Estudiantes: Benítez-Guaminga-Ordoñez
Universidad Politécnica Salesiana - Sede Sur

Facultad de Ciencias de la Vida - Carrera de Ingeniería Ambiental

Manejo y Tratamiento de Aguas / Docente: Ing. Renato Sánchez

Autor: Benítez Andrés - Guaminga Oscar – Ordoñez Juan Tema: Diseño PTAR Primario (El Peral – Ambato)

Fecha de envío: Viernes, 10 de febrero de 2017 Curso: Sexto “A” / Periodo: 2016-46

Tomado de: INFORME DE RESULTADOS ANALISIS FISICO QUIMICOS Y MICROBIOLOGICOS


Tipo de Muestra: AGUA RESIDUAL DOMESTICA
Procedencia de la muestra: PTAR. EL PERAL Humedad(%)=44
Cliente: Ing. Renato Sánchez Temperatura=20C
ANALISIS REALIZADOS
RESULTADOS
PARÁMETROS UNIDAD METODO
ENTRADA PTAR SALIDA PTAR
Coliformes Totales NMP/100mL COLILERT 15530000 396000
Coliformes Fecales NMP/100mL COLILERT 6480000 204000
DBO5 mg/L APHA-5210-B 654 125
DQO mg/L HACH 8000 1304 212
pH UpH APHA-4500HB 7,38 7,50
Sólidos Suspendidos mg/L APHA-2540-D 1803 10
Sulfatos mg/L HACH-8051 47 1
Tensoactivos mg/L HACH-8026 7,251 8,063
Temperatura C APHA-2550-B 18 18

RESUMEN

El presente trabajo está enfocado en el diseño de todo un sistema secundario de descontaminación, aplicando
todos los conocimientos impartidos en la catedra de Manejo y Tratamiento de Aguas (todas las constantes y
relaciones). Para esto se realizaron diferentes cálculos para obtener las dimensiones, se debe aclarar que el
caudal dado para este diseño fue de 1 L/seg de aguas residuales domésticas, sin embargo al ser este valor tan
pequeño las dimensiones salen en proporción a eso.

Se diseñó un Sistema de Floculacion-Coagulacion de manera mecánica e hidráulico, se diseñó un Filtro


Percolador utilizando el parámetro de DBO de entrada(654 mg/L) y salida(125 mg/L) para agua residual
domiciliaria, solidos suspendidos de 1803 mg/L y su respectiva densidad; se diseñó un tanque de desinfección
con el dato de solidos suspendidos de la PTAR. EL PERAL con su respectiva densidad de 1,5 Kg/L y con un
tiempo de vaciado de 15 días, se diseñó un sistema UASB para ello necesitamos los datos de dotación rural
que fue de 70 L/hab.dia y el parámetro de DBO de entrada que es 654 mg/L y por último se diseñó un sistema
de lodos de secado con el dato de solidos suspendidos y el caudal dispuestos por la PTAR, para finalizar se
realizó cálculos para la obtención de la tasa de cobro de agua residual de la PTAR ubicada en la ciudad de
Ambato.

El diseño se lo realizo en el software AutoCAD lo que permitió llegar a un mejor resultado en cuanto a todas
las dimensiones que fueron calculadas, todos los datos están especificados en los Anexos en tablas de
constantes según el lugar de la planta.
Estudiantes: Benítez-Guaminga-Ordoñez

I. DISEÑO DE SISTEMA DE FLOCULACION-


8 ∗ 6 ∗ 5.367 61.154
COAGULACION HIDRAULICA 𝑎1 = √ ∗ 𝑐𝑜𝑠 ( ) = 8,758
3 3
Para este sistema se deberá realizar en tres partes:
𝟑. 𝒂𝒍𝒕𝒖𝒓𝒂 𝒂𝒏𝒕𝒆𝒔 𝒅𝒆𝒍 𝒓𝒆𝒔𝒂𝒍𝒕𝒐 (𝒅𝟏):
 DISEÑO CANAL DE MEZCLA RAPIDA (tipo rampa)
𝑔 = 9,8 → 𝑔𝑟𝑎𝑣𝑒𝑑𝑎𝑑
Datos:
3 𝑄2
L 𝑚3 𝑑1 = √ 2
𝑄=1 → 0.001 𝐹1 ∗ 𝑔
𝑠𝑒𝑔 𝑠𝑒𝑔
3
Parámetros que se debe cumplir: −3 𝑚 )2
√(1 ∗ 10
3

