Está en la página 1de 2

MAIN :EXISTING

CONNECTED : BUILDING
CCT. LOAD (V/A) CIRCUIT BREAKER
DESCRPTION
NO. O.R. O.S. O.T. POLE AT
1 GA-FL1-004 120 1 16
3 GA-FL1-005 120 1 16
5 GA-FL1-006 120 1 16
7 GA-FL1-007 120 1 16
9 GA-FL1-008 120 1 16
11 GA-FL1-010 120 1 16
13 GA-FL1-011 120 1 16
15 GA-FL1-012 120 1 16
17
19 GA-FL2-003 2895
21 GA-FL2-003 2895 3 16
23 GA-FL2-003 2895
25 CDU-FL2-003 14611
27 CDU-FL2-003 14611 3 25
29 CDU-FL2-003 14611

2 GA-FL2-010 190 1 16
4 GA-FL2-011 50 1 16
6 GA-FL2-012 50 1 16
8 GA-FL2-015 150 1 16
10 GA-FL2-016 150 1 16
12 GA-FL2-017 150 1 16
14 GA-FL2-018 150 1 16
16 CDU-FL2-010 3221 1 32
18
20 GA-FL2-014 2895
22 GA-FL2-014 2895 3 16
24 GA-FL2-014 2895
26 CDU-FL2-014 14611
28 CDU-FL2-014 14611 3 25
30 CDU-FL2-014 14611

35,862 38,793 35,452


TOTL LOAD (VA) 110,107 VA
3 EXISING
DEMAND LOAD 100% (VA) RENOVATION 110,107 VA
MOUNTING :

RCUIT BREAKER CONDUCTOR CONDUIT


REMARK
IC SIZE TYPE SIZE TYPE
2x2.5/2.5 IECO1 3/4" EMT.
2x2.5/2.5 IECO1 3/4" EMT.
2x2.5/2.5 IECO1 3/4" EMT.
2x2.5/2.5 IECO1 3/4" EMT.
2x2.5/2.5 IECO1 3/4" EMT.
2x2.5/2.5 IECO1 3/4" EMT.
2x2.5/2.5 IECO1 3/4" EMT.
2x2.5/2.5 IECO1 3/4" EMT.

4x2.5/2.5 IECO1 3/4" EMT.

4x4/4 IECO1 1-1/2" EMT.

IC>=6KA
2x2.5/2.5 IECO1 3/4" EMT.
2x2.5/2.5 IECO1 3/4" EMT.
2x2.5/2.5 IECO1 3/4" EMT.
2x2.5/2.5 IECO1 3/4" EMT.
2x2.5/2.5 IECO1 3/4" EMT.
2x2.5/2.5 IECO1 3/4" EMT.
2x2.5/2.5 IECO1 3/4" EMT.
2x4/4 IECO1 1-1/2" EMT.

4x2.5/2.5 IECO1 3/4" EMT.

4x4/4 IECO1 1-1/2" EMT.

EXISING EXISING EXISING EXISING EXISING