Está en la página 1de 84

MEMORIA CALCULO TOMA CORRIENTE

CALCULO DE TOMA CORRIENTE NIVEL 1

NOMBRE AREA No Ambiente CKT Panel CT PT COSɸ S ST V I IT KVA L C TIPO Smm2 E%

Toma Corriente Covencionales vestibulo, Sala de espera,


Pasillo 1, Pasillo 2 100-123 28 PTN1 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 39.79 M 10 THHN 5.26 mm2 2.36 %

Toma Corriente Oasis Sala de espera 101 41 PTN1 1 und 510.00 W 0.96 531.25VA 531.25VA 120V 4.43A 4.43A 0.53 KvA 39.00 M 10 THHN 5.26 mm2 1.09 %

Toma Corriente Sala de espera 101 13 PTN1 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 34.00 M 10 THHN 5.26 mm2 2.02 %

Toma Corriente Procedimiento y choque 103 36 PTN1 3 und 180.00 W 0.96 187.50VA 562.50VA 120V 1.56A 4.69A 0.56 KvA 42.00 M 10 THHN 5.26 mm2 1.25 %

Toma Corriente Observacion 119 15 PTN1 4 und 180.00 W 0.96 187.50VA 750.00VA 120V 1.56A 6.25A 0.75 KvA 30.00 M 10 THHN 5.26 mm2 1.19 %

Toma Corriente Clinica 1, Clinica 2 106 6 PTN1 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 24.00 M 10 THHN 5.26 mm2 1.43 %
Toma Corriente Estacion de enfermeria, Bodega y Cuarto
Sucio 111-112-115 7 PTN1 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 20.00 M 10 THHN 5.26 mm2 1.19 %

Toma Corriente Pasillo 3 131 34 PTN1 3 und 180.00 W 0.96 187.50VA 562.50VA 120V 1.56A 4.69A 0.56 KvA 35.00 M 10 THHN 5.26 mm2 1.04 %

Toma Corriente Vestidor de Mujeres, Vestidor de Varones 135 9 PTN1 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 35.00 M 10 THHN 5.26 mm2 2.08 %

Toma Corriente Anestecia 143 26 PTN1 4 und 180.00 W 0.96 187.50VA 750.00VA 120V 1.56A 6.25A 0.75 KvA 21.00 M 10 THHN 5.26 mm2 0.83 %

Toma Corriente Estacion de enfermeria, Bodega MRP 145 11 PTN1 5 und 180.00 W 0.96 187.50VA 937.50VA 120V 1.56A 7.81A 0.94 KvA 25.00 M 10 THHN 5.26 mm2 1.24 %

Toma Corriente Covencionales Cuarto Sucio, Arsenal y


pasillo 146-154-152 30 PTN1 4 und 180.00 W 0.96 187.50VA 750.00VA 120V 1.56A 6.25A 0.75 KvA 21.00 M 10 THHN 5.26 mm2 0.83 %
Toma Corriente Covencionales Cuarto Electrico, Voz y
Datos 124-125 32 PTN1 4 und 180.00 W 0.96 187.50VA 750.00VA 120V 1.56A 6.25A 0.75 KvA 10.00 M 10 THHN 5.26 mm2 0.40 %

Toma Corriente Pasillo Externo Costado Oeste y Norte 34 PTN1 3 und 180.00 W 0.96 187.50VA 562.50VA 120V 1.56A 4.69A 0.56 KvA 10.00 M 10 THHN 5.26 mm2 0.30 %

Toma corriente Cuarto de Maquinas 127 40 PTN1 2 und 180.00 W 0.96 187.50VA 375.00VA 120V 1.56A 3.13A 0.38 KvA 10.00 M 10 THHN 5.26 mm2 0.20 %
Toma corriente Cabecero de Cama Area de Procedimiento
y Choque 103 5 PTN1 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 31.00 M 10 THHN 5.26 mm2 1.84 %
Toma Corriente Desfibrilador Area de Procedimiento y
Choque 103 25 PTN1 1 und 900.00 W 0.96 937.50VA 937.50VA 120V 7.81A 7.81A 0.94 KvA 39.79 M 10 THHN 5.26 mm2 1.97 %

Toma corriente Cabecero de Cama Observacion 119 8 PTN1 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 31.00 M 10 THHN 5.26 mm2 1.84 %

Toma corriente Cabecero de Cama Observacion 119 39 PTN1 3 und 180.00 W 0.96 187.50VA 562.50VA 120V 1.56A 4.69A 0.56 KvA 31.00 M 10 THHN 5.26 mm2 0.92 %

Toma corriente Cabecero de Cama Recuperacion 119 35 PTN1 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 31.00 M 10 THHN 5.26 mm2 1.84 %

Toma corriente Cabecero de Cama Recuperacion 119 37 PTN1 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 31.00 M 10 THHN 5.26 mm2 1.84 %

Toma corriente Cabecero de Cama Recuperacion 119 38 PTN1 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 31.00 M 10 THHN 5.26 mm2 1.84 %
1 PTN1
103 2 und 432.00 W 0.96 450.00VA 900.00VA 240V 1.88A 3.75A 0.90 KvA 31.00 M 10 THHN 5.26 mm2 0.37 %
Toma corriente camilla Area de Procedimiento y Choque 3 PTN1
2
119 PTN1 3 und 432.00 W 0.96 450.00VA 1350.00VA 240V 1.88A 5.63A 1.35 KvA 31.00 M 10 THHN 5.26 mm2 0.55 %
Toma corriente camilla Observacion 4
10
119 PTN1 6 und 432.00 W 0.96 450.00VA 2700.00VA 240V 1.88A 11.25A 2.70 KvA 31.00 M 10 THHN 5.26 mm2 1.11 %
Toma corriente camilla Recuperacion 12

18
136 PTN1 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 30.00 M 10 THHN 5.26 mm2 1.32 %
Ducha S/S 2 20
21
138 PTN1 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 34.00 M 10 THHN 5.26 mm2 1.50 %
Ducha S/S 1 23
22
144 PTN1 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 30.00 M 10 THHN 5.26 mm2 1.32 %
Ducha S/S 3 24
14
PTN1 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 24.00 M 10 THHN 5.26 mm2 1.06 %
Ducha SS 5 113 16
17
116 PTN1 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 20.00 M 10 THHN 5.26 mm2 0.88 %
Ducha S.S. Pacientes 1 19

27
118 PTN1 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 25.00 M 10 THHN 5.26 mm2 1.10 %
Ducha S.S. Pacientes 2 29

31
Toma Corriente Evaporador sala de Espera, Clinica 1, PTN1 1 und 1450.00 W 0.96 1510.42VA 1510.42VA 240V 6.29A 6.29A 1.51 KvA 35.00 M 12 THHN 3.31 mm2 1.11 %
Clinica 2, Observacion, Pasillo, Estacion de Enfermeria,
Sala de Espera, Voz y Datos, Cuarto de Maquinas 33

Toma Corriente Evaporador Area de Procedimiento y 31


Choque, Vestidor de Mujeres, Vestidor de Varones, PTN1 1 und 1350.00 W 0.96 1406.25VA 1406.25VA 240V 5.86A 5.86A 1.41 KvA 35.00 M 12 THHN 3.31 mm2 1.03 %
Anestecia, Pasillo interno 1 y 2, Estacion de Enfermeria y
Recuperacion 33

Toma corriente Area de Condensadoras 15 PTAN1 3 und 250.00 W 0.96 260.42VA 781.25VA 120V 2.17A 6.51A 0.78 KvA 31.00 M 10 THHN 5.26 mm2 1.28 %

Panel Tierra Aislada Quirofano 1 5 PTAN1 1 und 4500.00 W 0.96 4687.50VA 4687.50VA 120V 39.06A 39.06A 4.69 KvA 35.00 M 2 THHN 33.63 mm2 1.36 %

Panel Tierra Aislada Quirofano 2 6 PTAN1 1 und 4500.00 W 0.96 4687.50VA 4687.50VA 120V 39.06A 39.06A 4.69 KvA 40.00 M 2 THHN 33.63 mm2 1.55 %

Panel Tierra Aislada Quirofano 3 14 PTAN1 1 und 4500.00 W 0.96 4687.50VA 4687.50VA 120V 39.06A 39.06A 4.69 KvA 30.00 M 2 THHN 33.63 mm2 1.16 %

Panel Tierra Aislada Quirofano 4 16 PTAN1 1 und 4500.00 W 0.96 4687.50VA 4687.50VA 120V 39.06A 39.06A 4.69 KvA 30.00 M 2 THHN 33.63 mm2 1.16 %
1
PTAN1 1 und 1014.00 W 0.96 1056.25VA 1056.25VA 208V 5.08A 5.08A 1.06 KvA 40.00 M 10 THHN 5.26 mm2 0.74 %
Extractor de Aire CUE-900 Quirofano 1 3

1
PTAN1 1 und 1014.00 W 0.96 1056.25VA 1056.25VA 208V 5.08A 5.08A 1.06 KvA 40.00 M 10 THHN 5.26 mm2 0.74 %
Extractor de Aire CUE-900 Quirofano 2 3

7
PTAN1 1 und 1014.00 W 0.96 1056.25VA 1056.25VA 208V 5.08A 5.08A 1.06 KvA 40.00 M 10 THHN 5.26 mm2 0.74 %
Extractor de Aire CUE-900 Quirofano 3 9

7
PTAN1 1 und 1014.00 W 0.96 1056.25VA 1056.25VA 208V 5.08A 5.08A 1.06 KvA 40.00 M 10 THHN 5.26 mm2 0.74 %
Extractor de Aire CUE-900 Quirofano 4 9

2
PTAN1 1 und 1014.00 W 0.96 1056.25VA 1056.25VA 208V 5.08A 5.08A 1.06 KvA 40.00 M 10 THHN 5.26 mm2 0.74 %
INYECTOR CUE-099-VG-1/4 - C-1/8 Quirofano 1 4

2
PTAN1 1 und 1014.00 W 0.96 1056.25VA 1056.25VA 208V 5.08A 5.08A 1.06 KvA 40.00 M 10 THHN 5.26 mm2 0.74 %
INYECTOR CUE-099-VG-1/4 - C-1/8 Quirofano 2 4
8
PTAN1 1 und 1014.00 W 0.96 1056.25VA 1056.25VA 208V 5.08A 5.08A 1.06 KvA 40.00 M 10 THHN 5.26 mm2 0.74 %
INYECTOR CUE-099-VG-1/4 - C-1/8 Quirofano 3 10

8
PTAN1 1 und 1014.00 W 0.96 1056.25VA 1056.25VA 208V 5.08A 5.08A 1.06 KvA 40.00 M 10 THHN 5.26 mm2 0.74 %
INYECTOR CUE-099-VG-1/4 - C-1/8 Quirofano 4 10

11
PTAN1 1 und 2200.00 W 0.96 2291.67VA 2291.67VA 208V 11.02A 11.02A 2.29 KvA 40.00 M 10 THHN 5.26 mm2 1.61 %
Toma Corriente Arco en C Quirofano 1 13

21
PTAN1 1 und 2200.00 W 0.96 2291.67VA 2291.67VA 208V 11.02A 11.02A 2.29 KvA 40.00 M 10 THHN 5.26 mm2 1.61 %
Toma Corriente Arco en C Quirofano 2 23

18
PTAN1 1 und 2200.00 W 0.96 2291.67VA 2291.67VA 208V 11.02A 11.02A 2.29 KvA 40.00 M 10 THHN 5.26 mm2 1.61 %
Toma Corriente Arco en C Quirofano 3 20
25
PTAN1 1 und 2200.00 W 0.96 2291.67VA 2291.67VA 208V 11.02A 11.02A 2.29 KvA 40.00 M 10 THHN 5.26 mm2 1.61 %
Toma Corriente Arco en C Quirofano 4 27

ECUACION

(2*n*L*I)
cv% =
(V*mm2)

Cv% = CAIDA DE VOLTAJE MENOR O IGUAL A 3%


n= VALOR CONSTANTE
n=2 CUANDO ES MONOFASICA
n=√3 CUANDO ES TRIFASICA
L= DISTANCIA DEL CIRCUITO
I = CORRIENTE
V = VOLTAJE DE OPERACIÓN
mm2 = SECCION DEL CONDUCTOR

CKT = NUMERO DE CIRCUITO


PANEL = CENTRO DE CARGA CORRESPONDIENTE
CT = CANTIDAD TOTAL DE TOMA CORRIENTE
PT = POTENCIA ACTIVA TOTAL EN WATTS
COSɸ = FACTOR DE POTENCIA
S = POTENCIA APARENTE
ST= POTENCIA APARENTE TOTAL EN VOLT AMPERE
V = VOLTAJE
I = CORRIENTE EN AMPERIOS
I T = CORRIENTE TOTAL EN AMPERIOS
KVA = POTENCIA APARENTE TOTAL EN KILO VOLT AMPERE
L = LONGITUD TOTAL DEL CIRCUITO
C = CONDUCTOR ASIGNADO
Smm2 = SECCION TRANSVERSAL DEL CONDUCTOR EN MILIMETROS CUADRADOS
E % = CAIDA DE VOLTAJE EN PORCIENTO MAX PERMITIDO (3 %) PARA CIRCUITOS DERIVADOS
MEMORIA CALCULO TOMA CORRIENTE
CALCULO DE TOMA CORRIENTE NIVEL 2

NOMBRE AREA No Ambiente CKT Panel CT P COSɸ S ST V I IT Kva L C TIPO Smm2 E%

Toma Corriente Dormitorio 1 203 1 PTN2 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 38.00 M 10 THHN 5.26 mm2 2.26 %

Toma Corriente Dormitorio 2 205 5 PTN2 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 34.00 M 10 THHN 5.26 mm2 2.02 %

Toma Corriente Dormitorio 3 207 2 PTN2 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 29.00 M 10 THHN 5.26 mm2 1.72 %

Toma Corriente Dormitorio 4 209 6 PTN2 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 31.00 M 10 THHN 5.26 mm2 1.84 %

Toma Corriente Dormitorio 5 211 7 PTN2 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 35.00 M 10 THHN 5.26 mm2 2.08 %

Toma Corriente Dormitorio 6 213 11 PTN2 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 42.00 M 10 THHN 5.26 mm2 2.50 %

Toma Corriente Pasillo 2, Repetidor de llamado de


Emergencia 202 28 PTN2 5 und 180.00 W 0.96 187.50VA 937.50VA 120V 1.56A 7.81A 0.94 KvA 31.00 M 10 THHN 5.26 mm2 1.53 %

Toma Corriente Dormitorio 7 215 8 PTN2 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 31.00 M 10 THHN 5.26 mm2 1.84 %

Toma Corriente Dormitorio 8 217 12 PTN2 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 26.00 M 10 THHN 5.26 mm2 1.54 %

Toma Corriente Dormitorio 11 Aislado 224 14 PTN2 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 29.00 M 10 THHN 5.26 mm2 1.72 %

Toma Corriente Dormitorio 10 222 16 PTN2 5 und 180.00 W 0.96 187.50VA 937.50VA 120V 1.56A 7.81A 0.94 KvA 25.00 M 10 THHN 5.26 mm2 1.24 %

Toma Corriente Dormitorio 9 220 18 PTN2 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 20.00 M 10 THHN 5.26 mm2 1.19 %

Toma Corriente Pasillo 1, Vestibulo 201-200 13 PTN2 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 19.00 M 10 THHN 5.26 mm2 1.13 %

229 25 3 und 180.00 W 0.96 187.50VA 562.50VA 120V 1.56A 4.69A 0.56 KvA 15.00 M 5.26 mm2 0.45 %
Toma Corriente Sub estacion de Enfermeria PTN2 10 THHN

233-234-235-
Toma Corriente Estacion de Enfermeria, Bodega de 24 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 21.00 M 5.26 mm2 1.25 %
236
Enfermeria, S.S. Enfermeria y Area Sucia PTN2 10 THHN
237 17 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 26.00 M 5.26 mm2 1.54 %
Toma Corriente Dormitorio 12 PTN2 10 THHN

Toma Corriente Dormitorio 13 239 20 PTN2 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 33.00 M 10 THHN 5.26 mm2 1.96 %

227-228
Toma Corriente Cuarto Electrico, Voz y Datos 19 PTN2 5 und 180.00 W 0.96 187.50VA 937.50VA 120V 1.56A 7.81A 0.94 KvA 10.00 M 12 THHN 3.31 mm2 0.79 %

T. corriente Cabecera de Cama Cuarto 1, cuarto 2 203-205 4 PTN2 6 und 192.00 W 0.96 200.00VA 1200.00VA 120V 1.67A 10.00A 1.20 KvA 42.00 M 10 THHN 5.26 mm2 2.66 %

Toma corriente Cabecera de Cama Cuarto 3, cuarto 4 207-209 3 PTN2 6 und 192.00 W 0.96 200.00VA 1200.00VA 120V 1.67A 10.00A 1.20 KvA 31.00 M 10 THHN 5.26 mm2 1.96 %

Toma corriente Cabecera de Cama Cuarto 5, cuarto 6 211-213 9 PTN2 6 und 192.00 W 0.96 200.00VA 1200.00VA 120V 1.67A 10.00A 1.20 KvA 31.00 M 10 THHN 5.26 mm2 1.96 %

Toma corriente Cabecera de Cama Cuarto 7, cuarto 8 215-217 10 PTN2 6 und 192.00 W 0.96 200.00VA 1200.00VA 120V 1.67A 10.00A 1.20 KvA 26.00 M 10 THHN 5.26 mm2 1.65 %

Toma corriente Cabecera de Cama Cuarto 9, cuarto 10 220-222 15 PTN2 6 und 192.00 W 0.96 200.00VA 1200.00VA 120V 1.67A 10.00A 1.20 KvA 26.00 M 10 THHN 5.26 mm2 1.65 %

Toma corriente Cabecera de Cama Cuarto 11 224 21 PTN2 3 und 192.00 W 0.96 200.00VA 600.00VA 120V 1.67A 5.00A 0.60 KvA 29.00 M 10 THHN 5.26 mm2 0.92 %
Toma corriente Cabecera de Cama Cuarto 12, cuarto 13 237-239 22 PTN2 6 und 192.00 W 0.96 200.00VA 1200.00VA 120V 1.67A 10.00A 1.20 KvA 25.00 M 10 THHN 5.26 mm2 1.58 %

Toma Corriente Oasis de Estacion de Enfermeria 229 29 PTN2 1 und 850.00 W 0.96
885.42VA
885.42VA
120V 7.38A 7.38A 0.89 KvA 42.00 M 10 THHN 5.26 mm2 1.96 %

Toma Corriente Oasis sub Estacion de Enfermeria 233 30 PTN2 1 und 850.00 W 0.96
885.42VA
885.42VA
120V 7.38A 7.38A 0.89 KvA 35.00 M 10 THHN 5.26 mm2 1.64 %

ECUACION

(2*n*L*I)
cv% =
(V*mm2)

Cv% = CAIDA DE VOLTAJE MENOR O IGUAL A 3%


n= VALOR CONSTANTE
n=2 CUANDO ES MONOFASICA
n=√3 CUANDO ES TRIFASICA
L= DISTANCIA DEL CIRCUITO
I = CORRIENTE
V = VOLTAJE DE OPERACIÓN
mm2 = SECCION DEL CONDUCTOR

CKT = NUMERO DE CIRCUITO


PANEL = CENTRO DE CARGA CORRESPONDIENTE
CT = CANTIDAD TOTAL DE TOMA CORRIENTE
PT = POTENCIA ACTIVA TOTAL EN WATTS
COSɸ = FACTOR DE POTENCIA
S = POTENCIA APARENTE
ST= POTENCIA APARENTE TOTAL EN VOLT AMPERE
V = VOLTAJE
I = CORRIENTE EN AMPERIOS
I T = CORRIENTE TOTAL EN AMPERIOS
KVA = POTENCIA APARENTE TOTAL EN KILO VOLT AMPERE
L = LONGITUD TOTAL DEL CIRCUITO
C = CONDUCTOR ASIGNADO
Smm2 = SECCION TRANSVERSAL DEL CONDUCTOR EN MILIMETROS CUADRADOS
E % = CAIDA DE VOLTAJE EN PORCIENTO MAX PERMITIDO (3 %) PARA CIRCUITOS DERIVADOS
MEMORIA CALCULO TOMA CORRIENTE
CALCULO DE TOMA CORRIENTE (T2) NIVEL 2

Nombre area No Ambiente CKT Panel CT P COSɸ S ST V I IT Kva L C TIPO Smm2 E%

203-205-215- 31
Evaporador Cuarto 1, 2, 7, 8, 11 217-224
PT3N3 1 und 450.00 W 0.96 468.75VA 468.75VA 240V 1.95A 1.95A 0.47 KvA 26.00 M 12 THHN 3.31 mm2 0.26 %

33

Evaporador Cuarto 5, 6, 12, 13, Estacion de Enfermeria, 3, 209-211-213- 36


233-237-239
PT3N3 1 und 900.00 W 0.96 937.50VA 937.50VA 240V 3.91A 3.91A 0.94 KvA 30.00 M 12 THHN 3.31 mm2 0.59 %
4, 9, 10, Sub Estacion de Enfermeria
38

Toma corriente camilla Dormitorio 7, Dormitorio 8, 35


215-217 PTN2 5 und 432.00 W 0.96 450.00VA 2250.00VA 240V 1.88A 9.38A 2.25 KvA 26.00 M 10 THHN 5.26 mm2 0.77 %
Dormitorio 9, Dormitorio 10, Dormitorio 11
37

Toma corriente camilla Dormitorio 5, Dormitorio 6, 211-213-237- 39


PTN2 4 und 432.00 W 0.96 450.00VA 1800.00VA 240V 1.88A 7.50A 1.80 KvA 35.00 M 10 THHN 5.26 mm2 0.83 %
Dormitorio 12, Dormitorio 13 239
41

Toma corriente camilla Dormitorio 1, Dormitorio 2, 203-205-207- 6


PTN2 4 und 432.00 W 0.96 450.00VA 1800.00VA 240V 1.88A 7.50A 1.80 KvA 38.00 M 10 THHN 5.26 mm2 0.90 %
Dormitorio 3, Dormitorio 4 209
8

1
203 PT2N2 1 und 3200.00 W 0.96 3333.33VA 0.00VA 240V 13.89A 13.89A 3.33 KvA 38.00 M 10 THHN 5.26 mm2 1.67 %
Ducha Dormitorio 1 3

40
205 PT2N2 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 34.00 M 10 THHN 5.26 mm2 1.50 %
Ducha Dormitorio 2 42

7
207 PT2N2 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 29.00 M 10 THHN 5.26 mm2 1.28 %
Ducha Dormitorio 3 9

2
209 PT2N2 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 31.00 M 10 THHN 5.26 mm2 1.36 %
Ducha Dormitorio 4 4

11
211 PT2N2 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 35.00 M 10 THHN 5.26 mm2 1.54 %
Ducha Dormitorio 5 13

12
213 PT2N2 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 42.00 M 10 THHN 5.26 mm2 1.85 %
Ducha Dormitorio 6 14

15
215 PT2N2 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 31.00 M 10 THHN 5.26 mm2 1.36 %
Ducha Dormitorio 7 17

16
217 PT2N2 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 26.00 M 10 THHN 5.26 mm2 1.14 %
Ducha Dormitorio 8 18

23
224 PT2N2 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 29.00 M 10 THHN 5.26 mm2 1.28 %
Ducha Dormitorio 11 Aislado 25

20
222 PT2N2 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 25.00 M 10 THHN 5.26 mm2 1.10 %
Ducha Dormitorio 10 22
19
220 PT2N2 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 20.00 M 10 THHN 5.26 mm2 0.88 %
Ducha Dormitorio 9 21

24
237 PT2N2 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 26.00 M 10 THHN 5.26 mm2 1.14 %
Ducha Dormitorio 12 26
27
239 PT2N2 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 33.00 M 10 THHN 5.26 mm2 1.45 %
29
Ducha Dormitorio 13
28
234 PT2N2 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 21.00 M 10 THHN 5.26 mm2 0.92 %
30
Ducha SS Enfermeria

ECUACION

(2*n*L*I)
cv% =
(V*mm2)

Cv% = CAIDA DE VOLTAJE MENOR O IGUAL A 3%


n= VALOR CONSTANTE

n=2 CUANDO ES MONOFASICA


n=√3 CUANDO ES TRIFASICA
L= DISTANCIA DEL CIRCUITO
I = CORRIENTE
V = VOLTAJE DE OPERACIÓN
mm2 = SECCION DEL CONDUCTOR

CKT = NUMERO DE CIRCUITO


PANEL = CENTRO DE CARGA CORRESPONDIENTE
CT = CANTIDAD TOTAL DE TOMA CORRIENTE
PT = POTENCIA ACTIVA TOTAL EN WATTS
COSɸ = FACTOR DE POTENCIA
S = POTENCIA APARENTE
ST= POTENCIA APARENTE TOTAL EN VOLT AMPERE
V = VOLTAJE
I = CORRIENTE EN AMPERIOS
I T = CORRIENTE TOTAL EN AMPERIOS
KVA = POTENCIA APARENTE TOTAL EN KILO VOLT AMPERE
L = LONGITUD TOTAL DEL CIRCUITO
C = CONDUCTOR ASIGNADO
Smm2 = SECCION TRANSVERSAL DEL CONDUCTOR EN MILIMETROS CUADRADOS
E % = CAIDA DE VOLTAJE EN PORCIENTO MAX PERMITIDO (3 %) PARA CIRCUITOS DERIVADOS
MEMORIA CALCULO TOMA CORRIENTE
CALCULO DE TOMA CORRIENTE NIVEL 3