𝑑1 = 𝑠 = 2.570 ∗ 10−3 𝑚
Rango de resolución: 62 ∗ 9.8

4,5 < 𝐹 > 9,0 𝟒. 𝒑𝒓𝒐𝒇𝒖𝒏𝒅𝒊𝒅𝒂𝒅 𝒂𝒏𝒕𝒆𝒔 𝒅𝒆𝒍 𝒓𝒆𝒔𝒂𝒍𝒕𝒐(𝒉𝟏):

L 𝑚3 𝑑1
𝑄=1 → 0.001 ℎ1 =
𝑠𝑒𝑔 𝑠𝑒𝑔 𝑐𝑜𝑠𝜃

𝑎𝑛𝑐ℎ𝑜 𝑜𝑝𝑡𝑖𝑚𝑜 𝑑𝑒 𝑙𝑎 𝑟𝑎𝑚𝑝𝑎 → 𝑎 = 0,6m 2.570 ∗ 10−3 𝑚


ℎ1 = = 2.95 ∗ 10−3 𝑚
cos(29.58)
𝑫𝒊𝒎𝒆𝒏𝒔𝒊𝒐𝒏𝒆𝒔 =?
𝟓. 𝒑𝒓𝒐𝒇𝒖𝒏𝒅𝒊𝒅𝒂𝒅 𝒅𝒆𝒔𝒑𝒖𝒆𝒔 𝒅𝒆𝒍 𝒓𝒆𝒔𝒂𝒍𝒕𝒐(𝒅𝟐):
𝟏. 𝒄𝒂𝒍𝒄𝒖𝒍𝒐 𝒅𝒆 𝒍𝒂 𝒑𝒆𝒏𝒅𝒊𝒆𝒏𝒕𝒆 𝒅𝒆 𝒍𝒂 𝒓𝒂𝒎𝒑𝒂:
𝑑2 = 𝑎 ∗ 𝑑1
𝐸𝑜 = 0,4𝑚 → 𝑎𝑙𝑡𝑢𝑟𝑎 𝑐𝑎𝑖𝑑𝑎 → 𝑒𝑠𝑡𝑎𝑛𝑑𝑎𝑟
𝑑2 = 8.758 ∗ 2.570 ∗ 10−3 = 0.02525𝑚
𝑥 = 𝑙𝑜𝑛𝑔𝑖𝑡𝑢𝑑 → 0,7𝑚
𝟔. 𝒍𝒐𝒏𝒈𝒊𝒕𝒖𝒅 𝒅𝒆𝒍 𝒓𝒆𝒔𝒂𝒍𝒕𝒐:
𝐸𝑜
𝜃 = Arc tang ( ) 𝐿 = 6(ℎ2 − ℎ1)
𝑥
0,4 𝐿 = 6(0.0225 − 2.95 ∗ 10−3 ) = 0.1173𝑚
𝜃 = Arc tang ( ) = 29,58°
0,7
𝟕. 𝒑𝒆𝒓𝒅𝒊𝒅𝒂 𝒅𝒆 𝒄𝒂𝒓𝒈𝒂(𝒉𝒑):
𝟐. 𝒄𝒂𝒍𝒄𝒖𝒍𝒐 𝒅𝒆𝒍 𝒇𝒂𝒄𝒕𝒐𝒓 𝒓𝒆𝒔𝒐𝒍𝒖𝒄𝒊𝒐𝒏 (𝒂𝟏):
(ℎ2 − ℎ1)3
𝐹1 = 6 ∗ 1 → 𝑒𝑠𝑡𝑎𝑛𝑑𝑎𝑟 ℎ𝑝 =
4(ℎ1 ∗ ℎ2)
𝑐𝑜𝑠𝜃 (0.0225 − 2.95 ∗ 10−3 )3
𝐾 = 𝑐𝑜𝑠𝜃(𝐹1) + ℎ𝑝 = = 0.028𝑚
2𝐹1 4(0.0225 ∗ 2.95 ∗ 10−3 )
cos(29.588)
𝐾 = 𝑐𝑜𝑠(29,588)(6) + = 5.367 𝟖. 𝒗𝒐𝒍𝒖𝒎𝒆𝒏 𝒅𝒆𝒍 𝒓𝒆𝒔𝒂𝒍𝒕𝒐:
2(6)
(ℎ1 + ℎ2) ∗ 𝐿
𝑉= ∗𝑎
2
𝐹12
∅ = 𝑐𝑜𝑠 −1 2
(0.0225 + 2.95 ∗ 10−3 ) ∗ 0.1173
3
𝑉= ∗ 0.6 = 8.95 ∗ 10−4 𝑚3
2 2
(( ) + 𝐹1 + 𝑘)
( 3 ) 𝟗. 𝒂𝒍𝒕𝒖𝒓𝒂 𝒅𝒆 𝒍𝒂 𝒈𝒓𝒂𝒅𝒂 𝒇𝒊𝒏𝒂𝒍(𝒉𝒈):

