdrawal tube.
These gravity limits are adjusted at the factory and will not require any further adjusting during
the life of the battery unless electrolyte is actually lost from a cell. If electrolyte should
accidentally be lost, it should be replaced with electrolyte of the same specific gravity as that in
the adjacent cells.
When taking hydrometer readings, hold the hydrometer stem in an upright position so that the
hydrometer floats freely and does not touch at either the top or the sides (See Figure 9.1).
1.215
FLOAT
STEM
Hydrometer
Cat. 81332
Figure 9.1
Periodically clean the hydrometer barrel and float with soap and water for ease of reading and
improved accuracy.
Specific gravity readings should be corrected for temperature. For every 3o F (1.67o C) of
temperature above 77o F (258o C), add one point (.001) to the hydrometer reading. For every 3o F
(1.67o C) of temperature below 77o F (25o C), subtract one point (.001) from the hydrometer
reading.
Determine the equalizing voltage based on the maximum voltage allowed by the system
equipment connected to the DC bus.
The charge table shown in Table 9.3 lists the minimum hours of equalizing charge to be given
after the charging current has stabilized (no further current reduction for 24 hrs).
Table 9.3 applies for cell temperatures between 60o to 90o F (16o to 32o C). For cell
temperatures 40o to 59o F (5o to 15o C), use twice the number of hours. For cell temperatures
39o F (4o C) or below, use four times the number of hours.
NOTE: The voltage of a warm cell will be lower than the average. Its voltage can be
corrected for temperature by adding 0.003V for each degree Fahrenheit (0.005 V/oC)
that the cell temperature is above the average temperature of the other cells.
During the equalizing charge, monitor the temperature of a pilot cell. It should not rise above
110o F (43o C). If it does, the equalizing voltage should be lowered to 2.20 or 2.25 VPC until
the cells cool down to a temperature of 100o F (38o C), or lower.
Failure to follow this warning may result in severe overcharge and damage
to the cell/battery. At this point, the equalizing charge may be resumed.
The room air circulation should be adequate to maintain all cells in the battery within 5o F (3o C)
of each other.
High temperature increases realized capacity but decreases life expectancy, while low
temperatures decrease capacity, but may not affect life expectancy. Table 9.5 shows the
relationship between average temperature and battery life.
Because a small amount of electrolyte may be lost in taking hydrometer readings, you should
select a different cell as the pilot cell annually.
Read and record the pilot cell voltage on a monthly basis between regularly scheduled
individual cell readings.
12.0 MAINTENANCE
EnerSys also recommends to follow IEEE Std. 450 for the battery maintenance in
addition to the following:
Observe the battery for cleanliness at regular intervals. Keep cell terminals and connectors free
of corrosion. Terminal corrosion may adversely affect the performance of the battery, and it
could present a safety hazard.
2. Wipe off any accumulation of dust on the cell covers with a cloth dampened with clean
water.
3. If the cell covers or jars are damp with spilled electrolyte, wipe with a cloth dampened with a
solution of sodium bicarbonate and cold water, mixed in the proportions of 1.0 lb/1.0 gal (0.5
kg/5.0 liter) of water. Follow this by wiping with a cloth dampened in clear water and then
wipe dry with a clean cloth.
2. Remove corrosion by wiping with a cloth dampened with bicarbonate of soda solution [mix 1
gallon (4l) of water with 1 lb. (500g) of bicarbonate of soda]. Follow with a cloth dampened
with clear water.
4. With a small paintbrush, apply a light coat of heated NO-OX-ID grease to the entire bolted
connection.
3. Apply a solution of bicarbonate of soda and water to the cell posts and connectors to
neutralize the corrosion (as described in Section 12.1.2, Procedure 2).
4. Clean the contact surfaces by rubbing the surface of the post or terminal and plated contact
surfaces with a stiff-bristle nonmetallic brush/pad. Exercise care so you do NOT remove
the plating on the connectors, terminal plates or lugs, exposing copper.
5. Recoat the contact surfaces with a thin application of the NO-OX-ID grease, heated to a
liquid form and applied with a small paintbrush.
Immerse the flame arrestor several times in a plastic bucket filled with fresh water. After each
immersion, eject the water by vigorous shaking or with an air blast. Following the immersion of
15 flame arrestors, dump and refill the bucket with clean water.
