ALBAÑILERÍA ESTRUCTURAL
Tercera Práctica - CIV364
Grupo : Nº 2
Alumnos :
Karina Flores Huiman 19961163
Irma Alvarado Lara 19990245
Carlos Asalde Wong 19990318
Fiorella Rojas Rivera 19992142
ÍNDICE
2. ESTRUCTURACIÓN Y PREDIMENSIONAMIENTO................................................... 6
4. CENTRO DE MASA.....................................................................................................15
7. MODELAMIENTO........................................................................................................18
8. ANÁLISIS SÍSMICO.....................................................................................................26
10. DISEÑO DE LOS MUROS DEL PRIMER PISO ANTE SISMO SEVERO
(AGRIETAMIENTO POR CORTE) ......................................................................................32
14. BIBLIOGRAFÍA............................................................................................................49
INTRODUCCIÓN
Para cumplir con los fines anteriormente mencionados y considerando que el Perú es un
país sísmico, la nueva Norma considera varias verificaciones y consideraciones a tomar
en cuenta en el diseño, que son coherentes con lo estipulado en la Norma Sísmica
E – 030, garantizando proveer a la estructura de gran rigidez y disminuir por ende los
requerimientos de desplazamiento que se generan en una estructura flexible.
2. ESTRUCTURACIÓN Y PREDIMENSIONAMIENTO
Para considerar nuestra estructura como albañilería confinada, los muros portantes
deben cumplir las siguientes condiciones:
Quedarán enmarcados en sus cuatro lados por elementos de concreto armado
verticales (columnas) y horizontales (vigas soleras), aceptando la cimentación
de concreto como elemento de confinamiento horizontal para los muros del
primer nivel.
Se asumirá inicialmente columnas de confinamiento de 0.15 x 0.15 m (peralte
mínimo y espesor de columna mayor al espesor efectivo del muro).
Pm h 2
σm = ≤ 0.2 f 'm 1 − ≤ 0.15 f 'm
t×L 35 t
Área tributaria
correspondiente
al Muro X2
31.78 2.4 2
σm = = 77.61 ton m 2 ≤ 0.2 × 850 1 − = 122.7 ton / m 2 ≤ 0.15 f 'm = 127.5 ton m 2
(0.13 x 3.15) 35 x 0.13
Nota:
Si se empleara otro tipo de albañilería como: King Kong industrial de arcilla,
tenemos:
Pilas: f’m = 65 kg/cm2 = 650 ton/m 2
Y hallando el esfuerzo axial:
σm = Pm / t * L = 31.78 / (0.13 * 3.15) = 77.61 ton/m2 = 0.2 * f ’m *( 1 –(h/35*t)2) =
93.83 ton/m 2 = 0.15* f ’m = 97.5 ton Ok!!
Con lo que verificamos que es posible emplear una albañilería de menos calidad,
hasta el las cálculos realizados hasta el momento.
3. METRADO DE CARGAS
Zona de ventanas:
w = 1.4x0.02 + 0.9x0.21 + 0.1x0.15x2.4 + 0.15x0.3x2.4 = 0.361 ton/m
Zona de vigas:
w = 0.15x0.3x2.4 + 0.15x0.1 = 0.123 ton/m
Zona de muros:
w = 0.285x2.4 + 0.15x0.3x2.4 = 0.792 ton/m
Parapeto:
w = 0.9x0.21 + 0.1x0.15x2.4 = 0.225 ton/m
Zona de vigas con parapeto:
w = 0.225 + 0.15x0.3x2.4 = 0.333 ton/m
Zona de vigas sin parapeto:
w = 0.15x0.3x2.4 + 0.15x0.1 = 0.123 ton/m
Zona de muros con parapetos:
w = 0.225 + 0.15x0.3x2.4 + 0.285x1.2 = 0.675 ton/m
Zona de muros sin parapeto (ejemplo X2):
w = 0.15x0.3x2.4 +0.285x1.2+0.15x0.1=0.465 ton/m
Modelamiento SAP
Las cargas totales por nivel se obtienen sumando las cargas directas con las
indirectas.
