RANGO ALTO Tabla 2.

Factores de simultaneidad
Consumo Tasa Anual de No Factor de No
promedio Potencia Inicial Crecimiento(%) Clientes Simultaneidad Clientes
301 - 600 3.5 1 1 1 16
2 0.91 17
3 0.83 18
CALIBRE K 4 0.76 19
4 0.00332 5 0.71 20
2 0.00224 6 0.66 21
1/0 0.00155 7 0.62 22
2/0 0.00131 8 0.59 23
9 0.56 24
10 0.53 25
11 0.51 26
12 0.5 27
13 0.48 28
14 0.47 29
15 0.46 30 o mas
de simultaneidad
Factor de CANTIDAD DE kw POR USUARIO A
Simultaneidad USUARIOS kw POR USUARIO 15 AÑOS
0.45 1 3.50 4.06
0.44 2 6.37 7.40
0.44 3 8.72 10.12
0.43 4 10.64 12.35
0.43 5 12.43 14.43
0.42 6 13.86 16.09
0.42 7 15.19 17.64
0.42 8 16.52 19.18
0.41 9 17.64 20.48
0.41 10 18.55 21.54
0.41 11 19.64 22.80
0.41 12 21.00 24.38
0.41 13 21.84 25.36
0.41 14 23.03 26.74
0.4 15 24.15 28.04
16 25.20 29.26
17 26.18 30.39
18 27.72 32.18
19 28.60 33.20
20 30.10 34.95
21 30.87 35.84
22 32.34 37.55
23 33.81 39.25
24 34.44 39.98
25 35.88 41.65
26 37.31 43.32
27 38.75 44.98
28 40.18 46.65
29 41.62 48.31
30 42.00 48.76
0.43
CALCULO D
Tramo Numero de Lotes
LINEA 1 A-B 6
E-F 9
LINEA 2
A-E 18
G-H 7
LINEA 3
A-G 16

TOTAL USUARIOS 45

CALCULO D

Columna1 Tramo Numero de Lotes

LINEA 1 80-79 1
79-71 1
71-70 2
70-68 1
69-67 2
67-66 3
66-64 2
75-74 2
74-76 2
72-73 3
73-76 2
76-83 1
83-tr1 2
24

LINEA 2 109-111 2
110-111 2
108-111 2
111-112 2
112-92 1
93-92 1
92-91 1
91-87 1
90-87 2
87-88 1
89-81 1
81-82 2
82-TR1 5
23

LINEA 3 100-101 2
101-102 2
102-103 4
103-105 3
104-105 3
107-105 4
105-106 5
106-96 1
99-98 3
98-96 4
94-95 5
95-96 4
96-97 1
86-85 3
85-84 2
84-TR1 3

TOTAL USUARIOS 143

CALCULO D
Columna1 CALCULO DE REGULACION DE TENSIONCALCULO
TRAFO 3DE REGULACION DE TENSION TRAFO 4

Tramo Numero de Lotes

LINEA 1 173-174 1
145-144 1
174-143 2
143-142 1
139-142 2
138-139 2
146-147 3
138-135 1
135-134 1
134-T3 1
1
3
LINEA 2 2
2
3
6
1
1
2
2
1
2
3
3
3
LINEA 3 2
2
2
3
5
4
4
4
3
2
3
1
3
2
1
1
3
3
2
1
LINEA 4 1
1
1
1
1
1
2
1
4
3
2
3
122-121 2
121-133 2
133-132 1
132-T3 3
TOTAL USUARIOS

CALCULO D
Tramo Numero de Lotes
C-D 5
LINEA 1 B-C 12
A-B 22

F-G 5
LINEA 2 E-F 13
A-E 20
TOTAL USUARIOS 46

CALCULO D
Tramo Numero de Lotes
D-E 3
C-D 8
LINEA 1
B-C 12
A-B 19

J-I 3
I-H 6
LINEA 2 H-G 11
G-F 14
F-A 17
TOTAL USUARIOS 42

CALCULO D
Tramo Numero de Lotes
B-C 10
LINEA 1
A-B 21

E-F 4
LINEA 2 D-E 11
A-D 18
TOTAL USUARIOS 44

CALCULO D
Tramo Numero de Lotes
E-D 4
LINEA 1
LINEA 1 D-C 8
C-B 14
A-B 19

G-F 4
LINEA 2 E-F 10
A-E 16
TOTAL USUARIOS 40

USUARIOS TOTALES 368


75 Kva
TRAFOS
7
CALCULO DE REGULACION DE TENSION TRAFO 1
Carga del Tramo (kva) Longitud (m) Momento kVA x m Calibre conductor
8.80 5 44.00 1/0
11.65 30 349.50 1/0
18.95 30 568.50 1/0
9.80 30 294.00 1/0
17.25 30 517.50 1/0

