SAT Procedures and Test Forms for Transformer Differential protection relay
SAT Procedures and Test Forms for Transformer Differential protection relay
Elimination
Side 1 R-E 1.0 1.0 0.0 0.0 1.0 401 0.0 0.0 401
(HV) Y-E 1.0 0.0 1.0 0.0 1.0 0.0 399 0.0 400
B-E 1.0 0.0 0.0 1.0 1.0 0.0 0.0 400 399
R-Y 1.0 1.0 1.0 0.0 0.0 400 400 0.0 0.0
Y-B 1.0 0.0 1.0 1.0 0.0 0.0 400 400 0.0
B-R 1.0 1.0 0.0 1.0 0.0 400 0.0 400 0.0
R-Y-B 1.0 1.0 1.0 1.0 0.0 400 400 399 0.0
Side 2 R-E 1.0 1.0 0.0 0.0 1.0 2.49 0.0 0.0 2.49
(LV) Y-E 1.0 1.0 0.0 0.0 1.0 0.0 2.49 0.0 2.50
B-E 1.0 0.0 0.0 1.0 1.0 0.0 0.0 2.50 2.49
R-Y 1.0 1.0 1.0 0.0 0.0 2.50 2.50 0.0 0.0
Y-B 1.0 0.0 1.0 1.0 0.0 0.0 2.49 2.49 0.0
B-R 1.0 1.0 0.0 1.0 0.0 2.50 0.0 2.49 0.0
R-Y-B 1.0 1.0 1.0 1.0 0.0 2.50 2.50 2.50 0.0
SAT Procedures and Test Forms for Transformer Differential protection relay
2. DIFFERENTIAL PROTECTION :
3a. Setting for 87-1 Pick-Up = 0.20 x I/InO
T I-Diff> Time Delay setting = 0.00 sec
SAT Procedures and Test Forms for Transformer Differential protection relay
SAT Procedures and Test Forms for Transformer Differential protection relay
SAT Procedures and Test Forms for Transformer Differential protection relay
Idiff>Set = 0.20I/InO
Slope 1 Set = 0.25
Base Point 1 Set = 0.00I/In
Irest. Calculated Start Point of Slope 1 = 0.0
Idiff. Calculated Start Point of Slope 1 = 0.0
Idiff>>Set = 6.00I/InO
SAT Procedures and Test Forms for Transformer Differential protection relay
CT:
Winding/Leg Primary Secondary
Name:
CT Current Prim: 400.00 A 2500.00 A
CT Current Sec: 1.00 A 1.00 A
CT Grounding: tow. Prot. Obj. tow. Prot. Obj.
Gnd CT Prim 200.00 A 800.00 A
Current:
Gnd CT Sec 1.00 A 1.00 A
Current:
Gnd CT n/a n/a
Grounding:
Protection device:
Reference Primary
Winding:
Ibias Calculation: ( |Ip| + |Is| ) / K1 (K1 =
1.00)
Zero Seq. IL-I0
Elimination:
Reference PO nominal current
Current:
Ground CT Used:No
Disable Comb. No
char.:
tdiff>: 0.03 s
SIEMENS ENERGOPROJEKT KAHRAMAA.
Signature Signature Signature
SAT Procedures and Test Forms for Transformer Differential protection relay
Test Module
Name: OMICRON Diff Operating Version: 2.40
Characteristic
Test Start: 05-Dec-2010 15:03:55 Test End: 05-Dec-2010 15:05:35
User Name: Manager:
Company:
Test Settings:
.
General Settings:
Testing: Primary / Secondary
Max. Test Time: 1.50 s Delay Time: 0.25 s
Prefault: No
Prefault current: 0.00 In Prefault time: 0.000 s
Vout enabled: No Vout winding: Secondary
GPS/IRIG-B enabled: No GPS/IRIG-B side: Primary
SAT Procedures and Test Forms for Transformer Differential protection relay
Idiff 210[In]
.205
.5
.7
.0 Operating
1 2 Characteristic
3 4Ibias5[In] 6Diagram
7 8 9
SAT Procedures and Test Forms for Transformer Differential protection relay
Idiff 210[In]
.205
.5
.7
.0 Operating
1 2 Characteristic
SIEMENS
3 4IbiasENERGOPROJEKT
5[In] 6Diagram
7 8 9 KAHRAMAA.