§ Muro X1:
PD:
Losa: 4.719 * 0.388 = 1.831ton
Muro: 3.15 * 0.792 = 2.495 ton
Ventana: 0.75 * 0.361 = 0.271 ton
PD(X1)= 4.597 ton
PL:
Losa: 4.719 * 0.25 = 1.18 ton
PL(X1)= 1.18 ton
§ Muro X2:
PD:
Losa: 8.938*0.388 = 3.468 ton
Muro: 3.15*0.792 = 2.495 ton
Viga: 0.75*0.123 = 0.092 ton
PD(X2)= 6.055 ton
PL:
Losa: 8.938*0.25 = 2.235 ton
Viga: 0.75*0.15*0.25 = 0.028 ton
PL(X2)= 2.263 ton
§ Muro X3:
PD:
Losa: 4.219*0.388 =1.637 ton
Muro: 3.15*0.792 = 2.495 ton
Ventana: 0.75*0.361 = 0.271 ton
PD(X3)= 4.403 ton
PL:
Losa: 4.219*0.25 = 1.055 ton
PL(X3)= 1.055 ton
§ Muro X4:
PD:
Losa: 2*0.281*0.388 = 0.218 ton
Muro: 3.00*0.792 = 2.376 ton
Ventana: 2*0.75*0.361 = 0.542 ton
Escalera: 2*1.060 = 2.120 ton
PD(X4)= 5.256 ton
PL:
Losa: 2*0.281*0.25 = 0.141 ton
Escalera: 2*0.79 = 1.580 ton
PL(X4)= 1.721 ton
§ Muro Y1:
PD:
PL:
Losa: 6.25*0.25 = 1.563 ton
PL(Y1)= 1.563 ton
§ Muro Y2:
PD:
Losa: 7.511*0.388 = 2.914 ton
Muro: 3.30*0.792 = 2.614 ton
Escalera: = 1.18 ton
Vigas: (2+0.75+1.35)*0.123 = 0.504 ton
PD(Y2)= 7.212 ton
PL:
Losa: 7.511*0.25 = 1.878 ton
Escalera: = 0.76 ton
Vigas: (2+0.75+1.35)*0.25*0.15 = 0.154 ton
PL(Y2)= 2.792 ton
§ Columna C:
PD:
Columna: 2.4*0.0675*2.7 = 0.437 ton
Losa: 4.981*0.388 = 1.933 ton
Ventana: 0.75*0.361 = 0.271 ton
Viga: (2+1.35)*0.123 = 0.412 ton
PD(C) = 3.053 ton
PL:
Losa: 4.981*0.25 = 1.245 ton
Viga: 3.35*0.15*0.25 = 0.126 ton
PL(C) = 1.371 ton
§ Muro X1:
PD:
Losa: 4.719*0.388 = 1.831ton
Muro + parapeto: 3.15*0.675 = 2.126 ton
Viga + parapeto: 0.75*0.333 = 0.250 ton
PD(X1) = 4.207 ton
PL:
Losa: 4.719*0.1 = 0.472 ton
PL(X1) = 1.18 ton
§ Muro X2:
PD:
Losa: 8.938*0.388 = 3.468 ton
Muro sin parapeto: 3.15*0.465 = 1.465 ton
Viga sin parapeto: 0.75*0.123 = 0.092 ton
PD(X2) = 5.025ton
PL:
Losa: 8.938*0.1 = 0.8938 ton
Muro sin parapeto: 3.15*0.15*0.10 = 0.047 ton
§ Muro X3:
PD:
Losa: 4.219*0.388 = 1.637 ton
Muro + parapeto: 3.15*0.675 = 2.126 ton
Viga + parapeto: 0.75*0.333 = 0.250 ton
PD(X3) = 4.013 ton
PL:
Losa: 4.219*0.10 = 0.422 ton
PL(X3) = 0.422 ton
§ Muro X4:
PD:
Losa: 2*0.281*0.388 = 0.218 ton
Muro + parapeto: 3.00*0.675 = 2.025 ton
Viga + parapeto: 1.5*0.333 = 0.4995 ton
PD(X4) = 2.743 ton
PL:
Losa: 2*0.281*0.10 = 0.056 ton
PL(X4) = 0.056 ton
§ Muro Y1:
PD:
Losa: 6.25*0.388 = 2.425 ton
Muro + parapeto: 7.45*0.675 = 5.029 ton
PD(Y1) = 7.454 ton
PL:
Losa: 6.25*0.10 = 0.625ton
PL(Y1) = 0.625 ton
§ Muro Y2:
PD:
Losa: 7.511*0.388 = 2.914 ton
Muro + parapeto: 3.30*0.675 = 2.228 ton
Viga sin parapeto:(2+0.75+1.35)*0.123 = 0.504 ton
Escalera ( un solo tramo): = 0.885ton
PD(Y2) = 6.531 ton
PL:
Losa: 7.511*0.10 = 0.7511 ton
Escalera: = 0.57 ton
Viga s/ parap:(2+0.75+1.35)*0.10*0.15 = 0.0615 ton
PL(Y2) = 1.383ton
§ Columna C:
PD:
Losa: 4.981*0.388 = 1.933 ton
Parapeto: 0.30*0.225 = 0.0675 ton
Viga + parapeto: (0.75+1.35)*0.333 = 0.699 ton