TRAFO QUE SE
CAPACIDAD TRAFO 1 73.14 75 Kva
UTILIZA

CALCULO DE REGULACON DE TENSION TRAFO 1

Suma de lotes Carga del Tramo (kva) Longitud (m) Momento kVA x m

2 3.90 35 136.50
3 5.30 35 185.50
10 12.55 35 439.25
12 14.40 35 504.00
14 15.90 35 556.50
16 17.25 35 603.75
17 18.15 35 635.25
20 20.50 35 717.50
22 22.10 35 773.50
23 22.90 35 801.50
1 2.30 35 80.50
2 3.90 35 136.50
4 6.55 35 229.25
146

2 3.90 35 136.50
2 3.90 35 136.50
4 6.55 35 229.25
4 6.55 35 229.25
3 5.30 35 185.50
3 5.30 35 185.50
2 3.90 35 136.50
2 3.90 35 136.50
3 5.30 35 185.50
2 3.90 35 136.50
3 5.30 35 185.50
11 13.40 35 469.00
4 6.55 35 229.25
45

1 2.30 35 80.50
2 3.90 35 136.50
7 9.80 35 343.00
10 12.55 35 439.25
1 2.30 35 80.50
12 14.40 35 504.00
15 16.60 35 581.00
16 17.25 35 603.75

2 3.90 35 136.50
1 2.30 35 80.50
5 7.70 35 269.50
6 8.80 35 308.00
3 5.30 35 185.50
14 15.90 35 556.50
17 18.15 35 635.25

#REF! CAPACIDAD TRAFO 2 1435.00 Suma de momento

CALCULO DE REGULACON DE TENSION TRAFO 3


Columna2 Columna3 Columna4 Columna5

Suma de lotes Carga del Tramo (kva) Longitud (m) Momento kVA x m

1 2.30 20.00 46.00


1.00 2.30 20.00 46.00
5.00 7.70 22.00 169.40
6.00
8.00
10.00
3.00
13.00
14.00
15.00
#N/A 28.00 #N/A
#N/A 30.00 #N/A

#N/A 25.00 #N/A


#N/A 20.00 #N/A
#N/A 20.00 #N/A
#N/A 23.00 #N/A
#N/A 30.00 #N/A

2.00
4.00
5.00
8.00
8.00 CAPACIDAD TRAFO 3 13.00 TRAFO QUE SE UTILIZA

CALCULO DE REGULACION DE TENSION TRAFO 4


Carga del Tramo (kva) Longitud (m) Momento kVA x m Calibre conductor
7.70 20 154.00 1/0
14.40 20 288.00 1/0
22.10 30 663.00 1/0

7.70 20 154.00 1/0


15.20 20 304.00 1/0
20.50 22 451.00 1/0
CAPACIDAD TRAFO 4 74.77 TRAFO QUE SE 75 kVA
UTILIZA

CALCULO DE REGULACION DE TENSION TRAFO 5


Carga del Tramo (kva) Longitud (m) Momento kVA x m Calibre conductor
5.30 30 159.00 1/0
10.70 22 235.40 1/0
14.40 30 432.00 2/0
19.70 30 591.00 2/0

5.30 20 106.00 1/0


8.80 20 176.00 1/0
13.40 22 294.80 1/0
15.90 5 79.50 1/0
18.15 22 399.30 1/0
TRAFO QUE SE
CAPACIDAD TRAFO 5 68.26 75 kVA
UTILIZA

CALCULO DE REGULACION DE TENSION TRAFO 6


Carga del Tramo (kva) Longitud (m) Momento kVA x m Calibre conductor
12.55 23 288.65 1/0
21.30 28 596.40 1/0