Do not use any cleaning or neutralizing agents in the cleaning water, since any dry residue may
clog the pores of the diffuser materials.
Should you have ANY questions concerning how to perform the required maintenance, contact
your nearest EnerSys sales/service representative or call the corporate office number listed on
the back of this manual and ask for EnerSys Reserve Power Service.
Accumulate and permanently record the following data for review by supervisory personnel so
that any necessary remedial action may be taken:
The initial records are those readings taken after the battery has been in regular float service for
3 months (90 days). These should include the battery terminal float voltage and specific gravity
reading of each cell corrected to 77o F (25o C), all cell voltages, the electrolyte level,
temperature of one cell on each row of each rack, and cell-to-cell and terminal connection detail
resistance readings. It is important that these readings be retained for future comparison.
The frequency and types of readings recorded are usually governed by the standard operating
procedures and policies of the user. Adequate battery records are an invaluable aid as a check
on maintenance procedures, environmental problems, system failures and corrective actions
taken in the past.
While specific gravity readings are a good indication of the health of a cell, other readings can
be used to indicate relative health. However, it is highly recommended that a supplimental full
set of readings on each cell (including specific gravity) be taken approximately two years after
service initilization to verify that the floating conditions of the battery are appropriate.
Monthly
• General appearance and cleanliness
• Charger output amps and volts
• Electrolyte levels
• Cracks in cells or leakage of electrolyte
• Evidence of corrosion at terminals or connectors
• Ambient temperature and condition of ventilating equipment
• Pilot cell voltage, specific gravity and electrolyte temperature
• Evidence of voltage leaks to ground
Quarterly
In addition to the monthly items also obtain and record the following:
• For antimony cells, specific gravity of each cell (optional for calcium cells)
• Voltage of each cell
• Total battery voltage
• Temperature of one cell on each row on each rack
• Randomly select and check 10% of intercell connection resistances
AnnuaIIy
In addition to the quarterly items, also do the following:
• Perform detailed visual inspection of each cell
• Check all bolted connections as indicated in IEEE 450 to see if retorquing is
required. Tighten all bolted connections to the retorque value specified in Table 7.1.
Then obtain and record the connection resistance of cell-to-cell and cell-to-terminal
connections.
• Check integrity of rack.
If charger output voltage is not within the recommended voltage range, make adjustments. Then
determine the cause of the shift and correct the problem.
Keep cells clean, terminal posts and connectors corrosion-free, and grounds eliminated by
following the procedures in Section 12.1.
When cell temperatures deviate more than 5o F (3o C), from each other during an inspection,
determine the cause and correct the problem.
When the connection resistance value of any intercell or terminal connection exceeds the
installation base value by more than 20%, correct it using the procedures in Section 12.1.3.
At regular intervals this water loss must be replaced with distilled, deionized or approved water,
so as to maintain the electrolyte level at the mid-point between the high and low level lines
marked on the jar while on float.
Cells are equipped with flame arrestors with a filling funnel. Add water through the filling funnel
by removing the dust cap, but without removing the flame arrestors from the cell covers.
The best time to add water to the stationary lead-acid battery is when the recharge or equalizing
charge is about two-thirds completed. In this condition the electrolyte should be brought up to
the high line. Water tends to float on top of the electrolyte for awhile, but the gassing action of
the latter part of the charging period will mix the water into the electrolyte. If temperatures may
possibly drop below freezing, water should be added at the start of the recharge or equalizing
charge to ensure thorough mixing with the acid solution.
Take care to keep the solution level below the top mark of the cell jar’s solution level markings
while on equalize. Overflow of solution can occur during gassing if too much water is added to
the electrolyte.
Under certain conditions some batteries may never require an equalizing charge. These
batteries may be watered when required. The mixing of the water with the electrolyte is a very
slow process, especially with the low float currents of lead-calcium cells. In these cases realistic
specific gravity readings may be obtained only after six or more weeks of charging at float
voltages.
In cold climate with unheated battery rooms, water should be added only when the battery
temperature is 50o F (10o C), or above.
Never add any special types of powders, solutions or jellies to the batteries.
