Cliente: Novicompu

Proyecto: Subsuelo
Notas: Plano-Eléctrico

Diseñador:

Rev. n1 Fecha: Calculado por: DOC


Rev. n2 Dibujante:
Diseñador: Nombre de archivo:
Rev. n3
REVISIONES Fecha: Firmas Aprobador: Record #:
Criterios de cálculo y dimensionamiento

Método-Estándar de Cálculo CEI 11-25

Standard for cable dimensioning CEI 64-8

Overload Overload verifications are made according the following relations: IB <= In <= Iz and I2 <= 1.45*Iz

Legenda:

IB = the current for which the circuit is designed

In = nominal current of the protective device (For adjustable protective devices, the nominal current In is the current setting selected)

I2 = current ensuring effective operation in the conventional time of the protective device

Iz = capacidad de conducción del cable acorde al estándar elegido

Cortocircuito Interruptores automáticos y fusibles son dimensions con la capacidad de ruptura mayor a la máxima corriente de cortocircuito en el punto de instalación.

Circuit breakers dimensioned according to IEC 60497-2 are also chosen with the making capacity Icm higher than the maxiimum peak current

La protección por cortocircuito debe satisfacer la siguiente regla I2t <= K2S2

Legenda:

I2t = energía pasante a la corriente máxima de cortocircuito (definida por el fabricante)

S = sección de los conductores

K = factor definido en IEC60364-4-43 tabla 43A y IEC60364-5-54 tablas A.54.2, A.54.4 y A-54.5

Contacto indirecto Sistemas TT: la verificación es Idn * Rt <= Vo, o Im <= Ib mín

Sistemas TN: la verificación es Im <= Ib mín

Leyenda:

Idn = sensibilidad del interruptor diferencial

Ra = resistencia a tierra

Vo = max admitted contact voltage

Im = valor de tripeo del dispositivo de protección al tiempo límite

Ib mín = mínima corriente de cortocircuito al final de la línea

Selectividad y Back-up Los valores de selectividad y back-up son determinados por tests de laboratorio del fabricante

Discriminación no requerida en la instalación

Backup not required in the installation

Rev. n1 Fecha: Descripcion Cliente: Novicompu Numero de Dibujo:


Rev. n2 Dibujante: Plano-Eléctrico Proyecto: Subsuelo
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 1 1
1 2 3 4 5 6 7 8 9

    
-QF1.1 -QF1.2 -QF1.3 -QF1.4 -QF1.5
A

Un [V] 120
LLLN / TN-S
Ik LLL [kA]10.0
Ik LN [kA]6.0
Ik LPE [kA]6.0
B P [kW] 0.0
Q [kvar]0.0

D    

   

E Descripcion Iluminacion 1 Dicroicos Luces led TomaCorrientes


Carga

Voltaje [V] dV % 69 0.04 120 0.00 120 0.00 120 0.01

(!) Important notice about coordination to be verified in Discrimination report


Potencia Activa [kW] UF % 0.50 0.7 0.03 0.7 0.04 0.7 0.50 0.4
Ir [A] Cosphi 8.0 0.90 0.2 0.90 0.2 0.90 2.7 0.90
Fabricante ABB ABB ABB ABB ABB

(*) El interruptor automático es selectivo con otro insterruptores.


Circuit breaker/Disconnector A1A 125 TMF 15-300 S201L-C6 NA S204-C10 S204-C10 S204-Z10
ComandO / protección

(**) El interruptor tiene back-up con otros interruptores.