Nombre area No Ambiente CKT Panel CT P COSɸ S ST V I IT Kva L C TIPO Smm2 E%

T. Corriente Direccion 313 4 PT3N 5 und 180.00 W 0.96 187.50VA 937.50VA 120V 1.56A 7.81A 0.94 KvA 45.00 M 10 THHN 5.26 mm2 2.23 %

Toma Corriente Direccion 313 7 PT3N 4 und 180.00 W 0.96 187.50VA 750.00VA 120V 1.56A 6.25A 0.75 KvA 44.00 M 10 THHN 5.26 mm2 1.74 %

Toma Corriente Motor de Pantalla electrica Direccion 313 20 PT3N 1 und 180.00 W 0.96 187.50VA 187.50VA 120V 1.56A 1.56A 0.19 KvA 44.00 M 10 THHN 5.26 mm2 0.44 %

Toma Corriente Secretaria de Direccion 314 5 PT3N 5 und 180.00 W 0.96 187.50VA 937.50VA 120V 1.56A 7.81A 0.94 KvA 38.00 M 10 THHN 5.26 mm2 1.88 %

T. Corriente Clinica 1 318 25 PT3N 4 und 180.00 W 0.96 187.50VA 750.00VA 120V 1.56A 6.25A 0.75 KvA 36.00 M 10 THHN 5.26 mm2 1.43 %

T. Corriente Clinica 2 316 2 PT3N 3 und 180.00 W 0.96 187.50VA 562.50VA 120V 1.56A 4.69A 0.56 KvA 36.00 M 10 THHN 5.26 mm2 1.07 %

Toma Corriente Camilla Clinica 1 y Clinica 2 316-318 28 PT3N 2 und 180.00 W 0.96 187.50VA 375.00VA 120V 1.56A 3.13A 0.38 KvA 36.00 M 10 THHN 5.26 mm2 0.71 %

Toma Corriente Gymnacio 320 3 PT3N 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 29.00 M 10 THHN 5.26 mm2 1.72 %

300 6
T. Corriente Sala de Espera 1 y TV sala de Espera 1 PT3N 4 und 180.00 W 0.96 187.50VA 750.00VA 120V 1.56A 6.25A 0.75 KvA 19.00 M 10 THHN 5.26 mm2 0.75 %

T. Corriente Pasillo 1 303 11 PT3N 3 und 180.00 W 0.96 187.50VA 562.50VA 120V 1.56A 4.69A 0.56 KvA 34.00 M 10 THHN 5.26 mm2 1.01 %

Toma Corriente Neurologia Pediatrica 309 1 PT3N 4 und 180.00 W 0.96 187.50VA 750.00VA 120V 1.56A 6.25A 0.75 KvA 41.00 M 10 THHN 5.26 mm2 1.62 %

T. Corriente Vestidor de Mujeres y Vestidor de hombres 336-334 8 PT3N 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 46.00 M 10 THHN 5.26 mm2 2.73 %

T. Corriente Sueño + Video + EEG 307 12 PT3N 4 und 180.00 W 0.96 187.50VA 750.00VA 120V 1.56A 6.25A 0.75 KvA 37.00 M 10 THHN 5.26 mm2 1.47 %

T. Corriente Cabecero Clinica 2, Sueño + Video + EEG 316-307 31 PTTA2N 2 und 180.00 W 0.96 187.50VA 375.00VA 120V 1.56A 3.13A 0.38 KvA 38.00 M 10 THHN 5.26 mm2 0.75 %

T. Corriente Camilla Sueño + Video + EEG 307 19 PT3N 1 und 180.00 W 0.96 187.50VA 187.50VA 120V 1.56A 1.56A 0.19 KvA 37.00 M 10 THHN 5.26 mm2 0.37 %

T. Corriente Estacion de enfermeria y Admision 304-302 10 PT3N 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 31.00 M 10 THHN 5.56 mm2 1.74 %
T. Corriente Caja
301 17 PT3N 5 und 180.00 W 0.96 187.50VA 937.50VA 120V 1.56A 7.81A 0.94 KvA 22.00 M 10 THHN 5.26 mm2 1.09 %
23
T. Corriente Cuarto de Control 338 PT3N 4 und 180.00 W 0.96 187.50VA 750.00VA 120V 1.56A 6.25A 0.75 KvA 33.00 M 10 THHN 5.26 mm2 1.31 %

T. Corriente Cabecero de Cama Recuperacion 342 27 PT3N 6 und 180.00 W 0.96 187.50VA 1125.00VA 120V 1.56A 9.38A 1.13 KvA 45.00 M 10 THHN 5.26 mm2 2.67 %

T. Corriente Cabecero de Cama Recuperacion 342 9 PT3N 3 und 180.00 W 0.96 187.50VA 562.50VA 120V 1.56A 4.69A 0.56 KvA 45.00 M 10 THHN 5.26 mm2 1.34 %

T. Corriente Estacion de enfermeria 344 18 PT3N 4 und 180.00 W 0.96 187.50VA 750.00VA 120V 1.56A 6.25A 0.75 KvA 32.00 M 10 THHN 5.26 mm2 1.27 %

T. Corriente Cuarto Electrico, Voz y Datos 324-323 14 PT3N 4 und 180.00 W 0.96 187.50VA 750.00VA 120V 1.56A 6.25A 0.75 KvA 10.00 M 10 THHN 5.26 mm2 0.40 %

Toma Corriente Bodega de Direccion, Bodega de Mtto y 400-401-403 13


Vestibulo PT3N 4 und 180.00 W 0.96 187.50VA 750.00VA 120V 1.56A 6.25A 0.75 KvA 20.00 M 10 THHN 5.26 mm2 0.79 %

338 29
T. Corriente Cuarto de Control PT3N 4 und 180.00 W 0.96 187.50VA 750.00VA 120V 1.56A 6.25A 0.75 KvA 33.00 M 10 THHN 5.26 mm2 1.31 %
338 16
T. Corriente Cuarto de Control PT3N 4 und 180.00 W 0.96 187.50VA 750.00VA 120V 1.56A 6.25A 0.75 KvA 33.00 M 10 THHN 5.26 mm2 1.31 %

338 24
T. Corriente Cuarto de Control PT3N 4 und 180.00 W 0.96 187.50VA 750.00VA 120V 1.56A 6.25A 0.75 KvA 33.00 M 10 THHN 5.26 mm2 1.31 %

345-348-350 22
T. Corriente Area Sucia y Arsenal PT3N 4 und 180.00 W 0.96 187.50VA 750.00VA 120V 1.56A 6.25A 0.75 KvA 33.00 M 10 THHN 5.26 mm2 1.31 %

343-345 26
T. Corriente Bodega, Anestecia PT3N 3 und 180.00 W 0.96 187.50VA 562.50VA 120V 1.56A 4.69A 0.56 KvA 33.00 M 10 THHN 5.26 mm2 0.98 %

ECUACION

(2*n*L*I)
cv% =
(V*mm2)

Cv% = CAIDA DE VOLTAJE MENOR O IGUAL A 3%


n= VALOR CONSTANTE
n=2 CUANDO ES MONOFASICA
n=√3 CUANDO ES TRIFASICA
L= DISTANCIA DEL CIRCUITO
I = CORRIENTE
V = VOLTAJE DE OPERACIÓN
mm2 = SECCION DEL CONDUCTOR

CKT = NUMERO DE CIRCUITO


PANEL = CENTRO DE CARGA CORRESPONDIENTE
CT = CANTIDAD TOTAL DE TOMA CORRIENTE
PT = POTENCIA ACTIVA TOTAL EN WATTS
COSɸ = FACTOR DE POTENCIA
S = POTENCIA APARENTE
ST= POTENCIA APARENTE TOTAL EN VOLT AMPERE
V = VOLTAJE
I = CORRIENTE EN AMPERIOS
I T = CORRIENTE TOTAL EN AMPERIOS
KVA = POTENCIA APARENTE TOTAL EN KILO VOLT AMPERE
L = LONGITUD TOTAL DEL CIRCUITO
C = CONDUCTOR ASIGNADO
Smm2 = SECCION TRANSVERSAL DEL CONDUCTOR EN MILIMETROS CUADRADOS
E % = CAIDA DE VOLTAJE EN PORCIENTO MAX PERMITIDO (3 %) PARA CIRCUITOS DERIVADOS
MEMORIA CALCULO TOMA CORRIENTE
CALCULO DE TOMACORRIENTE (T2) NIVEL 3

Nombre area No Ambiente CKT Panel CT P COSɸ S ST V I IT Kva L C TIPO Smm2 E%

1
Ducha Direccion 313 PT2N3 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 38.00 M 10 THHN 5.26 mm2 1.67 %
3

4
Ducha Clinica 2 316 PT2N3 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 34.00 M 10 THHN 5.26 mm2 1.50 %
6

5
Ducha Clinica 1 318 PT2N3 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 29.00 M 10 THHN 5.26 mm2 1.28 %
7

32
Ducha SS - 7 308 PT2N3 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 31.00 M 10 THHN 5.26 mm2 1.36 %
34

8
Ducha SS 8 335 PT2N3 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 35.00 M 10 THHN 5.26 mm2 1.54 %
10

12
Ducha SS / 7 337 PT2N3 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 42.00 M 10 THHN 5.26 mm2 1.85 %
14

13
Ducha SS 10 346 PT2N3 1 und 3200.00 W 0.96 3333.33VA 3333.33VA 240V 13.89A 13.89A 3.33 KvA 31.00 M 10 THHN 5.26 mm2 1.36 %
15
T. corriente Oasis Sala de espera 1 541.67VA 120V 4.51A 4.51A 1.20 %
300 21 PT2N3 1 und 520.00 W 0.96 541.67VA 0.54 KvA 42.00 M 10 THHN 5.26 mm2
T. Corriente Oasis Estacion de Enfermeria 541.67VA 120V 4.51A 4.51A 1.00 %
344 22 PT2N3 1 und 520.00 W 0.96 541.67VA 0.54 KvA 35.00 M 10 THHN 5.26 mm2

Toma corriente Area de Condensadoras 15 PT2N3 1 und 180.00 W 0.96 187.50VA 187.50VA 120V 1.56A 1.56A 0.19 KvA 31.00 M 10 THHN 5.26 mm2 0.31 %
Evaporador Sala de Espera 1, Caja, Admision, Gymnasio,
Clinica 1 y 2, Estacion de Enfermeria, Vestidor de
Hombres y Vestidor de Mujeres 18
PT2N3 1 und 1122.00 W 0.96 1168.75VA 1168.75VA 240V 4.87A 4.87A 1.17 KvA 40.00 M 12 THHN 3.31 mm2 0.98 %

20
Evaporador Secretaria Direccion, Direccion, Neurologia
Pediatrica, Sueño +Video+EEG, Cuarto de Control, Pasillo 31
3, Recuperacion, Estacion de enfermeria, Anestecia
PT2N3 1 und 1142.00 W 0.96 1189.58VA 1189.58VA 240V 4.96A 4.96A 1.19 KvA 45.00 M 12 THHN 3.31 mm2 1.12 %

33

23
Toma Corriente camilla Recuperacion 342 PT2N3 3 und 432.00 W 0.96 450.00VA 1350.00VA 240V 1.88A 5.63A 1.35 KvA 38.00 M 10 THHN 5.26 mm2 0.68 %
25

Panel Tierra Aislada Sala de Hemodinamia 30 PT2N3 1 und 4500.00 W 0.96 4687.50VA 4687.50VA 120V 39.06A 39.06A 4.69 KvA 45.00 M 2 THHN 33.63 mm2 1.74 %

27
PT2N3 1 und 2200.00 W 0.96 2291.67VA 2291.67VA 208V 11.02A 11.02A 2.29 KvA 40.00 M 10 THHN 5.26 mm2 1.61 %

Toma Corriente Arco en C Sala de Hemodinamia 29


MEMORIA CALCULO TOMA CORRIENTE
CALCULO DE TOMACORRIENTE (T2) NIVEL 3

Nombre area No Ambiente CKT Panel CT P COSɸ S ST V I IT Kva L C TIPO Smm2 E%

26
PT2N3 1 und 1014.00 W 0.96 1056.25VA 1056.25VA 208V 5.08A 5.08A 1.06 KvA 40.00 M 10 THHN 5.26 mm2 0.74 %

Extractor de Aire CUE-900 Sala de Hemodinamia 28

26
PT2N3 1 und 1014.00 W 0.96 1056.25VA 1056.25VA 208V 5.08A 5.08A 1.06 KvA 40.00 M 10 THHN 5.26 mm2 0.74 %
INYECTOR CUE-099-VG-1/4 - C-1/8 Sala de
Hemodinamia 28

Aire acondicionado 1 Cuarto Equipo Hemodinamia PT2N3 1 und 2599.00 W 0.96 2707.29VA 2707.29VA 208V 13.02A 13.02A 2.71 KvA 40.00 M 10 THHN 5.26 mm2 1.90 %

Aire acondicionado 2 Cuarto Equipo Hemodinamia PT2N3 1 und 2599.00 W 0.96 2707.29VA 2707.29VA 208V 13.02A 13.02A 2.71 KvA 40.00 M 10 THHN 5.26 mm2 1.90 %

ECUACION

(2*n*L*I)
cv% =
(V*mm2)

Cv% = CAIDA DE VOLTAJE MENOR O IGUAL A 3%


n= VALOR CONSTANTE
n=2 CUANDO ES MONOFASICA
n=√3 CUANDO ES TRIFASICA
L= DISTANCIA DEL CIRCUITO
I = CORRIENTE
V = VOLTAJE DE OPERACIÓN
mm2 = SECCION DEL CONDUCTOR

CKT = NUMERO DE CIRCUITO


PANEL = CENTRO DE CARGA CORRESPONDIENTE
CT = CANTIDAD TOTAL DE TOMA CORRIENTE
PT = POTENCIA ACTIVA TOTAL EN WATTS
COSɸ = FACTOR DE POTENCIA
S = POTENCIA APARENTE
ST= POTENCIA APARENTE TOTAL EN VOLT AMPERE
V = VOLTAJE
I = CORRIENTE EN AMPERIOS
I T = CORRIENTE TOTAL EN AMPERIOS
KVA = POTENCIA APARENTE TOTAL EN KILO VOLT AMPERE
L = LONGITUD TOTAL DEL CIRCUITO
MEMORIA CALCULO TOMA CORRIENTE
CALCULO DE TOMACORRIENTE (T2) NIVEL 3

Nombre area No Ambiente CKT Panel CT P COSɸ S ST V I IT Kva L C TIPO Smm2 E%

C = CONDUCTOR ASIGNADO
Smm2 = SECCION TRANSVERSAL DEL CONDUCTOR EN MILIMETROS CUADRADOS
E % = CAIDA DE VOLTAJE EN PORCIENTO MAX PERMITIDO (3 %) PARA CIRCUITOS DERIVADOS
MEMORIA CALCULO DE LUMINOTECNIA (SEGÚN SOFTWARE DIALUX)

CALCULO DE LUMINARIAS NIVEL 1


Total
Nombre area NOTA (A) (F.d) (E) (ƞ ) (ɸ L ) NL Luminaria P PT COSɸ ST V
s

VICE-PRESIDENCIA JUNTA 3- 3000lm /4-630


GENERAL CORNAP lm-156W 15.13 M2 1.25 Fd 500 E 0.8 ƞ 3000 lm 3.94 4 und 40.00 W 160.00 W 0.85 188.24VA 120V

ASISTENTES DE PRESIDENCIA 11.35 M2 1.25 Fd 500 E 0.8 ƞ 3000 lm 2.96 3 und 40.00 W 120.00 W 0.85 141.18VA 120V
Direccion de Ascesoria Legal y
8.25 M2 1.25 Fd 0.8 ƞ 2.15 2 und 80.00 W 94.12VA 120V
litigio 500 E 3000 lm 40.00 W 0.85
Asesoria Legal y Litigio 21.10 M2 1.25 Fd 500 E 0.8 ƞ 3000 lm 5.49 6 und 40.00 W 240.00 W 0.85 282.35VA 120V

SECRETARÍA DE JUNTA
10.38 M2 1.25 Fd 0.8 ƞ 2.70 3 und 120.00 W 141.18VA 120V
GENERAL CORNAP 500 E 3000 lm 40.00 W 0.85
DIVISION DE ADMINISTRACION
28.90 M2 1.25 Fd 0.8 ƞ 3000 lm 7.53 8 und 320.00 W 376.47VA 120V
Y FINANZAS
500 E 40.00 W 0.85
TECNOLOGIA INFORMATICA 9.00 M2 1.25 Fd 500 E 0.8 ƞ 3000 lm 2.34 2 und 40.00 W 80.00 W 0.85 94.12VA 120V

AUDITOR INTERNO 9.00 M2 1.25 Fd 500 E 0.8 ƞ 3000 lm 2.34 2 und 40.00 W 80.00 W 0.85 94.12VA 120V

PLANIFICACION 8.29 M2 1.25 Fd 500 E 0.8 ƞ 3000 lm 2.16 2 und 40.00 W 80.00 W 0.85 94.12VA 120V

AREA DE ARCHIVO INTERNO 6.00 M2 1.25 Fd 300 E 0.8 ƞ 3000 lm 0.94 1 und 40.00 W 40.00 W 0.85 47.06VA 120V
UNIDAD TECNICA DE
17.78 M2 1.25 Fd 500 E 0.8 ƞ 3000 lm 4.63 6 und 240.00 W 282.35VA 120V
PROYECTOS 40.00 W 0.85
RECURSOS HUMANOS 6-3000 lm 8.60 M2 1.25 Fd 500 E 0.8 ƞ 3000 lm 2.24 2 und 40.00 W 80.00 W 0.85 94.12VA 120V

ASISTENTE ADMINISTRATIVO
CNPC, DIRECCION
14.36 M2 1.25 Fd 500 E 0.8 ƞ 3000 lm 3.74 4 und 40.00 W 160.00 W 188.24VA 120V
ADMINISTRATIVA FINANCIERA
CNPC 0.85
DIRECCION ADMINISTRATIVA
10.29 M2 1.25 Fd 500 E 0.8 ƞ 3000 lm 2.68 3 und 40.00 W 120.00 W 141.18VA 120V
FINANCIERA CORNAP
0.85

AREA DE COCINA 7.00 M2 1.25 Fd 300 E 0.8 ƞ 1250 lm 2.63 3 und 18.00 W 54.00 W 63.53VA 120V
0.85
RECEPCION CORNAP 11.29 M2 1.25 Fd 500 E 0.8 ƞ 3000 lm 2.94 3 und 40.00 W 120.00 W 0.85 141.18VA 120V

AREA DE PANELES ELÉCTRICOS 3.91 M2 1.25 Fd 500 E 0.8 ƞ 4800 lm 0.64 1 und 60.00 W 60.00 W 70.59VA 120V
0.85
UNIDAD DE ADQUISICIONES 13.66 M2 1.25 Fd 500 E 0.8 ƞ 3000 lm 3.56 4 und 40.00 W 160.00 W 0.85 188.24VA 120V

SALA DE REUNIONES CORNAP3- 3000lm /4-630 lm 18.24 M2 1.25 Fd 400 E 0.8 ƞ 3000 lm 3.80 4 und 40.00 W 160.00 W 188.24VA 120V
0.85
PRESIDENCIA DE JUNTA
3- 3000lm /4-630 lm 15.62 M2 1.25 Fd 500 E 0.8 ƞ 3000 lm 4.07 4 und 40.00 W 160.00 W 188.24VA 120V
GENERAL DE CORNAP 0.85
PASILLO INTERNO 1 10.17 M2 1.25 Fd 150 E 0.8 ƞ 1250 lm 1.91 2 und 18.00 W 36.00 W 0.85 42.35VA 120V

PASILLO INTERNO 2 7.42 M2 1.25 Fd 150 E 0.8 ƞ 1250 lm 1.39 2 und 18.00 W 36.00 W 0.85 42.35VA 120V

PASILLO INTERNO 3 7.59 M2 1.25 Fd 150 E 0.8 ƞ 1250 lm 1.42 2 und 18.00 W 36.00 W 0.85 42.35VA 120V

PASILLO INTERNO 4 7.90 M2 1.25 Fd 150 E 0.8 ƞ 1250 lm 1.48 2 und 18.00 W 36.00 W 0.85 42.35VA 120V
PASILLO INTERNO 5 10.32 M2 1.25 Fd 150 E 0.8 ƞ 1250 lm 1.94 2 und 18.00 W 36.00 W 0.85 42.35VA 120V
PASILLO INTERNO 6 3.22 M2 1.25 Fd 150 E 0.8 ƞ 1250 lm 0.60 1 und 18.00 W 18.00 W 0.85 21.18VA 120V
BOD.PRESIDENCIA 3.65 M2 1.25 Fd 200 E 0.8 ƞ 1250 lm 0.91 1 und 18.00 W 18.00 W 0.85 21.18VA 120V
BOD. VICEPRESIDENCIA 3.31 M2 1.25 Fd 200 E 0.8 ƞ 1250 lm 0.83 1 und 18.00 W 18.00 W 0.85 21.18VA 120V
PASILLO EXTERNO OESTE 1 26.0214 1.25 Fd 100 E 0.8 ƞ 1250 lm 3.25 4 und 18.00 W 72.00 W 0.85 84.71VA 120V
PASILLO EXTERNO OESTE 2 29.9971 1.25 Fd 100 E 0.8 ƞ 1250 lm 3.75 4 und 18.00 W 72.00 W 0.85 84.71VA 120V
PASILLO EXTERNO ENTRADA 22.6602 1.25 Fd 150 E 0.8 ƞ 1250 lm 4.25 4 und 18.00 W 72.00 W 0.85 84.71VA 120V
S.S PRESIDENCIA EXT.CON LUZ 4.212 800 lm 1 und 192.00 W 192.00 W 0.85 225.88VA 120V
S.S VICEPRESIDENCIA EXT.CON LUZ 4.2749 800 lm 1 und 192.00 W 192.00 W 0.85 225.88VA 120V
S,S DAMAS EXT.CON LUZ 6.0555 800 lm 3 und 192.00 W 576.00 W 0.85 677.65VA 120V
S,S DAMAS 4.037 1.25 Fd 150 E 0.8 ƞ 1250 lm 0.76 1 und 18.00 W 18.00 W 0.85 21.18VA 120V
S,S CABALLEROS EXT.CON LUZ 2.364 800 lm 1 und 192.00 W 192.00 W 0.85 225.88VA 120V
S,S GUARDAS DE SEGURIDAD EXT.CON LUZ 800lm 1 und 192.00 W 192.00 W 0.85 225.88VA 120V
S,S CABALLEROS 4.0979 1.25 Fd 150 E 0.8 ƞ 1250 0.770 1 und 18.00 W 18.00 W 0.85 21.18VA 120V
PARQUEO DE PRESIDENCIA 127.5137 1.25 Fd 30 E 0.8 ƞ 1950 3.07 3 und 18.00 W 54.00 W 0.85 63.53VA 120V
PARQUEO GENERAL 532 1.25 Fd 30 E 0.8 ƞ 9000 2.77 3 und 100.00 W 300.00 W 0.85 352.94VA 120V
VENTILADOR DE PARED VENT.SIN LUZ 1 und 192.00 W 192.00 W 0.85 225.88VA 120V
ARCHIVO CENTRAL CORNAP 52.64 1.25 Fd 300 E 0.8 ƞ 4800 5.14 6 und 60.00 W 360.00 W 0.85 423.53VA 120V
ECUACION
NA = NUMERO DE AREA

A = AREA A*E*F.D DISTRIBUCIÓN DE LÁMPARAS.


NL =
Fd = FACTOR DE ENVEJECIMIENTO (ƞ*ɸL) LONG. NL CONSTANTEEXTREMO

E = ILUMINACION REQUERIDA LARGO 20.2737 4 2 2.5342125

ƞ = FACTOR DE EFICIENCIA ANCHO 17.5966 4 2 2.199575


ECUACION LUX
ɸ L = LUMENES DE LAMPARA

NL = NUMERO DE LUMINARIAS ƞ * ɸ L * NL
E=
P = POTENCIA ACTIVA WATTS (A * Fd )
PT = POTENCIA ACTIVA TOTAL EN WATTS
COSɸ = FACTOR DE POTENCIA

ST = POTENCIA APARENTE TOTAL EN VOLT AMPERE

V = VOLTAJE

I = CORRIENTE EN AMPERIOS
CALCULO CAIDA DE TENSION PARA CIRCUITOS DE ILUMINACION NIVEL 1

Nombre area No Ambiente CKT Panel PT COSɸ ST V IT KVA L CAL TIPO Smm2

VICE-PRESIDENCIA JUNTA
1 160.00 W 0.85 188.24VA 120V 1.57A 0.19 60.00 M 12 THHN 3.31 mm2
GENERAL CORNAP.

