A/A#1 EN ÁREA EXTERIOR


UMA 17 TON 70A/3P TAB TAB
UMA 17 TON 70A/3P RECTIFICADOR TAB TAB "A/A"
HUAWEI "E" "D"
70A/3P UMA 25 TON 8 # 500 THHN CU
70A/3P UMA 25 TON 60A/3P UMA 9 TON BATTERIES ROOM
2 # 1/0 CU DESN.
20A/2P A/A SPLIT BATT ROOM
2 - 4"Ø P.V.C.
A/A SPLIT BATT ROOM 20A/2P
3 # 2/0 THHN CU
UBICADO EN LOBBY 1 # 2 CU DESN. EN BATTERIES ROOM UBICADO EN
TAB TAB 1 - 2 1/2"Ø P.V.C. UBICADO EN LOBBY
TAB CHILLER 225KVA 6 # 350 THHN CU CTO ELECTRICO TAB TAB
DEPOSITO LUCES BK 4 # 8THHN CU
A/A#2 #1 2 # 2 CU DESN. 3 # 8 THWN TAB "C" TOMACORRIENTES GARITA
400A TX 1 # 8 CU DESN.
208V 2 - 3"Ø P.V.C. 1 # 8 CU D. BK
1 - 1 "Ø P.V.C. 1 - 1-1/4"Ø P.V.C. 100A/2P
3 # 1/0 THHN CU 3 # 3/0 THWN 480V 80A/3P EN
1 # 2 CU DESN. 1 # 2 THWN 100A/3P
NEUTRAL SUELTO CAJA CTO ICT ROOM
4 # 2 THHN CU 4 # 2 THWN
1 - 2 "Ø P.V.C. 1 # 8 CU D. PDP
1 # 8 CU DESN. 1 # 8 CU D. 4 # 2/0 THHN CU 4 # 2 THHN CU 3 # 2 THHN CU
1 - 2"Ø P.V.C. 1 - 2-21 "Ø P.V.C. 600A/3P 1 - 1-1/4"Ø P.V.C. 1 # 2 CU DESN. 1 # 8 CU DESN. 1 # 8 CU DESN.
4 # 2 THHN CU
4 # 6 THHN CU 600A/3P 1 - 2 1/2 "Ø P.V.C. 1 - 1 1/2 "Ø P.V.C. 1 - 1 1/2 "Ø P.V.C.
1 # 8 CU DESN.
1 # 8 CU DESN. 225A/3P 200A/3P
TAB 1 - 2 "Ø P.V.C.
1 - 1 "Ø P.V.C. 80A/3P 80A/3P
"B"
125A/3P 90A/3P
LIBRE 225A/3P 50A/2P
TVSS 15A/3P 225A/3P LIBRE
80A/3P EN BATTERIES ROOM 3 # 250 THHN CU
250A/3P 1 # 2/0 THHN CU
4 # 4 THHN CU EN BATTERIES ROOM 3 # 12 THHN CU 400A/3P
1 # 8 CU DESN. 1 # 12 CU DESN. TAB
1 # 2 CU DESN.
400A/3P 3 # 250 THHN CU
1 - 1 1/4"Ø P.V.C. RECTIFICADORES 1 - 3"Ø P.V.C.
EMERSON 1 # 2/0 THHN CU
1 # 2 CU DESN. BK EN BK EN
TVSS 225A/3P 225A/3P
15A/3P 175A/2P LIBRE CAJA CAJA
GENERADOR DE EMERGENCIA GENERADOR DE EMERGENCIA UBICADO EN 1 - 3"Ø P.V.C.
DE 625kVA/500kW @ 0.8 FP DE 625kVA/500kW @ 0.8 FP REC 4 175A/2P 175A/2P REC 1 4 # 2/0 XHWN AL
REC 5 REC 2
ITC
TRIFASICO TRIFASICO
120/208 VAC, 60 Hz 120/208 VAC, 60 Hz
175A/2P 125A/2P ROOM 1 # 6 XHWN AL
REC 3
1600A/3P 1600A/3P 125A/2P 175A/2P 1 - 1-1/4"Ø P.V.C.
TAB-VACIO

