VARILLA DE ACERO
G G 3 # 500 THHN CU
1 # 4/0 CU THHN
SWITCH ROOM
3# 2 THHN CU
1# 8 CU DESN.
TAB06
80KVA UPS
#1
80KVA UPS
#2
VARILLA DE ACERO 1 # 1/0 CU DESN. 225A
COBRIZADO 3/4"-8' COBRIZADO 3/4"-8' 1-1 1/4" P.V.C
1 - 4"Ø P.V.C. 30 CTOS 3 # 4/0 THHN CU 4 # 2/0 XHWN AL
NO ATERRIZAR NEUTRAL NO ATERRIZAR NEUTRAL
PDU DC 1 # 2 THHN CU 1 # 6 XHWN AL
CAJA DE CT
48"x36"x17" VIENE DE 100A/2P 1 # 6 CU DESN. 1 - 1-1/4"Ø P.V.C.
MEDIDOR TAB05 TAB
TRANSFORMADOR
24"x12"x9" ATS #1 RECTIFICADOR
225A 1 -2-21"Ø P.V.C.
IP ATS #2 "F"
3F,4HILOS, 60HZ
2000A/3P 28 # 500 XHHN AL 2000 A/3P 3 # 500 THHN CU EMERSON 42 CTOS E ATS 1
1200 A/3P 4#4 THHN CU BK
500 kVA 1 # 4/0 CU THHN 40KVA INVERSOR 05 C LIBRE
7 # 500 DESN. AL N
13.2KV 120/208V. Y 1 # 1/0 CU DESN. 2#3/0THHN CU -48VDC / 1# 6 CU DESN. 150A 4#2THHN CU
E E TX01
8 - 4"Ø P.V.C. N 1#3/0THHN CU 230VAC GROUND VIENE DE PANEL P03
C 1 - 4"Ø P.V.C. 208V/ 100A/2P
ITESA
05/12/2004
N C 1# 4 CU DESN. 1 #6 DESN CU
NG 12 # 500MCM AL
230V = 3#2/0 THHN CU 125A/3P
12 # 500MCM AL 1-1" P.V.C
4 # 500MCM AL N. 1# 3/0 CU DESN.
4 # 500MCM AL N. BK TAB UBICADO EN TC/TU
CP 4 # 2 CU D. BYPASS
4 # 2 CU D. 90A/3P "A" ITC P03 P02
3#1 THHN CU UPS
HASTA 4 - 4"Ø 4 - 4"Ø ROOM UPS1 UPS1
STRANDER 3# 4 THHN CU 4#4THHN CU
POSTE
3# 8 THHN CU P01 1 #6 DESN CU
DUCTO UPS1
1# 8 CU DESN. 4#4THHN CU 1-1 1/4" P.V.C
25"X25"X25"
21 # 500 XHHN AL BX EN BK EN CAJA PDU DC 1-1 1/4" P.V.C 1 #6 DESN CU
TAB 80A/3P
12 # 500 DESN. CAJA 150KVA 600A VIENE DE 125A/3P 1-1 1/4" P.V.C
# 1/0 6 # 350 THHN CU TRANSF 30 CIR 80A/3P
12 - 4"Ø P.V.C. 1"Ø 400A TX RECTIFICADOR TAB04
28 # 500 XHHN AL CHILLER 2 # 1/0 CU DESN. EN SWITCH ROOM
TAB
208V TVSS EMERSON 225A
7 # 500 DESN. AL VIEJO 2 - 4"Ø P.V.C. INTERCONEXION
480V 15A/3P INVERSOR 04 42 CTOS
8 - 4"Ø P.V.C. 4#2THHN CU
175A/2P 40KVA -48VDC /
10' 10'
175A/2P TX02 1 #6 DESN CU
2#3/0THHN CU 230VAC
VARILLAS DE ACERO 175A/2P 208V/ 1-2" P.V.C
3/4"X 8' LARGO 3 # 3/0 THWN CONECTADO DIRECTO A LAS BARRAS 1#3/0THHN CU =
230V 3#2/0 THHN CU
CON POZO DE INSPECCION 1 # 2 THWN DEL PDP 1# 4 CU DESN.
8"Øx6" DE PROFUNDIDAD 1 # 8 CU D. 1# 3/0 CU DESN.
1 - 2-21 "Ø P.V.C. BYPASS
UBICADO EN
ITC
3#1 THHN CU ROOM
STRANDER
TAB06
225A 3# 2 THHN CU
PDU DC 12 CTOS/3P 1# 8 CU DESN.
VIENE DE 1-1 1/4" P.V.C
RECTIFICADOR
EMERSON TAB03
225A 100/2P
INVERSOR 03 30 CTOS 3#1/0 THHN CU NOTA: SECUNDARIO DE TX EN EL PISO SIN
40KVA -48VDC / CANALIZACION
2#3/0THHN CU
TX03 230VAC
1#3/0THHN CU
1# 4 CU DESN.
208V/ = 100/2P
230V 3#2/0 THHN CU INV=32KVA
1# 3/0 CU DESN. IMAX=140 AMP.
BYPASS Vout/ac 230V/2P
Vin/dc -48V
3#1 THHN CU
STRANDER