𝑑22
(6)2 ℎ𝑔 =
∅ = 𝑐𝑜𝑠 −1 = 61.154 6
2
3
2 0.02252
(( ) + 6 + 5.367)
( 3 ) ℎ𝑔 = = 3.75 ∗ 10−3
6

𝑑2 8 ∗ 𝐹1 ∗ 𝑘 ∅ 𝟏𝟎. 𝑮𝒓𝒂𝒅𝒊𝒆𝒏𝒕𝒆 𝒅𝒆 𝒗𝒆𝒍𝒐𝒄𝒊𝒅𝒂𝒅(𝑮):


𝑎1 = =√ ∗ 𝑐𝑜𝑠 ( )
𝑑1 3 3
𝑦 ℎ𝑝
𝐺 =√ ∗√
𝑢 𝑡
Estudiante: Guaminga Oscar
𝑦
→ 𝑑𝑎𝑡𝑜=3114.64 𝟑. 𝒄𝒂𝒍𝒄𝒖𝒍𝒐 𝒅𝒆 𝒍𝒂 𝒍𝒐𝒏𝒈𝒊𝒕𝒖𝒅:
𝑢

L = v ∗ tiemp. retencion
ℎ𝑝
𝐺 = √3114.64 ∗ √ 𝑚 60𝑠
𝑡
L = 0.3 ∗ 3 min ∗ = 54𝑚
𝑠 𝑚
𝑉 8.95 ∗ 10−4 𝑚3
𝑡 → 𝒕𝒊𝒆𝒎𝒑𝒐 𝒅𝒆 𝒎𝒆𝒛𝒄𝒍𝒂 = = 0.895 𝟒. 𝒄𝒂𝒍𝒄𝒖𝒍𝒐 𝒅𝒆 𝒍𝒂 𝒂𝒍𝒕𝒖𝒓𝒂 𝒆𝒇𝒊𝒄𝒊𝒆𝒏𝒕𝒆:
𝑄 𝑚3
1 ∗ 10−3
𝑠
h = altura de la placa − borde libre
0.028
𝐺 = √3114.64 ∗ √ = 550𝑠𝑒𝑔
0.895
h = 1.2m − 0.1m = 1.1𝑚
𝟏𝟏. 𝒗𝒆𝒍𝒐𝒄𝒊𝒅𝒂𝒅 𝒂𝒍 𝒊𝒏𝒊𝒄𝒊𝒂𝒓 𝒆𝒍 𝒓𝒆𝒔𝒂𝒍𝒕𝒐 (𝒗𝟏):
𝟓. 𝒄𝒂𝒍𝒄𝒖𝒍𝒐 𝒅𝒆𝒍 𝒏𝒖𝒎𝒆𝒓𝒐 𝒅𝒆 𝒃𝒖𝒇𝒇𝒍𝒆𝒔:
𝑄
𝑣1 = 𝐿
(ℎ1)2 #buff =
𝑎𝑙𝑡𝑢𝑟𝑎 𝑑𝑒 𝑙𝑎 𝑝𝑙𝑎𝑐𝑎
𝑚3
1 ∗ 10−3 𝑚
𝑣1 = 𝑠 = 0.33 54
(2.95 ∗ 10−3 𝑚)2 𝑠 #buff = = 45 + 1(seguridad) = 46 buffles
1.2
𝟏𝟐. 𝒗𝒆𝒍𝒐𝒄𝒊𝒅𝒂𝒅 𝒇𝒊𝒏𝒂𝒍(𝒗𝟐):

𝑄
𝑣2 = 𝟓. 𝒍𝒐𝒏𝒈𝒊𝒕𝒖𝒅 𝒅𝒆𝒍 𝒕𝒂𝒏𝒒𝒖𝒆 𝒇𝒍𝒐𝒄𝒖𝒍𝒂𝒅𝒐𝒓:
(ℎ2)2
l = #buff ∗ ancho + (45 + 1) + ancho pared
𝑚3
1 ∗ 10−3
𝑣2 = 𝑠 = 0.044 𝑚
(0.0225𝑚)2 𝑠
l = 46 ∗ 0.057 + (45 + 1) + 0.05 = 4.92m
𝟓. 𝒂𝒏𝒄𝒉𝒐 𝒅𝒆𝒍 𝒕𝒂𝒏𝒒𝒖𝒆 𝒇𝒍𝒐𝒄𝒖𝒍𝒂𝒅𝒐𝒓
 DISEÑO FLOCULADOR-COAGULADOR

