CIE 442 – Homework#11 Spring 2023

1. The following reinforced section below has a concrete clear cover of 1.5” all around
and #4 ties. Fy = 60 ksi, f’c = 7 ksi, with As = 5 #8’s. Use normal weight concrete.

b=15”

h=24”

The beam is fully fixed at the supports by 18” wide columns and has a point load at
a = 6 ft from the left support of 50 kips due to live load and 40 kips due to dead load.
Do not forget that the beam has self-weight.
a

20 ft (columns out to out)

a) State what is the maximum (Vu_max) shear load to be used in design.


b) Would a tie spacing of 12” be adequate near the right support? How about the left
support? Why? Check Vu<Vn and determine what would be the most efficient
tie spacing at each of the supports.
c) What is the maximum tie spacing allowed by the ACI code? And the minimum?
CIE 442 – Tarea #11 Primavera 2023

1. La siguiente sección reforzada a continuación tiene una cubierta transparente de


concreto de 1.5” alrededor y amarres #4. Fy = 60 ksi, f'c = 7 ksi, con As = 5 #8. Use
concreto de peso normal.

La viga está completamente fijada a los soportes por columnas de 18” de ancho y
tiene una carga puntual en
a = 6 pies desde el soporte izquierdo de 50 kips debido a la carga viva y 40 kips
debido a la carga muerta. No olvide que la viga tiene peso propio.

a) Indique cuál es la carga cortante máxima (Vu_max) que se utilizará en el diseño.


b) ¿Sería adecuado un espacio entre tirantes de 12” cerca del soporte correcto? ¿Qué
tal el soporte izquierdo? ¿Por qué? Compruebe Vu<Vn y determine cuál sería el
espaciamiento más eficiente entre tirantes en cada uno de los soportes.
c) ¿Cuál es el espaciamiento máximo entre tirantes permitido por el código ACI? ¿Y
el mínimo?