Documentos de Académico
Documentos de Profesional
Documentos de Cultura
D a ve Ka h n , P.E.
The Industries Ventilation Standard
Consensus Standard
Standard of Care
Used in NFPA 5000 Building
Construction and Safety Code
LEED Requirement
Not adopted by 06 IMC –Some
similarities
1973 First Issued office 15 cfm/p
1981 Lower Rates office 5 cfm/p
1989 Higher Rates office 20 cfm/p
1999 Little Change office 20 cfm/p
2001 More Mandatory Language
2004 occupancy component +
area component
2007 Incorporate Addendums
Exceptions to 65% RH requirements for
dehumidification systems
Appendix B references expanded & updated
Added Appendix H documentation requirements
Separation of ETS areas
Requirement for residential spaces in buildings
over 3 stories
Means to balance the system to achieve minimum
airflow.
Design documentation to state ventilation rate and
air distribution assumptions.
Controls to enable the fan to operate whenever
the spaces served are occupied.
VAV systems with fixed OA dampers must comply
at minimum supply airflow.
MERV 6 filters upstream of all coils or other
devices with wetted surfaces.
Treatment of Outdoor air is required if in a
“nonattainment” area.
National Ambient Air Quality Standards
NAAQS
1. Ozone
2. Particulate Matter
3. Carbon Monoxide
4. Sulfur Oxides
5. Nitrogen Dioxide
6. Lead
Prescriptive
Space must be within 25’ of permanent wall or
roof opening
Openable area 4%of net occupiable floor area
Free area of opening must be used
Ventilation through adjoining rooms can be used
Engineered
Must be approved by the Authority Having
Jursdiction
Ventilation Rate Procedure
Most commonly used method
Lookup table
Need zone air distribution effectiveness
LEED requires this method
Space type (select from pull-down list) Office Reception Classrooms (age 9 Conference / Office
space areas plus) meeting space
Az* 60 60 120 30 0
Ra
Ez Zone air distribution effectiveness, Table 6.2 0.9 0.9 0.9 0.9
Voz Outdoor airflow to the zone corrected for zone 178 89 356 89 #DIV/0!
air distribution effectiveness, (Pz*Rp +
Az*Ra)/Ez, cfm
Vpz Primary airflow to zone from air handler. In 1200 1200 1200 1200
VAV systems, use the design value. cfm
Vpz The minimum value of the primary airflow to 1200 1200 1200 1200
m zone from air handler. In CAV systems, Vpzm
= Vpz. cfm
Xs Mixing ratio at primary air handler of uncorrected outdoor air intake 0.09 Not used in calculation
to system primary flow, = Vou/Vps
SYSTEM EFFICIENCY
Vot Minimum outdoor air intake, Vou/Ev, cfm 552 11% = Vot/Sum of Vpz
Time Averaging
Fluctuating occupancy
Intermittent interruption of the supply air
flow
Intermittent closure of the OA damper
Reset outdoor air intake flow.
Occupancy
Expected occupancy scheduled by time of day.
Occupancy sensors.
Estimate occupancy based on CO2.
Air Distribution Efficiency
If min OA determined in heating mode, OA can be reduced during
cooling due to a higher Ez
Solve equations in appendix A dynamically based on zone and
system flows to reset zone minimums and outdoor airflow.
Don’t drop below the area outdoor air rate Ra.
Economically limited to high-density occupancies.
CO2 with VAV Systems
%CO2 = (CR -400)/(CR-max – 400) 400 ppm ambient assumed
CR –zone concentration
Cooling Max