Signature Signature Signature
SAT Procedures and Test Forms for Transformer Differential protection relay
SAT Procedures and Test Forms for Transformer Differential protection relay
Idiff 210[In]
.205
.5
.7
.0 Operating
1 2 Characteristic
3 4Ibias5[In] 6Diagram
7 8 9
SAT Procedures and Test Forms for Transformer Differential protection relay
Idiff 210[In]
.205
.5
.7
.0 Operating
1 2 Characteristic
3 4Ibias 5[In] Diagram
6 7 8 9
SAT Procedures and Test Forms for Transformer Differential protection relay
SAT Procedures and Test Forms for Transformer Differential protection relay
Idiff 210[In]
.205
.5
.7
.0 Operating
1 2 Characteristic
3 4Ibias 5[In] Diagram
6 7 8 9
SAT Procedures and Test Forms for Transformer Differential protection relay
In
8.00 In 2.000 In 1.997 In -0.16 % -0.0031 Tested Passed
In
9.00 In 2.000 In 1.997 In -0.16 % -0.0031 Tested Passed
In
Idiff 210[In]
.205
.5
.7
.0 Operating
1 2 Characteristic
3 4Ibias 5[In] Diagram
6 7 8 9
SAT Procedures and Test Forms for Transformer Differential protection relay
SAT Procedures and Test Forms for Transformer Differential protection relay
Idiff 210[In]
.205
.5
.7
.0 Operating
1 2 Characteristic
3 4Ibias 5[In] Diagram
6 7 8 9
SAT Procedures and Test Forms for Transformer Differential protection relay
Inject current greater than 87-1 setting; first with harmonic content less than setting, then with
harmonic content greater than setting; verify 87-1 operation / blocking
SAT Procedures and Test Forms for Transformer Differential protection relay
Protected Object:
Protected Object: Transformer
Vector Group: DY1
CT:
Winding/Leg Primary Secondary
Name:
CT Current Prim: 400.00 A 2500.00 A
CT Current Sec: 1.00 A 1.00 A
CT Grounding: tow. Prot. Obj. tow. Prot. Obj.
Gnd CT Prim 200.00 A 800.00 A
Current:
Gnd CT Sec 1.00 A 1.00 A
Current:
Gnd CT n/a n/a
Grounding:
Protection device:
Reference Primary
Winding:
Ibias Calculation: ( |Ip| + |Is| ) / K1 (K1 =
1.00)
Zero Seq. IL-I0
Elimination:
Reference PO nominal current
Current:
Ground CT Used:No
Disable Comb. No
char.:
tdiff>: 0.03 s
Idiff>: 0.20 In tdiff>>: 0.03 s
Idiff>>: 2.00 In
SIEMENS ENERGOPROJEKT KAHRAMAA.
Signature Signature Signature
SAT Procedures and Test Forms for Transformer Differential protection relay
Harmonic Settings:
HR tol abs: 1.00 % HR tol rel: 3.00 %
Test Module
Name: OMICRON Diff Harmonic Version: 2.40
Restraint
Test Start: 05-Dec-2010 15:26:18 Test End: 05-Dec-2010 15:26:30
User Name: Manager:
Company:
Test Settings:
Testing: Primary Tested Harmonic: 2
Max. Test Time: 1.50 s Delay Time: 0.25 s
Active Postfault: No Postfault Time: 0.04 s
Vout enabled: No Vout winding: Primary
Test Results for Test phase L1-E at Reference Side Primary for 2. Harmonic
Idiff Ixf/Idiff
Angle Trip State Result
(Ixf,Idiff)
1.00 I/In 9.00 % -120.0 ° Yes Tested Passed
1.00 I/In 10.00 % -120.0 ° No Tested Passed
1.00 I/In 11.00 % -120.0 ° No Tested Passed
SAT Procedures and Test Forms for Transformer Differential protection relay
Idiff/In 210[In]
.205
.5
.7
.0 1 Harmonic
2 3 Restraint
4 5I2f/Idiff
6Test
[%]7 Plane
8 9 10 11
Test Results for Test phase L2-E at Reference Side Primary for 2. Harmonic
Idiff Ixf/Idiff
Angle Trip State Result
(Ixf,Idiff)
1.00 I/In 9.00 % -120.0 ° Yes Tested Passed
1.00 I/In 10.00 % -120.0 ° No Tested Passed
1.00 I/In 11.00 % -120.0 ° No Tested Passed
SAT Procedures and Test Forms for Transformer Differential protection relay
Idiff/In 210[In]
.205
.5
.7
.0 1 Harmonic
2 3 Restraint
4 5I2f/Idiff
6Test
[%]7 Plane
8 9 10 11
Test Results for Test phase L3-E at Reference Side Primary for 2. Harmonic
Idiff Ixf/Idiff
Angle Trip State Result
(Ixf,Idiff)
1.00 I/In 9.00 % -120.0 ° Yes Tested Passed
1.00 I/In 10.00 % -120.0 ° No Tested Passed
SIEMENS ENERGOPROJEKT KAHRAMAA.