6.55 20 131.00 1/0


13.40 20 268.00 1/0
18.95 25 473.75 1/0
TRAFO QUE SE
CAPACIDAD TRAFO 6 71.52 75 kVA
UTILIZA

CALCULO DE REGULACION DE TENSION TRAFO 7


Carga del Tramo (kva) Longitud (m) Momento kVA x m Calibre conductor
6.55 28 183.40 1/0
10.70 26 278.20 1/0
15.90 28 445.20 1/0
19.70 5 98.50 1/0

6.55 28 183.40 1/0


12.55 26 326.30 1/0
17.25 28 483.00 1/0
TRAFO QUE SE
CAPACIDAD TRAFO 7 65.01 75 kVA
UTILIZA

CALIBRE
1/0 2/0 TOTAL
TRAMOS 30 2 32
METROS LINEALES TOTAL 683 60 743
Caida de tension %V parcial Caida de Tesion %V total CASAS EN NODO DE TRAFO
0.07 0.07 5
0.54 1.42
0.88 -0-
0.46 1.26
0.80 -0-

CASAS EN
Calibre conductor Caida de tension %V parcial Caida de Tesion %V total NODO DE
TRAFO
4 0.45 19.25 4
4 0.62 18.80
4 1.46 18.64
4 1.67 17.63
4 1.85 16.72
4 2.00 15.63
4 2.11 14.25
4 2.38 12.75
4 2.57 10.82
4 2.66 8.71
4 0.27 6.66
4 0.45 6.85
4 0.76 7.01

4 0.45 8.84
4 0.45 8.84
4 0.76 9.52
4 0.76 10.22
4 0.62 9.73
4 0.62 10.78
4 0.45 12.10
4 0.45 13.65
4 0.62 13.19
4 0.45 13.03
4 0.62 12.85
4 1.56 13.12
4 0.76 12.59

4 0.27
4 0.45
4 1.14
4 1.46
4 0.27
4 1.67
4 1.93
4 2.00
#N/A
4 0.45
4 0.27
4 0.89
4 1.02
4 0.62
4 1.85
4 2.11

13321.00 9.283 #N/A

Columna6 Columna7 Columna8 Columna9


CASAS EN
Calibre conductor Caida de tension %V parcial Caida de Tesion %V total NODO DE
TRAFO
4.00 0.15 #N/A 6
4.00 0.15 -0-
4.00 0.56 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 -0-
4.00 #N/A -0-
4.00 #N/A -0-
4.00 -0-
4.00 #N/A -0-
4.00 #N/A -0-
4.00 #N/A -0-
4.00 #N/A -0-
4.00 #N/A -0-
75 kVA