Approved water is water that has been analyzed by a qualified laboratory and found safe for use
with lead-acid storage batteries. Local municipal water supplies in the U.S.A. & Canada are
usually satisfactory. Obtain an analysis from the local municipality to be sure the results comply
with the impurity levels in Table 12.1.
Before drawing water from a tap or spigot, run the water for several minutes to clear metallic
impurities from the pipes.
Do not store the water in a metal container. Use a clean container made of glass, rubber or
plastic. The container should not have stored anything but water in the past.
_______________
Location _______________________________ Pilot Cell No. __________ (rotate as needed)
To activate the cells, remove and discard the pressure-relief valves and fill the cells to the low
level line with an approved grade electrolyte. Mix the electrolyte before use to eliminate
stratification.
When mixing electrolyte, always add acid to water. Pour slowly and stir constantly, to avoid
excessive heat or violent chemical reaction.
Allow the battery to stand for four hours after filling. Add additional sulfuric acid of the filling
electrolyte specific gravity to bring the electrolyte level up to the low level line. The charge must
be started within 12 hours of the initial fill.
Before charging, install the flame arrestors, and then lock in place with one quarter turn
clockwise. Then install the dust cap, when provided, on each arrestor.
The preferable way to charge antimony alloy cells is a constant voltage averaging 2.50 volts per
cell. For calcium alloy cells, the voltage needs to be 2.70 volts per cell. Charge for the time
shown in Table 8.1 after current stabilization.
• Parallel the battery to reduce the effective number of cells by half when the charger
voltage can be reduced significantly to achieve the volts per cell specified above, or
• Charge 80% of the cells on system charger, and use an auxiliary charger to charge the
remaining cells, or
• Charge about 80% of the cells from the positive end, using the maximum voltage
indicated previously. Then reconnect about 80% of the cells from the negative end,
and using maximum voltage indicated, charge until the remaining 20% of the cells that
were not charged the first time are fully charged. Do not be concerned if 60% of the
cells obtain twice the normal charge; however, they may require some additional
water.
If cell temperatures exceed 110o F (43o C), interrupt the charge and wait until the
temperature has dropped to 100o F (38o C). Then the charging may be resumed.
Add filling electrolyte, where necessary, so all cells are at the high level line when the activating
charge is about two-thirds complete.
At the completion of the charge, the specific gravity of all cells, corrected to 77o F (25o C),
should be within the range indicated on the nameplate. At the end of charge, if the specific
gravity is higher, remove some electrolyte and replace with water. If lower, remove some
electrolyte and replace with electrolyte of higher specific gravity. At some remote locations,
electrolyte with higher specific gravity may not be available. In this case, adjust the level with
electrolyte instead of water. Measure the specific gravity and keep adjusting the level with
electrolyte until a normal specific gravity reading is achieved.
TABLE 12.2
ELECTROLYTE QUALITY
DILUTE SULFURIC ACID (H2SO4)
MAXIMUM IMPURITIES
% By Weight 1.250 – 1.300 1.170 – 1.215
Sp. Gr. Sp. Gr.
Organic Matter None None
Platinum (Pt) None None
Sulfurous Acid (SO2) 0.0016 0.0013
Iron (Fe) 0.0020 0.0016
Copper (Cu) 0.0001 0.00008
Zinc (Zn) 0.0016 0.0013
Arsenic (As) 0.00004 0.00003
Antimony (Sb) 0.00004 0.00003
Selenium (Se) 0.0008 0.0006
Nickel (Ni) 0.00004 0.00003
Manganese (Mn) 0.000008 0.000006
Nitrates (NO3) 0.0002 0.00016
Ammonium (NH4) 0.0004 0.0003
Chloride (Cl) 0.0004 0.0003
Fixed Residue 0.012 0.009
2. While the battery is on float, read and record the specific gravity and voltage of each cell,
the temperature of at least every tenth cell, and battery terminal float voltage.
3. Disconnect the battery charger and any other load on the battery to be tested.
4. To perform a rate adjusted discharge test, select the discharge rate based upon the critical
load and time period. The test discharge current is equal to the rated discharge current
divided by the K Factor (see Table 13.1) for the initial battery electrolyte temperature (See
IEEE-450-2002 for reference).