ASISTENTES DE PRESIDENCIA 20 120.00 W 0.85 141.18VA 120V 1.18A 0.14 KvA 240.00 M 12 THHN 3.31 mm2

DIRECCIÓN DE ASESORIA 9 80.00 W 0.85 94.12VA 120V 0.78A 0.09 KvA 37.00 M 12 THHN 3.31 mm2
LEGAL Y LITIGIO

ASESORIA LEGAL Y LITIGIO 2 240.00 W 0.85 282.35VA 120V 2.35A 0.28 KvA 33.00 M 12 THHN 3.31 mm2

SECRETARIA DE JUNTA
19 120.00 W 0.85 141.18VA 120V 1.18A 0.14 KvA 23.00 M 12 THHN 3.31 mm2
GENERAL CORNAP

DIVISIÓN DE ADMINISTRACIÓN
6 PLN1 #REF! 0.96 #REF! 120V #REF! #REF! 28.00 M 12 THHN 3.31 mm2
Y FINANZAS

TÉCNOLOGIA INFORMATICA 14 PLN1 #REF! 0.96 #REF! 120V #REF! #REF! 31.00 M 12 THHN 3.31 mm2

AUDITOR INTERNO 12 PLN1 #REF! 0.96 #REF! 120V #REF! #REF! 29.00 M 12 THHN 3.31 mm2

PLANIFICACIÓN 8 PLN1 #REF! 0.96 #REF! 120V #REF! #REF! 37.00 M 12 XHHW 3.31 mm2

ÁREA DE ARCHIVO INTERNO 22 PLN1 #REF! 0.96 #REF! 120V #REF! #REF! 40.00 M 12 XHHW 3.31 mm2

UNIDAD TÉCNICA DE
11 PLN1 #REF! 0.96 #REF! 120V #REF! #REF! 31.00 M 12 THHN 3.31 mm2
PROYECTOS

RECURSOS HUMANOS 17 PLN1 #REF! 0.96 #REF! 120V #REF! #REF! 32.00 M 12 THHN 3.31 mm2

ASISTENTE ADMINISTRATIVO
CNPC,DIRECCIÓN ADMINISTRA 12 XHHW
TIVA FINANCIERA CNPC
21 PLN1 #REF! 0.96 #REF! 120V #REF! #REF! 24.00 M 3.31 mm2

DIRECCIÓN ADMINISTRATIVA
12 XHHW
FINANCIERA CORNAP
16 PLN1 #REF! 0.96 #REF! 120V #REF! #REF! 17.00 M 3.31 mm2

4 PLN1 #REF! 0.96 #REF! 120V #REF! #REF! 19.00 M 12 THHN 3.31 mm2
ÁREA DE COCINA

10 PLN1 #REF! 0.96 #REF! 120V #REF! #REF! 44.00 M 12 THHN 3.31 mm2
RECEPCIÓN CORNAP

13 #REF!
ÁREA DE PANELES ELÉCTRICOS PLN1 #REF! 0.96 240V #REF! #REF! 35.14 M 10 THHN 5.26 mm2
15

3 PLN1 600.00 W 0.96 312.50VA 240V 2.60A 0.31 KvA 35.14 M 10 THHN 5.26 mm2
UNIDAD DE ADQUISICIONES
5
18 PLN1 #REF! 0.96 #REF! 120V #REF! #REF! 50.00 M 12 THHN 3.31 mm2
SALA DE REUNIONES CORNAP

PRESIDENCIA DE JUNTA
23 PLN1 #REF! 12 THHN
GENERAL CORNAP
#REF! 0.96 #REF! 120V #REF! 50.00 M 3.31 mm2

PASILLO INTERNO1

PASILLO INTERNO 2

PASILLO INTERNO 3

PASILLO INTERNO 4

PASILLO INTERNO 5

PASILLO INTERNO 6

BOD.PRESIDENCIA

BOD.VICEPRESIDENCIA

PASILLO EXTERNO OESTE 1

PASILLO EXTERNO OESTE 2

PASILLO EXTERNO ENTRADA

S,S PRESIDENCIA

S,S VICEPRESIDENCIA
S,S DAMAS

S,S DAMAS

S,S CABALLEROS

S,S CABALLEROS

PARQUEO DE PRESIDENCIA

PARQUEO GENERAL

ARCHIVO CENTRAL CORNAP

ECUACION

(2*n*L*I)
cv% =
(V*mm2)

Cv% = Caida de voltaje el cual debe de ser menor o igual a 3%

n= Valor Constante

n=2 Cuando es monofásica


n=√3 Cuando es trifásica

L= Distancia del Circuito

I = Corriente

V = Voltaje de Operación
mm2 = Sección del Conductor

CKT = NUMERO DE CIRCUITO


PANEL = CENTRO DE CARGA CORRESPONDIENTE

PT = POTENCIA ACTIVA TOTAL EN WATTS

COSɸ = FACTOR DE POTENCIA

ST= POTENCIA APARENTE TOTAL EN VOLT AMPERE

V = VOLTAJE

I T = CORRIENTE TOTAL EN AMPERIOS


KVA = POTENCIA APARENTE TOTAL EN KILO VOLT AMPERE
L = LONGITUD TOTAL DEL CIRCUITO

CAL = CALIBRE DEL CONDUCTOR ASIGNADO


Smm2 = SECCION TRANSVERSAL DEL CONDUCTOR EN MILIMETROS CUADRADOS
E % = CAIDA DE VOLTAJE EN PORCIENTO MAX PERMITIDO (3 %) PARA CIRCUITOS DERIVADOS
I

1.57A

1.18A

0.78A

2.35A

1.18A

3.14A

0.78A

0.78A

0.78A

0.39A

2.35A

0.78A

1.57A

1.18A

0.53A

1.18A

0.59A

1.57A

1.57A

1.57A

0.35A

0.35A

0.35A

0.35A
0.35A
0.18A
0.18A
0.18A
0.71A
0.71A
0.71A
1.88A
1.88A
5.65A
0.18A
1.88A
1.88A
0.18A
0.53A
2.94A
1.88A
3.53A
E%

0.95 %

2.84 %

0.29 %

0.78 %

0.27 %

#REF!

#REF!

#REF!

#REF!

#REF!

#REF!

#REF!

#REF!

#REF!

#REF!

#REF!

#REF!

0.29 %

#REF!

#REF!
CALCULO SISTEMA DE PUESTA A TIERRA

Para el cálculo de resistencia que aportará la varilla y el conductor de la malla de tierra, se usará la
fórmula de Laurent y Niemann, por medio de ella se determinará la contribución de resistencias de la malla.

Para el ejercicio dado se utilizará varillas copperweld de 10ft de largo y 5/8” de diámetro, con una
Resistencia del suelo (Ƥ)= rho = 60 Ω. Para realizar un cálculo efectivo debe medirse la resistencia del
suelo con un Telurómetro.

Primer Paso.
Convertir la longitud de la varilla de ft a metros por medio de una regla de tres simple.
Longitud Varilla 10 FT = 3.05 M

Segundo Paso.
Convertir el diámetro de la varilla de pulgada a ft.
D. Varilla 5/8 " 0.052 FT

Tercer Paso.
Convertir el diámetro de la varilla de ft a metros.
D Varilla 0.052 FT 0.016 M

Cuarto Paso.
Se introduce los datos a la ecuación de resistencia de la varilla
Determinar la resistencia del electrodo de puesta a tierra

R varilla = (Ƥ)/ (2 π L) x Ln (4 x L / d -1) = Ω


Longitud (Ƥ) R.Varilla
3.05 M 60.00Ω / 20.77Ω

Ƥ= Resistividad del suelo en este caso es de 60Ω.


L = longitud de una varilla (Electrodo de Puesta a Tierra)
d = diámetro de la varilla 5/8” en metro

5to Paso.
Resistencia que aportan las varillas.
R varillas = Resistencia Total de varilla / número de varillas a instalar.
R.Varilla No de Varillas R. Aportacion
20.77Ω / 24.00und = 0.87Ω

67
6to Paso.
Calcular la resistencia del conductor de material cobre, que se instalará en la malla.
El conductor que se utilizara es: 2/0 clase A, sin aislamiento (Desnudo).
Ƥ = resistividad del suelo en Ω / m.
L = longitud del conductor.
A = Área ocupada por la malla, será de 130 metros lineal.
A = (longitud del conductor en m) (diámetro de la varilla de cobre en m) = m2.

A Malla D. Varilla A=
130.00 M x 0.016 M 2.06 M2

Resistencia del conductor = Ƥ / 4 x ( √ π / A+Ƥ/L)


R conductor = 60Ω / 4 x( √ π / 2.06m2+60Ω/130m )=21.14 Ω

Ƥ (Suelo) R.Conductor
60.00Ω / 21.13 M2

7mo Paso.
Cálculo de la red de la malla de tierra.

RT = 1 / (1 / R.Aportacion + 1 / R Conductor) =
RT = 1 / (1 / 0.87 Ω + 1 / 21.13 Ω) = 1.077 Ω

R. Aportacion R.Conductor RT
0.87Ω 21.13 M2 0.83Ω

El resultado del cálculo es muy bueno, es menor de 3 Ω

67
PANEL PRINCIPAL (PP1) DE AIRES ACONDICIONADOS/ IMPRESORAS/INT. TERMOMAGNETICOS DE SUBPANELES (PS1) ,(PS2).
PANEL PRINCIPAL : PP1 BARRAS DE 400 AMP VOLTAJE: 120 /208 4HILOS

ESPACIOS INTERCAMBIABLES: 42 INTERRUPTOR TERMOMAGNETICO PRINCIPAL INTEGRADO :3 X400A

MARCA: CUTLER HAMMER PB424KI400IN BARRAS DE NEUTRO Y TIERRA CONDUCTOR: 6 x 3/0 AWG F, 2 X 3/0 AWG N.

POTENCIA POTENCIA
FASES/AMPS. FASES/AMPS.
N° CONDUITS TIERRA CONDUCTOR BREAKER APARENTE APARENTE BREAKER CONDUCTOR TIERRA CONDUITS N°
DESCRIPCION DESCRIPCION
CKT TIPO
ф TIPO CAL TIPO CAL AMP KVA A B C A B C KVA AMP TIPO CAL TIPO CAL TIPO ф CKT

1 8.6 8.6 2
EQUIPO DE AIRE ACONDICIONADO 220V- PVC PVC EQUIPO DE AIRE ACONDICIONADO
8.6A 18,000 BTU, INVERTER PARA OFICINA CEDULA 3/4" THHN 10 AWG THHN 10 AWG 2x20 2.226 2.226 2x20 THHN 10 AWG THHN 10 AWG CEDULA 3/4" 220V-8.6A 18,000 BTU ,INVERTER PARA
DE PRESIDENTA CORNAP 40 40 OFICINA DE VICEPRESIDENTA CORNAP
3 8.6 8.6 4

5 EQUIPO DE AIRE ACONDICIONADO 220V- 8.6 8.6 EQUIPO DE AIRE ACONDICIONADO 6


PVC PVC
8.6A 18,000 BTU, INVERTER PARA SALA DE CEDULA 3/4" THHN 10 AWG THHN 10 AWG 2x20 2.226 2.226 2x20 THHN 10 AWG THHN 10 AWG CEDULA 3/4" 220V-8.6A 18,000 BTU ,INVERTER PARA
REUNIONES 40 40 TECNOLOGIA INFORMATICA
7 8.6 8.6 8

9 13 13 10
EQUIPO DE AIRE ACONDICIONADO 220V- PVC PVC EQUIPO DE AIRE ACONDICIONADO
13A 24,000 BTU, INVERTER PARA OFICINA CEDULA 3/4" THHN 10 AWG THHN 10 AWG 2x20 3.365 3.365 2x20 THHN 10 AWG THHN 10 AWG CEDULA 3/4" 220V-13A 24,000 BTU INVERTER
DE SECRETARIAS DE PRESIDENCIA 40 40 UNIDAD DE ADQUISICIONES
11 13 13 12

13 EQUIPO DE AIRE ACONDICIONADO 220V- 13 13 EQUIPO DE AIRE ACONDICIONADO 14


PVC PVC
13A 24,000 BTU, INVERTER DIRECCIÓN CEDULA 3/4" THHN 10 AWG THHN 10 AWG 2x20 3.365 3.365 2x20 THHN 10 AWG THHN 10 AWG CEDULA 3/4" 220V-13A 24,000 BTU INVERTER
ADMINISTRATIVA FINANCIERA CNPC 40 40 RECURSOS HUMANOS
15 13 13 16

17 13 13 18
EQUIPO DE AIRE ACONDICIONADO 220V- PVC PVC EQUIPO DE AIRE ACONDICIONADO
13A 24,000 BTU, INVERTER UNIDAD CEDULA 3/4" THHN 10 AWG THHN 10 AWG 2x20 3.365 3.365 2x20 THHN 10 AWG THHN 10 AWG CEDULA 3/4" 220V-13A 24,000 BTU INVERTER
TECNICA DE PROYECTOS 40 40 PLANIFICACIÓN
19 13 13 20

21 EQUIPO DE AIRE ACONDICIONADO 220V- 16.8 16.8 EQUIPO DE AIRE ACONDICIONADO 22


PVC PVC
16.80A 36,000 BTU, INVERTER ASESORIA CEDULA 3/4" THHN 10 AWG THHN 10 AWG 2x30 4.348 4.348 2x30 THHN 10 AWG THHN 10 AWG CEDULA 3/4" 220V-16.80A 36,000 BTU, INVERTER
LEGAL Y LITIGIOS 40 40 RECEPCIÓN
23 16.8 16.8 24

25 16.8 4.8 26
EQUIPO DE AIRE ACONDICIONADO
EQUIPO DE AIRE ACONDICIONADO 220V- PVC PVC
220V-4.80A 9,000 BTU, INVERTER
16.80A 36,000 BTU, INVERTER DIVISIÓN DE CEDULA 3/4" THHN 10 AWG THHN 10 AWG 2x30 4.348 1.242 2x20 THHN 10 AWG THHN 10 AWG CEDULA 3/4"
40 40 SECRETARÍA DE JUNTA GENERAL
27 ADMINISTRACIÓN Y FINANZAS 16.8 4.8 28
CORNAP

PVC PVC
TOMACORRIENTE PARA EL SERVIDOR TOMACORRIENTE 120V-ESPERA DEL
29 CEDULA 3/4" THHN 10 AWG THHN 10 AWG 1x20 1x20 THHN 10 AWG THHN 10AWG CEDULA 3/4" 30
CORNAP 120V-10A SERVIDOR CORNAP NUEVO
40 40
1.765 10 10 1.765
PVC
TOMACORRIENTE PARA EL SERVIDOR CNPC
31 CEDULA 3/4" THHN 10 AWG THHN 10 AWG 1x20 10 32
120V-10A
40 SUPRESOR DE PICOS 208V-3 FASES
1.765
3x20 THHN 12 AWG THHN 12 AWG LT 3/4" SIMILAR A LEVINTON TYPO 2
33 LIBRE MODELO:51120-3 34

35 LIBRE 36

37 38
PVC
INTERRUPTOR TERMOMAGNETICO PRINCIPAL PVC CEDULA INTERRUPTOR TERMOMAGNETICO
39 CEDULA 2" THHN 6 AWG THHN 1/0 AWG 3x150 3x175 THHN 2/0 AWG THHN 4 AWG 40 2" 40
DEL PANEL DE SERVICIO (SP1) PRINCIPAL DEL PANEL DE SERVICIO (SP2)
40
41 42
70 68.2 61.4 48 56.2 61.4

SELECCIÓN DE ALIMENTADORES PRINCIPALES NIVEL 1 Potencia aparente


Potencia Aparente en kva = Potencia Activa en kva / factor de potencia

DESBALANCE DE CARGAS DE USO


CONTINUO Y NO CONTINUO IN S = P/FP
BARRA A 118 1.5 0.85 1.765

BARRA B 124.4
BARRA C 122.8
PROMEDIO 121.73333
DESBALANCE PERMISIBLE 5% 5.26 %

Sumatoria(Ʃ)= (a+b+c)
(a+b+c)
Promedio =
3
(I Mayor - I Menor)
Desbalance % = x 100
Promedio

SC = SNC =ST = FS FP

2.23 KVA ### ### 1.25 0.85

CALCULO DEL ALIMENTADOR PRINCIPAL SEGÚN NEC CALCULO CAIDA DE VOLTAJE


ITC #C A-C FA FT FA V C R√3 L ITC V Scu E%

7.72 A 8 50 A ### 0.96 38.4 0.208 Kv 2 1.732 10.00 M 7.72 A 208 V 8.37 0.15 %

ST = Potencia Aparente Total


SNC = Potencia Aparente uso no Continuo
SC = Potencia Aparente de uso Continuo
IN = Corriente Nominal
FS = Factor de Seguridad (25%)
FD = Factor de Demanda (70%)
ITC = Corriente Total Corregida
# C = Numero del Conductor Asignado
A-C = Ampacidad del Conductor
FA = Factor Agrupamiento
FT = Factor Temperatura
FAC = Factor Ampacidad Coregida
C = Constante
√3 = Raiz de tres (1.732)
L = Longitud del circuito
V = Voltaje
Scu = Seccion transversal del conductor de cobre en mm2
E % = Porcentaje Maximo permisible (3%)

Nota: De acuerdo a indicaciones del Articulo 230 y 210.3 Acometidas y Circuitos Ramales del NEC
( Codigo Nacional Electrico) y CIEN (Codigo de instalaciones Electricas en Nicaragua se instalara un conductor de cobre
Calibre # 8 AWG con una seccion transversal de 8.37 mm2, con una Ampacidad 50 Amperios a 75°C,
Aplicando los Factores de correccion Temperatura y Agrupamiento la Ampacidad del conductor sera de 42.2 Amperios y un Breaker de 3x20
Segun tabla 250-66 del NEC se instalara un conductor de cobre para puesta a tierra calibre # 8 con una Ampacidad de 50 Amperios

PANEL DE TOMACORRIENTES Y LAMPARAS (PS1)


PANEL DE SERVICIO : PS1 BARRAS DE 225 AMP VOLTAJE: 120 /208 5 HILOS

ESPACIOS INTERCAMBIABLES: 42 INTERUPTOR PRINCIPAL: INTEGRADO 3 X 125A

MARCA: CUTLER HAMMER CHP424CC225F BARRAS DE NEUTRO Y TIERRA CONDUCTOR: 3 x 1/0AWG F, 1 X 1/0 AWG N, 1 X 6 AWG P.E

N° CONDUITS TIERRA CONDUCTOR BREAKER S FASES FASES S BREAKER CONDUCTOR TIERRA CONDUITS N°
DESCRIPCION DESCRIPCION
TIPO A B C A B C KVA
CKT ф TIPO CAL TIPO CAL AMP KVA AMP TIPO CAL TIPO CAL TIPO ф CKT

TOMACORRIENTES 120V DE OFICINAS


TOMACORRIENTES 120V DE OFICINAS PVC PVC
ASISTENTE DE VICEPRESIDENCIA Y
1 PRESIDENCIA Y VICEPRESIDENCIA JUNTA CEDULA 1/2 THHN 12 THHN 12 1x20 0.16 8.066 10 0.13 1x20 THHN 12 THHN 12 CEDULA 1/2 2
PRESIDENCIA / DIRECCCIÓN DE ASESORIA
GENERAL CORNAP 40 40
LEGAL Y LITIGIOS

PVC PVC
TOMACORRIENTES 120V DE SALA DE TOMACORRIENTES 120V MICROONDAS
3 CEDULA 1/2 THHN 12 THHN 12 1x20 0.13 8 10 0.09 1x20 THHN 12 THHN 12 CEDULA 1/2 4
REUNIONES CORNAP DEL ÁREA COSINA
40 40

PVC PVC
TOMACORRIENTES 120V DE ASESORIA LEGAL TOMACORRIENTES 120V UNIDAD TÉCNICA
5 CEDULA 1/2 THHN 12 THHN 12 1x20 0.13 8 10 0.13 1x20 THHN 12 THHN 12 CEDULA 1/2 6
Y LITIGIOS DE PROYECTOS
40 40

TOMACORRIENTES 120V DE OFICINA PVC PVC TOMACORRIENTES 120V -REFRIGERADOR


7 SECRETARÍA DE JUNTA GRAL CORNAP / CEDULA 1/2 THHN 12 THHN 12 1x20 0.13 7.433 0.806 0.13 1x20 THHN 12 THHN 12 CEDULA 1/2 OFICINA DE PRESIDENCIA JUNTA 8
RECEPCIÓN / RELOJ CONTROL DE ASISTENCIA 40 40 GENERAL CORNAP

TOMACORRIENTES 120V -CONTADOR


PVC PVC
TOMACORRIENTES 120V CAFETERA 1 DEL GRAL CNPC / DIRECCIÓN
9 CEDULA 1/2 THHN 12 THHN 12 1x20 0.13 9.08 9.6 0.02 1x20 THHN 12 THHN 12 CEDULA 1/2 10
ÁREA COSINA ADMINISTRATIVA FINANCIERA CNPC /
40 40
ASISTENTE ADMINISTRATIVA CNPC

PVC PVC
TOMACORRIENTES 120V CAFETERA 2 DEL RRHH / ASISTENTE CONTABLE CORNAP /
11 CEDULA 1/2 THHN 12 THHN 12 1x20 0.13 9.08 9.6 0.14 1x20 THHN 12 THHN 12 CEDULA 1/2 12
ÁREA COSINA CONTADOR GENERAL CORNAP
40 40
PVC PVC TOMACORRIENTES 120V -REFRIGERADOR
TOMACORRIENTES 120V DE AUDITOR INTERNO
13 CEDULA 1/2 THHN 12 THHN 12 1x20 0.18 6.4 0.806 0.11 1x20 THHN 12 THHN 12 CEDULA 1/2 OFICINA DE VICEPRESIDENCIA JUNTA 14
Y PLANIFICACIÓN
40 40 GENERAL CORNAP

TOMACORRIENTES 120V -DIRECCIÓN


TOMACORRIENTES 120V - DATASHOW,CORTINA PVC PVC
ADMINISTRATIVA FINANCIERA CORNAO /
15 DE PROYECCIÓN Y ACCESSPOINT DE SALA DE CEDULA 1/2 THHN 12 THHN 12 1x20 0.14 7.5 6 0.14 1x20 THHN 12 THHN 12 CEDULA 1/2 16
RESPONSABLE CAJA CHICA / CARTERA Y
REUNIONES CORNAP 40 40
RECUPERACIÓN CORNAP

TOMACORRIENTES 120V -IMPRESORA DE PVC PVC


TOMACORRIENTES 120V -CENTRAL
17 DIRECCIÓN Y ASISTENTE ADMINISTRATIVA CEDULA 1/2 THHN 12 THHN 12 1x20 0.13 5.2 0.567 0.15 1x15 THHN 12 THHN 12 CEDULA 1/2 18
TELEFONICA CORNAP
FINANCIERA CNPC 40 40

PVC PVC
TOMACORRIENTES 120V -REFRIGERADOR DEL TOMACORRIENTES 120V -COMPUTADORA
19 CEDULA 1/2 THHN 12 THHN 12 1x20 3 6 1x20 THHN 12 THHN 12 CEDULA 1/2 20
ÁREA COSINA MASTER DE INFORMÁTICA CORNAP
40 40

PVC PVC
21 CEDULA 1/2 THHN 12 THHN 12 1x20 0.13 12.498 1x20 THHN 12 THHN 12 CEDULA 1/2 22
40 40 VACIO

PVC PVC
23 CEDULA 1/2 THHN 12 THHN 12 1x20 10.5 1x20 THHN 12 THHN 12 CEDULA 1/2 24
40 40

VACIO
PVC PVC
25 CEDULA 1/2 THHN 12 THHN 12 1x20 7.2 12.498 1x20 THHN 12 THHN 12 CEDULA 1/2 26
40 40 VACIO
PVC PVC
27 CEDULA 1/2 THHN 12 THHN 12 1x20 1x20 THHN 12 THHN 12 CEDULA 1/2 28
VACIO 40 40 VACIO
PVC PVC
29 CEDULA 5.2 CEDULA 30
40 40
PVC PVC
31 CEDULA CEDULA 32
40 40
PVC PVC
33 CEDULA CEDULA 34
40 40

35 36

37 38

39 40

41 42
VACIO VACIO

32.099 37.078 37.98 30.11 25.6 20.167

SELECCIÓN DE ALIMENTADORES PRINCIPALES NIVEL 2

SUMA DE BARRAS IN

BARRA A 62.209

BARRA B 62.678

BARRA C 58.147

PROMEDIO 61.0113333

DESBALANCE PERMISIBLE 5% 7.43 %


SC = SNC =ST = FD FS FP

1.51 KVA ### ### 0.7 1.25 0.96

CALCULO DEL ALIMENTADOR PRINCIPAL SEGÚN NEC CALCULO CAIDA DE VOLTAJE


ITC #C A-C FA FT FAC V C R√3 L IN V Scu E%

5.77 A 8 50 A ### 0.96 38.4 0.208 Kv 2 1.732 10.00 M 5.77 A 208 V 8.37 0.11 %

ST = Potencia Aparente Total


SNC = Potencia Aparente uso no Continuo
SC = Potencia Aparente de uso Continuo
IN = Corriente Nominal
FS = Factor de Seguridad (25%)
FD = Factor de Demanda (70%)
ITC = Corriente Total Corregida
# C = Numero del Conductor Asignado
A-C = Ampacidad del Conductor
FA = Factor Agrupamiento
FT = Factor Temperatura
FAC = Factor Ampacidad Coregida
C = Constante
√3 = Raiz de tres (1.732)
L = Longitud del circuito
V = Voltaje
Scu = Seccion transversal del conductor de cobre en mm2
E % = Porcentaje Maximo permisible (3%)