Viga sin parapeto : 2*0.123 = 0.246 ton
PD(C) = 2.945 ton
PL:
Cuadro resumen
PISO TIPICO AZOTEA
MURO
PD + PL PD + 0.25PL PD + PL PD + 0.25PL
X1 5.78 4.89 4.68 4.33
X2 8.32 6.62 5.98 5.26
X3 5.46 4.67 4.44 4.12
X4 6.98 5.69 2.80 2.76
Y1 9.89 8.72 8.08 7.61
Y2 10.00 7.91 7.91 6.88
C 4.42 3.40 3.47 3.08
Peso del Nivel 78.09 ton 65.30 ton
4. CENTRO DE MASA
Muro X1 X2 X3 X4 Y1 Y2 C S
* Yi 0.00 4.15 7.30 7.30 3.65 5.725 0.00
Pi 4.89 6.62 4.67 5.69/2 8.72 7.91 3.40 39.06
Pi Yi 0.00 27.48 34.07 20.77 31.81 45.28 0.00 159.45
159 .45
Finalmente calculamos YCM = = 4.082 m à CM = ( 6.075 , 4.082 )
39.06
§ En los siguientes casilleros, los valores son obtenidos de acumular la carga que
soporta cada piso, empezando desde el Piso 4 hasta el Piso 1
Pi x hi x H
Fi =
Σ Pi . hi
Σ 1970.24 49.98
7. MODELAMIENTO
Para poder analizar este edificio y conocer su comportamiento, se puede hacer uso
del análisis manual aproximado o algún programa computacional tales como Edificio,
ETABS, SAP, entre otros. Para el modelamiento de la presente estructura se ha
considerado el uso del programa SAP 2000 (versión 7.21).
Concreto
Albañilería
Material Rígido
Estructuración de la edificación
El edificio en análisis consta de 4 pisos, todos ellos con la misma planta típica y la
misma altura de entrepiso por lo que no se presentan irregularidades estructurales en
altura, como son: Presencia de piso blando, Irregularidad de masa, Irregularidad
geométrica vertical y Discontinuidad en los sistemas resistentes.
Eje 1
Eje 2
Eje 3
Se aprecia elemento
rígido de constante
torsional cero
Eje B – C
SECCIONES DE LA ESCALERA.
SECCIÓN: DESCANSO
SECCIÓN: PARED
SECCIÓN: PASOS
8. ANÁLISIS SÍSMICO
Sismo en Dirección X:
Sismo en Dirección Y:
PISO 1
Muro Pg (Ton) Ve (ton) Me(t-m) L (m)
X1 19.00 7.06 35.87 3.15
X2 25.12 6.88 36.37 3.15
X3 18.12 7.12 31.84 3.15
X4 19.82 7.31 28.98 3
Y1 33.76 20.39 146.97 7.45
Y2 30.61 5.99 30.05 3.3
C 13.27
PISO 2
Muro Pg (Ton) Ve (ton) Me(t-m) L (m)
X1 14.11 5.71 19.64 3.15
X2 18.50 5.71 20.19 3.15
X3 13.45 6.55 18.31 3.15
X4 14.13 7.87 18.74 3
Y1 25.04 19.56 100.89 7.45
Y2 22.70 3.99 15.1 3.3
C 9.87
PISO 3
Muro Pg (Ton) Ve (ton) Me(t-m) L (m)
X1 9.22 3.91 7.93 3.15
X2 11.88 3.91 8.06 3.15
X3 8.79 5.19 8.34 3.15
X4 8.44 7.05 10.35 3
Y1 16.33 15.2 55.92 7.45
Y2 14.79 2.6 5.95 3.3
C 6.47
SISMO XX
Cortantes en muros
SISMO YY
SISMO XX
Momentos en muros
SISMO YY
Momentos en Eje
Momentos en muros por sismo YY Momentos en Eje B y C
AyD
Para otorgar una adecuada rigidez y resistencia al edificio, cada entrepiso debe
presentar una resistencia al corte mayor que la fuerza cortante producida por el
sismo severo en cada dirección principal; de modo que se cumpla:
Σ Vmi ≥ VEi
Vm 1
Vui = Vei . donde 2 = Vm1/Ve1 = 3
Ve1
Vm 1
M ui = M ei .