Polos In [A] 4P 15 1P+N 6 4P 10 4P 10 4P 10
Ith [A] Idn [A] 15.0 6.0 10.0 10.0 10.0
Im [A] Icu/Icn [kA] 300.0 25.0 60.0 10.0 100.0 20.0 100.0 20.0 30.0 20.0
F Fusible Tamaño [A]
Contactor In [A]
Contactor In [A]
Relé de sobrecarga Configuración [A]
Tipo de cable Cu-PVC Cu-PVC Cu-PVC Cu-PVC
Línea de Distribución

Sección 2x(1x1.5)+1G1.5 4x(1x1.5)+1G1.5 4x(1x1.5)+1G1.5 4x(1x1.5)+1G1.5


Longitud (m) [m] Iz [A] 20 20.0 8 20.0 8 20.0 50 20.0
Ib L1 [A] Núm. instalación 0.1 0.1 11 0.0 11 0.0 11 0.0 11
Ib L2 [A] dV % 0.0 0.04 0.0 0.00 0.0 0.00 0.0 0.01
Ib L3 [A] Ik mín [kA] 0.0 0.08 0.0 0.20 0.0 0.20 0.0 0.03
Ib N [A] Ik máx [kA] 0.1 0.1 6.00 0.0 10.00 0.0 10.00 0.0 10.00
G
Rev. n1 Fecha: Descripcion Cliente: Novicompu Numero de Dibujo:
Rev. n2 Dibujante: Plano-Eléctrico Proyecto: Subsuelo
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 1 1
1 2 3 4 5 6 7 8 9
Distribución

Voltaje de Referencia [V] 120 Corriente de cortocircuito simétrica LLL [kA] 10.00
Fases LLLN Corriente de cortocircuito LN [kA] 6.00
Sistema de distribución TN-S Corriente de cortocircuito LPE [kA] 6.00

Potencia Activa P [kW] 0.01 Cmax 1.10


Potencia Reactiva Q [kvar] 0.00 Resistencia a Voltaje de Referencia [mOhm] 0.762
Ib (A) [A] 0.03 Reactancia a Voltaje Referencial [mOhm] 7.583
Factor de potencia Cosphi 0.90 Impedancia a Voltaje Referencial [mOhm] 7.621

Rev. n1 Fecha: Descripcion Cliente: Novicompu Numero de Dibujo:


Rev. n2 Dibujante: Plano-Eléctrico Proyecto: Subsuelo
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 1 1
Protección de cables

-WC1.2 Iluminacion 1
Datos de carga

Fases - Sistema de Distribución LN / TN-S (L1-N) Overload: protected by -QF1.2 S201L-C6 NA


Pasado
Voltaje [V] 69.282 Overload: Ib ( 0.06[A]) <= Ith ( 6.00[A]) <= Iz (20.00[A]) and If ( 8.70[A]) <= 1.45*Iz (29.00[A]); Uref=120V
IB (A) [A] 0.1
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF1.2 S201L-C6 NA
Protection checks

Cosphi 0.90 Pasado


Short-circuit: Protection guaranteed up to Ik LN ( 6.00[kA]), Ik L-PE ( 6.00[kA]); Uref=120V
Sección transversal de los cables 2x(1x1.5)+1G1.5
Aislador Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QF1.2 S201L-C6 NA
Pasado
Longitud (m) [m] 20 2 People protection: I@Max tripping time ( 0.06[kA])<=Ikmin L-PE ( 0.08[kA]); Trip time=0.80[s]; Uref=120V
Cable

Iz (A) [A] 20.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dV ( ) 0.04
Temp de Trabajo (°C) [°C] 30.0
Power loss [W] 0.00 Indirect touch at terminal 1 (current flowing upstream): protected by
K2S2 [A2s] 29672 2

-WC1.3 Dicroicos
Datos de carga

Fases - Sistema de Distribución LLLN / TN-S Overload: protected by -QF1.3 S204-C10


Pasado
Voltaje [V] 120 Overload: Ib ( 0.00[A]) <= Ith (10.00[A]) <= Iz (20.00[A]) and If (14.50[A]) <= 1.45*Iz (29.00[A]); Uref=120V
IB (A) [A] 0.0
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF1.3 S204-C10
Protection checks

Cosphi 0.90 Falla


Short-circuit: Intersection found in Energy Curvas at I ( 8.72[kA]) < Ik LLL max (10.00[kA]); Uref=120V
Sección transversal de los cables 4x(1x1.5)+1G1.5
Aislador Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QF1.3 S204-C10
Pasado
Longitud (m) [m] 8 2 People protection: I@Max tripping time ( 0.10[kA])<=Ikmin L-PE ( 0.20[kA]); Trip time=0.80[s]; Uref=120V
Cable

