Está en la página 1de 1
‘(OM-2084 / Operation and Maintenance Manual oft 90CU24 / Series 500392 Generator Sets ee som ches “D Zee mm fRlen clometes ‘Gain Electric Governor Control Box Figure 5 acruaton wacnenio TERMINALS PICK-UP © Set the “DROOP" potentiometer (1) COUNTER CLOCKWISE to minimum 0 (zero), * Tum the rated speed potentiometer (5) all the way COUNTER CLOCKWISE. Then count twolve full turns CLOCKWISE. * Start the engin, leave at IDLE speed and adjust the IDLE speed potentiometer in the ‘control box until the engine is operating at 850 RPM. Turing the potentiometer CLOCKWISE increases engine RPM. ‘+ Checking No-Load Operation of Controller (See fig. 5) * Press engine start switch (26, Fig. 1) a second time to increase engine RPMs to approximately the rated speed (2400 RPM). * Tum the “GAIN" potentiometer (4) full CLOCKWISE. The frequency meter gage and governor should become unstable and oscilate. Ifit does not, marwally bump the linkage to cause ito oscillate. + Slowly turn the "GAIN" potentiometer (3) COUNTER CLOCKWISE until the oscillations stop. Tum the “GAIN" potentiometer Yan increment past a point where the oscilatons ‘stop. + Tum the “D" potentiometer ful CLOCKWISE. The frequency meter gage and governor should become unstable and oscillate, iit does not, manvally bump the linkage to cause it to osciiate November 2771997 Chapter 23