Nota: De acuerdo a indicaciones del Articulo 230 y 210.3 Acometidas y Circuitos Ramales del NEC ( Codigo Nacional Electrico)
y CIEN (Codigo de instalaciones Electricas en Nicaragua se instalara un conductor de cobre Calibre # 8 AWG con una seccion
transversal de 8.37 mm2, con una Ampacidad 50 Amperios a 75°C, Aplicando los Factores de correccion Temperatura y Agrupamiento
la Ampacidad del conductor sera de 38.4 amperios y un Breaker de 3x15

PANEL DE SERVICIO (PS2)

PANEL DE SERVICIO : PLN3 BARRAS DE 200 AMP VOLTAJE: 120 /208 5 HILOS

ESPACIOS INTERCAMBIABLES: 30 INTERUPTOR PRINCIPAL: INTEGRADO 3 X 15 DUCTO METALICO 8"X6"

MARCA: CUTLER HAMMER EMPOTRABLE BARRAS DE NEUTRO Y TIERRA CONDUCTOR: 3 x 8 F, 1 X 8 N, 1 X 8 P.E

N° CONDUITS TIERRA CONDUCTOR BREAKER S FASES FASES S BREAKER CONDUCTOR TIERRA CONDUITS N°
DESCRIPCION DESCRIPCION
DESCRIPCION DESCRIPCION
CKT TIPO
ф TIPO CAL TIPO CAL AMP /POLOS KVA A B C A B C KVA AMP /POLOS TIPO CAL TIPO CAL TIPO ф CKT

1 Pasillo 1 PVC 1/2 THHN 12 THHN 12 1x15 0.08 0.63 6.12 0.73 1x15 THHN 12 XHHW 12 PVC 1/2 Sala de Hemodinamia 2

3 Filtro, Area Sucia, Cuarto de Aseo, Arsenal PVC 1/2 THHN 12 THHN 12 1x15 0.18 1.46 0.21 0.03 1x15 THHN 12 THHN 12 PVC 1/2 Luminaria Salidas de Emergencia 4

5 Gymnasio, SS 1 PVC 1/2 THHN 12 THHN 12 1x15 0.2 1.67 2.5 0.3 1x15 THHN 12 THHN 12 PVC 1/2 Transfer, Filtro, Cuarto de Control, Pasillo 3, 6
Camilla

7 Sueño+Video+EEG, SS 7, Cabecera de cama, PVC 1/2 THHN 12 THHN 12 1x15 0.48 4.48 VACIO 8
Neurologia Pediatrica, Cabecera de cama, SS 6,
Vestidor de Hombres, SS 8, Vestidor de Mujeres, SS 7

9 Clinica 2, SS 3, Cabecera de cama, Clinica 1, SS 2, PVC 1/2 THHN 12 THHN 12 1x15 0.28 3.02 2.97 0.28 1x15 THHN 12 THHN 12 PVC 1/2 Cuarto de Equipos, Recuperacion, cabecera de 10
Cabecera de cama cama

11 PVC 1/2 THHN 12 THHN 12 1x15 0.34 2.81 1.3 0.16 1x15 THHN 12 THHN 12 PVC 1/2 12
Vestibulo, Bodega de Direccion, Escalera, Azotea,
Bodega, SS 5, Direccion, Secretaria de Direccion, SS 4 Bodega Mantenimiento y Limpieza

13 VACIO 14

15 Voz Datos, Cuarto Electrico, Pasillo, SS Pacientes PVC 1/2 THHN 12 THHN 12 1x15 0.23 1.88 1.77 0.21 1x15 THHN 12 THHN 12 PVC 1/2 Anestecia, Estacion de Enfermeria, Bodega, SS 10 16
Mujeres, SS Pacientes Varones

17 Caja, Admision, Estacion de Enfermeria, SS 10, Bodega PVC 1/2 THHN 12 THHN 12 1x15 0.21 1.77 1.46 0.18 1x15 THHN 12 THHN 12 PVC 1/2 Sala de Espera 1, Pasillo 2 18
de Enfermeria

19 20
VACIO

21 22
VACIO

23 24
VACIO

25 26
VACIO

27 28
VACIO

29 30
VACIO

5.11 6.36 6.25 6.12 4.95 5.26

SELECCIÓN DE ALIMENTADORES PRINCIPALES NIVEL 3

SUMA DE BARRAS IN

BARRA A 11.23

BARRA B 11.31

BARRA C 11.51

PROMEDIO 11.35

DESBALANCE PERMISIBLE 5% 2.47 %

SC = SNC =ST = FD FS FP

1.80 KVA ### ### 0.7 1.25 0.96


CALCULO DEL ALIMENTADOR PRINCIPAL SEGÚN NEC CALCULO CAIDA DE VOLTAJE
ITC #C A-C FA FT FAC V C R√3 L IN V Scu E%

8.81 A 8 50 A ### 0.96 38.4 0.208 Kv 2 1.732 10.00 M 8.81 A 208 V 8.37 0.18 %

ST = Potencia Aparente Total


SNC = Potencia Aparente uso no Continuo
SC = Potencia Aparente de uso Continuo
IN = Corriente Nominal
FS = Factor de Seguridad (25%)
FD = Factor de Demanda (70%)
ITC = Corriente Total Corregida
# C = Numero del Conductor Asignado
A-C = Ampacidad del Conductor
FA = Factor Agrupamiento
FT = Factor Temperatura
FAC = Factor Ampacidad Coregida
C = Constante
√3 = Raiz de tres (1.732)
L = Longitud del circuito
V = Voltaje
Scu = Seccion transversal del conductor de cobre en mm2
E % = Porcentaje Maximo permisible (3%)

Nota: De acuerdo a indicaciones del Articulo 230 y 210.3 Acometidas y Circuitos Ramales del NEC ( Codigo Nacional Electrico)
y CIEN (Codigo de instalaciones Electricas en Nicaragua se instalara un conductor de cobre Calibre # 8 AWG con una seccion
transversal de 8.37 mm2, con una Ampacidad 50 Amperios a 75°C, Aplicando los Factores de correccion Temperatura y
Agrupamiento la Ampacidad del conductor sera de 38.4 amperios y un Breaker de 3x15

BALANCE PANELES DE TOMA CORRIENTES


PANEL TOMA CORRIENTE NIVEL 1 (PTN1)

PANEL DE SERVICIO : PTN1 BARRAS DE 200 AMP VOLTAJE: 120 /208 5 HILOS

ESPACIOS INTERCAMBIABLES: 42 INTERUPTOR PRINCIPAL: INTEGRADO 3 X 100 DUCTO METALICO 8"X6"

MARCA: CUTLER HAMMER EMPOTRABLE BARRAS DE NEUTRO Y TIERRA CONDUCTOR: 3 x 2 F, 1 X 2 N, 1 X 2 P.E

N° CONDUITS TIERRA CONDUCTOR BREAKER S FASES FASES S BREAKER CONDUCTOR TIERRA CONDUITS N°
DESCRIPCION DESCRIPCION
CKT TIPO
ф TIPO CAL TIPO CAL AMP /POLOS KVA A B C A B C KVA AMP /POLOS TIPO CAL TIPO CAL TIPO ф CKT

3.75 5.63 2
1 Toma corriente camilla Area de Procedimiento y
PVC 1/2 THHN 10 THHN 10 2X15 0.9 1.35 2x20 THHN 10 THHN 10 PVC 1/2 Toma corriente camilla Observacion
Choque
3 3.75 5.63 4

Toma corriente Cabecero de Cama Area de


5 PVC 1/2 THHN 10 THHN 10 1X20 1.13 9.38 9.38 1.13 1X20 THHN 10 THHN 10 PVC 1/2 Toma Corriente Clinica 1, Clinica 2 6
Procedimiento y Choque

Toma Corriente Estacion de enfermeria, Bodega y


7 PVC 1/2 THHN 10 THHN 10 1X20 1.31 9.38 9.38 1.13 1X20 THHN 10 THHN 10 PVC 1/2 Toma corriente Cabecero de Cama Observacion 8
Cuarto Sucio

Toma Corriente Vestidor de Mujeres, Vestidor de


9 PVC 1/2 THHN 10 THHN 10 1X20 1.5 9.38 11.25 10
Varones
2.7 1x20 THHN 10 THHN 10 PVC 1/2 Toma corriente camilla Recuperacion

11 Toma Corriente Estacion de enfermeria, Bodega MRP PVC 1/2 THHN 10 THHN 10 1X20 0.94 7.81 11.25 12

13 Toma Corriente Sala de espera PVC 1/2 THHN 10 THHN 10 1X20 1.13 9.38 13.89 14
3.33 2X20 THHN 10 THHN 10 PVC 1/2 Ducha SS 5
15 PVC 1/2 THHN 10 THHN 10 1X20 0.75 6.25 13.89 16
Toma Corriente Observacion

17 13.89 13.89 18
Ducha S.S. Pacientes 1 PVC 1/2 THHN 10 THHN 10 2x20 3.33 3.33 2X20 THHN 10 THHN 10 PVC 1/2 Ducha S/S 2
19 13.89 13.89 20

21 13.89 13.89 22
Ducha S/S 1 PVC 1/2 THHN 10 THHN 10 2x20 3.33 3.33 2X20 THHN 10 THHN 10 PVC 1/2 Ducha S/S 3
23 13.89 13.89 24

Toma Corriente Desfibrilador Area de Procedimiento y


25 PVC 1/2 THHN 10 THHN 10 1x20 0.94 7.81 6.25 0.75 1X20 THHN 10 THHN 10 PVC 1/2 Toma Corriente Anestecia 26
Choque

Toma Corriente vestibulo, Sala de espera, Pasillo


27 13.89 9.38 1.13 1X20 THHN 10 THHN 10 PVC 1/2 28
1, Pasillo 2
Ducha S.S. Pacientes 2 PVC 1/2 THHN 10 THHN 10 2x20 3.33
29 13.89 6.25 0.75 1X20 THHN 10 THHN 10 PVC 1/2 30
Toma Corriente Cuarto Sucio, Arsenal y pasillo
Toma Corriente Evaporador sala de Espera, Clinica 1,
31 Clinica 2, Observacion, Pasillo, Estacion de Enfermeria, 12.15 6.25 0.75 1X20 THHN 10 THHN 10 PVC 1/2 Toma Corriente Cuarto Electrico, Voz y Datos 32
Sala de Espera, Voz y Datos, Cuarto de Maquinas, Area
PVC 1/2 THHN 10 THHN 12 2x20 2.92
de Procedimiento y Choque, Vestidor de Mujeres,
Vestidor de Varones, Anestecia, Pasillo interno 1 y 2, Toma Corriente Pasillo Externo Costado Oeste y
33 12.15 9.38 1.12 1X20 THHN 10 THHN 10 PVC 1/2 34
Estacion de Enfermeria y Recuperacion Norte, Pasillo 3

35 Toma corriente Cabecero de Cama Recuperacion PVC 1/2 THHN 10 THHN 10 1X20 1.13 9.38 4.69 0.56 1X20 THHN 10 THHN 10 PVC 1/2 Toma Corriente Procedimiento y choque 36

37 Toma corriente Cabecero de Cama Recuperacion PVC 1/2 THHN 10 THHN 10 1X20 1.13 9.38 9.38 1.13 1X20 THHN 10 THHN 10 PVC 1/2 Toma corriente Cabecero de Cama Recuperacion 38

39 Toma corriente Cabecero de Cama Observacion PVC 1/2 THHN 10 THHN 10 1X20 0.56 4.69 3.13 0.38 1X20 THHN 10 THHN 10 PVC 1/2 Toma corriente Cuarto de Maquinas 40

41 Toma Corriente Oasis Sala de espera PVC 1/2 THHN 10 THHN 10 1X20 0.53 4.43 42

65.74 64 72.67 64.67 66.55 59.35


SELECCIÓN DE ALIMENTADOR ELECTRICO PRINCIPAL CENTRO DE CARGA DE TOMACORRIENTE (PTN1)

SUMA DE BARRAS IN

BARRA A 130.41

BARRA B 130.55

BARRA C 132.02

PROMEDIO 130.993333

DESBALANCE PERMISIBLE 5% 1.23 %

SC = SNC =ST = FD FS FP

4.52 KVA ### ### 0.7 1.25 0.96

CALCULO DEL ALIMENTADOR PRINCIPAL SEGÚN NEC CALCULO CAIDA DE VOLTAJE

ITC #C A-C FA FT FAC V C R√3 L IN V Scu E%

95.88 A 2 130 A ### 0.96 99.84 0.208 Kv 2 1.732 10.00 M 95.88 A 208 V 33.63 0.47 %

ST = Potencia Aparente Total


SNC = Potencia Aparente uso no Continuo
SC = Potencia Aparente de uso Continuo
IN = Corriente Nominal
FS = Factor de Seguridad (25%)
FD = Factor de Demanda (70%)
ITC = Corriente Total Corregida
# C = Numero del Conductor Asignado
A-C = Ampacidad del Conductor
FA = Factor Agrupamiento
FT = Factor Temperatura
FAC = Factor Ampacidad Coregida
C = Constante
√3 = Raiz de tres (1.732)

L = Longitud del circuito


V = Voltaje
Scu = Seccion transversal del conductor de cobre en mm2
E % = Porcentaje Maximo permisible (3%)

Nota: De acuerdo a indicaciones del Articulo 230 y 210.3 Acometidas y Circuitos Ramales del NEC ( Codigo Nacional Electrico) y
CIEN (Codigo de instalaciones Electricas en Nicaragua se instalara un conductor de cobre Calibre # 2 AWG con una seccion
transversal de 33.63 mm2, con una Ampacidad 130 Amperios a 90°C, Aplicando los Factores de correccion Temperatura y Agrupamiento
la Ampacidad del conductor sera de 99.8 amperios y un Breaker de 3x100
PANEL TRANSFORMADORES DE AISLAMIENTO NIVEL 1 (PTAN1)

PANEL DE SERVICIO : PTAN1 BARRAS DE 200 AMP VOLTAJE: 120 /208 5 HILOS

ESPACIOS INTERCAMBIABLES: 30 INTERUPTOR PRINCIPAL: INTEGRADO 3 X 100 DUCTO METALICO 8"X6"

MARCA: CUTLER HAMMER EMPOTRABLE BARRAS DE NEUTRO Y TIERRA CONDUCTOR: 3 x 2 F, 1 X 2 N, 1 X 2 P.E

FASES FASES S
N° CONDUITS TIERRA CONDUCTOR BREAKER S BREAKER CONDUCTOR TIERRA CONDUITS N°
DESCRIPCION DESCRIPCION
TIPO A B C A B C KVA
CKT ф TIPO CAL TIPO CAL AMP /POLOS KVA AMP /POLOS TIPO CAL TIPO CAL TIPO ф CKT
10.16 10.16 2
1 INYECTOR CUE-099-VG-1/4 - C-1/8 Quirofano
Extractor de Aire CUE-900 Quirofano 1Y2 (EAQ1Y2) PVC 1/2 THHN 10 THHN 10 2x20 2.12 2.12 2x20 THHN 10 THHN 10 PVC 1/2
1Y 2 (IAQ1Y2)
3 10.16 10.16 4

5 Panel Tierra Aislada Quirofano 1 (PTAQ1) EMT 1 1/2 THHN 2 THHN 2 1X50 4.69 39.06 39.06 4.69 1X50 THHN 2 THHN 2 EMT 1 1/2 Panel Tierra Aislada Quirofano 2 6

7 10.16 10.16 8
INYECTOR CUE-099-VG-1/4 - C-1/8 Quirofano
Extractor de Aire CUE-900 Quirofano 3Y 4 (EAQ3Y4) PVC 1/2 THHN 10 THHN 10 2x20 2.12 2.12 2x20 THHN 10 THHN 10 PVC 1/2
3 Y 4 (IAQ3Y4)
9 10.16 10.16 10

11 11.02 12
Toma Corriente Arco en C Quirofano 1 EMT 3/4 XHHW 10 XHHW 10 2x20 2.29
13 11.02 39.06 4.69 1X50 THHN 2 THHN 2 EMT 1 1/2 Panel Tierra Aislada Quirofano 3 14

15 Toma corriente Area de Condensadoras PVC 1/2 THHN 10 THHN 10 1X20 0.78 6.51 39.06 4.69 1X50 THHN 2 THHN 2 EMT 1 1/2 Panel Tierra Aislada Quirofano 4 16

17 11.02 18
2.29 2X20 XHHW 10 XHHW 10 EMT 3/4 Toma Corriente Arco en C Quirofano 3
19 11.02 20

21 11.02 VACIO 22
Toma Corriente Arco en C Quirofano 2 EMT 3/4 XHHW 10 XHHW 10 2X20 2.29
23 11.02 VACIO 24

25 11.02 VACIO 26
Toma Corriente Arco en C Quirofano 4 EMT 3/4 XHHW 10 XHHW 10 2X20 2.29
27 11.02 VACIO 28

29 VACIO VACIO 30

42.36 48.87 61.1 70.4 59.38 50.08

SELECCIÓN DE ALIMENTADOR ELECTRICO PRINCIPAL CENTRO DE CARGA DE TOMACORRIENTE (PTAN1)

SUMA DE BARRAS IN

BARRA A 112.76

BARRA B 108.25

BARRA C 111.18

PROMEDIO 110.73

DESBALANCE PERMISIBLE 5% 4.07 %


SC = SNC =ST = FD FS FP

5.94 KVA ### ### 0.7 1.25 0.96

CALCULO DEL ALIMENTADOR PRINCIPAL SEGÚN NEC CALCULO CAIDA DE VOLTAJE

ITC #C A-C FA FT FAC V C R√3 L IN V Scu E%

76.36 A 2 130 A ### 0.96 99.84 0.208 Kv 2 1.732 10.00 M 76.36 A 208 V 33.63 0.38 %

ST = Potencia Aparente Total


SNC = Potencia Aparente uso no Continuo
SC = Potencia Aparente de uso Continuo
IN = Corriente Nominal
FS = Factor de Seguridad (25%)
FD = Factor de Demanda (70%)
ITC = Corriente Total Corregida
# C = Numero del Conductor Asignado
A-C = Ampacidad del Conductor
FA = Factor Agrupamiento
FT = Factor Temperatura
FAC = Factor Ampacidad Coregida
C = Constante
√3 = Raiz de tres (1.732)

L = Longitud del circuito


V = Voltaje
Scu = Seccion transversal del conductor de cobre en mm2
E % = Porcentaje Maximo permisible (3%)

Nota: De acuerdo a indicaciones del Articulo 230 y 210.3 Acometidas y Circuitos Ramales del NEC ( Codigo Nacional Electrico) y
CIEN (Codigo de instalaciones Electricas en Nicaragua se instalara un conductor de cobre Calibre # 2 AWG con una seccion
transversal de 33.63 mm2, con una Ampacidad 130 Amperios a 90°C, Aplicando los Factores de correccion Temperatura y
Agrupamiento la Ampacidad del conductor sera de 99.8 amperios y un Main de 3x100
PANEL TOMA CORRIENTE NIVEL 2 (PTN2)

PANEL DE SERVICIO : PT2N BARRAS DE 200 AMP VOLTAJE: 120 /208 5 HILOS

ESPACIOS INTERCAMBIABLES: 30 INTERUPTOR PRINCIPAL: INTEGRADO 3 X 70 DUCTO METALICO 8"X6"

MARCA: CUTLER HAMMER EMPOTRABLE BARRAS DE NEUTRO Y TIERRA CONDUCTOR: 3 x 4 F, 1 X 4 N, 1 X 4 P.E

N° CONDUITS TIERRA CONDUCTOR BREAKER S FASES FASES S BREAKER CONDUCTOR TIERRA CONDUITS N°
DESCRIPCION DESCRIPCION
CKT TIPO
ф TIPO CAL TIPO CAL AMP /POLOS KVA A B C A B C KVA AMP /POLOS TIPO CAL TIPO CAL TIPO ф CKT

1 Toma Corriente Dormitorio 1 PVC 1/2 THHN 10 THHN 10 1x20 1.13 9.38 9.38 1.13 1x20 THHN 10 THHN 10 PVC 1/2 Toma Corriente Dormitorio 3 2

3 Toma corriente Cabecera de Cama Cuarto 3, cuarto 4 PVC 1/2 THHN 10 THHN 10 1x20 1.2 10 10 1.2 1x20 THHN 10 THHN 10 PVC 1/2 4
T. corriente Cabecera de Cama Cuarto 1, cuarto 2

5 Toma Corriente Dormitorio 2 PVC 1/2 THHN 10 THHN 10 1x20 1.13 9.38 9.38 1.13 1x20 THHN 10 THHN 10 PVC 1/2 Toma Corriente Dormitorio 4 6

7 Toma Corriente Dormitorio 5 PVC 1/2 THHN 10 THHN 10 1x20 1.13 9.38 9.38 1.13 1x20 THHN 10 THHN 10 PVC 1/2 Toma Corriente Dormitorio 7 8

Toma corriente Cabecera de Cama Cuarto 7,


9 PVC 1/2 THHN 10 THHN 10 1x20 1.2 10 10 1.2 1x20 THHN 12 THHN 12 PVC 1/2 10
Toma corriente Cabecera de Cama Cuarto 5, cuarto 6 cuarto 8

11 Toma Corriente Dormitorio 6 PVC 1/2 THHN 10 THHN 10 1x20 1.13 9.38 9.38 1.13 1x20 THHN 10 THHN 10 PVC 1/2 Toma Corriente Dormitorio 8 12

13 PVC 1/2 THHN 10 THHN 10 1x20 1.31 9.38 9.38 1.13 1x20 THHN 10 THHN 10 PVC 1/2 Toma Corriente Dormitorio 11 Aislado 14
Toma Corriente Pasillo 1, Vestibulo

15 PVC 1/2 THHN 10 THHN 10 1x20 1.2 10 7.81 1.13 1x20 THHN 10 THHN 10 PVC 1/2 Toma Corriente Dormitorio 10 16
Toma corriente Cabecera de Cama Cuarto 9, cuarto 10

17 Toma Corriente Dormitorio 12 PVC 1/2 THHN 10 THHN 10 1x20 1.13 9.38 9.38 1.13 1x20 THHN 10 THHN 10 PVC 1/2 Toma Corriente Dormitorio 9 18

19 PVC 1/2 THHN 12 THHN 12 1x20 0.75 7.81 9.38 1.13 1x20 THHN 10 THHN 10 PVC 1/2 20
Toma Corriente Cuarto Electrico, Voz y Datos Toma Corriente Dormitorio 13

21 PVC 1/2 THHN 10 THHN 10 1X20 0.6 5 10 1.2 1x20 THHN 10 THHN 10 PVC 1/2 Toma corriente Cabecera de Cama Cuarto 12, 22
Toma corriente Cabecera de Cama Cuarto 11 cuarto 13

23 9.38 1.31 1x20 THHN 10 THHN 10 PVC 1/2 24


Toma Corriente Estacion de Enfermeria, Bodega
VACIO de Enfermeria, S.S. Enfermeria y Area Sucia

25 PVC 1/2 THHN 10 THHN 10 1X20 0.56 4.69 26


Toma Corriente Sub estacion de Enfermeria VACIO

27 7.81 0.94 1x20 THHN 10 THHN 10 PVC 1/2 Toma Corriente Pasillo 2, Repetidor de llamado 28
VACIO de Emergencia
Toma Corriente Oasis sub Estacion de
29 PVC 1/2 THHN 10 THHN 10 1X20 0.89 7.38 7.38 0.89 1x20 THHN 12 THHN 12 PVC 1/2 30
Toma Corriente Oasis de Estacion de Enfermeria Enfermeria

40.64 35 35.52 37.52 45.62 44.9

SELECCIÓN DE ALIMENTADOR ELECTRICO PRINCIPAL CENTRO DE CARGA DE TOMACORRIENTE (PTN2)

SUMA DE BARRAS IN
BARRA A 78.16
BARRA B 80.62
BARRA C 80.42
PROMEDIO 79.733333
DESBALANCE PERMISIBLE 5% 3.09 %

SC = SNC =ST = FD FS FP

3.21 KVA ### ### 0.7 1.25 0.96

CALCULO DEL ALIMENTADOR PRINCIPAL SEGÚN NEC CALCULO CAIDA DE VOLTAJE


ITC #C A-C FA FT FAC V C R√3 L IN V Scu E%

58.85 A 4 95 A ### 0.96 72.96 0.208 Kv 2 1.732 10.00 M 58.85 A 208 V 21.15 0.46 %

ST = Potencia Aparente Total


SNC = Potencia Aparente uso no Continuo
SC = Potencia Aparente de uso Continuo
IN = Corriente Nominal
FS = Factor de Seguridad (25%)
FD = Factor de Demanda (70%)
ITC = Corriente Total Corregida
# C = Numero del Conductor Asignado
A-C = Ampacidad del Conductor
FA = Factor Agrupamiento
FT = Factor Temperatura
FAC = Factor Ampacidad Coregida
C = Constante
√3 = Raiz de tres (1.732)
L = Longitud del circuito
V = Voltaje
Scu = Seccion transversal del conductor de cobre en mm2
E % = Porcentaje Maximo permisible (3%)

Nota: De acuerdo a indicaciones del Articulo 230 y 210.3 Acometidas y Circuitos Ramales del NEC ( Codigo Nacional Electrico) y
CIEN (Codigo de instalaciones Electricas en Nicaragua se instalara un conductor de cobre Calibre # 4 AWG con una seccion
transversal de 21.15 mm2, con una Ampacidad 95 Amperios a 90°C,Aplicando los Factores de correccion Temperatura y
Agrupamiento la Ampacidad del conductor sera de 73 amperios y un Breaker de 3x70
PANEL TOMACORIENTES (T2) NIVEL 2 (PT2N2)