Signature Signature Signature
SAT Procedures and Test Forms for Transformer Differential protection relay
Idiff/In 210[In]
.205
.5
.7
.0 1 Harmonic
2 3 Restraint
4 5I2f/Idiff
6Test
[%]7 Plane
8 9 10 11
Test Results for Test phase L1-L2-L3 at Reference Side Primary for 2. Harmonic
SAT Procedures and Test Forms for Transformer Differential protection relay
Idiff Ixf/Idiff
Angle Trip State Result
(Ixf,Idiff)
1.00 I/In 9.00 % -120.0 ° Yes Tested Passed
1.00 I/In 10.00 % -120.0 ° No Tested Passed
1.00 I/In 11.00 % -120.0 ° No Tested Passed
Idiff/In 210[In]
.205
.5
.7
.0 1 Harmonic
2 3 Restraint
4 5I2f/Idiff
6Test
[%]7 Plane
8 9 10 11
SIEMENS ENERGOPROJEKT KAHRAMAA.
Signature Signature Signature
SAT Procedures and Test Forms for Transformer Differential protection relay
Test Results for Test phase L1-E at Reference Side Primary for 5. Harmonic
Idiff Ixf/Idiff
Angle Trip State Result
(Ixf,Idiff)
1.00 I/In 29.00 % -120.0 ° Yes Tested Passed
1.00 I/In 30.00 % -120.0 ° No Tested Passed
1.00 I/In 31.00 % -120.0 ° No Tested Passed
SAT Procedures and Test Forms for Transformer Differential protection relay
Idiff/In 210[In]
.205
.5
.7
.0 Harmonic
5 10 Restraint
15I5f/IdiffTest
[%
20] Plane
25 30 35
Test Results for Test phase L2-E at Reference Side Primary for 5. Harmonic
Idiff Ixf/Idiff
Angle Trip State Result
(Ixf,Idiff)
1.00 I/In 29.00 % -120.0 ° Yes Tested Passed
1.00 I/In 30.00 % -120.0 ° Yes Tested Passed
1.00 I/In 31.00 % -120.0 ° No Tested Passed
SAT Procedures and Test Forms for Transformer Differential protection relay
Idiff/In 210[In]
.205
.5
.7
.0 Harmonic
5 10 Restraint
15I5f/IdiffTest
[%
20] Plane
25 30 35
Test Results for Test phase L3-E at Reference Side Primary for 5. Harmonic
Idiff Ixf/Idiff
Angle Trip State Result
(Ixf,Idiff)
1.00 I/In 29.00 % -120.0 ° Yes Tested Passed
1.00 I/In 30.00 % -120.0 ° Yes Tested Passed
1.00 I/In 31.00 % -120.0 ° No Tested Passed
SAT Procedures and Test Forms for Transformer Differential protection relay
Idiff/In 210[In]
.205
.5
.7
.0 Harmonic
5 10 Restraint
15I5f/IdiffTest
[%
20] Plane
25 30 35
Test Results for Test phase L1-L2-L3 at Reference Side Primary for 5. Harmonic
Idiff Ixf/Idiff
Angle Trip State Result
(Ixf,Idiff)
1.00 I/In 29.00 % -120.0 ° Yes Tested Passed
SIEMENS ENERGOPROJEKT KAHRAMAA.
Signature Signature Signature
SAT Procedures and Test Forms for Transformer Differential protection relay
Idiff/In 210[In]
.205
.5
.7
.0 Harmonic
5 10 Restraint
15I5f/IdiffTest
[%
20] Plane
25 30 35
SAT Procedures and Test Forms for Transformer Differential protection relay
Definite Time:
50-1 Pickup Setting : 1.50 x I/I nS (I/InS = Rated current of the transformer)
50-1 Delay Setting : 0.50 sec
50-2 Pickup Setting : 2.00 x I/InS
50-2 Delay Setting (s) : 0.00 sec
Phase 50-1 50-1 Actual 50-1 Actual 50-2 50-2 Actual 50-2 Actual
Actual Drop Out Trip Time @ Actual Drop out Trip Time @
Pickup current 2 x setting Pickup current 2x setting
current (A) (msec) current (A) (msec)
(A) (A)
R 1.396 1.337 543.6 1.860 1.789 24.20
Y 1.395 1.335 538.9 1.859 1.785 28.00
B 1.396 1.336 533.7 1.860 1.799 23.60
Inverse Time:
IEC Curve : Very Inverse
51 Pickup Setting 1.00 x I/InS
51 Time Dial Setting : 0.60 sec
Phase Actual Actual Operating Time (s) Operating Time (s) Operating Time(s)
Pickup Drop out @ 2 x Setting @ 5 x Setting @ 10 x Setting
current current
(A) (A) Calculated Measured Calculated Measured Calculated Measured
R
Y
B
SAT Procedures and Test Forms for Transformer Differential protection relay
BI 1 : Spare Tested : Ok
BI 3 : Spare Tested : Ok
BI 4 : Spare Tested : Ok
SAT Procedures and Test Forms for Transformer Differential protection relay
SAT Procedures and Test Forms for Transformer Differential protection relay