V e1
A continuación se muestran los valores correspondientes al cálculo de Vm, los valores
de las fuerzas internas amplificadas para el diseño y las verificaciones anteriormente
mencionadas para cada piso.
Piso 1 :
Pg Ve Me Vm 0.55 Vm Vu Mu
Muro L (m) α V m1 / Ve1
(Ton) (ton) (t-m) (Ton) (Ton) (ton) (t-m)
X1 19.00 7.06 35.82 3.15 0.62 16.07 8.84 2.28 16.07 81.51
X2 25.12 6.87 36.32 3.15 0.60 17.00 9.35 2.47 17.00 89.88
X3 18.12 7.11 31.8 3.15 0.70 17.43 9.59 2.45 17.43 77.98
X4 19.82 7.3 28.94 3 0.76 18.13 9.97 2.48 18.13 71.89
Y1 33.76 17.05 146.74 7.45 0.87 46.33 25.48 2.72 46.33 398.73
Y2 30.61 5.98 30.01 3.3 0.66 20.02 11.01 3.00 17.94 90.03
C 13.27 3.47
Piso 2 :
Pg Ve Me 0.55 Vm Vu Mu
Muro L (m) α Vm (ton) V m1/V e1
(ton) (ton) (t-m) (ton) (ton) (t-m)
X1 14.11 5.7 19.6 3.15 0.92 20.50 11.28 2.28 12.97 44.60
X2 18.50 5.71 20.16 3.15 0.89 21.06 11.58 2.47 14.13 49.89
X3 13.45 6.54 18.28 3.15 1.00 21.93 12.06 2.45 16.04 44.82
X4 14.13 7.86 18.71 3 1.00 21.19 11.65 2.48 19.52 46.48
Y1 25.04 16.63 100.7 7.45 1.00 50.31 27.67 2.72 45.19 273.63
Y2 22.70 3.99 15.07 3.3 0.87 22.46 12.35 3.00 11.97 45.21
C 9.87 3.47
Piso 3 :
Pg Ve Me Vm 0.55 Vm Vu Mu
Muro L (m) α V m1/V e1
(Ton) (ton) (t-m) (Ton) (Ton) (ton) (t-m)
X1 9.22 3.91 7.91 3.15 1.00 20.96 11.53 2.28 8.90 18.00
X2 11.88 3.9 8.04 3.15 1.00 21.57 11.86 2.47 9.65 19.90
X3 8.79 5.18 8.31 3.15 1.00 20.86 11.47 2.45 12.70 20.38
X4 8.44 7.04 10.32 3 1.00 19.88 10.94 2.48 17.49 25.64
Y1 16.33 13.3 55.79 7.45 1.00 48.31 26.57 2.72 36.14 151.60
Y2 14.79 2.6 5.93 3.3 1.00 23.14 12.72 3.00 7.80 17.79
C 6.47 3.47
Nota:
Para los pisos superiores al tercero, el efecto de corte resulta menos significativo,
por lo tanto el cuarto piso pasará por corte.
De igual forma, con la relación anterior Vmi > Vui se verifica que no se produce el
agrietamiento diagonal en los entrepisos superiores.
10. DISEÑO DE LOS MUROS DEL PRIMER PISO ANTE SISMO SEVERO
(Agrietamiento por corte)
Pm = PD + PL
Muro X1 X2 X3 X4 Y1 Y2
PD + PL 5.78 8.32 5.46 6.98 9.89 10.00
Piso Tipico
PD + PL 4.68 5.98 4.44 2.80 8.08 7.91
Azotea
Pm ( Ton) 22.01 30.93 20.81 23.73 37.74 37.93
L (m) 3.15 3.15 3.15 3.00 7.45 3.30
σm (ton/m ) 2
53.75 75.54 50.82 60.85 38.97 88.41
Muro X1 X2 X3 X4 Y1 Y2
Pm ( Ton) 16.23 22.62 15.35 16.75 27.86 27.92
L (m) 3.15 3.15 3.15 3.00 7.45 3.30
σm (ton/m ) 2
39.64 55.23 37.49 42.96 28.76 65.09
Ref Horz 0.10% 0.10% 0.10%
Confinamos todos los muros con columnas de 0.15 x 0.15 m como vemos en la
planta
Donde :
Lt = el mayor valor entre: longitud del muro transversal entre 4 (Lt/4)
o 6t
Pg (t) = carga gravitacional proveniente del muro transversal.