5. With the variable load bank having an ammeter in series and a voltmeter across the battery
terminals, connect the load, simultaneously starting the timing device. Maintain the correct
current while periodically reading and recording total battery voltage. When the minimum
total voltage has been reached, it is desirable to read and record each cell voltage including
an intercell connector.
8. Recharge the battery, preferably using an equalizing charge (Section 9.4) to minimize the
recharge time.
K TABLE
TABLE 13.1
Initial Temperature
Factor K
(o C) (o F)
16.7 62 1.098
17.2 63 1.092
17.8 64 1.086
18.3 65 1.080
18.9 66 1.072
19.4 67 1.064
20.0 68 1.056
20.6 69 1.048
21.1 70 1.040
21.7 71 1.034
22.2 72 1.029
22.8 73 1.023
23.4 74 1.017
23.9 75 1.011
24.5 76 1.006
25.0 77 1.000
25.6 78 0.994
26.1 79 0.987
26.7 80 0.980
27.2 81 0.976
27.8 82 0.972
28.3 83 0.968
28.9 84 0.964
29.4 85 0.960
30.0 86 0.956
30.6 87 0.952
31.1 88 0.948
31.6 89 0.944
32.2 90 0.940
32.8 91 0.938
33.4 92 0.936
APPENDIX
Significant amounts of hydrogen are evolved only as the battery approaches full charge. The
maximum hydrogen evolution rate is 0.000267 cubic feet (7.56 x 10-6 cubic meters) per minute
per charging ampere per cell at 77o F (25o C).
To calculate the amount of hydrogen produced, consider an antimony alloy type (flat plate or
tubular) battery at a point where it is nearing end of life, or equalize charge at 2.33 VPC.
NOTE: The above values apply when the electrolyte temperature is 77o F (25o C).
The values will double for every 15o F (8o C) of temperature rise. If the
temperature drops, the current value will be halved for every 15o F (8o C)
decrease. Antimony ranges indicate current increases due to cell aging.
HYDROGEN FORMULA
Formula for hydrogen evolved evolved—C = FC x AH x K x N
1000 100
EXAMPLE
60 cell GT-41 (3730 AH) near end of life, on equalize at 2.33 VPC at 92o F (33o C)
electrolyte temperature
=
C 900 x 3730 x 0.000267 cu. ft. (7.56 x 10-6 cu. m.) x 60
1000 100
Hydrogen = 0.538 cu. ft. (0.0152 cu. m.) per minute
Assume a room size of 16,000 cu. ft. (452.5 cu. m.) that is allowed a 2% concentration of
hydrogen or 320 cu. ft. (9.06 cu. m.). At the above hydrogen evolution rate of 0.538 cu. ft.
(0.0152 cu. m.) per minute, it would require 10 hours to reach 2% concentration. Thus with one
air change every 10 hours, the hydrogen concentration could be maintained below 2%.
2. Do Not use any lubricant other than EnerSys Pro-Slide or Dow Corning Silicon
Compound #111 to lubricate rails to facilitate sliding of batteries.
3. Do Not lift any cells by the terminal posts.
4. Do Not tamper with seal nuts on the cell post.
5. Do Not remove coating from post or connectors and expose any bare copper.
Do Not allow cell temperature to exceed 110o F during charging.
Publication No. US-FL-IOM-002 January 2007 • Subject to revisions without prior notice. E.& O.E.
6.
7. Do Not clean cell with anything other than water/bicarbonate of soda.
8. Do Not over torque connections.
9. Do Not store EnerSys Lead Antimony batteries for over three months without charge –
EnerSys Lead Calcium for over six months without charge, at normal temperatures.
* These are only a few of the precautions. Please read this manual thoroughly for complete details.
Represented by:
EnerSys EnerSys EMEA
P.O. Box 14145 Brussels, Belgium
Reading, PA 19612-4145 Tel: +32 (0)2 247 94 47
USA EnerSys Asia
Tel: +1-610-208-1991 Guangdong, China Printed in U.S.A
© 2007 EnerSys. All rights reserved.
+1-800-538-3627 Tel: +86 755 2689 3639
www.enersys.com Trademarks and logos are the property
of EnerSys and its affiliates unless
246 otherwise noted.
