Está en la página 1de 7

Integrantes:

Zea Rivas, Mayeli Sarahi U17301016


Torres Espinoza, Fiorella Fernanda 1637054
Mengoa Chavez, Rogger Gonzalo U18214157
Bazan Motta, Bruno Alexander 1633960
Sucapuca Condori Melry Rosario U17106706
Salazar Flores Edwin Daniel U22243855

Cuadro N°1

Cálculo Hidráulico: Red de Agua Fría interior Módulo N°1


Área: Módulo 1 ( 5 niveles + azotea )

Unidades Q Ф V L tramo Accesorios


Tramo
UH (l/s) (pulg) (m/s) (m) Val. Codo

a-b 4 0.1600 1/2 1.263 2.90 0.00 5.00


b-c 6.5 0.2650 1/2 2.092 1.86 0.00 4.00
c-d 8.5 0.3050 1/2 2.408 2.06 0.00 2.00
d-e 25 0.6400 1 1.263 3.37 0.00 2.00
e-f 33.5 0.8075 1 1.594 2.52 0.00 1.00
f-g (medidor) 36.5 0.8600 1 1.697 6.82 1.00 8.00
g-h 146 2.0200 1 1/2 1.772 2.47 0.00 1.00
h-i 224 2.6200 1 1/2 2.298 2.47 0.00 0.00
i-j 302 3.3200 2 1.638 2.47 0.00 0.00
j-k 380 3.6700 2 1.811 2.47 0.00 0.00
k-l ( medidor 1°piso) 458 4.4000 2 1/2 1.389 0.40 0.00 1.00
l-m 458 4.4000 2 1/2 1.389 11.40 0.00 1.00

Gasto de 01 Departamento típico Lavadero de Ropa 3 UH


* 01 Baño completo 7.5 UH Lavatorio 3 UH
* 01 Lavadero de cocina 4 UH Ducha 4 UH
* 01 Lavadero de ropa 4 UH Inodoro 2.5 UH
* 01 Lavadora 4 UH Lavamanos 2 UH
Total 19.5 UH Lavaplatos 3 UH
Total por piso del 1 piso al 4 piso 19.5 UH x 4 departamentos = 78 UH por piso

Gasto de 01 Departamento duplex


* 02 Baño completo 19.5 UH
* 01 Lavadero de cocina 4 UH
* 01 Lavadero de ropa 4 UH
* 01 Lavadora 4 UH
Total 40.5 UH
Total piso duplex 5 piso+Azotea 40.5 UHx 4 departamentos = 162 UH por piso
Total UH Modulo N°1 UH
MEMORIA DE CALCULO
Calculo Hidráulico Red de Agua Fría

orios Lacc. Leq Desnivel(m)


S(o/oo) Hf (m)
Tee (m) (m) Cota Mayor Cota Menor Desnivel

0.00 5.20 8.10 181.751 1.471 14.190 12.370 1.82


1.00 6.23 8.09 462.665 3.745 12.370 12.770 -0.40
1.00 4.16 6.22 600.246 3.731 12.770 12.370 0.40
1.00 4.16 7.53 80.961 0.609 12.370 9.880 2.49
1.00 3.12 5.64 124.521 0.702 9.880 9.880 0.00
1.00 10.61 17.43 139.927 2.439 9.880 10.380 -0.50
1.00 3.12 5.59 94.414 0.528 10.380 7.910 2.47
1.00 2.08 4.55 152.829 0.695 7.910 5.440 2.47
1.00 2.08 4.55 58.364 0.265 5.440 2.970 2.47
1.00 2.08 4.55 70.267 0.320 2.970 0.500 2.47
0.00 1.04 1.44 33.164 0.048 0.500 0.000 0.50
0.00 1.04 12.44 33.164 0.413 0.000 0.000 0.00

Presión de salida en la ducha a = 2.00 m


Presión mínima requerida en el ingreso del módulo N°1 punto m = 23.92 m

LR: Lava ropa


Material: PVC
C: 140

Presión
Punto
(m)

a 2.00
b 5.29
c 8.64
d 9.42
e 11.74
f 12.44
g 14.38
h 17.37
i 20.54
j 23.27
k 26.06
l 26.61
m 27.02
TRAMOS UD
a-b 3
b-c 5
c-d 7
d-e 11
e-f 18
f-g (medidor) 21
g-h 84
h-i 164
i-j 244
j-k 324
k-l ( medidor 1°piso) 404
l-m 404
AZOTEA + DUPLEX 146 UH
4 PISOS TÍPICOS 312 UH
TOTAL 458 UH