Zero sequence impedance

Zero sequence currents are identical in each phase conductor and not displaced by 120° as positive and
negative sequence currents. the magnetic field due to zero sequence currents is very different from that
caused by either positive or negative sequence currents. The difference in magnetic field results in a zero
sequence reactance of a transmission line being in the range of 1,5 to 5 times the positive sequence
reactance. The zero sequence currents flow only if a return path exists through which a completed circuit
is provided. The impedance of the ground and ground wires is included in the zero sequence impedance
of the transmission line. The most common use of zero sequence impedance is in the calculation of
phase to ground short circuit currents. Such current calculations are required for setting ground fault
protection relays.

Las corrientes de secuencia cero son idénticas en cada conductor de fase y no se desplazan 120 ° como
corrientes de secuencia positiva y negativa. el campo magnético debido a corrientes de secuencia cero es
muy diferente del causado por corrientes de secuencia positiva o negativa. La diferencia en el campo
magnético da como resultado una reactancia de secuencia cero de una línea de transmisión que está en
el rango de 1,5 a 5 veces la reactancia de secuencia positiva. Las corrientes de secuencia cero fluyen solo
si existe una ruta de retorno a través de la cual se proporciona un circuito completo. La impedancia de
los cables de tierra y tierra se incluye en la impedancia de secuencia cero de la línea de transmisión. El
uso más común de la impedancia de secuencia cero es en el cálculo de corrientes de cortocircuito de
fase a tierra. Estos cálculos de corriente son necesarios para configurar relés de protección de falla a
tierra.