PANEL DE SERVICIO : PT2N2 BARRAS DE 200 AMP VOLTAJE: 120 /208 5 HILOS

ESPACIOS INTERCAMBIABLES: 42 INTERUPTOR PRINCIPAL: INTEGRADO 3 X 125 DUCTO METALICO 8"X6"

MARCA: CUTLER HAMMER EMPOTRABLE BARRAS DE NEUTRO Y TIERRA CONDUCTOR: 3 x 1/0 F, 1 X 1/0 N, 1 X 1/0 P.E

N° CONDUITS TIERRA CONDUCTOR BREAKER S FASES FASES S BREAKER CONDUCTOR TIERRA CONDUITS N°
DESCRIPCION DESCRIPCION
CKT TIPO
ф TIPO CAL TIPO CAL AMP /POLOS KVA A B C A B C KVA AMP /POLOS TIPO CAL TIPO CAL TIPO ф CKT

13.89 13.89 2
1 Ducha Dormitorio 1 PVC 1/2 THHN 10 THHN 10 2x20 3.33 3.33 2x20 THHN 10 THHN 10 PVC 1/2 Ducha Dormitorio 4
3 13.89 13.89 4

5 7.5 6
Toma corriente camilla Dormitorio 1, Dormitorio
1.8 2x20 THHN 10 THHN 10 PVC 1/2
2, Dormitorio 3, Dormitorio 4
7 13.89 7.5 8
Ducha Dormitorio 3 PVC 1/2 THHN 10 THHN 10 2x20 3.33
9 13.89 10

11 13.89 13.89 12
Ducha Dormitorio 5 PVC 1/2 THHN 10 THHN 10 2x20 3.33 3.33 2x20 THHN 10 THHN 10 PVC 1/2 Ducha Dormitorio 6
13 13.89 13.89 14

15 13.89 13.89 16
Ducha Dormitorio 7 PVC 1/2 THHN 10 THHN 10 2x20 3.33 3.33 2x20 THHN 10 THHN 10 PVC 1/2 Ducha Dormitorio 8
17 13.89 13.89 18

19 13.89 13.89 20
Ducha Dormitorio 9 PVC 1/2 THHN 10 THHN 10 2x20 3.33 3.33 2x20 THHN 10 THHN 10 PVC 1/2 Ducha Dormitorio 10
21 13.89 13.89 22

23 13.89 13.89 24
Ducha Dormitorio 11 PVC 1/2 THHN 10 THHN 10 2x20 3.33 3.33 2x20 THHN 10 THHN 10 PVC 1/2 Ducha Dormitorio 12
25 13.89 13.89 26

27 13.89 13.89 28
Ducha Dormitorio 13 PVC 1/2 THHN 10 THHN 10 2x20 3.33 3.33 2x20 THHN 10 THHN 10 PVC 1/2 Ducha SS Enfermeria
29 13.89 13.89 30

31 1.95 32
Evaporador Cuarto 1, 2, 7, 8, 11 PVC 1/2 THHN 12 THHN 12 2x15 0.47
33 1.95 34
35 9.38 3.91 36
Evaporador Cuarto 5, 6, 12, 13, Estacion de
Toma corriente camilla Dormitorio 7, Dormitorio 8,
PVC 1/2 THHN 10 THHN 10 2x20 2.25 0.94 2x20 THHN 12 THHN 12 PVC 1/2 Enfermeria, 3, 4, 9, 10, Sub Estacion de
Dormitorio 9, Dormitorio 10, Dormitorio 11
Enfermeria
37 9.38 3.91 38

39 7.5 13.89 40
Toma corriente camilla Dormitorio 5, Dormitorio 6,
PVC 1/2 THHN 10 THHN 10 2x20 1.8 3.33 2x20 THHN 10 THHN 10 PVC 1/2 Ducha Dormitorio 2
Dormitorio 12, Dormitorio 13
41 7.5 13.89 42

80.78 78.9 72.44 66.97 69.45 80.86

SELECCIÓN DE ALIMENTADOR ELECTRICO PRINCIPAL CENTRO DE CARGA DE TOMACORRIENTE (PT2N2)

SUMA DE BARRAS IN

BARRA A 147.75

BARRA B 148.35

BARRA C 153.3

PROMEDIO 149.8

DESBALANCE PERMISIBLE 5% 3.70 %

SC = SNC =ST = FD FS FP

0.99 KVA ### ### 0.7 1.25 0.96

CALCULO DEL ALIMENTADOR PRINCIPAL SEGÚN NEC CALCULO CAIDA DE VOLTAJE


ITC #C A-C FA FT FAC V C R√3 L IN V Scu E%

105.38 A 1/0 170 A ### 0.96 130.56 0.208 Kv 2 1.732 10.00 M 105.38 A 208 V 53.51 0.33 %

ST = Potencia Aparente Total


SNC = Potencia Aparente uso no Continuo
SC = Potencia Aparente de uso Continuo
IN = Corriente Nominal
FS = Factor de Seguridad (25%)
FD = Factor de Demanda (70%)
ITC = Corriente Total Corregida
# C = Numero del Conductor Asignado
A-C = Ampacidad del Conductor
FA = Factor Agrupamiento
FT = Factor Temperatura
FAC = Factor Ampacidad Coregida
C = Constante
√3 = Raiz de tres (1.732)

L = Longitud del circuito


V = Voltaje
Scu = Seccion transversal del conductor de cobre en mm2
E % = Porcentaje Maximo permisible (3%)

Nota: De acuerdo a indicaciones del Articulo 230 y 210.3 Acometidas y Circuitos Ramales del NEC ( Codigo Nacional Electrico) y
CIEN (Codigo de instalaciones Electricas en Nicaragua se instalara un conductor de cobre Calibre # 1/0 AWG con una seccion
transversal de 53.51 mm2, con una Ampacidad 170 Amperios a 90°C, Aplicando los Factores de correccion Temperatura y
Agrupamiento la Ampacidad del conductor sera de 131 amperios y un Main de 3x125

BALANCE DE PANELES DE TOMA CORRIENTES NIVEL 3

PANEL TOMA CORRIENTE (PTN3)

PANEL DE SERVICIO : PTN3 BARRAS DE 200 AMP VOLTAJE: 120 /208 5 HILOS

ESPACIOS INTERCAMBIABLES: 42 INTERUPTOR PRINCIPAL: INTEGRADO 3 X 50 DUCTO METALICO 8"X6"

MARCA: CUTLER HAMMER EMPOTRABLE BARRAS DE NEUTRO Y TIERRA CONDUCTOR: 3 x 6 F, 1 X 6 N, 1 X 6 P.E

N° CONDUITS TIERRA CONDUCTOR BREAKER S FASES FASES S BREAKER CONDUCTOR TIERRA CONDUITS N°
DESCRIPCION DESCRIPCION
CKT TIPO
ф TIPO CAL TIPO CAL AMP /POLOS KVA A B C A B C KVA AMP /POLOS TIPO CAL TIPO CAL TIPO ф CKT

Toma Corriente Neurologia Pediatrica PVC 1/2 THHN 10 THHN 10 1X20 0.75 6.25 4.69 0.56 1X20 THHN 10 THHN 10 1/2 T. Corriente Clinica 2 2
1 PVC

3 Toma Corriente Gymnacio PVC 1/2 THHN 10 THHN 10 1X20 1.13 9.38 7.81 0.94 1X20 THHN 10 THHN 10 PVC 1/2 Toma Corriente Direccion 4

T. Corriente Sala de Espera 1 y TV sala de Espera


5 Toma Corriente Secretaria de Direccion PVC 1/2 THHN 10 THHN 10 1X20 0.94 7.81 6.25 0.75 1X20 THHN 10 THHN 10 PVC 1/2 6
1

T. Corriente Vestidor de Mujeres, Vestidor de


7 T. Corriente Direccion PVC 1/2 THHN 10 THHN 10 1X20 0.75 6.25 9.38 1.13 1X20 THHN 10 THHN 10 PVC 1/2 8
hombres

9 PVC 1/2 THHN 10 THHN 10 1X20 0.56 4.69 9.38 1.31 1X20 THHN 10 THHN 10 PVC 1/2 T. Corriente Estacion de enfermeria y Admision 10
T. Corriente Cabecero de Cama Recuperacion
11 T. Corriente Pasillo 1 PVC 1/2 THHN 10 THHN 10 1X20 0.56 4.69 6.25 0.75 1X20 THHN 10 THHN 10 PVC 1/2 T. Corriente Sueño + Video + EEG 12

13 PVC 1/2 THHN 10 THHN 10 1X20 0.75 6.25 6.25 0.75 1X20 THHN 10 THHN 10 PVC 1/2 14
Toma Corriente Bodega de Direccion, Bodega de Mtto y
Vestibulo T. Corriente Cuarto Electrico, Voz y Datos

15 VACIO 6.25 0.75 1X20 THHN 10 THHN 10 PVC 1/2 T. Corriente Cuarto de Control 16

17 T. Corriente Caja PVC 1/2 THHN 10 THHN 10 1X20 0.94 7.81 6.25 0.75 1X20 THHN 10 THHN 10 PVC 1/2 T. Corriente Estacion de enfermeria 18

Toma Corriente Motor de Pantalla electrica


19 T. Corriente Camilla Sueño + Video + EEG PVC 1/2 THHN 10 THHN 10 1X20 0.19 3.13 1.56 0.19 1X20 THHN 10 THHN 10 PVC 1/2 20
Direccion

21 VACIO 6.25 0.75 1X20 THHN 10 THHN 10 PVC 1/2 T. Corriente Area Sucia y Arsenal 22

23 T. Corriente Cuarto de Control PVC 1/2 THHN 10 THHN 10 1X20 0.75 6.25 6.25 0.75 1X20 THHN 10 THHN 10 PVC 1/2 T. Corriente Cuarto de Control 24

25 T. Corriente Clinica 1 PVC 1/2 THHN 10 THHN 10 1X20 0.75 6.25 4.69 0.56 1X20 THHN 10 THHN 10 PVC 1/2 T. Corriente Bodega, Anestecia 26

27 T. Corriente Cabecero de Cama Recuperacion PVC 1/2 THHN 10 THHN 10 1X20 1.13 9.38 3.13 0.38 1X20 THHN 10 THHN 10 PVC 1/2 28
Toma Corriente Camilla Clinica 1 y Clinica 2

29 T. Corriente Cuarto de Control PVC 1/2 THHN 10 THHN 10 1X20 0.75 6.25 30
VACIO

31 T. Corriente Cabecero Clinica 2, Sueño + Video + EEG PVC 1/2 THHN 10 THHN 10 1X20 0.38 3.13 32
VACIO

33 VACIO 34
VACIO

35 VACIO 36
VACIO

37 VACIO 38
VACIO

39 VACIO 40
VACIO

41 VACIO 42
VACIO

31.26 23.45 32.81 26.57 32.82 25

SELECCIÓN DE ALIMENTADOR ELECTRICO PRINCIPAL CENTRO DE CARGA DE TOMACORRIENTE (PTN3)

SUMA DE BARRAS IN
BARRA A 57.83
BARRA B 56.27
BARRA C 57.81
PROMEDIO 57.303333
DESBALANCE PERMISIBLE 5% 0.03 %
SC = SNC =ST = FD FS FP

4.47 KVA ### ### 0.7 1.25 0.96

CALCULO DEL ALIMENTADOR PRINCIPAL SEGÚN NEC CALCULO CAIDA DE VOLTAJE


ITC #C A-C FA FT FAC V C R√3 L IN V Scu E%

43.22 A 6 75 A ### 0.96 57.6 0.208 Kv 2 1.732 10.00 M 43.22 A 208 V 13.3 0.54 %

ST = Potencia Aparente Total


SNC = Potencia Aparente uso no Continuo
SC = Potencia Aparente de uso Continuo
IN = Corriente Nominal
FS = Factor de Seguridad (25%)
FD = Factor de Demanda (70%)
ITC = Corriente Total Corregida
# C = Numero del Conductor Asignado
A-C = Ampacidad del Conductor
FA = Factor Agrupamiento
FT = Factor Temperatura
FAC = Factor Ampacidad Coregida
C = Constante
√3 = Raiz de tres (1.732)
L = Longitud del circuito
V = Voltaje
Scu = Seccion transversal del conductor de cobre en mm2
E % = Porcentaje Maximo permisible (3%)

Nota: De acuerdo a indicaciones del Articulo 230 y 210.3 Acometidas y Circuitos Ramales del NEC ( Codigo Nacional Electrico) y
CIEN (Codigo de instalaciones Electricas en Nicaragua se instalara un conductor de cobre Calibre # 6 AWG con una seccion
transversal de 13.3 mm2, con una Ampacidad 75 Amperios a 90°C, Aplicando los Factores de correccion Temperatura y
Agrupamiento la Ampacidad del conductor sera de 57.6 amperios y un Breaker de 3x50
PANEL TOMA CORRIENTE (T2) NIVEL 3 (PT2N3)

PANEL DE SERVICIO : PT2N3 BARRAS DE 200 AMP VOLTAJE: 120 /208 5 HILOS

ESPACIOS INTERCAMBIABLES: 42 INTERUPTOR PRINCIPAL: INTEGRADO 3 X 80 DUCTO METALICO 8"X6"

MARCA: CUTLER HAMMER EMPOTRABLE BARRAS DE NEUTRO Y TIERRA CONDUCTOR: 3 x 4 F, 1 X 4 N, 1 X 4 P.E

N° CONDUITS TIERRA CONDUCTOR BREAKER S FASES FASES S BREAKER CONDUCTOR TIERRA CONDUITS N°
DESCRIPCION DESCRIPCION
CKT TIPO
ф TIPO CAL TIPO CAL AMP /POLOS KVA A B C A B C KVA AMP /POLOS TIPO CAL TIPO CAL TIPO ф CKT

13.89 2
1 Ducha Direccion PVC 1/2 THHN 10 THHN 10 2x20 3.33
3 13.89 13.89 4
3.33 2x20 THHN 10 THHN 10 PVC 1/2 Ducha Clinica 2
5 13.89 13.89 6
Ducha Clinica 1 PVC 1/2 THHN 10 THHN 10 2x20 3.33
7 13.89 13.89 8
3.33 2x20 THHN 10 THHN 10 PVC 1/2 Ducha SS 8
9 VACIO 13.89 10

11 Toma corriente Area de Condensadoras PVC 1/2 THHN 10 THHN 10 1X20 0.19 1.56 13.89 12
3.33 2x20 THHN 10 THHN 10 PVC 1/2 Ducha SS / 7
13 13.89 13.89 14
Ducha SS 10 PVC 1/2 THHN 10 THHN 10 2x20 3.33
15 13.89 VACIO 16

17 4.87 18
VACIO Evaporador Sala de Espera 1, Caja, Admision,
1.17 2X15 THHN 12 THHN 12 PVC 1/2 Gymnasio, Clinica 1 y 2, Estacion de Enfermeria,
Vestidor de Hombres y Vestidor de Mujeres
19 VACIO 4.87 20

21 T. corriente Oasis Sala de espera 1 PVC 1/2 THHN 10 THHN 10 1X20 0.54 4.51 VACIO 22

23 13.89 4.51 0.54 1x15 THHN 10 THHN 10 PVC 1/2 T. Corriente Oasis Estacion de Enfermeria 24
Toma Corriente camilla Recuperacion PVC 1/2 THHN 10 THHN 10 2X20 1.35

25 13.89 10.16 26
Extractor de Aire CUE-900, INYECTOR CUE-
1.06 2X15 THHN 10 THHN 10 PVC 1/2
099-VG-1/4 - C-1/8 Sala de Hemodinamia
27 11.02 10.16 28
Toma Corriente Arco en C Sala de Hemodinamia PVC 1/2 THHN 10 THHN 10 2X20 2.29
29 11.02 39.06 4.69 1X50 THHN 2 THHN 2 PVC 1 1/2 Panel Tierra Aislada Sala de Hemodinamia 30

31 Evaporador Secretaria Direccion, Direccion, Neurologia 4.96 13.89 32


Pediatrica, Sueño +Video+EEG, Cuarto de Control,
PVC 1/2 THHN 12 THHN 12 2X15 1.19 3.33 2x20 THHN 10 THHN 10 PVC 1/2 Ducha SS -7
Pasillo 3, Recuperacion, Estacion de enfermeria,
33 Anestecia 4.96 13.89 34

35 VACIO VACIO 36

37 VACIO 13.02 38
Aire acondicionado 2 Cuarto Equipo
2.71 2x20 THHN 10 THHN 10 PVC 1/2
Hemodinamia
Aire acondicionado 2 Cuarto Equipo
2.71 2x20 THHN 10 THHN 10 PVC 1/2
Hemodinamia
39 13.02 13.02 40
Aire acondicionado 1 Cuarto Equipo Hemodinamia PVC 1/2 THHN 10 THHN 10 2X20 2.71
41 13.02 VACIO 42

60.52 61.29 53.38 69.72 64.85 76.22

SELECCIÓN DE ALIMENTADOR ELECTRICO PRINCIPAL CENTRO DE CARGA DE TOMACORRIENTE (PT2N3)

SUMA DE BARRAS IN
BARRA A 130.24
BARRA B 126.14
BARRA C 129.6
PROMEDIO 128.66
DESBALANCE PERMISIBLE 5% 3.19 %

SC = SNC =ST = FD FS FP

6.20 KVA ### ### 0.7 1.25 0.96

CALCULO DEL ALIMENTADOR PRINCIPAL SEGÚN NEC CALCULO CAIDA DE VOLTAJE


ITC #C A-C FA FT FAC V C R√3 L IN V Scu E%

85.43 A 4 95 A ### 0.96 72.96 0.208 Kv 2 1.732 10.00 M 85.43 A 208 V 21.15 0.67 %

ST = Potencia Aparente Total


SNC = Potencia Aparente uso no Continuo
SC = Potencia Aparente de uso Continuo
IN = Corriente Nominal
FS = Factor de Seguridad (25%)
FD = Factor de Demanda (70%)
ITC = Corriente Total Corregida
# C = Numero del Conductor Asignado
A-C = Ampacidad del Conductor
FA = Factor Agrupamiento
FT = Factor Temperatura
FAC = Factor Ampacidad Coregida
C = Constante
√3 = Raiz de tres (1.732)
L = Longitud del circuito
V = Voltaje
Scu = Seccion transversal del conductor de cobre en mm2
E % = Porcentaje Maximo permisible (3%)

Nota: De acuerdo a indicaciones del Articulo 230 y 210.3 Acometidas y Circuitos Ramales del NEC ( Codigo Nacional Electrico) y
CIEN (Codigo de instalaciones Electricas en Nicaragua se instalara un conductor de cobre Calibre # 4 AWG con una seccion
transversal de 21.15 mm2, con una Ampacidad 95 Amperios a 90°C, Aplicando los Factores de correccion Temperatura y
Agrupamiento la Ampacidad del conductor sera de 73 amperios y un Main de 3x80

BALANCE DE PANELES PRINCIPALES

PANEL PRL PRINCIPAL (PP)

PANEL PRL3A : PP BARRAS DE 600 AMP VOLTAJE: 120 /208 5 HILOS

ESPACIOS INTERCAMBIABLES: 32 INTERUPTOR PRINCIPAL: INTEGRADO 3 X 600 TUBO CONDUIT PVC 4"

MARCA: CUTLER HAMMER SUPERFICIAL BARRAS DE NEUTRO Y TIERRA CONDUCTOR: 6 x 350 F, 2 X 350 N, 1 X 2/0 P.E

N° CONDUITS TIERRA CONDUCTOR BREAKER S FASES FASES S BREAKER CONDUCTOR TIERRA CONDUITS N°
DESCRIPCION DESCRIPCION
CKT TIPO
ф TIPO CAL TIPO CAL AMP /POLOS KVA A B C A B C KVA AMP /POLOS TIPO CAL TIPO CAL TIPO ф CKT

18.06 7.02 2
1

3 PANEL DE LAMPARAS NIVEL 1 (PLN1) EMT 1 THHN 8 THHN 8 3x20 4.7 17.4 6.54 2.08 3X15 THHN 8 THHN 8 EMT 1 PANEL DE LAMPARAS NIVEL 2 (PLN2) 4

5 17.43 6.81 6

7 11.23 131.97 8

PANEL DE TOMA CORRIENTE NIVEL 1


9 PANEL DE LAMPARAS NIVEL 3 (PLN3) EMT 1 THHN 8 THHN 8 3X15 3.17 11.31 133.67 34.54 3X100 THHN 2 THHN 2 EMT 1 1/4 10
(PTN1)

11 11.51 132.02 12

13 112.76 78.16 14

PANEL TRANSFORMADORES DE AISLAMIENTO


15 EMT 1 1/4 THHN 2 THHN 2 3X100 27.51 108.25 82.19 21.2 3X70 THHN 4 THHN 4 EMT 1 1/4 PANEL TOMA CORRIENTE NIVEL 2 (PTN2) 16
NIVEL 1 (PTAN1)

17 111.18 81.98 18

19 147.75 20

21 PANEL TOMA CORRIENTE 2 NIVEL 2 (PT2N2) EMT 1 1/2 THHN 1/0 THHN 1/0 3X125 37.96 148.35 22

23 153.3 24

25 57.83 108.96 26

PANEL TOMA CORRIENTE 2 NIVEL 3


27 PANEL TOMA CORRIENTE NIVEL 3 (PTN3) EMT 1 THHN 6 THHN 6 3X50 15.57 57.83 104.61 26.03 3X80 THHN 4 THHN 4 EMT 1 1/4 28
(PT2N3)

29 57.81 103.81 30

31 32

347.63 343.14 351.23 326.11 327.01 324.62

SUMA DE BARRAS IN
BARRA A 673.74
BARRA B 670.15
BARRA C 675.85

PROMEDIO 673.24667
DESBALANCE PERMISIBLE 5% 0.85 %

ST =

172.76 KVA

CALCULO DEL ALIMENTADOR PRINCIPAL SEGÚN NEC CALCULO CAIDA DE VOLTAJE


ITC #C A-C FA FT FAC V C R√3 L IN V Scu E%

479.55 A 350 MCM 700 A ### 0.96 537.6 0.208 Kv 2 1.732 10.00 M 479.55 A 208 V 177.35 0.4503139

ST = Potencia Aparente Total


# C = Numero del Conductor Asignado
A-C = Ampacidad del Conductor
FA = Factor Agrupamiento
FT = Factor Temperatura
FAC = Factor Ampacidad Coregida

C = Constante
√3 = Raiz de tres (1.732)

L = Longitud del circuito


V = Voltaje
Scu = Seccion transversal del conductor de cobre en mm2
E % = Porcentaje Maximo permisible (3%)

Nota: De acuerdo a indicaciones del Articulo 230 y 210.3 Acometidas y Circuitos Ramales del NEC
( Codigo Nacional Electrico) y CIEN (Codigo de instalaciones Electricas en Nicaragua se instalara un conductor de
cobre Calibre # 350 MCM con una seccion transversal de 177.35 mm2, con una Ampacidad 350 Amperios a 90°C,
(Dos conductores en paralelo) Aplicando los Factores de correccion Temperatura y Agrupamiento la Ampacidad del
conductor sera de 268.8 amperios y un Main de 3x600 (Dos conductores en Paralelo)

PANEL PRL PRINCIPAL 2 (PP2)

PANEL PRL3A : PP2 BARRAS DE 800 AMP VOLTAJE: 240 4 HILOS

ESPACIOS INTERCAMBIABLES: 42 INTERUPTOR PRINCIPAL: INTEGRADO 3 X 600 TUBO CONDUIT PVC 4"

MARCA: CUTLER HAMMER EMPOTRABLE BARRAS DE NEUTRO Y TIERRA CONDUCTOR: 6 x 400 F, 1 X 2/0 P.E
N° CONDUITS TIERRA CONDUCTOR BREAKER S FASES FASES S BREAKER CONDUCTOR TIERRA CONDUITS N°
DESCRIPCION DESCRIPCION
CKT TIPO
ф TIPO CAL TIPO CAL AMP /POLOS KVA A B C A B C KVA AMP /POLOS TIPO CAL TIPO CAL TIPO ф CKT

54.61 54.61 2
1

3 UNIDAD CONDENSADORA # 1 VRF NIVEL 1 (UC- 54.61 54.61 UNIDAD CONDENSADORA # 3 VRF NIVEL 2 4
PVC 1 THHN 6 THHN 6 3X60 20.92 20.92 3X60 THHN 6 THHN 6 PVC 1
1) (UC-3)

5 54.61 54.61 6

7 54.61 54.61 8

UNIDAD CONDENSADORA # 2 VRF NIVEL 1 (UC- UNIDAD CONDENSADORA # 4 VRF NIVEL 2


9 PVC 1 THHN 6 THHN 6 3X60 20.92 54.61 54.61 20.92 3X60 THHN 6 THHN 6 PVC 1 10
2) (UC-4)

11 54.61 54.61 12

13 54.61 54.61 14

UNIDAD CONDENSADORA # 5 VRF NIVEL 3 (UC- UNIDAD CONDENSADORA # 6 VRF NIVEL 3


15 PVC 1 THHN 6 THHN 6 3X60 20.92 54.61 54.61 20.92 3X60 THHN 6 THHN 6 PVC 1 16
5) (UC-6)

17 54.61 54.61 18

19 46 46 20

21 UNIDAD CONDENSADORA TIPO PAQUETE 46 46 UNIDAD CONDENSADORA TIPO PAQUETE 22


PVC 1 THHN 6 THHN 6 3X60 17.62 17.62 3X60 THHN 6 THHN 6 PVC 1
QUIROFANO 1 (UCQ1) QUIROFANO 3 (UCQ3)