Datos: a = ancho pared ∗ 2 + altura

L 𝑚3 a = 0.056 ∗ 2 + 1.2 = 1.3m


𝑄=1 → 0.001
𝑠𝑒𝑔 𝑠𝑒𝑔

𝑡𝑖𝑒𝑚𝑝. 𝑟𝑒𝑡𝑒𝑛𝑐𝑖𝑜𝑛 = 3 min

𝑎𝑛𝑐ℎ𝑜 𝑝𝑎𝑟𝑒𝑑 = 5cm

ℎ(𝑎𝑙𝑡𝑢𝑟𝑎) = 1,2m
𝑚
𝑣(𝑣𝑒𝑙𝑜𝑐𝑖𝑑𝑎𝑑) = 0.3
𝑠
𝟏. 𝒄𝒂𝒍𝒄𝒖𝒍𝒐 𝒅𝒆𝒍 𝒂𝒓𝒆𝒂:

𝑄
𝐴=
𝑣

𝑚3
1 ∗ 10−3
𝑠
𝐴= 𝑚 = 3.33 ∗ 10−3 𝑚2
0.3
𝑠
𝟐. 𝒄𝒂𝒍𝒄𝒖𝒍𝒐 𝒅𝒆𝒍 𝒂𝒏𝒄𝒉𝒐 𝒅𝒆 𝒍𝒐𝒔 𝒄𝒂𝒏𝒂𝒍𝒆𝒔 𝒐 𝒃𝒖𝒇𝒇𝒍𝒆𝒔:

√𝐴 = ancho = 0.057m
Estudiante: Guaminga Oscar
𝑙 3.5088𝑚
𝑎= → = 1.7544𝑚
2 2
𝑙 3.5088𝑚
ℎ= → = 1.1696𝑚
3 2
Calculo de caudal solido:
3
𝑔 𝑚3 1𝑚 1000𝑙 1𝑘𝑔
𝑄(𝑠ó𝑙𝑖𝑑𝑜)𝑛𝑖 = 0.143 ∗ 0.001 ∗ ∗ ∗
𝐿 𝑠𝑒𝑔 1500kg 1𝑚3 1000𝑔
VISTA LATERAL 86400𝑠𝑒𝑔

1𝑑𝑖𝑎

𝑚3
𝑄(𝑠ó𝑙𝑖𝑑𝑜)𝑛𝑖 = 0.0082
𝑑𝑖𝑎
Volumen de un prisma:

𝑉𝑝𝑟𝑖𝑠𝑚𝑎 = 𝐴𝑟𝑒𝑎 𝑏𝑎𝑠𝑒 ∗ ℎ

𝑚∗𝑙 0.6187 ∗ 3.5088𝑚


𝐴𝑟𝑒𝑎𝑏𝑎𝑠𝑒 = → 𝐴𝑟𝑒𝑎𝑏𝑎𝑠𝑒 = = 1.0854𝑚2
2 2
𝑚
𝑡𝑔100 = → 𝑚 = 𝑙 ∗ 𝑡𝑔100 → 𝑚 = 3.5088𝑚 ∗ 𝑡𝑔100
𝑙
VISTA SUPERIOR = 0.6187
𝑉𝑝𝑟𝑖𝑠𝑚𝑎 = 𝐴𝑟𝑒𝑎 𝑏𝑎𝑠𝑒 ∗ ℎ

II. DISEÑO DE UN SEDIMENTADOR PRIMARIO 𝑉𝑝𝑟𝑖𝑠𝑚𝑎 = 1.0854𝑚2 ∗ 1.1696𝑚

Datos: 𝑉𝑝𝑟𝑖𝑠𝑚𝑎 = 1.2695𝑚3

Ηdomiciliaria = 2h = 7200seg Tiempo de vaciado:

𝑉𝑝𝑟𝑖𝑠𝑚𝑎
L 𝑚3 𝑡𝑣 =
𝑄=1 → 0.001 𝑄(𝑠ó𝑙𝑖𝑑𝑜)𝑛𝑖
𝑠𝑒𝑔 𝑠𝑒𝑔
𝑚𝑔 𝑔 1.2695𝑚3
𝑆𝑆𝑒𝑑 = 1803 = 1.803 𝑡𝑣 = = 154.8209𝑑𝑖𝑎
𝐿 𝐿 𝑚3
0.0082
kg 𝑑𝑖𝑎
𝜌 = 1500
𝑚3 𝑡𝑣 = 154.8209𝑑𝑖𝑎
Volumen del Sedimentador:
Comprobación si esta en Flujo Laminar:
V 𝑚
Q=
𝑡 𝑉𝑒𝑙. 𝐹𝑙𝑢𝑗𝑜 < 0.3
𝑠𝑒𝑔
𝑚3
V = 0.001 ∗ 7200seg 𝑄 𝑄
𝑠𝑒𝑔 𝑉𝑒𝑙𝑜𝑐𝑖𝑑𝑎𝑑 = → 𝑉𝑒𝑙. =
𝐴𝑟𝑒𝑎 𝑎∗ℎ
V = 7.2𝑚3
𝑚3
0.001 𝑠𝑒𝑔
Relación: 𝑙 = 2𝑎 = 3ℎ
𝑉𝑒𝑙. =
1.7544𝑚 ∗ 1.1696𝑚
𝑙
𝑙𝑎𝑟𝑔𝑜 → 𝑙 = 2𝑎 → 𝑎 = 𝑚 𝑚
2 −4
𝑉𝑒𝑙. = 4.8734 ∗ 10 → 𝑉𝑒𝑙. = 0.0004
𝑙 𝑠𝑒𝑔 𝑠𝑒𝑔
𝑙𝑎𝑟𝑔𝑜 → 𝑙 = 3ℎ → ℎ =
3 𝑚 𝑚
0.0004 < 0.3
𝑙 𝑙 𝑠𝑒𝑔 𝑠𝑒𝑔
𝑉= ∗𝑙∗
2 3
Si se encuentra en flujo laminar.
3
𝑙 = √6 ∗ 𝑉
3
𝑙 = √6 ∗ 7.2𝑚3 = 3.5088𝑚
Estudiante: Guaminga Oscar
III. DISEÑO DE UN FILTRO PERCOLADOR

Datos:

𝐿 𝑚3
Q=1 (𝑓𝑙𝑢𝑗𝑜) = 86,4
𝑠 𝑑𝑖𝑎
𝑚𝑔 𝑘𝑔
𝑆 = 654 (𝐷𝐵𝑂 𝑒𝑓𝑙𝑢𝑒𝑛𝑡𝑒) = 0.654 3
𝐿 𝑚
𝑚𝑔 𝑘𝑔
𝑆𝑜 = 125 (𝐷𝐵𝑂 𝑎𝑓𝑙𝑢𝑒𝑛𝑡𝑒) = 0.125 3
𝐿 𝑚
𝐻 = 1.5 (𝐴𝑙𝑡𝑢𝑟𝑎)

𝑅 = 2 (𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡𝑒)

𝑅𝑠𝑝 = 0.28 (𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡𝑒)

DBO de salida del sedimentador primario (Ssp)

Ssp = S (1 − Rsp)

654 kg
Ssp = (1 − 0.28)
1000 𝑚3
𝐾𝑔
Ssp = 0.4709
𝑚3

Eficiencia del filtro percolador


𝑆𝑠𝑝 − 𝑆𝑜
E=
𝑆𝑠𝑝

0.4709 − 0.125
E=
VISTA LATERAL 0.4709

E = 0.7346

Factor de recirculación
1+R
F=
𝑅
(1 + )
10
1+2
F=
2
(1 + )
10

F = 2.08

Calculo de la carga orgánica que ingresa al filtro percolador

Carga O = Ssp . Q
VISTA SUPERIOR
𝑘𝑔 𝑚3
Carga O = (0.4709 ) . (86.4 )
𝑚3 𝑑𝑖𝑎
𝑘𝑔
Carga O = 40.686
𝑑𝑖𝑎

Calculo del volumen del filtro percolador

𝐶𝑎𝑟𝑔𝑎 𝑂 0.4432 ∗ 𝐸 2
V= ( )( )
𝐹 1−𝐸

40.686 0.4432 ∗ 0.7346 2


V= ( )( )
2.08 1 − 0.7346
V = 29.44 𝑚3
Estudiante: Guaminga Oscar
Calculo del Área del filtro percolador SISTEMA FLOCULACIÓN – COAGULACIÓN (MECÁNICO)