161
247
162
248
163
249
164
250
165
251
166
252
167
253
168
254
169
255
170
256
171
257
172
04-07-2014
REVISIONES
DISEÑÓ: CHLORIDE REVISIÓ: CIICS
ELABORÓ: EMERSON APROBÓ:
PROYECTO:
FABRICACION Y SUMINISTRO DE RECTIFICADOR CHLORIDE Y BATERIAS ENERSYS
PARA EL PROYECTO PMSI ENERGIA & VAPOR
ORDEN DE COMPRA No:
1346-01-30-E0-4270-001
TITULO:
CATÁLOGOS
CODIGO DEL DOCUMENTO
SSDC5100-CAT-01
No. DE HOJAS: REVISIÓN:
11 02
173
The Chloride CP-70R industrial rectifier- The Chloride CP range is designed to meet the harshest electrical and
battery charger is the flagship rectifier mechanical requirements in industrial environments.
of Chloride Industrial Power. It combines Each Chloride CP product is based on interchangeable sub-assemblies to allow
conservative design topology with
full customization, in compliance with client’s technical specification and with
proven digital control technology to
project documentation requirements.
offer the best performances in any
electrical and environmental condition.
Associated with an industrial stand-by battery, the Chloride CP-70R range
The Chloride CP range is designed to meet
the stringent electrical and mechanical requi- protects DC critical industrial equipments and processes from the damaging
rements in industrial environments. effects of power interruptions and losses.
Each Chloride CP product is based on
interchangeable sub-assemblies to allow full
customization, in compliance with client’s
technical specification and with project docu-
mentation requirements.
Benefits
n Made to order DC back-up power solutions
to exactly fit the industrial application
requirements
n Complete power protection solution,
including switchgear, DC distribution,
monitoring suite
n Ruggedized solutions for demanding
environments: extended temperatures,
vibrations, dust, elevation, dripping water and
moisture.
Key Features
n Reliability - Unique design which allows the
rectifier to continuously operate at full load at
a permanent 40°C ambient temperature.
n High MTBF - Natural cooling available on
most of the range.
n Reduced MTTR - Direct access to
components from the front of the equipment.
n Robustness - Mechanical design to withstand
vertical and horizontal acceleration stress up
to 0.5g as standard.
n 20 years + life span - system design to meet
industrial requirements, with appropriate
maintenance.
n Isolation transformer
n Multilingual digital graphic display with
embedded event log
n Remote monitoring capabilities: Modbus,
Profibus, DF1, Ethernet, volt-free contacts,
monitoring software
n Full compatibility with lead-acid and nickel-
cadmium batteries, sealed or vented
Applications
The Chloride CP-70R Rectifier-Charger range suits
all DC applications requiring a large battery back-
up:
n Power Transmission and Distribution
n Continuous process industries
n Oil and Gas and Petrochemical industries
n Transportation (rail, metro, tramway)
174
While every precaution has been taken to ensure the accuracy and completeness of this literature, Emerson Network power assumes no responsability and disclaims all liability for damages resulting from use of this information or for any errors or
Ratings - Output current (A) vs voltage (VDC) Technical Data
24Vdc 48Vdc 110-120Vdc 220-240Vdc
Input
- - 16 16
25 25 25 25 Nominal AC voltage 3 x 400V (380, 415)*
Rectifier Ripple filters Battery current limitation 0.05C (Lead acid battery)
Blocking diode (typical, boost mode) 0.1C (Nickel Cadmium battery)
Dropping diodes
General Data
Other input voltage
Surge and Lightning protections Operating temperature 0 to 40°C*
Battery Battery circuit protection box Storage temperature (°C) -20 to +70°C
Battery cabinet
Low-voltage disconnect contactor Relative humidity (%) <90% non condensing
Battery middle-point measure
Operating altitude (m) 1000 m max without derating
Battery Management System
Battery room temperature sensor Cooling Natural convection
System Dual or trial configurations Efficiency Up to 96% according to rating
Hot stand-by configuration
DC/DC serial regulator External protection IP 20* according to IEC 60529
Isolated DC/DC converter
DC distribution Noise (dB) 55 – 65 dB according to rating
Earth fault monitoring Frame colour Grey RAL 7032
Internal lighting
Anti-condensation heater Dimensions Varying according to ratings & options
Temperature monitor
* other available on request
Special cabinet identification
Mechanical Up to IP65 external
Top cable entry
Other frame colour
Anti-seismic design
Communication Front-panel analog meters (72x72 class 1.5) Standards
Transducers Compliance IEC 60146 – IEC 60439 - IEC 60726 –IEC 61000-6-2 IEC 61000-6-
Volt-free contacts 4 – IEC 62040 (-1, -2, -3)
Remote monitoring via Modbus
Remote monitoring via other bus Conformity Low voltage directive: 2006/95/EC
omissions.
