Issue 1
00901145- 1
T535 Operating Manual_______________________________________Biccotest Limited
PREFACE
IMPORTANT NOTE
This instrument is supplied with the internal battery discharged. Before use,
charge the battery as described in 3.4.
Complete discharge of the internal battery ¡s prevented by a sensing circuit
which automatically disconnects the battery when its voltage falls below a
pre-determined level, thus rendering the equipment inoperative. In order to
restore operation either:
SAFETY PRECAUTIONS:
___________________________________________________________________
00901145 – 1 Page 3
T535 Operating Manual_______________________________________Biccotest Limited
Tel: (0992)629011
Int: +44992629011
Fax: (0992)636170
Int: +44 992 636170
___________________________________________________________________
Page 4 00901145 – 1
Biccotest Limited T535 Operating Manual
SAFETY PRECAUTIONS
There are minimal safety problems when operating the T535 ¡n accordance
with the Instruction Manual. However, special attention should be given to
the following:
Ensure that the unit is set to the correct voltage rating before connecting to
an a.c. supply (see Section 3.2).
___________________________________________________________________
00901145 – 1 Page 5
T535 Operating Manual_______________________________________Biccotest Limitedl
Internal work on the T535 shall only be performed by those acquainted with
the possible shock hazard of cathode ray oscilloscope circuits and with the
routine precautions to be taken to avoid such accidents.
Within the T535 there are voltages as high as 2 kV during operation, and
such voltages can exist even after the T535 has been switched off.
Do not operate the T535 with the case removed except when following the
procedures of the Service Manual.
___________________________________________________________________
Page 4 00901145 – 1
Biccotest Limited T535 Operating Manual
LIST OF CONTENTS
Page
Safety Precautions 5
1. Introduction 11
2. Description of controls 14
3. Preparation for use 20
3.1 Introduction 20
3.2 Operation from an a.c. supply 20
3.3 Operation from an external 11 .5-28 V d.c. supply 21
3.4 Operation from the internal battery 22
3.5 Re-initialising the T535 23
List of propagation velocity f actors 24
4. Operating Procedure 25
4.1 Initialising the Control Settings 25
4.2 Single Line Testing 26
00901145-1 Page 7
T535 Operating Manual Biccotest Limited
Page
4.3 Comparison of Two Lines 28
4.4 Difference between Two Lines 29
4.5 Location of Crosstalk (Splits and Resplits) 29
4.6 Use of the Memory 30
4.7 X - Y, Y - T Recording 32
4.8 Printing via RS232/V24 Compatible Interface 33
4.8.1 Interface Connections 34
4.8.2 Operation with an Epsom P40 Printer 36
5. Application Guide 38
5.1 General Hints on Fault Locating 38
5.2 To Determine the (DIELECTRIC) Velocity Factor 41
5.2.1 Velocity of Propagation Known 42
5.2.2 Dielectric Constant Known 42
5.2.3 Using Short Length Cable 43
5.2.4 Route Length Known 44
Page 8 00901145 - 1
Biccotest Limited___________________________________________T535 Operating Manual
1
Page
5.2.5 Route Length Known with both ends accessible 45
5.2.6 Route Length Unknown with both ends accessible 46
(Three Stake Method)
5.3 Practical Examples 48
(1 ) Open Conductors 48
(2) Shorted Conductors 48
(3) Joints/Splices 49
(4) Capacitor Networks 49
(5) Loading Coils 50
(6) Open Sheath 50
(7) Grounded Sheath 51
(8) Wet Section (Water Ingress) 52
(9) Crossed or Split Pairs 53
(10)Taps 53
(11) Change of Cable Insulation 54
5.4 Ghost Reflections 56
6. Specification 57
0901145 - 1 Page 9
T535 Operating Manual________________________________ _______Biccotest Limited
The T535 has been designed primarily for testing telephone pairs. Ranges
are from 30 meters, 100ft and O.S^s to 15km, 50,000ft and Measurement
accuracy is ±1% of selected range setting.
Examples of Displayed Waveforms
1. INTRODUCTION
___________________________________________________________________
00901145 – 1 Page 11
T535 Operating Manual________________________________ _______Biccotest Limited
___________________________________________________________________
Page 12 00901145 – 1
Biccotest Limited___________________________________________T535 Operating Manual
2. DESCRIPTION OF CONTROLS
___________________________________________________________________
Page 14 00901145 – 1
Biccotest Limited___________________________________________T535 Operating Manual
___________________________________________________________________
00901145 – 1 Page 15
T535 Operating Manual Biccotest Limited
___________________________________________________________________
Page 14 00901145 – 1
Biccotest Limited___________________________________________T535 Operating Manual
___________________________________________________________________
00901145 – 1 Page 17
T535 Operating Manual Biccotest Limited
___________________________________________________________________
Page 14 00901145 – 1
Biccotest Limited___________________________________________T535 Operating Manual
BATTERY
RANGE LOW CURSOR
The cover also acts as a tilt stand, by releasing the two retaining
clips and folding under the unit.
