CALCULO DE PERDIDAS ELECTRICAS EN BAJA TENSION

Voltaje
Constante          220
K 1 o 3 3

TRAMO LON CALIBRE DemandaMomento Corriente PERDIDA EN KW


I F Mts AWG KVA KVA*Mt Amp Tramo % Total

0 1 20 CU 2x4/0 89.7 1,794 235.4 0.31 0.35% 0.31


1 2 15 CU 2 29.9 449 78.5 0.17 0.56% 0.48
1 3 25 CU 2 29.9 748 78.5 0.28 0.93% 0.76
1 4 35 CU 2 29.9 1,047 78.5 0.39 1.30% 1.14
CALIBRE K R Capacidad
AWG 1/Mts*Kva  OHM/MT Amp
CU 8 0.00765 0.002360
CU 6 0.00501 0.001485
CU 4 0.00338 0.000934
CU 2 0.00135 0.000599
CU 1/0 0.00167 0.000377
CU 2/0 0.00142 0.000299
CU8C 0.00410 0.002360
CU 2x4/0 0.00024 0.00009
RED ABIERTA
ACSR 4 0.00532 0.001597
ACSR 2 0.00367 0.000696
ACSR 1/0 0.00260 0.000696
ACSR 2/0 0.00217 0.000556
ACSR 3/0 0.00175 0.000449
ACSR 4/0 0.00143 0.000368
TRIFASICO SUBTERRANEO
CU 4 S 0.00186 0.000934
CU 2 S 0.00135 0.000599
CU 1/0S 0.00089 0.000377
CU 2/0S 0.00072 0.000299
CU 3/0S 0.00059 0.000237
CU 4/0S 0.00049 0.000188
CU 250S 0.00041 0.000160
CU 300S 0.00036 0.000134
CU 350S 0.00051 0.000115
CU 400S 0.00046 0.000101
CU 500S 0.00040 0.000081
CU 600S 0.00036 0.000068