= Passenger protection active #
# Note this is the slip of the drive and can be adjusted
by using the variable parameter in the EEPROM ,
key 3-3-3. Set to 8% aprox.POCKET MANUAL for OTIS DO2000 Date Oct 1998
Page 6
MONITOR
STATUS 2 (serial) M-3-1-1
DCSS Address
Door supervisory state
Door command state via -
-serial link
Door state
Di: RDY DED []
any display
DCSS Address,
D1 = DCSS1 default address
Front door
D2 = DCSS2 alternate door
Rear door
D3 = DCSS3 double car door
Double deck car
D4 = DCSS4 double car alternate door
Double deck car rear door
Door supervisory state.
SHD = SHut Down mode.
INI = INItalisation mode(resets position)
RDY = ReaDY mode (normal operation)
ESM = Emergency Stop Mode.POCKET MANUAL for OTIS DO2000 Date Oct 1998
Page 7
Door command state via serial link.
Reversal inputs in operation
DOB LRD €DP
DED Deenergise = -----
OPD1 Open door
OPD2 Open door -
CLD1 Close door were sree ne
CLD2 Close door L E
CLD3 Close door L e
CLD4 Close door | e
CLD5 Close door (nudging)
CLD6 Close door
CLD7 Close door
CLD8 Close door
e2o000000
D= full/d= limited door reversal,no door reversal on DOB
L= full/ | = limited door reversal,no door reversal on LRD
E= full/e= limited door reversal,no door reversal on EDP
Limited door reversal.
This means that the door can be programmed
so that it will not fully reopen, but just stop at that point.
This may be required for some modernisation solutions.
If the safety link is interrupted by the EDS signal, the
DCSS shuts down, and disables the motor supply. In this
mode the SVT displays,
EMERGENCY STOPPOCKET MANUAL for OTIS DO2000 Date Oct 1998
Page 8
MONITOR
COMMAND status M-3-1-2
The top line shows the status as M-3-1-1, the bottom line
will now show the current command display. This
command can only be entered when the SVT is directly
connected to the DCSS and configured to SERIAL.
D1: RDY OPN < > |-—-sIatus as is,
CLD6é