23 46 46 24

25 46 46 26

UNIDAD CONDENSADORA TIPO PAQUETE UNIDAD CONDENSADORA TIPO PAQUETE


27 PVC 1 THHN 6 THHN 6 3X60 17.62 46 46 17.62 3X60 THHN 6 THHN 6 PVC 1 28
QUIROFANO 2 (UCQ2) QUIROFANO 4 (UCQ4)

29 46 46 30

31 53.25 83.86 32

UNIDAD CONDENSADORA TIPO PAQUETE SALA


33 PVC 1 THHN 6 THHN 6 3X80 20.4 53.25 83.86 32.13 3X125 THHN 2 THHN 2 PVC 1 1/4 ELEVADOR 1 (ELV-1) 34
DE HEMODINAMIA (UCSH)

35 53.25 83.86 36

37 49.89 83.86 38

39 BOMBA CONTRA INCNEDIO 1 Y 2 (BSCI) PVC 1 THHN 6 THHN 6 3X80 19.11 49.89 83.86 32.13 3X125 THHN 2 THHN 2 PVC 1 1/4 ELEVADOR 2 (ELV-2) 40

41 49.89 83.86 42

358.97 358.97 358.97 423.55 423.55 423.55


SUMA DE BARRAS IN
BARRA A 782.52
BARRA B 782.52
BARRA C 782.52

PROMEDIO 782.52
DESBALANCE PERMISIBLE 5% 0.00 %

SC = SNC =ST = FD FS FP

137.20 KVA ### ### 0.7 1.25 0.96

CALCULO DEL ALIMENTADOR PRINCIPAL SEGÚN NEC CALCULO CAIDA DE VOLTAJE


ITC #C A-C FA FT FAC V C R√3 L IN V Scu E%

587.32 A 400 MCM 760 A ### 0.96 583.68 0.240 Kv 2 1.732 10.00 M 587.32 A 240 V 202.68 0.42 %

ST = Potencia Aparente Total


SNC = Potencia Aparente uso no Continuo
SC = Potencia Aparente de uso Continuo
IN = Corriente Nominal
FS = Factor de Seguridad (25%)
FD = Factor de Demanda (70%)
ITC = Corriente Total Corregida
# C = Numero del Conductor Asignado
A-C = Ampacidad del Conductor
FA = Factor Agrupamiento
FT = Factor Temperatura
FAC = Factor Ampacidad Coregida
C = Constante
√3 = Raiz de tres (1.732)

L = Longitud del circuito


V = Voltaje
Scu = Seccion transversal del conductor de cobre en mm2
E % = Porcentaje Maximo permisible (3%)

Nota: De acuerdo a indicaciones del Articulo 230 y 210.3 Acometidas y Circuitos Ramales del NEC ( Codigo Nacional Electrico) y
CIEN (Codigo de instalaciones Electricas en Nicaragua se instalara un conductor de cobre Calibre # 400 MCM (en paralelo) con una seccion
transversal de 202.68 mm2, con una Ampacidad 760 Amperios a 90°C, Aplicando los Factores de correccion Temperatura y Agrupamiento la
Ampacidad del conductor sera de 584 amperios y un Main de 3x600
MEMORIA CALCULO DE CLIMATIZACION (SEGÚN SOFTWARE CARRIER)

DESCRIPCION TIPO CAP. BTU


TIPO SPLIT 9000.00
TIPO SPLIT 12000.00
TIPO SPLIT 18000.00
TIPO SPLIT 24000.00
TIPO SPLIT 36000.00
TIPO SPLIT 60000.00

CALCULO DE CLIMATIZACION NIVEL 1 (SEGÚN SOFTWARE CARRIER)


NOMBRE
CANTIDAD DE MODELO DE EQUIPO VRF
Nombre area No Ambiente A H V FC FGP CP CE C (BTU) DE
BTU ASIGNADO ASIGNADO AL AREA
UNIDAD

Sala de espera 101 50.38 M2 2.70 M 136.03 M3 230 476 20 1 41282 60000.00 BTU 50000.00 BTU 42VD054H113011010, 16Kw UC-1

Procedimiento y choque 103 34.23 M2 2.70 M 92.42 M3 230 476 10 1 26493 36000.00 BTU 28000.00 BTU 40VK030H11300010, 9Kw UC-2

Clinica 1 106 11.20 M2 2.70 M 30.24 M3 230 476 3 1 8859 9000.00 BTU 10000.00 BTU 40VK012H11300010, 3.6Kw UC-1
Clinica 2 108 11.64 M2 2.70 M 31.43 M3 230 476 3 1 9132 12000.00 BTU 10000.00 BTU 40VK012H11300010, 3.6Kw UC-1

Pasillo 110 16.51 M2 2.70 M 44.58 M3 231 477 3 0 11728 12000.00 BTU 12000.00 BTU

Estacion de enfermeria 111 12.31 M2 2.70 M 33.24 M3 230 476 4 2 10501 12000.00 BTU 12000.00 BTU 42VD054H113011010, 16Kw UC-1

Observacion 119 30.50 M2 2.70 M 82.35 M3 230 476 7 1 22749 24000.00 BTU 23000.00 BTU
Sala de espera 123 6.95 M2 2.70 M 18.77 M3 231 477 5 0 6720 9000.00 BTU 7500.00 BTU 40VX007H11300010, 2.2 Kw UC-1

Vestidor de Mujeres 135 10.55 M2 2.70 M 28.49 M3 231 477 4 0 8488 9000.00 BTU 9000.00 BTU 40VX009H11300010, 2.8 Kw UC-2

Vestidor de Varones 137 9.95 M2 2.70 M 26.87 M3 232 478 5 0 8623 9000.00 BTU 9000.00 BTU 40VX009H11300010, 2.8 Kw UC-2
Pasillo Interno 1 140 39.77 M2 2.70 M 107.38 M3 230 476 7 0 28029 36000.00 BTU 30000.00 BTU
42VD054H113011010, 16Kw UC-2
Pasillo interno 2 147 24.87 M2 2.70 M 67.15 M3 230 476 5 0 17824 18000.00 BTU 18000.00 BTU
MODELO 50TCM-D08A1A5-0A0A0,
Quirofano 1 141 26.53 M2 2.80 M 74.28 M3 230 476 7 7 23749 24000.00 BTU 7.5 TON CAPACIDAD 7.5 TON
MODELO 50TCM-D08A1A5-0A0A0,
Quirofano 2 142 26.65 M2 2.80 M 74.62 M3 230 476 7 7 23827 24000.00 BTU 7.5 TON CAPACIDAD 7.5 TON

Voz y Datos 124 5.38 M2 2.70 M 14.53 M3 230 476 0 2 4293 9000.00 BTU 7500.00 BTU 40VX007H11300010, 2.2 Kw UC-1
127 8.39 M2 2.70 M 22.65 M3 230 2 9000.00 BTU 40VX009H11300010, 2.8 Kw
Cuarto de Maquinas de Elevadores 476 0 6162 9000.00 BTU UC-1

Anestecia 143 9.05 M2 2.70 M 24.44 M3 230 476 4 2 8476 9000.00 BTU 9000.00 BTU 40VX009H11300010, 2.8 Kw UC-2

Estacion de enfermeria 145 10.49 M2 2.70 M 28.32 M3 230 476 4 2 9370 12000.00 BTU 10000.00 BTU
42VD054H113011010, 16Kw UC-2
Recuperacion 149 37.00 M2 2.70 M 99.90 M3 230 476 6 0 25833 36000.00 BTU 30000.00 BTU
MODELO 50TCM-D08A1A5-0A0A0,
Quirofano 3 150 25.38 M2 2.80 M 71.06 M3 230 477 7 7 23023 24000.00 BTU 7.5 TON CAPACIDAD 7.5 TON
MODELO 50TCM-D08A1A5-0A0A0,
Quirofano 4 151 26.67 M2 2.80 M 74.68 M3 230 478 7 7 23867 24000.00 BTU 7.5 TON CAPACIDAD 7.5 TON

ECUACION
C = (FC * V) + (CP+CE)*FGP

C= CAPACIDAD EN BTU

A= AREA DEL AMBIENTE EN M2

H= ALTURA DEL AMBIENTE

V= VOLUMEN DEL AMBIENTE EN M3

FC= FACTOR DE CALCULO TEMPERATURA MENOR 40°C (BTU/Hm3)

FGP= FACTOR DE GANANCIA Y PERDIDA (BTU/Hm3)

CP= CANTIDAD DE PERSONAS


CE= CANTIDAD DE EQUIPOS

BTU= UNIDAD TECNICA BRITANICA NECESARIA

MEMORIA CALCULO DE CLIMATIZACION (SEGÚN SOFTWARE CARRIER)

CALCULO DE CLIMATIZACION NIVEL 2 (SEGÚN SOFTWARE CARRIER)


NOMBRE
CANTIDAD DE MODELO DE EQUIPO VRF
Nombre area No Ambiente A H V FC FGP CP CE C (BTU) DE
BTU ASIGNADO ASIGNADO AL AREA
UNIDAD

Dormitorio 1 203 21.12 M2 2.70 M 57.02 M3 230 476 5 2 16448 18000.00 BTU 18000.00 BTU 40VK020H11300010, 5.6Kw UC-3

Dormitorio 2 205 20.76 M2 2.70 M 56.05 M3 230 476 5 2 16224 18000.00 BTU 18000.00 BTU 40VK020H11300010, 5.6Kw UC-3

Dormitorio 3 207 21.57 M2 2.70 M 58.24 M3 230 476 5 2 16727 18000.00 BTU 18000.00 BTU 40VK020H11300010, 5.6Kw UC-3

Dormitorio 4 209 19.92 M2 2.70 M 53.78 M3 230 476 5 2 15702 18000.00 BTU 18000.00 BTU 40VK020H11300010, 5.6Kw UC-3
Dormitorio 5 211 21.49 M2 2.70 M 58.02 M3 230 476 5 2 16677 18000.00 BTU 18000.00 BTU 40VK020H11300010, 5.6Kw UC-3

Dormitorio 6 213 21.06 M2 2.70 M 56.86 M3 230 476 5 2 16410 18000.00 BTU 18000.00 BTU 40VK020H11300010, 5.6Kw UC-3

Dormitorio 7 215 17.85 M2 2.70 M 48.20 M3 230 476 5 2 14417 18000.00 BTU 18000.00 BTU 40VK020H11300010, 5.6Kw UC-4
Dormitorio 8 217 18.26 M2 2.70 M 49.30 M3 230 476 5 2 14671 18000.00 BTU 18000.00 BTU 40VK020H11300010, 5.6Kw UC-4

Dormitorio 9 220 17.53 M2 2.70 M 47.33 M3 230 476 5 2 14218 18000.00 BTU 18000.00 BTU 40VK020H11300010, 5.6Kw UC-4

Dormitorio 10 222 17.53 M2 2.70 M 47.33 M3 230 476 5 2 14218 18000.00 BTU 18000.00 BTU 40VK020H11300010, 5.6Kw UC-4

Dormitorio 11 224 19.32 M2 2.70 M 52.16 M3 230 476 5 2 15330 18000.00 BTU 18000.00 BTU 40VK020H11300010, 5.6Kw UC-4
Dormitorio 12 237 23.92 M2 2.70 M 64.58 M3 230 476 5 2 18186 24000.00 BTU 18000.00 BTU 40VK020H11300010, 5.6Kw UC-4

Dormitorio 13 239 23.78 M2 2.70 M 64.21 M3 230 476 5 2 18099 24000.00 BTU 18000.00 BTU 40VK020H11300010, 5.6Kw UC-3

Estacion de enfermeria 233 23.78 M2 2.70 M 64.21 M3 230 476 5 2 18099 24000.00 BTU 18000.00 BTU 40VK020H11300010, 5.6Kw UC-4
Sub Estacion de enfermeria 229 10.90 M2 2.70 M 29.43 M3 230 476 4 2 9625 12000.00 BTU 9000.00 BTU 40VK012H11300010, 3.6Kw UC-4

ECUACION

C = (FC * V) + (CP+CE)*FGP

C= CAPACIDAD EN BTU

A= AREA DEL AMBIENTE EN M2


H= ALTURA DEL AMBIENTE

V= VOLUMEN DEL AMBIENTE EN M3

FC= FACTOR DE CALCULO TEMPERATURA MENOR 40°C (BTU/Hm3)

FGP= FACTOR DE GANANCIA Y PERDIDA (BTU/Hm3)

CP= CANTIDAD DE PERSONAS

CE= CANTIDAD DE EQUIPOS

BTU= UNIDAD TECNICA BRITANICA NECESARIA

MEMORIA CALCULO DE CLIMATIZACION (SEGÚN SOFTWARE CARRIER)

CALCULO DE CLIMATIZACION NIVEL 3 (SEGÚN SOFTWARE CARRIER)


NOMBRE
CANTIDAD DE MODELO DE EQUIPO VRF
Nombre area No Ambiente A H V FC FGP CP CE C (BTU) DE
BTU ASIGNADO ASIGNADO AL AREA
UNIDAD

Sala de espera 1 300 58.69 M2 2.70 M 158.46 M3 230 476 20 4 47870 60000.00 BTU 50000.00 BTU 42VD054H113011010, 16Kw UC-5

Caja 301 5.86 M2 2.70 M 15.82 M3 230 476 1 3 5543 9000.00 BTU 7500.00 BTU 40VX009H11300010, 2.8 Kw UC-5
Admision 302 6.84 M2 2.70 M 18.47 M3 230 476 2 3 6628 9000.00 BTU 7500.00 BTU 40VX009H11300010, 2.8 Kw UC-5

Gymnasio 320 26.10 M2 2.70 M 70.47 M3 230 476 8 2 20968 24000.00 BTU 22000.00 BTU 40VK030H11300010, 9Kw UC-5

Clinica 2 316 13.33 M2 2.70 M 35.99 M3 230 476 3 4 11610 12000.00 BTU 12000.00 BTU 40VK012H11300010, 3.6Kw UC-5

Clinica 1 318 13.41 M2 2.70 M 36.21 M3 230 476 3 4 11660 12000.00 BTU 12000.00 BTU 40VK012H11300010, 3.6Kw UC-5

Secretaria Direccion 314 13.46 M2 2.70 M 36.34 M3 230 476 3 2 10739 12000.00 BTU 12000.00 BTU 40VK012H11300010, 3.6Kw UC-6

Direccion 313 25.91 M2 2.70 M 69.96 M3 230 476 6 3 20374 24000.00 BTU 24000.00 BTU 40VK030H11300010, 9Kw UC-6

Neurologia Pediatrica 309 14.03 M2 2.70 M 37.88 M3 230 476 3 1 10617 12000.00 BTU 12000.00 BTU 40VK012H11300010, 3.6Kw UC-6

Sueño +Video+EEG 307 14.09 M2 2.70 M 38.04 M3 230 476 3 4 12082 18000.00 BTU 12000.00 BTU 40VK012H11300010, 3.6Kw UC-6

Estacion de enfermeria 304 9.69 M2 2.70 M 26.16 M3 230 476 2 2 7921 9000.00 BTU 9000.00 BTU 40VX009H11300010, 2.8 Kw UC-5

Vestidor de Hombres 334 6.05 M2 2.70 M 16.34 M3 230 476 2 0 4709 9000.00 BTU 7500.00 BTU 40VX007H11300010, 2.2 Kw UC-5

Vestidor de Mujeres 336 6.44 M2 2.70 M 17.39 M3 230 476 2 0 4951 9000.00 BTU 7500.00 BTU 40VX007H11300010, 2.2 Kw UC-5

Cuarto de Control 338 12.52 M2 2.70 M 33.80 M3 230 476 6 6 13487 18000.00 BTU 15000.00 BTU 40VK020H11300010, 5.6Kw UC-6
MODELO 50TCM-D012A1A5-0A0A0
20 55426 60000.00 BTU
sala de Homodinamia 340 65.37 M2 2.80 M 183.04 M3 230 476 8 CAPACIDAD 10 TON

Pasillo 3 339 34.34 M2 2.70 M 92.72 M3 230 476 8 0 25133 36000.00 BTU 27000.00 BTU

Recuperacion 342 19.00 M2 2.70 M 51.30 M3 230 476 3 3 14655 18000.00 BTU 16000.00 BTU 42VD054H113011010, 16Kw UC-6

Estacion de enfermeria 344 10.35 M2 2.70 M 27.95 M3 230 476 2 2 8331 9000.00 BTU 9000.00 BTU

Anestecia 343 12.44 M2 2.70 M 33.59 M3 231 477 4 2 10621 12000.00 BTU 12000.00 BTU 40VK012H11300010, 3.6Kw UC-6

ECUACION

C = (FC * V) + (CP+CE)*FGP

C= CAPACIDAD EN BTU

A= AREA DEL AMBIENTE EN M2

H= ALTURA DEL AMBIENTE

V= VOLUMEN DEL AMBIENTE EN M3

FC= FACTOR DE CALCULO TEMPERATURA MENOR 40°C (BTU/Hm3)

FGP= FACTOR DE GANANCIA Y PERDIDA (BTU/Hm3)

CP= CANTIDAD DE PERSONAS

CE= CANTIDAD DE EQUIPOS

BTU= UNIDAD TECNICA BRITANICA NECESARIA


CALCULO CAIDA DE TENSION EN CONDENSADORES VRF NIVEL 1

Disyuntor 3
MODELO DE EQUIPO UBICACIÓN CANT. CKT PANEL PT COSɸ ST V IT KVA √3 F.P V L C TIPO Smm2 E%
Polos

1
Unidad Condensadora X-Power Full
Inverter Super S Series Mod- NIVEL 1 1 3 PP 20920.00 W 0.96 21791.67VA 240 V 54.61 A 20.92 KVA 1.732 1.100 60.00A 240 V 30.00 M 6 THHN 13.30 mm2 1.78 %
38VF014H117010, 148100 BTU,
43.39 Kw (UC-1) 5

7
Unidad Condensadora X-Power Full
Inverter Super S Series Mod- NIVEL 1 1 9 PP 20920.00 W 0.96 21791.67VA 240 V 54.61 A 20.92 KVA 1.732 1.100 60.00A 240 V 30.00 M 6 THHN 13.30 mm2 1.78 %
38VF014H117010, 148100 BTU,
43.39 Kw (UC-2) 11

19
Unidad Condensadora Tipo Quirofano 1 1 PP2 17624.00 W 0.96 18358.33VA 240 V 46.00 A 17.62 KVA 1.732 1.300 60.00A 240 V 30.00 M 6 THHN 13.30 mm2 1.50 %
21
PAQUETE Mod: 50TCM-D08A1A5-
0A0A0, 7.5 TONS 23

25
Unidad Condensadora Tipo Quirofano 2 1 PP2 17624.00 W 0.96 18358.33VA 240 V 46.00 A 17.62 KVA 1.732 1.300 60.00A 240 V 30.00 M 6 THHN 13.30 mm2 1.50 %
27
PAQUETE Mod: 50TCM-D08A1A5-
0A0A0, 7.5 TONS 29

20

Unidad Condensadora Tipo Quirofano 3 1 22 PP2 17624.00 W 0.96 18358.33VA 240 V 46.00 A 17.62 KVA 1.732 1.300 60.00A 240 V 30.00 M 6 THHN 13.30 mm2 1.50 %
PAQUETE Mod: 50TCM-D08A1A5-
0A0A0, 7.5 TONS 24

26
Unidad Condensadora Tipo Quirofano 4 1 PP2 17624.00 W 0.96 18358.33VA 240 V 46.00 A 17.62 KVA 1.732 1.300 60.00A 240 V 30.00 M 6 THHN 13.30 mm2 1.50 %
28
PAQUETE Mod: 50TCM-D08A1A5-
0A0A0, 7.5 TONS 30

32
ELEVADOR 1 NIVEL 1 1 PP2 32125.00 W 0.96 33463.54VA 240 V 83.86 A 32.13 KVA 1.732 1.360 114.00A 240 V 30.00 M 2 THHN 33.63 mm2 1.08 %
34
36
38

ELEVADOR 2 NIVEL 1 1
40
PP2 32125.00 W 0.96 33463.54VA 240 V 83.86 A 32.13 KVA 1.732 1.360 114.00A 240 V 30.00 M 2 THHN 33.63 mm2 1.08 %

42
37
BOMBA CONTRA INCNEDIO 1 Y 2 NIVEL 1 1 39 PP2 19111.20 W 0.96 19907.50VA 240 V 49.89 A 19.11 KVA 1.732 1.700 85.00A 240 V 20.00 M 6 THHN 13.30 mm2 1.08 %

41

ECUACION
(√3*n*L*I)
cv% =
(V*mm2)

Cv% = CAIDA DE VOLTAJE MENOR O IGUAL A 3%

n= VALOR CONSTANTE

n=2 CUANDO ES MONOFASICA


n=√3 CUANDO ES TRIFASICA

L= DISTANCIA DEL CIRCUITO

I = CORRIENTE

V = VOLTAJE DE OPERACIÓN
mm2 = SECCION DEL CONDUCTOR

CKT = NUMERO DE CIRCUITO


PANEL = CENTRO DE CARGA CORRESPONDIENTE

PT = POTENCIA ACTIVA TOTAL EN WATTS

F.P = FACTOR DE PROTECCION APLICADO AL DISYUNTOR


COSɸ = FACTOR DE POTENCIA

ST= POTENCIA APARENTE TOTAL EN VOLT AMPERE

V = VOLTAJE

I T = CORRIENTE TOTAL EN AMPERIOS

KVA = POTENCIA APARENTE TOTAL EN KILO VOLT AMPERE

L = LONGITUD TOTAL DEL CIRCUITO

C = CONDUCTOR ASIGNADO

Smm2 = SECCION TRANSVERSAL DEL CONDUCTOR EN MILIMETROS CUADRADOS

E % = CAIDA DE VOLTAJE EN PORCIENTO MAX PERMITIDO (3 %) PARA CIRCUITOS DERIVADOS


CALCULO CAIDA DE TENSION EN CONDENSADORES VRF NIVEL 2

Disyuntor 3
MODELO DE EQUIPO AREA CANT. No CKT PANEL PT COSɸ ST V IT KVA √3 F.P V L C TIPO Smm2 E%
Polos

NIVEL 2 1 PP 20920.00 W 0.96 21791.67VA 240 V 54.61 A 20.92 KVA 1.732 1.100 60.00A 240 V 30.00 M 6 THHN 13.30 mm2 1.78 %
Unidad Condensadora X-Power Full 4
Inverter Super S Series Mod-
38VF014H117010, 148100 BTU,
43.39 Kw (UC-3) 6

NIVEL 2 1 PP 20920.00 W 0.96 21791.67VA 240 V 54.61 A 20.92 KVA 1.732 1.100 60.00A 240 V 30.00 M 6 THHN 13.30 mm2 1.78 %
Unidad Condensadora X-Power Full 10
Inverter Super S Series Mod-
38VF014H117010, 148100 BTU,
43.39 Kw (UC-4) 12

ECUACION
(√3*n*L*I)
cv% =
(V*mm2)

Cv% = CAIDA DE VOLTAJE MENOR O IGUAL A 3%

n= VALOR CONSTANTE

n=2 CUANDO ES MONOFASICA

n=√3 CUANDO ES TRIFASICA

L= DISTANCIA DEL CIRCUITO

I = CORRIENTE

V = VOLTAJE DE OPERACIÓN

mm2 = SECCION DEL CONDUCTOR

CKT = NUMERO DE CIRCUITO

PANEL = CENTRO DE CARGA CORRESPONDIENTE

PT = POTENCIA ACTIVA TOTAL EN WATTS

F.P = FACTOR DE PROTECCION APLICADO AL DISYUNTOR

COSɸ = FACTOR DE POTENCIA

ST= POTENCIA APARENTE TOTAL EN VOLT AMPERE

V = VOLTAJE

I T = CORRIENTE TOTAL EN AMPERIOS

KVA = POTENCIA APARENTE TOTAL EN KILO VOLT AMPERE

L = LONGITUD TOTAL DEL CIRCUITO

C = CONDUCTOR ASIGNADO

Smm2 = SECCION TRANSVERSAL DEL CONDUCTOR EN MILIMETROS CUADRADOS

E % = CAIDA DE VOLTAJE EN PORCIENTO MAX PERMITIDO (3 %) PARA CIRCUITOS DERIVADOS


CALCULO CAIDA DE TENSION EN CONDENSADORES VRF NIVEL 3

Disyuntor 3
MODELO DE EQUIPO AREA CANT. No CKT PANEL PT COSɸ ST V IT KVA √3 F.P V L C TIPO Smm2 E%
Polos

13

NIVEL 3 1 PP 20920.00 W 0.96 21791.67VA 240 V 54.61 A 20.92 KVA 1.732 1.100 60.00A 240 V 30.00 M 6 THHN 13.30 mm2 1.78 %
Unidad Condensadora X-Power Full 15
Inverter Super S Series Mod-
38VF014H117010, 148100 BTU,
43.39 Kw (UC-5) 17

14

NIVEL 3 1 PP 20920.00 W 0.96 21791.67VA 240 V 54.61 A 20.92 KVA 1.732 1.100 60.00A 240 V 30.00 M 6 THHN 13.30 mm2 1.78 %
Unidad Condensadora X-Power Full 16
Inverter Super S Series Mod-
38VF014H117010, 148100 BTU,
43.39 Kw (UC-6) 18

