SHARKY 775

ULTRASONIC COMPACT METER

APPLICATION SHARKY ultrasonic compact energy meter can be used for measuring the energy consumption in heating / cooling application for billing purposes. The measurement principle is static and based on the measurement of the transit time. Ultrasonic technology offers many benefits : no moving parts (avoids wear and tear of the metering components), low pressure loss, large metering dynamics and low start flowrate, insensitiveness to suspended particles... FEATURES

4 Approved according EN 1434 and MID in class 2 with dynamic range of 4 4 4 4


1:250 (qi:qp) in class 2 Complete range from ND 15 mm qp 1.5 m/h up to ND 100 mm qp 60 m/h Extermely low power consumption enabling a long battery lifetime (16 years in standard use) Radio option integrated Modular version, M-Bus, RS232, RS485, Analog outputs 4-20mA, pulse outputs and pulse inputs

SHARKY 775
ULTRASONIC COMPACT METER
GENERAL
Application Approval Mounting position flow sensor Protection class flow sensor Battery supply Mains supply Temperature sensor type Cable length of temperature sensor Volume measuring cycle Test possibilities
1

SHARKY Heating - cooling - heating/cooling MID (DE-10-MI004-PTB013) and PTB K7.2 (cooling) Any position Heating: IP 54; cooling, heating/cooling: IP 68 3.6 VDC- D-cell max. 16 years lifetime 24 VAC; 230 VAC Pt 100 or Pt 500 with 2-wire leads; 5.2 / 6 mm or direct sensor Pt 100: 2 m; Pt 500: 2 / 31 / 5 m With power supply: s; with D-cell battery: 1 s via display, optical test pulses, test output or via NOWA software

: Only for meters with PTB K 7.2 approval

CALCULATOR - BASIC FEATURES


Ambient class Ambient temperature Ambient storage temperature Protection class Communication Integrated Radio Interfaces standard Interfaces optional Temperature range heatmeter Temperature range cooling meter and heating/cooling meter Extensive readable data memory
1

SHARKY Class E1 + M1 C C 5 ... 55 -25 ... +70 IP 54 2 communication slots (e. g. M-Bus + M-Bus; 2 primary adresses, 1 secondary adress) Optional Optical ZVEI interface 2 Slots for modules with M-Bus, L-Bus, RS232, RS485, pulse output, pulse input, combined pulse in-/output or analogue output C 5 ... 130 / 150

5 ... 105 Monthly memory1; historical LOG memory; event memory

: Programmable storage interval (daily, weekly, monthly, ...)

CALCULATOR - INTEGRATED RADIO


Frequency band Type of radio telegram Transmission data updating Data transmission Sending interval SHARKY 868 or 434 MHz Real Data or Open Metering Standard (OMS) Online - no time delay between value measurement and data transmission Unidirectional 12 ... 20 s; depending on length of telegram (duty cycle)

21.01.2011 2

SHARKY 775
ULTRASONIC COMPACT METER
DISPLAY
Display indication Units Total values Values displayed SHARKY LCD, 8-digit MWh - kWh - GJ - Gcal - MBtu - gal - GPM - C - F - m - m/h 99,999,999 - 9,999,999.9 - 999,999.99 - 99,999.999 Energy - Power - Volume - Flow rate - Temperature and more

INTERFACES
Optical SHARKY ZVEI interface, for communication and testing, M-Bus protocol. Configurable telegram, according to EN1434-3, data reading and parametrization are via two wires with polarity reversal protection, auto baud detect (300 and 2400 baud), 2 M-Bus with 2 primary adresses. Adapter for external radio module, configurable telegram, according to EN1434-3, data reading and parametrization are via two wires with polarity reversal protection. Serial interface for communication with external devices, a special data cable is required, MBus protocol, 300 and 2400 baud. Serial interface for communication with external devices, power supply with 12V 5V, M-Bus protocol, 2400 baud. Module with 2 Open Collector pulse outputs (potential-free), 4 Hz (pulse width 125 ms), 100 Hz (pulse width 5 ms), ratio: pulse duration / pulse break ~ 1:1, configurable via IZAR@SET software. Module with 2 pulse inputs, max. 20Hz, configurable via IZAR@SET software, data can be transferred remotely. Module with 2 pulse inputs and 1 pulse output, configurable via IZAR@SET software, needed for leak detection. Module for 4 ... 20 mA with 2 programmable passive outputs, programmable value in case of error.