ES
155-1135 Ah
0.422-3.322 Kw/Cell
A P P L I C A T I O N S :
UPS
SWITCHGEAR
Specifications
PLATE DIMENSIONS:
Height Width
Pos: 11.4 in./290mm 9.4 in./239mm
Neg: 11.4 in./290mm 9.4 in./239mm
PLATE THICKNESS:
Pos: 0.20 inches (5.1 mm)
Neg: 0.14 inches (3.6mm)
PLATE SUSPENSION TYPE:
Pos: Bridge hung
Neg: Bottom supported
™ CONTAINER:
Styrene acrylonitrile copolymer
Description Container made from Flame Retardant PVC
(UL94-V0/L.O.I.28%) optional.
The EnerSys ES is an economical lead-calcium flat plate battery. The COVER: Made from Flame Retardant
ES unit is a medium power battery for high performance and short PVC (UL94-V0/L.O.I.28%)
duration rates. Ideal applications are UPS and switchgear. SEPARATORS: Microporous plastic
BOLT CONNECTORS:
Features Stainless steel, standard English
measure, hex-head
Application INTERUNIT CONNECTORS:
• UPS • Switchgear Lead-Plated Copper
Economical ELECTROLYE OVER PLATES:
• Calcium alloy grids for lowest water loss, resulting in lowest 2.1 inches (53.3mm)
maintenance costs. VENT TYPE:
Flame Arrestor, Fused Alumina
Performance
FLOAT VOLTAGE:
• High 1 - minute rates. ACCEPTABLE MIN/MAX: 2.17/2.26 VPC
• Computerized selection of number of plates and plate thickness RECOMMENDED: 2.25 VPC
with respect to available “free electrolyte” to ensure optimum SEDIMENT SPACE:
performance during short-duration discharges without sacrificing 0.75 inches (19.1 mm)
component integrity. POST TYPE:
Durable Lead-plated copper insert
ES-5 to ES-21 - one positive post and one negative
• 20 year life expectancy in float service at 770F (250C) ambient post per cell.
temperature. ES-23 to ES-37 - two positive posts and two negative
• Long Life Slide-Lock™ post seal design. posts per cell.
POST SEAL TYPE:
Installation services and preventative maintenance packages available. Slide-Lock™
SPECIFIC GRAVITY:
1.215 (1.250 available upon request)
WITHDRAWAL TUBE:
One per cell (except 37 plate size)
Rev. 2/02
www.enersysinc.com
176 Capacities - Dimensions - Weights
OVERALL DIMENSIONS WEIGHTS - VOLUMES OUTLINE
NOM. DRAWING:
LENGTH (L)** WIDTH (W) HEIGHT (H) UNPACKED DOMESTIC ELECTROLYTE ONLY
TYPE* Ah SEE
PACKED 1.215 S.G.