31

Hemodinamia 1 PAAN1 20400.00 W 0.96 21250.00VA 240 V 53.25 A 20.40 KVA 1.732 1.500 80.00A 240 V 30.00 M 6 THHN 13.30 mm2 1.73 %
33
Unidad Condensadora Tipo
PAQUETE Mod: 50TCM-
D012A1A5-0A0A0, 10 TONS 35

EQUIPO DE ANGIOGRAFO Sala Hemodinamia 1 Sub Estacion 60000.00 W 0.96 62500.00VA 480 V 78.31 A 60.00 KVA 1.732 1.500 117.00A 240 V 75.00 M 1/0 THHN 53.51 mm2 1.58 %

ECUACION
(√3*n*L*I)
cv% =
(V*mm2)

Cv% = CAIDA DE VOLTAJE MENOR O IGUAL A 3%

n= VALOR CONSTANTE

n=2 CUANDO ES MONOFASICA

n=√3 CUANDO ES TRIFASICA

L= DISTANCIA DEL CIRCUITO

I = CORRIENTE

V = VOLTAJE DE OPERACIÓN

mm2 = SECCION DEL CONDUCTOR

CKT = NUMERO DE CIRCUITO

PANEL = CENTRO DE CARGA CORRESPONDIENTE

PT = POTENCIA ACTIVA TOTAL EN WATTS

F.P = FACTOR DE PROTECCION APLICADO AL DISYUNTOR


COSɸ = FACTOR DE POTENCIA

ST= POTENCIA APARENTE TOTAL EN VOLT AMPERE

V = VOLTAJE
I T = CORRIENTE TOTAL EN AMPERIOS

KVA = POTENCIA APARENTE TOTAL EN KILO VOLT AMPERE

L = LONGITUD TOTAL DEL CIRCUITO


C = CONDUCTOR ASIGNADO

Smm2 = SECCION TRANSVERSAL DEL CONDUCTOR EN MILIMETROS CUADRADOS

E % = CAIDA DE VOLTAJE EN PORCIENTO MAX PERMITIDO (3 %) PARA CIRCUITOS DERIVADOS


CALCULO DE TRANSFORMADOR NUMERO 1

TRANSFORMADOR: TRIFASICO TIPO: SECO MARCA: EATON

LOCALIZACIÓN: Costado Sur Edificio 4 MODELO : V48M28T22CU TIPO : DT-3

SISTEMA: TRIFASICO TEMPERATURA : 150° C CONFIGURACION Δ-Ү

SERVICIO: ALIMENTADOR SECUNDARIO


CIA R√3 VLP VLS VFS CIVA
479.55A 1.732 480 V 208 V 120 V 172760.00VA

CALCULO DE CORRIENTE EN EL PRIMARIO (TENSIÓN 480 VOLTS)


I1= S1/(√3 * VL ) 207.80 A X 1.25% = 259.76 A

CALCULO DE CORRIENTE EN EL SECUNDARIO (TENSIÓN 208 VOLTS)


I2= S2/(√3 * VL ) 479.55 A X 1.20% = 575.457 A

CALCULO DE TRANSFORMADOR
KVA= (I2 * √3 * VL)/1000 207.31 KvA

TRANSFORMADOR SELECCIONADO = 225 KVA

SELECCIÓN DE PROTECCION EN EL PRIMARIO


INTP INTERRUPTOR
259.76 A 3X280

SELECCIÓN DE PROTECCION EN EL SECUNDARIO


INTS IT
575.46 A 3X600 A

CALCULO DEL ALIMENTADOR PRINCIPAL DEL TRANSFORMADOR SEGÚN NEC CALCULO CAIDA DE VOLTAJE
ITC #C A-C FA FT FAC C R√3 L IN V Scu E%

259.76 A 400 MCM 380 A 0.8 0.96 291.84 2 1.732 60.00 M 259.76 A 480 V 202.68 0.55 %

CI = CARGA INSTALADA EN AMPERIOS

RAIZ DE TRES (√3)

VLP = TENSIÓN LINEA EN EL PRIMARIO

VLS = TENSIÓN LINEA EN EL SECUNDARIO

VFS = TENSIÓN FASE EN EL SECUNDARIO

CIVA = CARGA INSTALADA EN VOL AMPER

1.20 % = FACTOR FUTURAS CARGAS

INTP = CORRIENTE NOMINAL EN EL PRIMARIO DEL TRANSFORMADOR

INTS = CORRIENTE NOMINAL EN EL SECUNDARIO DEL TRANSFORMADOR

IT = INTERRUPTOR TERMOMAGNETICO SELECCIONADO

1.25 % = FACTOR DE SEGURIDAD

Nota: De acuerdo a indicaciones del Articulo 230 y 210.3 Acometidas y Circuitos Ramales del NEC ( Codigo Nacional Electrico) y CIEN (Codigo de instalaciones

Electricas en Nicaragua se instalara un conductor de cobre para el alimentador del lado primario del transformador
Calibre # 400 MCM con una seccion transversal de 202.68 mm2, con una Ampacidad 380 Amperios a 90°C, (Dos conductores en paralelo)

Aplicando los Factores de correccion Temperatura y Agrupamiento la Ampacidad del conductor sera de 291.84 amperios y un
Main de 3x (Dos conductores en Paralelo)

NOTA:
PROTECCION DE TRANSFORMADORES EN INSTALACIONES INDUSTRIALES DE 600 V Ó MENORES

Los dispositivos de Sobrecorriente en el devanado primario deben ser calculados o ajustados a no mas de 125% de la corriente nominal de plena carga en el
devanado primario esta regla Basica, se modifica en las normas tecnicas para instalaciones electricas por una excepcion que es la siguiente:

1- Si la corriente primaria es 9 Amperios ó mayor, el dispositivo de sobrecorriente, no se puede designar o ajustar a mas del 125% del valor de la
corriente nominal primaria, en el caso de que no corresponda al valor normalizado, entonces se usa el valor que sigue de estos.
CALCULO DE TRANSFORMADOR NUMERO 2

TRANSFORMADOR: TRIFASICO TIPO: SECO MARCA: EATON

LOCALIZACIÓN: Costado Sur Edificio 4 MODELO : V48M24T33CU TIPO : DT-3

SISTEMA: TRIFASICO TEMPERATURA : 150° C CONFIGURACION Δ- Δ

SERVICIO: ALIMENTADOR SECUNDARIO


CI R√3 VLP VLS CIVA
587.32A 1.732 480 V 240 V 244139.00VA

CALCULO DE CORRIENTE EN EL PRIMARIO (TENSIÓN 480 VOLTS)


I1= S1/(√3 * VL ) 293.66 A X 1.25% = 367.08 A

CALCULO DE CORRIENTE EN EL SECUNDARIO (TENSIÓN 240 VOLTS)


I2= S2/(√3 * VL ) 587.32 A X 1.20% = 704.789 A

CALCULO DE TRANSFORMADOR
KVA= (I2 * √3 * VL)/1000 292.97 KvA

TRANSFORMADOR SELECCIONADO = 300 KVA

SELECCIÓN DE PROTECCION EN EL PRIMARIO


INTP INTERRUPTOR
367.08 A 3X400

SELECCIÓN DE PROTECCION EN EL SECUNDARIO


INTS IT
704.79 A 3X800 A

CALCULO DEL ALIMENTADOR PRINCIPAL DEL TRANSFORMADOR SEGÚN NEC CALCULO CAIDA DE VOLTAJE
ITC #C A-C FA FT FAC C R√3 L IN V Scu E%

367.08 A 4/0 520 A 0.8 0.96 399.36 2 1.732 60.00 M 367.08 A 480 V 107.22 1.48 %

CI = CARGA INSTALADA EN AMPERIOS


RAIZ DE TRES (√3)
VLP = TENSIÓN LINEA EN EL PRIMARIO
VLS = VLF = TENSIÓN LINEA EN EL SECUNDARIO ES IGUAL TENSION DE LINEA EN LA FASE
VFS = TENSIÓN FASE EN EL SECUNDARIO
CIVA = CARGA INSTALADA EN VOL AMPER
1.20 % = FACTOR FUTURAS CARGAS
INTP = CORRIENTE NOMINAL EN EL PRIMARIO DEL TRANSFORMADOR
INTS = CORRIENTE NOMINAL EN EL SECUNDARIO DEL TRANSFORMADOR
IT = INTERRUPTOR TERMOMAGNETICO SELECCIONADO
1.25 % = FACTOR DE SEGURIDAD

Nota: De acuerdo a indicaciones del Articulo 230 y 210.3 Acometidas y Circuitos Ramales del NEC ( Codigo Nacional Electrico) y CIEN (Codigo de instalaciones

Electricas en Nicaragua se instalara un conductor de cobre


Calibre # 4/0 AWG con una seccion transversal de 107.22 mm2, con una Ampacidad 520 Amperios a 90°C, (Dos conductores en paralelo)

Aplicando los Factores de correccion Temperatura y Agrupamiento la Ampacidad del conductor sera de 399.36 amperios y un Main de 3x400
(Dos conductores en Paralelo)

NOTA:
PROTECCION DE TRANSFORMADORES EN INSTALACIONES INDUSTRIALES DE 600 V Ó MENORES

Los dispositivos de Sobrecorriente en el devanado primario deben ser calculados o ajustados a no mas de 125% de la corriente nominal de plena carga en el
devanado primario esta regla Basica, se modifica en las normas tecnicas para instalaciones electricas por una excepcion que es la siguiente:

1- Si la corriente primaria es 9 Amperios ó mayor, el dispositivo de sobrecorriente, no se puede designar o ajustar a mas del 125% del valor de la
corriente nominal primaria, en el caso de que no corresponda al valor normalizado, entonces se usa el valor que sigue de estos.
CALCULO DE CLIMATIZACION

DESCRIPCION TIPO CAP. BTU


TIPO SPLIT 9000.00
TIPO SPLIT 12000.00
TIPO SPLIT 18000.00
TIPO SPLIT 24000.00
TIPO SPLIT 36000.00
TIPO SPLIT 60000.00

CALCULO DE CLIMATIZACION EDIFICIO HORIZONTAL CORNAP CENTRAL

EQUIPO Equipo a utilizar


Nombre area EXISTENTE A Area (A) Altura Volumen Capacidad según calculo en Cantidad CANTIDAD DE
ESTADO DE EQUIPOS
Factor de Factor de (C= (FC x equipo BTU ASIGNADO
INSTALAR (BTU)
calculo T-M ganancia y V)+((CP +
40°C perdida Cantidad de Cantidad CE) x FG)
(BTU/Hm3) (BTU/Hm3) personas de equipos *BTU*

VICE-PRESIDENCIA JUNTA
GENERAL CORNAP 15.13 M2 2.80 M 42.36 M3 230 476 3 2 12124 18000.00 BTU 1 UND 18,000BTU NUEVO

ASISTENTES DE PRESIDENCIA 21.54 M2 3.30 M 71.07 M3 230 476 2 4 19203 24000.00 BTU 1 UND 22,000 BTU USADO

DIRECCIÓN DE ASESOSORIA
NUEVO
LEGAL Y LITIGIO
VENTILADOR 1 UND

ASESORIA LEGAL Y LITIGIO /


NUEVOS
UNIDAD DE ADQUISICIONES 36,000BTU /
43.40 M2 3.30 M 143.22 M3 230 476 7 7 39606 60000.00 BTU 1 UND 24,000BTU
SECRETARÍA DE JUNTA
10.38 M2 NUEVO
GENERAL CORNAP 2.80 M 29.06 M3 230 476 2 2 8589 9000.00 BTU 1 UND 9,000BTU
DIVISION DE ADMINISTRACION
Y FINANZAS / ASISTENTE 36,000BTU / NUEVOS
ADMINISTRATIVO NPCN 65.56 M2 3.30 M 216.35 M3 230 476 8 8 57377 60000.00 BTU 1 UND 24,000BTU
RECURSOS HUMANOS / 24,000BTU /
PLANIFICACIÓN 53.79 M2 3.30 M 177.49 M3 230 476 5 6 46060 60000.00 BTU 1 UND 24,000BTU NUEVOS
TECNOLOGIA EN INFORMATICA 8.91 M2 3.30 M 29.39 M3 230 476 2 4 9615 12000.00 BTU 1 UND 18,000BTU NUEVO
PRESIDENCIA DE JUNTA
15.62 M2
GENERAL DE CORNAP 2.80 M 43.74 M3 230 476 3 2 12439 18000.00 BTU 1 UND 18,000BTU NUEVO

RECEPCIÓN 26.64 M2
3.30 M 87.90 M3 230 476 4 5 24501 36000.00 BTU 1 UND 36,000BTU USADO
UNIDAD TECNICA DE
PROYECTOS 17.782 3.00 M 53.35 M3 230 476 5 5 17030 18000.00 BTU 1 UND 6,000-22,000BTU USADO

ARCHIVO CENTRAL 52.64 3.00 M 157.92 M3 230 476 4 4 40130 60000.00 BTU 1 UND 60,000BTU USADO

ARCHIVO CENTRAL AUXILIAR 52.64 3.00 M 157.92 M3 231 477 5 4 40773 60000.00 BTU 1 UND 60,000BTU USADO

SALA DE REUNIONES CORNAP 18.25 BTU 3.00 BTU 54.75 M3 230 476 8.00 BTU 3.00 BTU 17829 18000.00 BTU 1 UND 18,000BTU NUEVO
230 = Factor de Calculo para temperatura Maxima de 40°C dado en (BTU/hm3)

hm3= Horas metros Cubicos


V= Volumen del Area donde se Instalara el Equipo A Climatizar

CP = Cantidad de Personas

CE = Cantidad de Equipos

476 = Factor de ganancia y Perdida aportado por cada persona y Equipo en (BTU/hm3)

CALCULO DEL SISTEMA ELÉCTRICO PARA EQUIPOS DE AIRE ACONDICIONADO - EDIFICIO HORIZONTAL CORNAP CENTRAL

Disyuntor 3
MODELO DE EQUIPO UBICACIÓN CANT. No CKT PANEL PT COSɸ STCKT V IT KVA F. Proteccion Longitud Conductor Smm2 E%
Polos

VICE-PRESIDENCIA JUNTA
1 1 PP 2857.00 W 0.8 3571.25VA 208 V 13.10 A 2.86 KVA 1.100 14.00A 30.00 M 6 AWG 13.30 mm2 #REF!
GENERAL CORNAP

ASISTENTES DE
1 7 PP 20920.00 W 0.96 21791.67VA 240 V #DIV/0! 20.92 KVA 1.100 #DIV/0! 30.00 M 6 AWG 13.30 mm2 #DIV/0!
PRESIDENCIA

11

DIRECCIÓN DE ASESOSORIA
1 PP2 17624.00 W 0.96 18358.33VA 240 V #DIV/0! 17.62 KVA 1.300 #DIV/0! 30.00 M 6 AWG 13.30 mm2 #DIV/0!
LEGAL Y LITIGIO 19

23

ASESORIA LEGAL Y LITIGIO 1 PP2 17624.00 W 0.96 18358.33VA 240 V #DIV/0! 17.62 KVA 1.300 #DIV/0! 30.00 M 6 AWG 13.30 mm2 #DIV/0!
25
29

SECRETARÍA DE JUNTA
1 PP2 17624.00 W 0.96 18358.33VA 240 V 46.00 A 17.62 KVA 1.732 1.300 60.00A 30.00 M 6 AWG 13.30 mm2 #REF!
GENERAL CORNAP 20

24

DIVISION DE
ADMINISTRACION Y 1
26
PP2 17624.00 W 0.96 18358.33VA 240 V 46.00 A 17.62 KVA 1.732 1.300 60.00A 30.00 M 6 AWG 13.30 mm2 #REF!
FINANZAS
30

RECURSOS HUMANOS 1 PP2 32125.00 W 0.96 33463.54VA 240 V 83.86 A 32.13 KVA 1.732 1.360 114.00A 30.00 M 2 AWG 33.63 mm2 #REF!
32
36

TECNOLOGIA EN 38
1 PP2 32125.00 W 0.96 33463.54VA 240 V 83.86 A 32.13 KVA 1.732 1.360 114.00A 30.00 M 2 AWG 33.63 mm2 #REF!
INFORMATICA

42
PRESIDENCIA DE JUNTA
GENERAL DE CORNAP

TIN1036H2V02 INNOVAR INVERTER RECEPCIÓN

CALCULO DE CONDENSADORES NIVEL 2

C. Red Disyuntor 3
MODELO DE EQUIPO AREA CANT. No CKT PANEL PT COSɸ STCKT V IT Kva F. Proteccion Longitud Conductor Smm2 E%
Trifasica Polos

NIVEL 2 1 PP 20920.00 W 0.96 21791.67VA 240 V 54.61 A 20.92 KVA 1.732 1.100 60.00A 30.00 M 6 AWG 13.30 mm2 #REF!
Unidad Condensadora X-Power Full 4
Inverter Super S Series Mod-
38VF014H117010, 148100 BTU,
43.39 Kw (UC-3) 6

NIVEL 2 1 PP 20920.00 W 0.96 21791.67VA 240 V 54.61 A 20.92 KVA 1.732 1.100 60.00A 30.00 M 6 AWG 13.30 mm2 #REF!
Unidad Condensadora X-Power Full 10
Inverter Super S Series Mod-
38VF014H117010, 148100 BTU,
43.39 Kw (UC-4) 12

CALCULO DE CONDENSADORES NIVEL 3

C. Red Disyuntor 3
MODELO DE EQUIPO AREA CANT. No CKT PANEL PT COSɸ STCKT V IT Kva F. Proteccion Longitud Conductor Smm2 E%
Trifasica Polos

13

NIVEL 3 1 PP 20920.00 W 0.96 21791.67VA 240 V 54.61 A 20.92 KVA 1.732 1.100 60.00A 30.00 M 6 AWG 13.30 mm2 #REF!
Unidad Condensadora X-Power Full 15
Inverter Super S Series Mod-
38VF014H117010, 148100 BTU,
43.39 Kw (UC-5) 17

14

NIVEL 3 1 PP 20920.00 W 0.96 21791.67VA 240 V 54.61 A 20.92 KVA 1.732 1.100 60.00A 30.00 M 6 AWG 13.30 mm2 #REF!
Unidad Condensadora X-Power Full 16
Inverter Super S Series Mod-
38VF014H117010, 148100 BTU,
43.39 Kw (UC-6) 18

31

Hemodinamia 1 PAAN1 20400.00 W 0.96 21250.00VA 240 V 53.25 A 20.40 KVA 1.732 1.500 80.00A 30.00 M 6 AWG 13.30 mm2 #REF!
33
Unidad Condensadora Tipo
PAQUETE Mod: 50TCM-
D012A1A5-0A0A0, 10 TONS 35

Sala Hemodinamia 1 Sub Estacion 60000.00 W 0.96 62500.00VA 480 V 78.31 A 60.00 KVA 1.732 1.500 117.00A 75.00 M 1/0 53.51 mm2 #REF!
Sala Hemodinamia 1 Sub Estacion 60000.00 W 0.96 62500.00VA 480 V 78.31 A 60.00 KVA 1.732 1.500 117.00A 75.00 M 1/0 53.51 mm2 #REF!

EQUIPO DE ANGIOGRAFO 35

CALCULO DE EVAPORADORES NIVEL 1


CANT
EQUIPO AREA CKT Panel PT COSɸ STCKT V IT Kva Longitud Conductor Smm2 E%
.

31
Evaporador Tipo Conductor de alta Presion Estatica Mod- Sala de espera 1 PAAN1 532.00 W 0.96 554.17VA 240V 2.22A 0.53 KvA 40.00 M 12 AWG 3.31 mm2 0.45 %
42VD054H113011010, CAP. 51,200 BTU, 16Kw, UC #1
33
Evaporador Tipo Cassette Mod. 40VK030H11300010,
9Kw, CAP. 30,700 BTU, UC #2 31
Procedimiento y choque 1 PAAN1 160.00 W 0.96 166.67VA 240V 0.67A 0.16 KvA 40.00 M 12 AWG 3.31 mm2 0.13 %
33

31
Evaporador Tipo Cassette Mod. 40VK012H11300010, Clinica 1 1 PAAN1 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
3.6Kw, CAP. 12,300 BTU, UC #1
33

31
Evaporador Tipo Cassette Mod. 40VK012H11300010, Clinica 2 1 PAAN1 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
3.6Kw, CAP. 12,300 BTU, UC #1
33

31
Pasillo, Estacion de enfermeria,
1 PAAN1 532.00 W 0.96 554.17VA 240V 2.22A 0.53 KvA 35.00 M 12 AWG 3.31 mm2 0.39 %
Evaporador Tipo Conductor de alta Presion Estatica Mod- Observacion
42VD054H113011010, CAP. 51,200 BTU, 16Kw, UC #1 33

31
Evaporador Tipo Cassette Mod. 40VX007H11300010, 2.2 Sala de espera 1 PAAN1 50.00 W 0.96 52.08VA 240V 0.21A 0.05 KvA 35.00 M 12 AWG 3.31 mm2 0.04 %
Kw, CAP. 7,500 BTU, UC #1 33

31
Evaporador Tipo Cassette Mod. 40VX009H11300010, 2.8 Vestidor de Mujeres 1 PAAN1 50.00 W 0.96 52.08VA 240V 0.21A 0.05 KvA 35.00 M 12 AWG 3.31 mm2 0.04 %
Kw, CAP. 9,600 BTU, UC #2 33

31
Evaporador Tipo Cassette Mod. 40VX009H11300010, 2.8 Vestidor de Varones 1 PAAN1 50.00 W 0.96 52.08VA 240V 0.21A 0.05 KvA 35.00 M 12 AWG 3.31 mm2 0.04 %
Kw, CAP. 9,600 BTU, UC #2 33

31
Pasillo Interno 1, Pasillo Interno 2 1 PAAN1 532.00 W 0.96 554.17VA 240V 2.22A 0.53 KvA 35.00 M 12 AWG 3.31 mm2 0.39 %
Evaporador Tipo Conductor de alta Presion Estatica Mod-
42VD054H113011010, CAP. 51,200 BTU, 16Kw, UC #2 33

31
Evaporador Tipo Cassette Mod. 40VX007H11300010, 2.2 Voz y Datos 1 PAAN1 50.00 W 0.96 52.08VA 240V 0.21A 0.05 KvA 35.00 M 12 AWG 3.31 mm2 0.04 %
Kw, CAP. 7,500 BTU, UC #1
33

31
Evaporador Tipo Cassette Mod. 40VX009H11300010, 2.8 Cuarto de Maquinas de Elevadores 1 PAAN1 50.00 W 0.96 52.08VA 240V 0.21A 0.05 KvA 35.00 M 12 AWG 3.31 mm2 0.04 %
Kw, CAP. 9,600 BTU, UC #1
Evaporador Tipo Cassette Mod. 40VX009H11300010, 2.8 Cuarto de Maquinas de Elevadores 1 PAAN1 50.00 W 0.96 52.08VA 240V 0.21A 0.05 KvA 35.00 M 12 AWG 3.31 mm2 0.04 %
Kw, CAP. 9,600 BTU, UC #1 33

31
Evaporador Tipo Cassette Mod. 40VX009H11300010, 2.8 Anestecia 1 PAAN1 50.00 W 0.96 52.08VA 240V 0.21A 0.05 KvA 35.00 M 12 AWG 3.31 mm2 0.04 %
Kw, CAP. 9,600 BTU, UC #2 33

31
Estacion de enfermeria, Recuperacion 1 PAAN1 532.00 W 0.96 554.17VA 240V 2.22A 0.53 KvA 35.00 M 12 AWG 3.31 mm2 0.39 %
Evaporador Tipo Conductor de alta Presion Estatica Mod-
42VD054H113011010, CAP. 51,200 BTU, 16Kw, UC #2 33

CALCULO DE EVAPORADORES NIVEL 2


CANT No
EQUIPO AREA Panel PT COSɸ STCKT V IT Kva Longitud Conductor Smm2 E%
. CKT

Evaporador Tipo Cassette Mod. 40VK020H11300010, 5.6Kw,


Dormitorio 1 1 31 PAAN1 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 40.00 M 12 AWG 3.31 mm2 0.08 %
CAP. 19,100 BTU, UC #3
33

Evaporador Tipo Cassette Mod. 40VK020H11300010, 5.6Kw, 31


Dormitorio 2 1 PAAN1 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 40.00 M 12 AWG 3.31 mm2 0.08 %
CAP. 19,100 BTU, UC #3
33

36
Evaporador Tipo Cassette Mod. 40VK020H11300010, 5.6Kw, Dormitorio 3 1 PAAN1 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
CAP. 19,100 BTU, UC #3
38

36
Evaporador Tipo Cassette Mod. 40VK020H11300010, 5.6Kw, Dormitorio 4 1 PAAN1 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
CAP. 19,100 BTU, UC #3
38

36
Evaporador Tipo Cassette Mod. 40VK020H11300010, 5.6Kw, Dormitorio 5 1 PAAN1 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
CAP. 19,100 BTU, UC #3
38

36
Evaporador Tipo Cassette Mod. 40VK020H11300010, 5.6Kw, Dormitorio 6 1 PAAN1 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
CAP. 19,100 BTU, UC #3 38

31
Evaporador Tipo Cassette Mod. 40VK020H11300010, 5.6Kw, Dormitorio 7 1 PAAN1 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
CAP. 19,100 BTU, UC #3 33

31
Evaporador Tipo Cassette Mod. 40VK020H11300010, 5.6Kw, Dormitorio 8 1 PAAN1 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
CAP. 19,100 BTU, UC #3 33

