DISEÑO DE ACERO ANCLAJES COLUMNA CASA COMUNAL

M= exc x Pu = 0.47 tn x m Pu= 4.70 tn FY= 3,515.00 kg/cm2

exc= 0.10 m M= 0.47 tn x m


Pu= 4.70 tn
F`c= 210.00 kg/cm2

RESISTENCIA DEL CONCRETO:

Fp= 0,35 x F`c = 73.50 kg/cm2

PERFIL 220 MM X 220 MM :

d= 10.00 cm
e= 0.30 cm
Sx= 35.02 cm4
B= 20.00 cm
C= 20.00 cm m= 5.25 cm
DISEÑO DE PLANCHA: n= 5.25 cm
B= 20.00
fp= Pu/BC +6M/BC^2 = 47.00 kg/cm2
-23.50 kg/cm2
p= 3.53
fp < Fp
C= 20.00
47.00 kg/cm2 < 73.50 kg/cm2

S
"Bien, Cumple"
M1= fp . m^2/2-p. m^3/6 = 562.71 kg xcm s= 15.10
X= 14.90
M2= P.n^2/2 = 419.50 kgxcm -23.50 p= fp/x
p= 3.15
M2 < M1
419.50 Kg.cm < 562.71 Kg.cm
Cumple

-23.50 47.00
ESPESOR NECESARIO DE PLACA: P= 30.44

tp= √6.M1/075.FY = 1.13 cm "Colocar una lamina de 13 mm" de 20 cm x 20 cm".

FUERZA DE TRACCION:
s= (d + m) 15.10 cm FY As= 4,200.00 kg/cm2 Ft Perno= 2,800.00 kg/cm2

T= M/s = 3,112.58 kg

AREA DE ACERO O PERNOS:

As= T/FY As = 0.74 cm2 Colocar 4 Ø 1/2" W-60 x 0,45 m , minimo por norma, como apoyo
de las columnas de 100mm x 100 mm x 3,00 mm
Nº Cabilla = 0.58

Aperno= 1.11 cm2 Colocar 4 pernos Ø 5/8" x 0,45 m A325, minimo por norma, de
8600 kg de traccion; como apoyo de las columnas de 100mm x 100
mm x 3,00 mm.
Nº Pernos= 0.70 Pernos 5/8"
"USAR ELECTRODOS E-7018 DE Ø 1/8" PARA ACORDONAR Y E-6013 PARA PUNTEAR"