The unit will operate from the internal battery in the absence of any
other supply.
lead through the slot provided and plug into the 11.5 - 28V socket
observing the polarity key.
Connect the a.c. power lead to the local supply. The 11.5-28V
indicator lamp will light to indicate the presence of the d.c. supply to
the unit.
Positive BROWN
Negative BLUE
Neither side is connected to ground.
Connect to a d.c. supply in the range 11.5 to 28 Volts, insert the plug
into the unit and observe that the 11.5-28V indicator lamp is lit.
__________________________________________________________________
00901145 – 1 Page 21
T535 Operating Manual Biccotest Limited
The T535 will operate from the internal battery in the absence of any
other supply.
The battery can be recharged either from a.c. or external d.c., i.e.
vehicle supply.
off. The battery will charge providing the supply exceeds 12.5 volts
i.e. with the vehicle engine running. Full recharge will take 14 hours.
__________________________________________________________________
00901145 – 1 Page 23
T535 Operating Manual______________________________________________Biccotest Limited
Air 0.980
Air Spaced Coaxial 0.940
RG 58U Coaxial 0.780
RG 59U Coaxial 0.660
RG High Temperature Coaxial 0.695
Foam Poly 0.820
PTFE(Teflon) 0.710
Polyethene (PIC) 0.667
Jelly Filled Poly 0.640
Paper (Pulp .083 uF/Mile 0.720
Paper (Pulp .072 uF/Mile 0.880
Paper, oil filled (PILC) 0.500-0.560
Cross Linked Poly (XLPE) 0.520-0.580
HMW 0.560-0.620
___________________________________________________________________
Page 24 00901145 – 1
Biccotest Limited___________________________________________T535 Operating Manual
4. OPERATING PROCEDURE
The following parameters are automatically set each time the unit is
switched on.
Display Mode L1
Amplitude Minimum
Pulse Width Narrow
Adjust SHIFT to position the trace ¡n the middle of the CRT screen.
4.2. Single Line Testing
Note: The fault distance displayed includes the length of the connecting lead
used which should be subtracted from the reading obtained.
The FILTER ¡s used to filter out low frequency components. This has the
effect of sharpening up the reflection from long cables. For short cables the
filter should be switched out.
1. Plug the test lead into the L1 sockets.
2. Sel the DIELECTRIC velocity factor to suit the cable type under
test. A list is provided on page 24.
___________________________________________________________________
Page 26 00901145 – 1
Biccotest Limited___________________________________________7535 Operating Manual
3. If the cable type or the velocity factor is not known refer to Para. 5.2.
and then continue with this procedure as appropriate. Select the
RANGE to cover the full cable length.
Increase the AMPLITUDE until the fault reflection is observed. Select the
wide pulse if preferred.
Adjust the BALANCE control to minimise the transmitted pulse at the start
of the trace.
The distance to the fault (cursor position) is displayed in trie top right
hand corner of the LCD.
___________________________________________________________________
Page 28 00901145 – 1
Biccotest Limited______________________________________________7535 Operating Manual
__________________________________________________________________
00901145 – 1 Page 29
T535 Operating Manual______________________________________________Biccotest Limited
TYPICAL RESPONSE
Split Resplit
Should crosstalk result from any form of
resistive or capacitive coupling, the location of the
fault point is determined in the same way.
Note: Only the trace of the line connected to L1 can be stored. To store a
trace, connect the line ¡n question to the L1 sockets.
___________________________________________________________________
Page 30 00901145 – 1
Biccotest Limited______________________________________________T535 Operating Manual
The one can now be disconnected from the T535 and subjected to
external stimulation to "enhance" the fault.
rendering the comparison between the direct and stored trace invalid,
the LCD will flash and indicate the parameter ¡n error. Note the
indicated error, switch back to L1 and correct the error.
Comparison between the line and stored trace can now proceed as
previously described.
4.7. X - Y, Y - T Recording
The output to the external plotter is via the 15 way D type interface
plug. The output voltage is O to 1V d.c.
To check the full scale deflection depress the SET control to obtain
a 1 volt signal.
Depress M to check that the trace has been transferred into memory.