𝑉 IV. Cálculos para el sistema de floculación- coagulación


A=
𝐻 (mecánico)
 Sistema Retro Mezclador
29.44 𝑚3
A=
1.5 𝑚 Datos:
A = 19.62 𝑚2 𝑚3
Q = 1 ∗ 10−3
Calculo del diámetro del filtro percolador 𝑠
𝑇 𝑑 = 10 𝑠𝑒𝑐
4∗𝐴
D= √ 𝐺𝑟𝑎𝑑𝑖𝑒𝑛𝑡𝑒 𝑑𝑒 𝑣𝑒𝑙𝑜𝑐𝑖𝑑𝑎𝑑 (𝐺) = 700 𝑠𝑒𝑐
𝜋
𝑉𝑜𝑙𝑢𝑚𝑒𝑛 𝑑𝑒𝑙 𝑡𝑛𝑎𝑞𝑢𝑒 = 𝑄 ∗ 𝑇𝑑
4 ∗ 19.62 𝑚2 𝑚3
D= √ 𝑉𝑜𝑙𝑢𝑚𝑒𝑛 𝑑𝑒 𝑎𝑔𝑢𝑎 𝑞𝑢𝑒 𝑒𝑛𝑡𝑟𝑎 = 1 ∗ 10−3 ∗ 10 𝑠 = 0.01 𝑚3
𝜋 𝑠

D = 4.99 m ≈ 5m Tanque cuadrado

𝑊 = 1.5 𝑚

𝑉𝑜𝑙𝑢𝑚𝑒𝑛 𝑑𝑒 𝑎𝑔𝑢𝑎 𝑞𝑢𝑒 𝑒𝑛𝑡𝑟𝑎 = 0.01 𝑚3

𝐴𝑟𝑒𝑎 𝑑𝑒𝑙 𝑡𝑎𝑛𝑞𝑢𝑒: 1.5 ∗ 1.5 = 2.25 𝑚2 𝐴𝑛𝑐ℎ𝑜 = 1 𝑚

Profundidad Útil

𝑉 0.01
= = 4.44 ∗ 10−3
𝐴 2.25
Potencia disipada

𝑃 = 𝐺2 ∗ 𝑈 ∗ 𝑉

𝑃 = 7002 ∗ 9.69 ∗ 10−4 ∗ 0.01

𝑃 = 4.74 𝑤𝑎𝑡𝑠

Nota: una paleta debe estar a 100 Rpm

𝑘𝑡 = 1.6  Dato

Calculo del largo de las paletas

5 𝑃
VISTA LATERAL 𝐷= √
𝑘𝑡 ∗ 𝑝 ∗ 𝑛3

p = 1024

n = 1.63

5 4.74 𝑤𝑎𝑡𝑠
𝐷= √
1.6 ∗ 1024 ∗ 1.633

𝐷 = 0.23 𝑚

Calculo de la potencia del motor

Perdida  25%

𝑝𝑜𝑡𝑒𝑛𝑐𝑖𝑎 𝑑𝑖𝑠𝑖𝑝𝑎𝑑𝑎
𝑃 𝑒𝑗𝑒 =
0.75

VISTA SUPERIOR
Estudiante: Guaminga Oscar
4.74
𝑃 𝑒𝑗𝑒 =
0.75
𝑃 𝑒𝑗𝑒 = 6.33 𝑤𝑎𝑡𝑠−→ (1 𝐻𝑝 𝑑𝑒 𝑝𝑜𝑡𝑒𝑛𝑐𝑖𝑎 𝑝𝑎𝑟𝑎 𝑐𝑎𝑑𝑎 𝑝𝑎𝑙𝑒𝑡𝑎)

SISTEMA FLOCULADOR- COAGULADOR

Datos

Potencia para 2 compartimientos

4.74
𝑃 𝑒𝑗𝑒 =
0.75
El primer compartimiento tendrá un Td = 30 s

El segundo compartimiento tendrá un Td = 20 s

Calculo del volumen

𝑉 = 𝑄∗𝑡

𝑉 = 1 ∗ 10−3 ∗ 30𝑠

𝑉 = 0.03 𝑚3

Como son 2 compartimientos el volumen se divide para 2

0.03 𝑚3
𝑉= = 0.015
2
Calculo de las potencias para los compartimientos

Datos

𝑈 = 1.139 ∗ 10−3 VISTA LATERAL

𝑃1 = 𝐺 2 ∗ 𝑉 ∗ 𝑈

𝑃1 = 302 ∗ 0.015 ∗ 1.139 ∗ 10−3

𝑃1 = 0.015 𝑘𝑤

𝑃2 = 𝐺 2 ∗ 𝑉 ∗ 𝑈

𝑃2 = 202 ∗ 0.015 ∗ 1.139 ∗ 10−3

𝑃2 = 0.00683𝑘𝑤

Cantidad de coagulante de 𝑨𝒍𝟐 (𝑺𝑶𝟒 )𝟑

Concentración al 20% donde VISTA SUPERIOR

𝐷∗𝑄
𝑞=
𝐶∗𝑃
𝑞∗𝑃∗𝐶
𝐷=
𝑄
𝑚𝑔
0.03 ∗ 0.89 ∗ 200000
𝐷= 𝐿
𝐿
1
𝑠
𝑚𝑔
𝐷 = 5.34
𝐿
Estudiante: Guaminga Oscar
V. DISEÑO DEL SISTEMA DE DESINFECCION
(CLARIFICADOR)