CAP.1 CATALOG
in mm in mm in mm lbs kgs lbs kgs lbs kgs gal L SECTION
ES-5 140 5.10 130 11.06 274 18.7 475 55 24.9 57 25.9 24 10.9 2.4 9.1
ES-7 200 5.10 130 11.06 274 18.7 475 61 27.7 63 28.6 23 10.5 2.3 8.7
ES-9 260 5.10 130 11.06 274 18.7 475 68 30.8 70 31.8 22 10.0 2.2 8.3
ES-11 315 5.10 130 11.06 274 18.7 475 74 33.6 76 34.5 21 9.5 2.1 7.9
ES-13 375 5.10 130 11.06 274 18.7 475 81 36.7 83 37.6 20 9.1 2.0 7.6
ES-15 470 6.60 168 11.06 274 18.7 475 98 44.5 101 45.8 30 13.6 3.0 11.4
ES-17 525 6.60 168 11.06 274 18.7 475 105 47.6 108 49.0 29 13.2 2.9 11.0
ES-19 580 6.60 168 11.06 274 18.7 475 112 50.8 115 52.2 28 12.7 2.8 10.6 57.30
ES-21 650 6.60 168 11.06 274 18.7 475 119 54.0 123 55.8 27 12.2 2.7 10.2
ES-23 700 8.10 206 11.06 274 18.7 475 143 64.9 147 66.7 36 16.3 3.6 13.6
ES-25 740 8.10 206 11.06 274 18.7 475 149 67.6 153 69.5 35 15.9 3.5 13.2
ES-27 790 8.10 206 11.06 274 18.7 475 155 70.3 160 72.6 34 15.4 3.4 12.9
ES-29 880 10.10 257 11.06 274 18.7 475 176 79.8 181 82.2 46 20.9 4.5 17.0
ES-31 915 10.10 257 11.06 274 18.7 475 183 83.0 188 85.4 45 20.4 4.4 16.7
ES-33 950 10.10 257 11.06 274 18.7 475 190 86.2 196 89.0 44 20.0 4.3 16.3
ES-35 985 10.10 257 11.06 274 18.7 475 196 88.9 202 91.7 44 20.0 4.3 16.3
ES-37 1030 10.10 257 11.06 274 18.7 475 203 92.1 209 94.9 43 19.5 4.2 15.9
2
Rev. 2/02
Per Cell kW* Discharge Rates in kW** 1.250 Specific Gravity
177
TYPE 5 6 7 8 9 10 11 14 15 16 20 25 30 45 60 90 120 180
MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN
*kW values listed represent 100% of the cell’s initial capacity per IEEE 450.
**1.250 S.G. electrolyte at 770F (250C) includes intercell connector drop.
Rev. 2/02 All data subject to change without notice.
3
Per Cell kW* Discharge Rates in kW** 1.215 Specific Gravity
178
TYPE 5 6 7 8 9 10 11 14 15 16 20 25 30 45 60 90 120 180
MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN
*kW values listed represent 100% of the cell’s initial capacity per IEEE 450.
**1.215 S.G. electrolyte at 770F (250C) includes intercell connector drop.
Rev. 2/02 All data subject to change without notice.
4
Average Cell Performance Data* Discharge Rates in Amperes**
179 1MIN1
TYPE 8 7 6 5 4 3 2 90 60 30 15 5 1 TO 1.50
HR HR HR HR HR HR HR MIN MIN MIN MIN MIN MIN VPC
TO 1.75 END VOLTS PER CELL 1.215 SPECIFIC GRAVITY
ES-5 17.7 20 23 26 32 39 53 65 87 144 212 265 324 796
ES-7 25.2 28 32 38 45 56 76 93 124 201 294 388 473 1165
ES-9 32.4 37 42 49 59 73 99 122 162 258 375 504 615 1514
ES-11 39.6 45 51 60 72 90 122 149 198 315 456 613 748 1847
ES-13 46.8 53 60 70 84 105 142 175 233 370 534 716 872 2158
ES-15 58.5 66 76 88 106 134 182 224 295 448 617 811 988 2453
ES-17 65.7 74 85 99 119 149 203 250 330 506 699 899 1096 2727
ES-19 72.9 82 94 109 131 163 222 273 363 562 779 981 1196 2983
ES-21 81.0 91 104 122 146 183 249 306 406 625 858 1056 1287 3219
ES-23 87.3 98 113 131 158 197 268 329 437 688 987 1329 1621 4010
ES-25 92.7 105 120 140 168 211 286 352 467 740 1067 1430 1743 4317
ES-27 99.0 112 127 148 176 220 298 368 491 788 1147 1527 1862 4615
ES-29 109.8 124 142 165 197 247 335 412 548 860 1223 1621 1976 4904
ES-31 114.3 129 147 171 205 257 348 429 572 905 1298 1710 2086 5183
ES-33 118.8 134 153 179 214 268 363 446 594 948 1372 1797 2192 5455
ES-35 123.3 139 159 186 222 278 376 463 618 994 1445 1880 2293 5713
ES-37 128.7 145 166 193 230 288 389 479 641 1037 1514 1960 2391 5964
TO 1.67 END VOLTS PER CELL