L = longitud total del muro transversal.
El diseño de estas columnas no debe ser considerado porque existe otra columna con mayores requerimientos.
10.2.2. Diseño de Vigas Soleras:
Los estribos utilizados en soleras y columnas son: [] φ ¼",1@5, 4@10, r@25 cm.
Las columnas internas tienen refuerzo mínimo.
t = 13 cm = espesor efectivo.
Donde:
Lt = el mayor valor entre longitud del muro transversal entre 4 ( Lt / 4)
o 6t
Pg (t) = carga gravitacional proveniente del muro transversal.
L = longitud total del muro transversal.
10. T = F - Pc - Pt = tracción en la columna extrema
11. C = Pc + F = compresión en la columna extrema
12. As = T / (fy φ) = área de acero vertical requerida, usar φ = 0.9 según
Norma E-060, y un acero mínimo de 4 φ 8 mm
13. As = área de acero vertical colocada
14. δ = factor de confinamiento: δ = 0.8 para columnas sin muros
transversales o con un solo muro transversal.
δ = 1.0 para columnas con 2 muros transversales.
15. An = As + (C / φ - As fy) / (0.85 δ f´c) = área del núcleo de concreto, usar
φ = 0.7 según Norma E-060.
16. Dimensiones de la columna a emplear
17. Ac = área de concreto de la columna definitiva
18. An = área del núcleo de la columna definitiva considerando 4cms de
recubrimiento.
19. El área de acero vertical mínima se halla con:
El diseño de estas columnas no debe ser considerado porque existe otra columna con mayores requerimientos en pisos inferiores
12. DISEÑO DE ALFÉIZAR.
Según la norma de albañilería, existe una carga sísmica (w) que actúa
ortogonalmente en forma uniforme sobre el plano del muro y que es equivalente a:
W = 0.8 Z U C1 ? e
Donde:
Z = 0.4 (Dado que el edificio se encuentra ubicado en la ciudad de Lima que
pertenece a la zona sísmica Nro 3)
U = 1.0 (Estipulado en la norma sísmica y dependiendo del uso de la edificación)
C1= 1.3 (Estipulado en la norma sísmica para el diseño de parapetos o alféizars)
? = 1800 Kg/m 3 (Peso volumétrico de la albañilería – Arcilla)
e = 15 cm (Espesor del muro incluyendo tarrajeo)
a = 1.5 m
b = 1.0 m
Por lo tanto w = 0.8 x 0.4 x 1.0 x 1.3 x 1800 x 0.15 = 112.32 Kg/m 2
Por lo tanto para este caso el momento actuante en la albañilería según la Norma
será de:
Ms = m w a2
Donde:
m = Coeficiente de la norma (adimensional)
w = Carga sísmica uniformemente repartida sobre el muro.
a = Longitud libre del muro
Albañilería Estructural Grupo Nro. 2
ft = 15 000 >fm
Donde:
fm = 6 Ms / (t2) = 6 x 21.00 / (0.13)2 = 7455.99 Kg/m 2
Distribución de Fuerzas
sobre columnas de
arriostre de alféizar
Para la obtención del momento se halló el valor de la carga ejercida por la albañilería
sobre la columna y el punto de aplicación desde la parte inferior del mismo que fueron
en este caso 52.65 Kg y 0.65 m respectivamente; por lo tanto el Momento Flector que
ocurre en la columna será de 3 422 Kg.cm
ft = 15 000 >fm
Donde:
fm = 6 Ms / (t2) = 6 x 12.69 / (0.13)2 = 4506 Kg/m 2
Distribución de Fuerzas
sobre columnas de
arriostre de alféizar
Para la obtención del momento en la columna se halló el valor de la carga ejercida por
su respectiva área tributaria (albañilería), el punto de aplicación desde la parte inferior
de la columna y la fuerza trasmitida por la viga solera sobre esta. Los cuales
resultaron Falbañilería = 28.08 Kg, y = 0.50 m y Fsolera = 61.78 Kg; por lo tanto el
Momento Flector que ocurre en la columna será de 7 582 Kg.cm
• El valor del esfuerzo axial máximo permitido en un muro (σm ) debe ser menor a:
Pm h
2
σ m = ≤ 0 . 2 f m 1 − < 0 . 15 f ' m
t xL 35 t
• El área mínima de acero vertical u horizontal es, según la Norma actual: 0.1
f´c Ac / fy o 4 # 8.