VARILLA DE ACERO
G G 3 # 500 THHN CU
1 # 4/0 CU THHN
SWITCH ROOM
3# 2 THHN CU
1# 8 CU DESN.
TAB06
80KVA UPS
#1
80KVA UPS
#2
VARILLA DE ACERO 1 # 1/0 CU DESN. 225A
COBRIZADO 3/4"-8' COBRIZADO 3/4"-8' 1-1 1/4" P.V.C
1 - 4"Ø P.V.C. 30 CTOS 3 # 4/0 THHN CU 4 # 2/0 XHWN AL
NO ATERRIZAR NEUTRAL NO ATERRIZAR NEUTRAL
PDU DC 1 # 2 THHN CU 1 # 6 XHWN AL
CAJA DE CT
48"x36"x17" VIENE DE 100A/2P 1 # 6 CU DESN. 1 - 1-1/4"Ø P.V.C.
MEDIDOR TAB05 TAB
TRANSFORMADOR
24"x12"x9" ATS #1 RECTIFICADOR
225A 1 -2-21"Ø P.V.C.
IP ATS #2 "F"
3F,4HILOS, 60HZ
2000A/3P 28 # 500 XHHN AL 2000 A/3P 3 # 500 THHN CU EMERSON 42 CTOS E ATS 1
1200 A/3P 4#4 THHN CU BK
500 kVA 1 # 4/0 CU THHN 40KVA INVERSOR 05 C LIBRE
7 # 500 DESN. AL N
13.2KV 120/208V. Y 1 # 1/0 CU DESN. 2#3/0THHN CU -48VDC / 1# 6 CU DESN. 150A 4#2THHN CU
E E TX01
8 - 4"Ø P.V.C. N 1#3/0THHN CU 230VAC GROUND VIENE DE PANEL P03
C 1 - 4"Ø P.V.C. 208V/ 100A/2P
ITESA
05/12/2004
N C 1# 4 CU DESN. 1 #6 DESN CU
NG 12 # 500MCM AL
230V = 3#2/0 THHN CU 125A/3P
12 # 500MCM AL 1-1" P.V.C
4 # 500MCM AL N. 1# 3/0 CU DESN.
4 # 500MCM AL N. BK TAB UBICADO EN TC/TU
CP 4 # 2 CU D. BYPASS
4 # 2 CU D. 90A/3P "A" ITC P03 P02
3#1 THHN CU UPS
HASTA 4 - 4"Ø 4 - 4"Ø ROOM UPS1 UPS1
STRANDER 3# 4 THHN CU 4#4THHN CU
POSTE
3# 8 THHN CU P01 1 #6 DESN CU
DUCTO UPS1
1# 8 CU DESN. 4#4THHN CU 1-1 1/4" P.V.C
25"X25"X25"
21 # 500 XHHN AL BX EN BK EN CAJA PDU DC 1-1 1/4" P.V.C 1 #6 DESN CU
TAB 80A/3P
12 # 500 DESN. CAJA 150KVA 600A VIENE DE 125A/3P 1-1 1/4" P.V.C
# 1/0 6 # 350 THHN CU TRANSF 30 CIR 80A/3P
12 - 4"Ø P.V.C. 1"Ø 400A TX RECTIFICADOR TAB04
28 # 500 XHHN AL CHILLER 2 # 1/0 CU DESN. EN SWITCH ROOM
TAB
208V TVSS EMERSON 225A
7 # 500 DESN. AL VIEJO 2 - 4"Ø P.V.C. INTERCONEXION
480V 15A/3P INVERSOR 04 42 CTOS
8 - 4"Ø P.V.C. 4#2THHN CU
175A/2P 40KVA -48VDC /
10' 10'
175A/2P TX02 1 #6 DESN CU
2#3/0THHN CU 230VAC
VARILLAS DE ACERO 175A/2P 208V/ 1-2" P.V.C
3/4"X 8' LARGO 3 # 3/0 THWN CONECTADO DIRECTO A LAS BARRAS 1#3/0THHN CU =
230V 3#2/0 THHN CU
CON POZO DE INSPECCION 1 # 2 THWN DEL PDP 1# 4 CU DESN.
8"Øx6" DE PROFUNDIDAD 1 # 8 CU D. 1# 3/0 CU DESN.
1 - 2-21 "Ø P.V.C. BYPASS
UBICADO EN
ITC
3#1 THHN CU ROOM
STRANDER
TAB06
225A 3# 2 THHN CU
PDU DC 12 CTOS/3P 1# 8 CU DESN.
VIENE DE 1-1 1/4" P.V.C
RECTIFICADOR
EMERSON TAB03
225A 100/2P
INVERSOR 03 30 CTOS 3#1/0 THHN CU NOTA: SECUNDARIO DE TX EN EL PISO SIN
40KVA -48VDC / CANALIZACION
2#3/0THHN CU
TX03 230VAC
1#3/0THHN CU
1# 4 CU DESN.
208V/ = 100/2P
230V 3#2/0 THHN CU INV=32KVA
1# 3/0 CU DESN. IMAX=140 AMP.
BYPASS Vout/ac 230V/2P
Vin/dc -48V

3#1 THHN CU
STRANDER