Datos:

𝑚3
Q = 1 ∗ 10−3
𝑠
𝑚𝑔
𝑆𝑜𝑙𝑖𝑑𝑜𝑠 = 1803
𝐿
𝑇 𝑣𝑎𝑐𝑖𝑎𝑑𝑜 = 15 𝑑𝑖𝑎𝑠

𝐸 = 20 %

𝑘𝑔 𝑘𝑔
𝑑𝑒𝑛𝑠𝑖𝑑𝑎𝑑 = 1.5 = 1500 3
𝐿 𝑚

𝐻 =3𝑚

Calculo del volumen de la tolva

𝑚3 𝑚𝑔 1000 𝐿 1𝑘𝑔 1 𝑚3
𝑉 𝑡𝑜𝑙𝑣𝑎 = 10−3 ∗ 1803 ∗ ∗ ∗
𝑠 𝐿 1𝑚 3 1000000 𝑚𝑔 1500 𝑚𝑔
VISTA LATERAL 86400 𝑠
∗ 15 𝑑𝑖𝑎𝑠 ∗
1 𝑑𝑖𝑎

𝑉 𝑡𝑜𝑙𝑣𝑎 = 1.55 𝑚3

Calculo del volumen del clarificador

1.55 𝑚3
Vc =
0.2

Vc = 7.75 𝑚3

Dimensionamiento

𝜋 ∅2
Vc = ∗3
12
VISTA SUPERIOR
12 ∗ (7.75)
∅= √
3∗ 𝜋

∅ = 3.14 𝑚
Estudiante: Guaminga Oscar
VI. DISEÑO DEL REACTOR UASB

Datos:
−1
𝑇𝑎𝑠𝑎 𝑑𝑒 𝑑𝑒𝑔𝑟𝑎𝑑𝑎𝑐𝑖ó𝑛 = 1.5𝑑í𝑎𝑠

L 𝐿
𝑄=1 → 86400
𝑠𝑒𝑔 𝑑𝑖𝑎
𝑚𝑔
𝐷𝐵𝑂 𝑠𝑒 𝑟𝑒𝑑𝑢𝑐𝑒 = 125
𝐿
𝑽𝒐𝒍𝒖𝒎𝒆𝒏 =?

Tiempo:

100
ln( )
𝑡= 125
−1.5𝑑𝑖𝑎𝑠
𝑡 = 0.148𝑑𝑖𝑎
Volumen:
VISTA LATERAL
𝑉 =𝑄∗𝑡
𝐿
𝑉 = 86400 ∗ 0.148𝑑𝑖𝑎
𝑑𝑖𝑎
𝑉 = 12787.2𝐿

𝑉 = 12.787𝑚3

VISTA SUPERIOR
Estudiante: Guaminga Oscar
VII. DISEÑO DE UN LECHO DE SECADO

Datos:

L
𝑄=1
𝑠𝑒𝑔
𝑚𝑔
𝑆𝑆𝑒𝑑 = 1803
𝐿
kg kg
𝜌 = 1500 = 1.5
𝑚3 𝐿
Carga de solidos que ingresan al sedimentador:

C = Q ∗ SSed

L 𝑚𝑔 1𝑔 1𝑘𝑔 86400𝑠
C=1 ∗ 1803 ∗ ∗ ∗
𝑠𝑒𝑔 𝐿 1000𝑚𝑔 1000𝑔 1𝑑
𝑘𝑔
C = 155.779
𝑑
Masa de solidos que conforman los lodos:
𝑘𝑔 𝑘𝑔
𝑀𝑠𝑑 = (0.5 ∗ 0.7 ∗ 0.5 ∗ 155.779 ) + (0.5 ∗ 0.3 ∗ 155.779 )
𝑑 𝑑

𝑘𝑔 𝑘𝑔
VISTA LATERAL 𝑀𝑠𝑑 = (0.5 ∗ 0.7 ∗ 0.5 ∗ 155.779 ) + (0.5 ∗ 0.3 ∗ 155.779 )
𝑑 𝑑
𝑘𝑔
𝑀𝑠𝑑 = 50.628
𝑑
Volumen diario de lodos digeridos:

𝑀𝑠𝑑
𝑉𝑙𝑑 =
%𝑆𝑜𝑙𝑖𝑑𝑜𝑠
𝜌∗( )
100%
𝑘𝑔
50.628
𝑉𝑙𝑑 = 𝑑
kg 12%
1.5 𝐿 ∗ (100%)

𝐿
𝑉𝑙𝑑 = 281.267
𝑑
Volumen de lodos a extraerse:

𝑉𝑙𝑑 ∗ 𝑇𝑑
𝑉𝑒𝑙 =
VISTA SUPERIOR 1000

𝐿 1𝑚3
𝑉𝑒𝑙 = 281.267 ∗ 40𝑑 ∗
𝑑 1000𝐿

𝑉𝑒𝑙 = 11.251𝑚3

Área de Lecho de Secado:

𝑉𝑒𝑙
𝐴𝑙𝑠 =
𝐻𝑎

11.251𝑚3
𝐴𝑙𝑠 =
0.4𝑚

𝐴𝑙𝑠 = 28.127𝑚2
Estudiante: Guaminga Oscar
Área Individual de los lechos de secado:

𝐴𝑙𝑠
𝐴𝑙𝑠𝑖 =
𝑁𝑜 𝐿𝑒𝑐ℎ𝑜𝑠

28.127𝑚2
𝐴𝑙𝑠𝑖 =
4

𝐴𝑙𝑠𝑖 = 7.032𝑚2

Longitud del lecho de secado:

7.032𝑚2
𝐿=
1.5𝑚
𝐿 = 2.344𝑚

VIII. TASA DE COBRANZA DE PTAR. EL PERAL-AMBATO

 TASA DE COBRO

Datos:

L 𝑚3
𝑄=1 → 0.001
𝑠𝑒𝑔 𝑠𝑒𝑔
𝑖 = 1.5 %

tiempo = 10 años

Se necesita Cantidad de floculante y cloro


𝑚𝑔
Floculante (sulfato de aluminio)  5.33
𝐿

𝑔
Cloro  0.01
𝐿

Calculo del precio del floculante

𝑚𝑔 1000𝐿 18 $ 1𝑘𝑔 1 𝑞𝑞
5.33 ∗ ∗ ∗ ∗
𝐿 1𝑚3 𝑞𝑞 1000000𝑚𝑔 50 𝑘𝑔

= 1.919 ∗ 10−3

Calculo del precio del cloro

𝑔 1000𝐿 13 $ 1𝑘𝑔 1 𝑞𝑞
0.01 ∗ 3
∗ ∗ ∗
𝐿 1𝑚 𝑞𝑞 1000𝑔 50 𝑘𝑔

= 2.6 ∗ 10−3

Suma de los costos

∑ 2.6 ∗ 10−3 + 1.91 ∗ 10−3 = 4.519 ∗ 10−3


Estudiante: Guaminga Oscar
Servicios extras 𝑻𝒂𝒔𝒂 ∗ #𝒉𝒂𝒃 = 9671.17 + (1781222.4*1.31)

Luz: 355 $ 9671.17 ∗ + (1781222.4 ∗ 1.31)


𝑻𝒂𝒔𝒂 =
329856 ℎ𝑎𝑏
Servicios básicos: 100 $
$
Operador 1: 450 $ 𝑻𝒂𝒔𝒂 = 7.10
𝑚𝑒𝑠
Operador 2: 500 $

Técnico: 2000 $

Costo total de los servicios = 𝟑𝟒𝟎𝟓 $/𝒎𝒆𝒔

Costo caudal/mes

3405$ $
= 1.31
1∗ 10−3 𝑚3
∗ 30𝑑𝑖𝑎𝑠 ∗ 86400𝑠
𝑠

Costo operacional = 100000$


$
Costo total = 1.31
𝑚3

Costo final de la PTAR

𝐶𝑜𝑠𝑡𝑜 𝑓𝑖𝑛𝑎𝑙 = 100000 (1 + 0.015)10

𝐶𝑜𝑠𝑡𝑜 𝑓𝑖𝑛𝑎𝑙 = 1160540.82 $

Calculo del volumen de agua

𝐿
329856 ℎ𝑎𝑏 ∗ 180 ∗ 30 𝑑𝑖𝑎𝑠
𝐻𝑎𝑏 . 𝑑𝑖𝑎
= 1781222.4 𝑚3

Costo del agua en 10 años para la población de Ambato

1160540.82 $
12 ∗ 10 𝑎ñ𝑜𝑠
= 9671.17 $

Tasa de cobranza de la PTAR en la ciudad de Ambato

View publication stats