ES-5 17.7 20 23 26 32 39 53 65 90 165 244 365 419
ES-7 25.2 28 32 38 45 56 76 93 132 228 338 507 613
ES-9 32.4 37 42 49 59 73 99 122 173 291 432 647 797
ES-11 39.6 45 51 60 72 90 122 149 212 354 525 789 972
ES-13 46.8 53 60 70 84 105 142 175 249 414 614 921 1136
ES-15 58.5 66 76 88 106 134 182 224 313 479 710 1065 1291
ES-17 65.7 74 85 99 119 149 203 250 352 542 804 1205 1435
ES-19 72.9 82 94 109 131 163 222 273 389 605 896 1344 1570
ES-21 81.0 91 104 122 146 183 249 306 423 665 986 1479 1694
ES-23 87.3 98 113 131 158 197 268 329 456 766 1136 1704 2110
ES-25 92.7 105 120 140 168 211 286 352 488 829 1228 1841 2272
ES-27 99.0 112 127 148 176 220 298 368 518 889 1318 1977 2429
ES-29 109.8 124 142 165 197 247 335 412 581 950 1406 2109 2581
ES-31 114.3 129 147 171 205 257 348 429 610 1007 1493 2239 2728
ES-33 118.8 134 153 179 214 268 363 446 638 1065 1577 2366 2870
ES-35 123.3 139 159 186 222 278 376 463 663 1121 1660 2491 3007
ES-37 128.7 145 166 193 230 288 389 479 687 1176 1741 2611 3139
Accessories
CATALOG
NUMBER
CELL NUMBER SET: 1-12 802360
1-24 802361
1-60 802362
1-120 802363
1-240 802364
1-300 802365
CELL LIFTING DEVICE:
ES-5,7,9,11,13 62257
ES-15,17,19,21 80135
ES-23,25,27 80136
ES-29,31,33,35,37 80137
†PORTABLE HYDROMETER 81332
†HYDROMETER - WALL MOUNT 27717
†THERMOMETER
(Portable or flame arrestor mounting) 88330
FLAME ARRESTOR (Supplied with each cell) 96300
†Included with 12 or more cells
For complete information about these and all other accessories, see catalog SECTION 80.05.
NOTE: All inter-cell, inter-tier, inter-step, end-to-end inter-rack, back-to-back inter-rack connectors, and terminal
plates are included with every battery. Terminal lugs and across-aisle inter-rack connectors are not included.
Represented by:
RE
TU
LE
RN
™
RECYCLE Please check our website for literature updates Printed in USA
Rev. - 2/02
www.enersysinc.com
181 UBC – Zone 2L, 2 Tier Battery Rack
EA, EC, ES AZMS UD32
Essential – At or Below Grade
RACK SPECIFICATIONS:
FRAMES: Steel members covered with gray acid-resistant polyester powder coating
RAILS: Steel members powder coated with acid-resistant polyester
RAIL INSULATION: Plastic channel fastened with double-sided tape
HARDWARE: Zinc-plated steel – RoHS compliant
RACK NOTES:
1. Each seismic rack must stand alone with a minimum clearance of 4.0 inches (102 mm) from any other object (walls, other racks, etc.).
2. Each frame must be anchored to the floor. Holes are provided at the base of each frame. Please refer to rack diagram for hole size and
spacing. Determining the anchor bolt size and securing the anchor bolts to the floor is the responsibility of the customer.
3. Racks are shipped unassembled. All necessary assembly hardware is included.
4. To select the proper rack, refer to the chart(s) on the reverse side of this sheet and to EnerSys Section 55.01, Battery Rack Selection Guide.
5. For rack installation instructions, please refer to EnerSys Section US-KUBC-IM, Instructions for Assembling Stationary UBC Battery Racks.
6. Also refer to EnerSys Section 80.15, Spill Containment Systems and Section 80.05, Battery Charger and Accessories.
Publication No. US-UD32-RK-01 February 2007 Subject to revisions without prior notice. E.&O.E.
12 144 3658 52 40 32 26
13 156 3962 56 44 36 28
14 168 4267 60 46 38 30
15 180 4572 64 50 42 34
16 192 4877 70 54 44 36
17 204 5182 74 58 46 38
18 216 5486 78 60 50 40
19 228 5791 82 64 52 42
20 240 6096 88 68 56 44