Iz (A) [A] 20.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dV ( ) 0.00
Temp de Trabajo (°C) [°C] 30.0
Power loss [W] 0.00 Indirect touch at terminal 1 (current flowing upstream): protected by
K2S2 [A2s] 29672 2

-WC1.4 Luces led


Datos de carga

Fases - Sistema de Distribución LLLN / TN-S Overload: protected by -QF1.4 S204-C10


Pasado
Voltaje [V] 120 Overload: Ib ( 0.00[A]) <= Ith (10.00[A]) <= Iz (20.00[A]) and If (14.50[A]) <= 1.45*Iz (29.00[A]); Uref=120V
IB (A) [A] 0.0
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF1.4 S204-C10
Falla
Protection checks

Cosphi 0.90
Short-circuit: Intersection found in Energy Curvas at I ( 8.72[kA]) < Ik LLL max (10.00[kA]); Uref=120V
Sección transversal de los cables 4x(1x1.5)+1G1.5
Aislador Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QF1.4 S204-C10
Pasado
Longitud (m) [m] 8 2 People protection: I@Max tripping time ( 0.10[kA])<=Ikmin L-PE ( 0.20[kA]); Trip time=0.80[s]; Uref=120V
Cable

Iz (A) [A] 20.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dV ( ) 0.00
Temp de Trabajo (°C) [°C] 30.0
Power loss [W] 0.00 Indirect touch at terminal 1 (current flowing upstream): protected by
K2S2 [A2s] 29672 2

Rev. n1 Fecha: Descripcion Cliente: Novicompu Numero de Dibujo:


Rev. n2 Dibujante: Plano-Eléctrico Proyecto: Subsuelo
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 1 2 2
Protección de cables

-WC1.5 TomaCorrientes
Datos de carga

Fases - Sistema de Distribución LLLN / TN-S Overload: protected by -QF1.5 S204-Z10


Pasado
Voltaje [V] 120 Overload: Ib ( 0.01[A]) <= Ith (10.00[A]) <= Iz (20.00[A]) and If (14.50[A]) <= 1.45*Iz (29.00[A]); Uref=120V
IB (A) [A] 0.0
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF1.5 S204-Z10
Protection checks

Cosphi 0.90 Falla


Short-circuit: Intersection found in Energy Curvas at I ( 8.72[kA]) < Ik LLL max (10.00[kA]); Uref=120V
Sección transversal de los cables 4x(1x1.5)+1G1.5
Aislador Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QF1.5 S204-Z10
Pasado
Longitud (m) [m] 50 2 People protection: I@Max tripping time ( 0.03[kA])<=Ikmin L-PE ( 0.03[kA]); Trip time=0.80[s]; Uref=120V
Cable

Iz (A) [A] 20.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dV ( ) 0.01
Temp de Trabajo (°C) [°C] 30.0
Power loss [W] 0.00 Indirect touch at terminal 1 (current flowing upstream): protected by
K2S2 [A2s] 29672 2
Datos de carga

Fases - Sistema de Distribución Overload: protected by


Voltaje [V]
IB (A) [A]
1 Short circuit at terminal 1 (current flowing downstream): protected by
Protection checks

Cosphi
Sección transversal de los cables
Aislador Indirect touch at terminal 2 (current flowing downstream): protected by
Longitud (m) [m] 2
Cable

Iz (A) [A]
1 Short circuit at terminal 2 (current flowing upstream): protected by
dV ( )
Temp de Trabajo (°C) [°C]
Power loss [W] Indirect touch at terminal 1 (current flowing upstream): protected by
K2S2 [A2s] 2
Datos de carga

Fases - Sistema de Distribución Overload: protected by


Voltaje [V]
IB (A) [A]
1 Short circuit at terminal 1 (current flowing downstream): protected by
Protection checks