M-Bus L-Bus RS232 RS485

Pulse output Pulse input Combined pulse in-/output Analogue output

TEMPERATURE INPUT
Sensor current Measuring cycle Starting temperature difference Min. temperature difference Max. temperature difference Absolute temperature measuring range T min max mA s K K K C SHARKY Pt 100 peak < 8; rms < 0.015, Pt 500 peak < 2; rms < 0.012 With mains unit: 2 s; with A-cell battery: 16 s; with D-cell battery: 4 s 0.125 3 177 1 ... 180

21.01.2011 3

SHARKY 775
ULTRASONIC COMPACT METER
TECHNICAL DATA FLOW SENSOR
Nominal flow rate Nominal diameter Overall length Starting flow rate Minimum flow rate Maximum flow rate Overload flow rate Operating pressure Pressure loss at qp Temp. range heating Temp. range cooling Temp. range heating/cooling Flow resistance coefficient Nominal flow rate Nominal diameter Overall length Starting flow rate Minimum flow rate Maximum flow rate Overload flow rate Operating pressure Pressure loss at qp Temp. range heating Temp. range cooling Temp. range heating/cooling Flow resistance coefficient
1 2

qp

m3/h

DN L qi qs PN p

mm mm l/h l/h m3/h m3/h bar mbar C C C

1.5 15 110 2.5 6 3 4.6 161 75 5 ... 130 5 ... 50 5 ... 105 4.3

2.5 20 130 4 10 5 6.7 161 100 5 ... 130 5 ... 50 5 ... 105 4 25 65 300 50 1003/250 50 60 25
2

6 25 260 7 24 12 18.4 161 128 5 ... 150 5 ... 50 5 ... 105 2.8 40 80 300 80 160 80 90 25
2

6 32 260 7 24 12 18.4 161 128 5 ... 150 5 ... 50 5 ... 105 7.4 60 100 360 120 2403/6004/12005 120 132 16/252 75 5 ... 150 5 ... 50 5 ... 105 3.8

10 40 300 20 40 /100 20 24 161 95 5 ... 150 5 ... 50 5 ... 105 3.8


3

Zeta
qp m3/h

DN L qi qs PN p

mm mm l/h l/h m3/h m3/h bar mbar C C C

15 50 270 40 603/150 30 36 25
2

80 5 ... 150 5 ... 50 5 ... 105 3.5

75 5 ... 150 5 ... 50 5 ... 105 3.4

80 5 ... 150 5 ... 50 5 ... 105 3.4

Zeta

: Also available in PN 25 bar : Also available in PN 40 bar 3 : Only for horizontal installation 4 : Only in rising or falling pipes or tilted installation 5 : Only up side down installation

21.01.2011 4

SHARKY 775
ULTRASONIC COMPACT METER
DIMENSIONS THREAD VERSION

Nominal flow rate Nominal diameter Overall length Overall length with coupling Length of calculator Height Height Height of calculator Width of calculator Connection thread on meter Connection thread of coupling Weight Nominal flow rate Nominal diameter Overall length Overall length with coupling Length of calculator Height Height Height of calculator Width of calculator Connection thread on meter Connection thread of coupling Weight

qp

m3/h

DN L L2 L1 H H1 H2 B

mm mm mm mm mm mm mm mm Inch Inch kg

1.5 15 110 190 150 14.5 82 54 100 GB R 0.76 15 50 270 -

2.5 20 130 230 150 18 84 54 100 G1B R 0.85 25 65 300 -

6 25 260 380 150 23 88.5 54 100 G1B R1 1.5 40 80 300 -

6 32 260 60 100 360

10 40 300 440 150 33 94 54 100 G2B R1 3

qp

m3/h

DN L L2 L1 H H1 H2 B

mm mm mm mm mm mm mm mm Inch Inch kg

21.01.2011 5

SHARKY 775
ULTRASONIC COMPACT METER
DIMENSIONS FLANGE VERSION

Nominal flow rate Nominal diameter Overall length Length of calculator Height Height Height of calculator Width of calculator Flange dimension Flange diameter Hole circle diameter Screwhole diameter Number of screwholes Weight Nominal flow rate Nominal diameter Overall length Length of calculator Height Height Height of calculator Width of calculator Flange dimension Flange diameter Hole circle diameter Screwhole diameter Number of screwholes Weight
1

qp

m3/h

DN L L1 H H1 H2 B F D K D1

mm mm mm mm mm mm mm mm mm mm mm pcs kg

1.5 15 110 15 50 270 150 73.5 99 54 100 147 163 125 18 4 7.6

2.5 20 130 25 65 300 150 85 106.5 54 100 170 184 145 18 8 9.6

6 25 260 150 50 88.5 54 100 100 114 85 14 4 3.5 40 80 300 150 92.5 114 54 100 185 200 160 19 8 11.2

6 32 260 150 62.5 88.5 54 100 125 139 100 18 4 4.8 60 100 360 150 108 119 54 100 216 235 1801/190 191/22 8 17

10 40 300 150 69 94 54 100 138 148 110 18 4 6.8

qp

m3/h

DN L L1 H H1 H2 B F D K D1

mm mm mm mm mm mm mm mm mm mm mm pcs kg

: Values for PN16 housing

21.01.2011 6

SHARKY 775
ULTRASONIC COMPACT METER
PRESSURE LOSS GRAPH / TYPICAL ERROR GRAPH

Pressure loss graph

Typical error graph

21.01.2011 7