Caida de tension %V parcial Caida de Tesion %V total CASAS EN NODO DE TRAFO


0.24 1.71 4
0.45 -0-
1.03 -0-

0.24 1.41
0.47 -0-
0.70 -0-

Caida de tension %V parcial Caida de Tesion %V total CASAS EN NODO DE TRAFO


0.25 1.95 6
0.36 -0-
0.57 -0-
0.77 -0-

0.16 1.64
0.27 -0-
0.46 -0-
0.12 -0-
0.62 -0-

Caida de tension %V parcial Caida de Tesion %V total CASAS EN NODO DE TRAFO


0.45 1.37 5
0.92 -0-

0.20 1.35
0.42 -0-
0.73 -0-

Caida de tension %V parcial Caida de Tesion %V total CASAS EN NODO DE TRAFO


0.28 1.56 5
0.43 -0-
0.69 -0-
0.15 -0-

0.28 1.54
0.51 -0-
0.75 -0-
Union desde el 64 a linea 1

17.25
#REF!
1 2.30
2 3.90
3 5.30
4 6.55
5 7.70
6 8.80
7 9.80
8 10.70
9 11.65
10 12.55
11 13.40
12 14.40
13 15.20
14 15.90
15 16.60
16 17.25
17 18.15
18 18.95
19 19.70
20 20.50
21 21.30
22 22.10
23 22.90
24 23.80
25 24.60
26 25.35
27 26.10
28 26.90
29 27.70
30 28.50
31 29.30
32 30.10
33 30.80
34 31.65
35 32.45
36 33.30
37 34.10
38 34.80
39 35.65
40 36.40
41 37.20
42 38.00
43 38.80
44 39.50
45 40.30
46 41.15
47 42.00
48 42.75
49 43.60
50 44.30
51 45.39
52 46.28
53 47.17
54 48.06
55 48.95
56 49.84
57 50.73
58 51.62
59 52.51
60 53.40
61 54.29
62 55.18
63 56.07
64 56.96
65 57.85
66 58.74
67 59.63
68 60.52
69 61.41
70 62.30
71 63.19
72 64.08
73 64.97
74 65.86
75 66.75
76 67.64
77 68.53
78 69.42
79 70.31
80 71.20
81 72.09
82 72.98
83 73.87
84 74.76
85 75.65
86 76.54
87 77.43
88 78.32
89 79.21
90 80.10
91 80.99
92 81.88
93 82.77
94 83.66
95 84.55
96 85.44
97 86.33
98 87.22
99 88.11
100 89.00
101 89.89
102 90.78
103 91.67
104 92.56
105 93.45
106 94.34
107 95.23
108 96.12
109 97.01
110 97.90
111 98.79
112 99.68
113 100.57
114 101.46
115 102.35
116 103.24
117 104.13
118 105.02
119 105.91
120 106.80
121 107.69
122 108.58
123 109.47
124 110.36
125 111.25
126 112.14
127 113.03
128 113.92
129 114.81
130 115.70
131 116.59
132 117.48
133 118.37
134 119.26
135 120.15
136 121.04
137 121.93
138 122.82
139 123.71
140 124.60
141 125.49
142 126.38
143 127.27
144 128.16
145 129.05
146 129.94
147 130.83
148 131.72
149 132.61
150 133.50
151 134.39
152 135.28
153 136.17
154 137.06
155 137.95
156 138.84
157 139.73
158 140.62
159 141.51
160 142.40
161 143.29
162 144.18
163 145.07
164 145.96
165 146.85
166 147.74
167 148.63
168 149.52
169 150.41
170 151.30
171 152.19
172 153.08
173 153.97
174 154.86
175 155.75
176 156.64
177 157.53
178 158.42
179 159.31
180 160.20
181 161.09
182 161.98
183 162.87
184 163.76
185 164.65
186 165.54
187 166.43
188 167.32
189 168.21
190 169.10
191 169.99
192 170.88
193 171.77
194 172.66
195 173.55
196 174.44
197 175.33
198 176.22
199 177.11
200 178.00
201 178.89
202 179.78
203 180.67
204 181.56
205 182.45
206 183.34
207 184.23
208 185.12
209 186.01
210 186.90
211 187.79
212 188.68
213 189.57
214 190.46
215 191.35
216 192.24
217 193.13
218 194.02
219 194.91
220 195.80
221 196.69
222 197.58
223 198.47
224 199.36
225 200.25
226 201.14
227 202.03
228 202.92
229 203.81
230 204.70
231 205.59
232 206.48
233 207.37
234 208.26
235 209.15
236 210.04
237 210.93
238 211.82
239 212.71
240 213.60
241 214.49
242 215.38
243 216.27
244 217.16
245 218.05
246 218.94
247 219.83
248 220.72
249 221.61
250 222.50
251 223.39
252 224.28
253 225.17
254 226.06
255 226.95
256 227.84
257 228.73
258 229.62
259 230.51
260 231.40
261 232.29
262 233.18
263 234.07
264 234.96
265 235.85
266 236.74
267 237.63
268 238.52
269 239.41
270 240.30
271 241.19
272 242.08
273 242.97
274 243.86
275 244.75
CALIBRE K
4 0.00332
2 0.00224
1/0 0.00155
2/0 0.00131

Tabla 1. Cargas de diseño


Consumo Potencia Tasa Anual de
Rango promedio Inicial Crecimiento(%)
Bajo Bajo de 1 a 80 0.7 2.0
Bajo de 81 a 130 1.0 2.0
Medio de 131 a 180 1.2 1.0
Medio Alto de 181 a 300 2.0 1.0
Alto de 301 a 600 3.5 1.0

CALIBRE K
1/0 0.00155
2/0 0.00131
CALIBRE
USUARIOS
TOTALES 242 1/0 2/0 TOTAL

75 kVA TRAMOS 22 25 47
TRB METROS
6 LINEALES 510 585 1095
TOTAL