Cosphi
Sección transversal de los cables
Aislador Indirect touch at terminal 2 (current flowing downstream): protected by
Longitud (m) [m] 2
Cable

Iz (A) [A]
1 Short circuit at terminal 2 (current flowing upstream): protected by
dV ( )
Temp de Trabajo (°C) [°C]
Power loss [W] Indirect touch at terminal 1 (current flowing upstream): protected by
K2S2 [A2s] 2

Rev. n1 Fecha: Descripcion Cliente: Novicompu Numero de Dibujo:


Rev. n2 Dibujante: Plano-Eléctrico Proyecto: Subsuelo
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 2 2
Lista de Cargas

-L1.2 Iluminacion 1
Fases - Sistema de Distribución LN / TN-S (L1-N) Factor de utlización [%] 0.7 Voltage computado [V] 69.3
Voltaje nominal [V] 69.282 Potencia Activa P [kW] 0.00 Máx caída de tensión admitida por el standard [%] 4.0
IB [A] 8.0 Potencia Reactiva Q [kvar] 0.00 Máx caída de tensión admitida por el usuario [%] 4.0
Cosphi 0.90 Caída de tensión calculada [%] 0.04

-L1.3 Dicroicos
Fases - Sistema de Distribución LLLN / TN-S Factor de utlización [%] 0.7 Voltage computado [V] 120.0
Voltaje nominal [V] 120 Potencia Activa P [kW] 0.00 Máx caída de tensión admitida por el standard [%] 4.0
IB [A] 0.2 Potencia Reactiva Q [kvar] 0.00 Máx caída de tensión admitida por el usuario [%] 4.0
Cosphi 0.90 Caída de tensión calculada [%] 0.00

-L1.4 Luces led


Fases - Sistema de Distribución LLLN / TN-S Factor de utlización [%] 0.7 Voltage computado [V] 120.0
Voltaje nominal [V] 120 Potencia Activa P [kW] 0.00 Máx caída de tensión admitida por el standard [%] 4.0
IB [A] 0.2 Potencia Reactiva Q [kvar] 0.00 Máx caída de tensión admitida por el usuario [%] 4.0
Cosphi 0.90 Caída de tensión calculada [%] 0.00

-L1.5 TomaCorrientes
Fases - Sistema de Distribución LLLN / TN-S Factor de utlización [%] 0.4 Voltage computado [V] 120.0
Voltaje nominal [V] 120 Potencia Activa P [kW] 0.00 Máx caída de tensión admitida por el standard [%] 4.0
IB [A] 2.7 Potencia Reactiva Q [kvar] 0.00 Máx caída de tensión admitida por el usuario [%] 4.0
Cosphi 0.90 Caída de tensión calculada [%] 0.01

Fases - Sistema de Distribución Factor de utlización [%] Voltage computado [V]


Voltaje nominal [V] Potencia Activa P [kW] Máx caída de tensión admitida por el standard [%] 4.0
IB [A] Potencia Reactiva Q [kvar] Máx caída de tensión admitida por el usuario [%]
Cosphi Caída de tensión calculada [%]

Fases - Sistema de Distribución Factor de utlización [%] Voltage computado [V]


Voltaje nominal [V] Potencia Activa P [kW] Máx caída de tensión admitida por el standard [%] 4.0
IB [A] Potencia Reactiva Q [kvar] Máx caída de tensión admitida por el usuario [%]
Cosphi Caída de tensión calculada [%]

Fases - Sistema de Distribución Factor de utlización [%] Voltage computado [V]


Voltaje nominal [V] Potencia Activa P [kW] Máx caída de tensión admitida por el standard [%] 4.0
IB [A] Potencia Reactiva Q [kvar] Máx caída de tensión admitida por el usuario [%]
Cosphi Caída de tensión calculada [%]

Rev. n1 Fecha: Descripcion Cliente: Novicompu Numero de Dibujo:


Rev. n2 Dibujante: Plano-Eléctrico Proyecto: Subsuelo
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 1 1