14. BIBLIOGRAFÍA
ANEXO
MODELAJE EN EL SAP
Para analizar el comportamiento del edificio no solo ante cargas muertas y vivas, sino
también ante efectos de sismo moderado y severo, utilizamos el programa SAP 2000.
Se modela la estructura en base a Pórticos Planos en cada dirección principal; con esta
técnica los muros son considerados como barras verticales que en conjunto con las vigas
forman dichos pórticos planos interconectados por diafragmas rígidos (losas de techo) en
cada nivel.
MODELAJE DE LA ESTRUCTURA
Materiales
El edificio es una estructura de albañilería confinada, por lo tanto los elementos
estructurales vienen a ser los muros portantes de albañilería y los elementos de
confinamiento (columnas y vigas) de concreto.
En el SAP definimos estos dos materiales:
Albañilería
Masa = 0
γ = 1.8 ton/m3
5 2
Ea = 4.25 x10 ton/m
Ga = Ea / [2 x (1 + υ) ]
Ea / Ga = 2.5
υ = 0.25
Concreto
Masa = 0
γ = 2.4 ton/m3
6 2
Ec = 2.0 x10 ton/m
Gc = Ec / [2 x (1 + υ) ]
Ec / Gc = 2.3
υ = 0.15
Rígido
Masa = 0
γ = 2.4 ton/m3
9 2
Ec = 2.0 x10 ton/m
Ec / Gc = 2.3
υ = 0.15
Muro X1:
Material = Albañilería.
2
Área = 0.731 m
4
Iy y = 0.992 m
-6
Ixx = 10e (damos una inercia pequeña
en la dirección que no
trabajará)
2
A’ = 0.410 m
Muro X2:
Material = Albañilería.
2
Área = 0.84 m
4
Iy y = 1.131 m
-7 4
Ixx = 1 x 10e m
2
A’ = 0.410 m
Muro X3:
Material = Albañilería.
2
Área = 0.717 m
4
Iy y = 1.057 m
-7 4
Ixx = 1 x 10e m
2
A’ = 0.429 m
Muro X4:
Material = Albañilería.
2
Área = 0.795 m
4
Iy y = 1.116 m
-7 4
Ixx = 1 x 10e m
2
A’ = 0.39 m
Muro Y1:
Material = Albañilería.
2
Área = 1.576 m
-7 4
Iy y = 1 x 10e m
4
Ixx = 9.92 m
2
A’ = 0.97 m
Muro Y2:
Material = Albañilería.
2
Área = 0.717 m
-7 4
Iy y = 1 x 10e m
4
Ixx = 1.057 m
2
A’ = 0.43 m
Muro Y2:
Material = Albañilería.
2
Área = 0.717 m
-7 4
Iy y = 1 x 10e m
4
Ixx = 1.057 m
2
A’ = 0.43 m
Secciones de concreto: Son las columnas C1 y las vigas dinteles. Las secciones de las
vigas se calculan considerando un ancho efectivo igual a 4 tlosa, dando vigas de secciones
L (vigas perimétricas) y T (vigas internas).
Columna C1 :
Material = Concreto.
Sección = Ángulo
Dimensiones = 0.30 x 0.30 m
Espesores :
txx = 0.15 m
ty y = 0.15 m
Vigas Perimetrales :
Material = Concreto.
Sección = Ángulo
Ancho = tmuro + 4 tlosa = 0.61 m
Peralte = 0.30 m
Espesores :
txx = 0.13 m (igual a muros)
ty y = 0.12 m (igual a losa)
Vigas Interiores:
Material = Concreto.
Sección = Tee
Ancho = tmuro + 2 ( 4 tlosa ) = 1.09
m
Peralte = 0.30 m
Espesores :
txx = 0.13 m (igual a muros)
ty y = 0.12 m (igual a losa)
Sección de Material Rígido: En esta sección las propiedades estarán dadas por el
material rígido que se asigna, solo se debe asegurar que la torsión para esta sección sea
prácticamente cero.
Elemento Rígido :
Material = Rígido.
Sección = General
-8
Constante torsional = 1 x 10