36

Evaporador Tipo Cassette Mod. 40VK020H11300010, 5.6Kw, Dormitorio 9 1 PAAN1 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
CAP. 19,100 BTU, UC #3 38

36
Evaporador Tipo Cassette Mod. 40VK020H11300010, 5.6Kw, Dormitorio 10 1 PAAN1 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
CAP. 19,100 BTU, UC #3
38
31
Evaporador Tipo Cassette Mod. 40VK020H11300010, 5.6Kw, Dormitorio 11 1 PAAN1 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
CAP. 19,100 BTU, UC #3 33

36
Evaporador Tipo Cassette Mod. 40VK020H11300010, 5.6Kw, Dormitorio 12 1 PAAN1 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
CAP. 19,100 BTU, UC #3
Evaporador Tipo Cassette Mod. 40VK020H11300010, 5.6Kw, Dormitorio 12 1 PAAN1 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
CAP. 19,100 BTU, UC #3
38

36
Evaporador Tipo Cassette Mod. 40VK020H11300010, 5.6Kw, Dormitorio 13 1 PAAN1 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
CAP. 19,100 BTU, UC #3
38

36
Evaporador Tipo Cassette Mod. 40VK020H11300010, 5.6Kw, Estacion de Enfermeria 1 PAAN1 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
CAP. 19,100 BTU, UC #3
38

36
Evaporador Tipo Cassette Mod. 40VK012H11300010, 3.6Kw, Sub Estacion de Enfermeria 1 PAAN1 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
CAP. 12,300 BTU, UC #5
38

CALCULO DE EVAPORADORES NIVEL 3

CANT No
EQUIPO AREA Panel PT COSɸ STCKT V IT Kva Longitud Conductor Smm2 E%
. CKT

18
Evaporador Tipo Conductor de alta Presion Estatica Mod- Sala de espera 1 PT2N3 532.00 W 0.96 554.17VA 240V 2.22A 0.53 KvA 40.00 M 12 AWG 3.31 mm2 0.45 %
42VD054H113011010, CAP. 51,200 BTU, 16Kw, UC #5
20
18
Evaporador Tipo Cassette Mod. 40VX009H11300010, 2.8 Kw,
CAP. 9,600 BTU, UC #5
Caja 1 PT2N3 50.00 W 0.96 52.08VA 240V 0.21A 0.05 KvA 40.00 M 12 AWG 3.31 mm2 0.04 %
20

18
Evaporador Tipo Cassette Mod. 40VX009H11300010, 2.8 Kw, Admision 1 PT2N3 50.00 W 0.96 52.08VA 240V 0.21A 0.05 KvA 35.00 M 12 AWG 3.31 mm2 0.04 %
CAP. 9,600 BTU, UC #5 20

Evaporador Tipo Cassette Mod. 40VK030H11300010, 9Kw,


18
CAP. 30,700 BTU, UC #5 Gymnasio 1 PT2N3 160.00 W 0.96 166.67VA 240V 0.67A 0.16 KvA 35.00 M 12 AWG 3.31 mm2 0.12 %
20

Evaporador Tipo Cassette Mod. 40VK012H11300010, 3.6Kw, 18


CAP. 12,300 BTU, UC #5 Clinica 2 1 PT2N3 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
20
Evaporador Tipo Cassette Mod. 40VK012H11300010, 3.6Kw, 18
CAP. 12,300 BTU, UC #5 Clinica 1 1 PT2N3 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
20

Evaporador Tipo Cassette Mod. 40VK012H11300010, 3.6Kw, 31


Secretaria Direccion 1 PT2N3 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
CAP. 12,300 BTU, UC #6 33

Evaporador Tipo Cassette Mod. 40VK030H11300010, 9Kw, 31


CAP. 30,700 BTU, UC #6 Direccion 1 PT2N3 160.00 W 0.96 166.67VA 240V 0.67A 0.16 KvA 35.00 M 12 AWG 3.31 mm2 0.12 %
33

Evaporador Tipo Cassette Mod. 40VK012H11300010, 3.6Kw, 31


CAP. 12,300 BTU, UC #6
Neurologia Pediatrica 1 PT2N3 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
33
Evaporador Tipo Cassette Mod. 40VK012H11300010, 3.6Kw,
CAP. 12,300 BTU, UC #6 Sueño +Video+EEG 1 31 PT2N3 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
33
18
Evaporador Tipo Cassette Mod. 40VX009H11300010, 2.8 Kw,
Estacion de enfermeria 1 PT2N3 50.00 W 0.96 52.08VA 240V 0.21A 0.05 KvA 35.00 M 12 AWG 3.31 mm2 0.04 %
CAP. 9,600 BTU, UC #5 20

Evaporador Tipo Cassette Mod. 40VX007H11300010, 2.2 Kw, 18


CAP. 7,500 BTU, UC #5 Vestidor de Hombres 1 PT2N3 50.00 W 0.96 52.08VA 240V 0.21A 0.05 KvA 35.00 M 12 AWG 3.31 mm2 0.04 %
20
Evaporador Tipo Cassette Mod. 40VX007H11300010, 2.2 Kw, 18
CAP. 7,500 BTU, UC #5 Vestidor de Mujeres 1 PT2N3 50.00 W 0.96 52.08VA 240V 0.21A 0.05 KvA 35.00 M 12 AWG 3.31 mm2 0.04 %
Evaporador Tipo Cassette Mod. 40VX007H11300010, 2.2 Kw,
CAP. 7,500 BTU, UC #5 Vestidor de Mujeres 1 PT2N3 50.00 W 0.96 52.08VA 240V 0.21A 0.05 KvA 35.00 M 12 AWG 3.31 mm2 0.04 %
20

Evaporador Tipo Cassette Mod. 40VK020H11300010, 5.6Kw, Cuarto de Control 1 31 PT2N3 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
CAP. 19,100 BTU, UC #6
33

Pasillo 3, Recuperacion, Estacion de 31


Evaporador Tipo Conductor de alta Presion Estatica Mod- 1 PT2N3 532.00 W 0.96 554.17VA 240V 2.22A 0.53 KvA 35.00 M 12 AWG 3.31 mm2 0.39 %
42VD054H113011010, CAP. 51,200 BTU, 16Kw, UC #6
enfermeria
33

Anestecia 1 31 PT2N3 90.00 W 0.96 93.75VA 240V 0.38A 0.09 KvA 35.00 M 12 AWG 3.31 mm2 0.07 %
Evaporador Tipo Cassette Mod. 40VK012H11300010, 3.6Kw,
CAP. 12,300 BTU, UC #6 33
Tipo de Instalación COMERCIAL (Oficinas CORNAP)
Equipos de A/A a Instalar Carga M
Item Cant Descripción Vn (V)
1 1 Aire acondicionado de 9,000 btu 220
2 4 Aire acondicionado de 18,000 btu 220
3 6 Aire acondicionado de 24,000 btu 220
4 3 Aire acondicionado de 36,000 btu 220
5 2 Aire acondicionado de 60,000 btu 220
Potencia Activa kW Monofásicos de A/A
Potencia Aparente KVA Monofásico de A/A
Carga M

Item Cant Descripción Vn (V)


6 58 Luminaria LED cuadrada de 2'x2´de 40 watts 120
7 7 Luminaria LED cuadrada de 2'x4´de 60 watts 120
8 19 Luminaria LED circular de 18 watts 120
9 16 Luminaria LED circular de 9 watts 120
10 13 Luminaria LED cuadrada de 18 watts 120
11 2 Luminaria LED superficial de 10 watts (Exterior) 120
12 10 Luminaria led de emergencia 2.4watts 120
13 5 Luminaria tubo led superficial de 18 watts 120
14 4 Luminaria tubo led superficial de 9 watts 120
15 3 Reflector de luz led superficial de 100watts ( IP65) 120
16 4 Televisor pantalla led 100 watts 120
17 7 Extractor de gases con luz integrada 192watts 120
18 1 Abanico tipo techo uso comercial 65watts 120
19 1 Abanico de pedestal 50 watts 120
20 1 Oasis para climatizar agua 720 watts 120
21 2 Refrigerador inverter grande 360 watts 120
22 2 Refrigerador inverter pequeño 96.72 watts 120
23 3 Microondas 1.2 KW 120
24 2 Cafeteras 1,089.6 watts 120
25 1 Servidor CORNAP-120V 120
26 1 Servidor CNPC-120V 120
27 1 UPS Central Telefonica Panasonic tes824-58 w 120
28 1 Impresora Grande para Archivo 1,920 watts 120
29 1 Impresora Grande 1,260 watts 120
30 2 Impresora pequeña 624 watts 120
31 12 Impresoras personales, pequeñas 144 watts 120
32 2 Scanner 192 watts 120
33 2 Accesspoint 120 watts 120
34 1 Datashow 360 wattts 120
35 1 Cortina de proyección 120
36 12 T/C para máquina herramientas pequeñas 250 W 120
37 2 Computador del servidor /ARCHIVO 120
38 1 Espera para el Servido Nuevo CORNAP -120V 120
39 42 Computadora 120V- 240 watts 120
40 1 Espera para Máquina de Soldar 220
41 1 Ventilador para encustrar en pared 192 watts 120
42 16 Bomba de condensado para A/A 120
Potencia Total a Instalar kW Monofásicos Insta
Nota: Datos Obligatorios a digitar Factor de Demand
* Tipo de Utilizacion kW Monofásicos Máx
* Cantidad de Equipos con iguales características Factor de Carga
* Potencia por equipo en kW kW Monofásicos Prom
Para Cargas de Uso Continuo FS=1.25 Factor de Potenci
Para Cargas de Uso no Continuo FS = 1 kVA Monofásicos Pro
Para el Factor Demanda al 100% =1

PTD = Potencia Total Demandada KVA

Potencia Activa Instalada = Ʃ de las Pote


PTinst. = Ʃ Pinst.

Potencia Activa Máxima= Potencia Activa Instalada x Factor Demanda


Pmáx. = Pinst. X FD

Potencia Activa Promedio = Potencia Activa Máxima x Factor de Carga


Pprom. = Pmáx. X (FC)

Potencia Aparente Promedio en KVA = Potencia Activa Promedio / Factor de Pot


Sprom. = Pprom. / FP

Potencia Total Demandada en KVA = Potencia Activa Máxima / Factor de Po


PTD en (KVA) = Pmáx.(KW) / (FP) + S( KVA) de A / A
MERCIAL (Oficinas CORNAP)
Carga Monofásica Carga Trifásica
In (A) FD=100% P (kW) Total (kW) A/A Vn (V) In (A) P (kW)
4.8 1 1.056 1.056
8.6 1 1.892 7.568
13 1 2.86 17.16
16.8 1 3.696 11.088
29.5 1 6.49 12.98
kW Monofásicos de A/A a Instalar 49.852
KVA Monofásico de A/A a Instalar 58.65
Carga Monofásica
Factor de
In (A) seguridad P (kW) Total (kW)
0.333 1.25 0.05 2.90
0.50 1.25 0.075 0.525
0.15 1.25 0.023 0.437
0.075 1.25 0.012 0.192
0.15 1.25 0.023 0.299
0.083 1.25 0.013 0.026
0.02 1.25 0.003 0.03
0.15 1 0.018 0.09
0.075 1 0.009 0.036
0.833 1 0.1 0.3
0.833 1.25 0.125 0.5
1.6 1 0.192 1.344
0.542 1.25 0.082 0.082
0.417 1.25 0.063 0.063
6 1.25 0.9 0.9
3 1.25 0.45 0.9
0.806 1.25 0.121 0.242
10 1 1.2 3.6
9.08 1.25 1.362 2.724
10 1.25 1.5 1.5
10 1.25 1.5 1.5
0.567 1.25 0.086 0.086
16 1.25 2.4 2.4
10.5 1.25 1.575 1.575
5.2 1.25 0.78 1.56
1.2 1.25 0.18 2.16
1.6 1.25 0.24 0.48
1 1.25 0.15 0.3
3 1.25 0.45 0.45
2 1.25 0.3 0.3
2.083 1 0.25 3
6 1.25 0.9 1.8
12 1.25 1.8 1.8
2 1.25 0.3 12.6
30 1.25 8.25 8.25
1.6 1 0.192 0.192
0.6 1 0.072 1.152
kW Monofásicos Instalados 56.30 kW Trifásicos Instalados
Factor de Demanda 0.65 Factor de Demanda
kW Monofásicos Máximos 36.59 kW Trifásicos Máximos
Factor de Carga 0.80 Factor de Carga
kW Monofásicos Promedio 29.27 kW Trifásicos Promedio
Factor de Potencia 0.85 Factor de Potencia
kVA Monofásicos Promedio 34.44 kVA Trifásicos Promedio

a Total Demandada KVA 101.70 Equivalente a: 112.5KVA , Primario = 7.6KV / 13.2 KV


Banco de transformadores de Distribución = 3 x 37.5KVA
Secundario = 120V/208V

ia Activa Instalada = Ʃ de las Potencias Instaladas.

talada x Factor Demanda

Máxima x Factor de Carga

cia Activa Promedio / Factor de Potencia

cia Activa Máxima / Factor de Potencia + Potencia Aparente de Aires Acondicionados


A/A
sica
Total (kW)

0.00

0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1.00
0.00
1.00
0.00
0.85
0.00

ario = 7.6KV / 13.2 KV


stribución = 3 x 37.5KVA
ecundario = 120V/208V
Tipo de Instalación
Equipo
Item Cant
1 1
2 4
3 6
4 3
5 2
Potencia
Potencia A

Item Cant
6 58
7 7
8 19
9 16
10 13
11 2
12 10
13 5
14 4
15 3
16 4
17 7
18 1
19 1
20 1
21 2
22 2
23 3
24 2
25 1
26 1
27 1
28 1
29 1
30 2
31 12
32 2
33 2
34 1
35 1
36 12
37 2
38 1
39 42
40 1
41 1
42 16
Potenc
Nota: Datos Obligatorios a digitar
* Tipo de Utilizacion
* Cantidad de Equipos con iguales caracter
* Potencia por equipo en kW
Para Cargas de Uso Continuo FS=1.25
Para Cargas de Uso no Continuo FS = 1
Para el Factor Demanda al 100% =1
Tipo de Instalación COMERCIAL (Oficinas CORNAP)
Equipos de A/A a Instalar Carga Monofásica
Descripción Vn (V) In (A) FD=100%
Aire acondicionado de 9,000 btu 220 4.8 1
Aire acondicionado de 18,000 btu 220 8.6 1
Aire acondicionado de 24,000 btu 220 13 1
Aire acondicionado de 36,000 btu 220 16.8 1
Aire acondicionado de 60,000 btu 220 29.5 1
Potencia Activa kW Monofásicos de A/A a Instalar
Potencia Aparente KVA Monofásico de A/A a Instalar
Carga Monofásica
Factor de
Descripción Vn (V) In (A) seguridad
Luminaria LED cuadrada de 2'x2´de 40 watts 120 0.333 1.25
Luminaria LED cuadrada de 2'x4´de 60 watts 120 0.50 1.25
Luminaria LED circular de 18 watts 120 0.15 1.25
Luminaria LED circular de 9 watts 120 0.075 1.25
Luminaria LED cuadrada de 18 watts 120 0.15 1.25
Luminaria LED superficial de 10 watts (Exterior) 120 0.083 1.25
Luminaria led de emergencia 2.4watts 120 0.02 1.25
Luminaria tubo led superficial de 18 watts 120 0.15 1
Luminaria tubo led superficial de 9 watts 120 0.075 1
Reflector de luz led superficial de 100watts ( IP65) 120 0.833 1
Televisor pantalla led 100 watts 120 0.833 1.25
Extractor de gases con luz integrada 192watts 120 1.6 1
Abanico tipo techo uso comercial 65watts 120 0.542 1.25
Abanico de pedestal 50 watts 120 0.417 1.25
Oasis para climatizar agua 720 watts 120 6 1.25
Refrigerador inverter grande 360 watts 120 3 1.25
Refrigerador inverter pequeño 96.72 watts 120 0.806 1.25
Microondas 1.2 KW 120 10 1
Cafeteras 1,089.6 watts 120 9.08 1.25
Servidor CORNAP-120V 120 10 1.25
Servidor CNPC-120V 120 10 1.25
UPS Central Telefonica Panasonic tes824-58 w 120 0.567 1.25
Impresora Grande para Archivo 1,920 watts 120 16 1.25
Impresora Grande 1,260 watts 120 10.5 1.25
Impresora pequeña 624 watts 120 5.2 1.25
Impresoras personales, pequeñas 144 watts 120 1.2 1.25
Scanner 192 watts 120 1.6 1.25
Accesspoint 120 watts 120 1 1.25
Datashow 360 wattts 120 3 1.25
Cortina de proyección 120 2 1.25
T/C para máquina herramientas pequeñas 250 W 120 2.083 1
Computador del servidor /ARCHIVO 120 6 1.25
Espera para el Servido Nuevo CORNAP -120V 120 12 1.25
Computadora 120V- 240 watts 120 2 1.25
Espera para Máquina de Soldar 220 30 1.25
Ventilador para encustrar en pared 192 watts 120 1.6 1
Bomba de condensado para A/A 120 0.6 1
Potencia Total a Instalar kW Monofásicos Instalados
Obligatorios a digitar Factor de Demanda
kW Monofásicos Máximos
e Equipos con iguales características Factor de Carga
or equipo en kW kW Monofásicos Promedio
de Uso Continuo FS=1.25 Factor de Potencia
de Uso no Continuo FS = 1 kVA Monofásicos Promedio
r Demanda al 100% =1

PTD = Potencia Total Demandada KVA

Potencia Activa Instalada = Ʃ de las Potencias Instaladas.


PTinst. = Ʃ Pinst.

Potencia Activa Máxima= Potencia Activa Instalada x Factor Demanda


Pmáx. = Pinst. X FD

Potencia Activa Promedio = Potencia Activa Máxima x Factor de Carga


Pprom. = Pmáx. X (FC)

Potencia Aparente Promedio en KVA = Potencia Activa Promedio / Factor de Potencia


Sprom. = Pprom. / FP

Potencia Total Demandada en KVA = Potencia Activa Máxima / Factor de Potencia


STD = Pmáx. / (FP)
P)
arga Monofásica Carga Trifásica
P (kW) Total (kW) A/A Vn (V) In (A) P (kW) Total (kW)
1.056 1.056
1.892 7.568
2.86 17.16
3.696 11.088
6.49 12.98 0.00
e A/A a Instalar 49.852
e A/A a Instalar 58.65
arga Monofásica

P (kW) Total (kW)


0.05 2.90 0.00
0.075 0.525 0.00
0.023 0.437 0.00
0.012 0.192 0.00
0.023 0.299 0.00
0.013 0.026 0.00
0.003 0.03 0.00
0.018 0.09 0.00
0.009 0.036 0.00
0.1 0.3 0.00
0.125 0.5 0.00
0.192 1.344 0.00
0.082 0.082 0.00
0.063 0.063 0.00
0.9 0.9 0.00
0.45 0.9 0.00
0.121 0.242 0.00
1.2 3.6 0.00
1.362 2.724 0.00
1.5 1.5 0.00
1.5 1.5 0.00
0.086 0.086 0.00 0.483
2.4 2.4 0.00
1.575 1.575 0.00
0.78 1.56 0.00
0.18 2.16 0.00
0.24 0.48 0.00
0.15 0.3 0.00
0.45 0.45 0.00
0.3 0.3 0.00
0.25 3 0.00
0.9 1.8 0.00
1.8 1.8 0.00
0.3 12.6 0.00
8.25 8.25 0.00
0.192 0.192 0.00
0.072 1.152 0.00
os Instalados 56.30 kW Trifásicos Instalados 0.00
emanda 0.65 Factor de Demanda 1.00
os Máximos 36.59 kW Trifásicos Máximos 0.00
Carga 0.80 Factor de Carga 1.00
os Promedio 29.27 kW Trifásicos Promedio 0.00
Potencia 0.85 Factor de Potencia 0.85
os Promedio 34.44 kVA Trifásicos Promedio 0.00

101.70 Banco de transformadores de Distribución = 3 x 37.5KVA


Equivalente a: 112.5KVA , 7.6KV / 13.2 KV

Potencias Instaladas.

r de Potencia

or de Potencia
Hora Dinst Dprom Dmáx Censo FD Hora
0 0.2 0.379 0.725 1.21 0.52 0
1 0.175 0.379 0.725 1.21 0.52 1
2 0.175 0.379 0.725 1.21 0.52 2
3 0.175 0.379 0.725 1.21 0.52 3
4 0.175 0.379 0.725 1.21 0.52 4
5 0.2 0.379 0.725 1.21 0.52 5
6 0.225 0.379 0.725 1.21 0.52 6
7 0.3 0.379 0.725 1.21 0.52 7
8 0.35 0.379 0.725 1.21 0.52 8
9 0.35 0.379 0.725 1.21 0.52 9
10 0.35 0.379 0.725 1.21 0.52 10
11 0.325 0.379 0.725 1.21 0.52 11
12 0.3 0.379 0.725 1.21 0.52 12
13 0.325 0.379 0.725 1.21 0.52 13
14 0.375 0.379 0.725 1.21 0.52 14
15 0.4 0.379 0.725 1.21 0.52 15
16 0.475 0.379 0.725 1.21 0.52 16
17 0.525 0.379 0.725 1.21 0.52 17
18 0.65 0.379 0.725 1.21 0.52 18
19 0.725 0.379 0.725 1.21 0.52 19
20 0.7 0.379 0.725 1.21 0.52 20
21 0.65 0.379 0.725 1.21 0.52 21
22 0.55 0.379 0.725 1.21 0.52 22
23 0.475 0.379 0.725 1.21 0.52 23
24 0.325 0.379 0.725 1.21 0.52 24
0.52 0.6 0.87
Dinst Dprom Dmáx FD Hora Dinst Dprom
0.60 2.92 5.30 0.55 0 0.00 2.92
0.60 2.92 5.30 0.55 1 0.00 2.92
0.60 2.92 5.30 0.55 2 0.00 2.92
0.60 2.92 5.30 0.55 3 0.00 2.92
0.60 2.92 5.30 0.55 4 0.00 2.92
0.60 2.92 5.30 0.55 5 0.00 2.92
0.70 2.92 5.30 0.55 6 0.00 2.92
4.00 2.92 5.30 0.55 7 0.00 2.92
4.50 2.92 5.30 0.55 8 0.00 2.92
4.50 2.92 5.30 0.55 9 0.00 2.92
4.50 2.92 5.30 0.55 10 0.00 2.92
4.50 2.92 5.30 0.55 11 0.00 2.92
5.00 2.92 5.30 0.55 12 0.00 2.92
5.20 2.92 5.30 0.55 13 1.90 2.92
5.20 2.92 5.30 0.55 14 6.80 2.92
5.30 2.92 5.30 0.55 15 10.50 2.92
5.20 2.92 5.30 0.55 16 11.50 2.92
5.20 2.92 5.30 0.55 17 12.00 2.92
5.00 2.92 5.30 0.55 18 11.00 2.92
5.00 2.92 5.30 0.55 19 10.50 2.92
2.30 2.92 5.30 0.55 20 6.80 2.92
1.30 2.92 5.30 0.55 21 1.90 2.92
0.70 2.92 5.30 0.55 22 0.00 2.92
0.60 2.92 5.30 0.55 23 0.00 2.92
0.60 2.92 5.30 0.55 24 0.00 2.92
72.90 72.90
5.20714286 11.2153846
Dmáx FD
6
12.00 0.24
12.00 0.24 5
12.00 0.24
12.00 0.24 4

Potencia (kW)
12.00 0.24
12.00 0.24 3
12.00 0.24
2
12.00 0.24
12.00 0.24 1
12.00 0.24
12.00 0.24 0
12.00 0.24 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
12.00 0.24 Tiempo (h)
12.00 0.24
12.00 0.24
12.00 0.24 14
13
12.00 0.24
12
12.00 0.24 11
12.00 0.24 10
9
12.00 0.24
Potencia (kW)

8
12.00 0.24 7
12.00 0.24 6
12.00 0.24 5
4
12.00 0.24 3
12.00 0.24 2
1
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Tiempo (h)
Dinst
Dprom
Dmáx

6 17 18 19 20 21 22 23 24

Dinst
Dprom
Dmáx

6 17 18 19 20 21 22 23 24
Factores de Demanda y de Cargas Típicas Demandas en Residencias Típicas
Instalación Típica FD FC Clasificación
kW instalados
kW Demandado
Residencia 32% 60% Clase A 41.67 8.0 8.00064
Residencia 50% 70% Clase B 26.05 5.0 5.0016
Apartamen 40% 50% Clase C 15.63 3.0 3.00096
Hospitales 40% 65% Clase D 7.82 1.5 1.50144
Escuelas 70% 80% Clase E 5.21 1.0 1.00032
Bancos y F 70% 80% Clase F 4.17 0.8 0.80064
Iglesias 60% 70% Clase G 3.13 0.6 0.60096
Hoteles 50% 60% Clase H 2.09 0.4 0.40128
Oficinas 65% 80%
Tiendas, Li 65% 60%
Supermerc 80% 75%
Coeficiente de Simultaneidad
Suministros Factor
1 1.00
2a4 0.80
5 a 15 0.60
16 o más 0.40
1.2

0.8
Demanda en KiloWatts

0.6

0.4

0.2

0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22

Tiempo en Horas
Dinst
Dprom
Dmáx
Censo

6 17 18 19 20 21 22 23 24