__________________________________________________________________
00901145 – 1 Page 33
T535 Operating Manual______________________________________________Biccotest Limited
Pin 2 Tx Data
Pin 4 RTS
Pin 5 CTS (RFS)
Pin 7 OV Link on mating socket to set data
PinSSLO ) rates defined in table below.
Pin9SL1 )
Pin10SL2)
Pin 11 Mode Select Link to 7 (OV) for printer. Leave open
circuit for Analogue Plotter.
The following settings of the DIP switch on the printer are required
for correct operation. (These are normally the factory settings of
the printer).
___________________________________________________________________
Page 36 00901145 – 1
Biccotest Limited___________________________________________T535 Operating Manual
The printer should be connected to the T535 with the lead as detailed
in 4.8.1. This ¡s available as an accessory, Part No. 31302402
When printing has finished, pressing SET will output Line Feeds to the
printer, causing the paper to advance.
Note:
If the settings of RANGE, PULSE WIDTH, FILTER, UNITS, or
DIELECTRIC differ between M and L1 then the M & L1 and M - L1
screens cannot be printed. See 4.6.
__________________________________________________________________
00901145 – 1 Page 37
T535 Operating Manual___________________________________________Biccotest Limited
5. APPLICATION CUIDE
___________________________________________________________________
Page 38 00901145 – 1
Biccotest Limited______________________________________________T535 Operating Manual
Experience has shown that most faults occur at joints, pillars, splices,
cabinets, or where the cable has been damaged.
__________________________________________________________________
00901145 – 1 Page 37
T535 Operating Manual___________________________________________Biccotest Limited
Insulation faults with resistance above a few kilohms are more likely to be
located by using a high-resistance bridge; unless water is present, when the
T535 will locate the change in capacitance caused by the water ingress.
The T535 will not 'see' through load coils, which appear as high-impedance
series faults.
___________________________________________________________________
Page 40 00901145 – 1
Biccotest Limited___________________________________________T535 Operating Manual
__________________________________________________________________
00901145 – 1 Page 41
T535 Operating Manual___________________________________________Biccotest Limited
3. Obtain a reading for the apparent distance to the end of the cable
indicated by the first reflection after the transmitted pulse.
__________________________________________________________________
00901145 – 1 Page 43
T535 Operating Manual______________________________________________Biccotest Limited
Method 1
1. Connect the T535 to a good pair.
2. Determine the propagation velocity factor as previously
described for a sample length and set the DIELECTRIC control.
3. Connect to the faulty pair and measure the distance to the fault.
Method 2
1. Connect the T535 to a good pair with any DIELECTRIC setting
in the range 0.400 to 0.999 and measure the apparent distance
(d1) to the end of the cable.
2. Connect the T535 to the faulty pair with the same DIELECTRIC
setting and measure the apparent distance (d2 )
___________________________________________________________________
Page 44 00901145 – 1
Biccotest Limited___________________________________________T535 Operating Manual
__________________________________________________________________
00901145 – 1 Page 43
T535 Operating Manual______________________________________________Biccotest Limited
x = Stake or marker
Df = Unknown distance to fault
___________________________________________________________________
Page 46 00901145 – 1
Biccotest Limited___________________________________________T535 Operating Manual
2. Shorted Conductors
The reflection from a shorted pair
is a negative or downward pulse.
Note: No reflection from the far
end of the cable.
___________________________________________________________________
Page 48 00901145 – 1
Biccotest Limited___________________________________________T535 Operating Manual
3. Joints (splices)
A joint (splice) produces an "S"
shaped reflection.
4. Capacitor Networks
A capacitor network presents a
low shunt impedance to the
transmitted pulse and produces a
negative or downward reflection
followed by a small positive
overshoot.
__________________________________________________________________
00901145 – 1 Page 49
T535 Operating Manual______________________________________________Biccotest Limited
5. Loading Coils
A loading coil presents a high
series impedance to the
transmitted pulse and positive or
upward reflection. It is not
possible to 'see' beyond the first
loading coil.
6. Open Sheath
An open sheath may be located
where the sheath is completely
open, for example, where there is
a missing strap. The sheath must
be isolated in the measuring
direction and the lest connection
made between the sheath and a
shorted, twisted pair.
___________________________________________________________________
Page 50 00901145 – 1
Biccotest Limited___________________________________________T535 Operating Manual
7. Grounded Sheath
Grounded sheaths are difficult to
locate with pulse echo equipment
and may be more readily located
by using a high-resistance bridge.
__________________________________________________________________
00901145 – 1 Page 51
T535 Operating Manual Biccotest Limited
___________________________________________________________________
Page 52 00901145 – 1
Biccotest Limited T535 Operating Manual
10. Taps
The tap appears as a negative
pulse followed immediately by a
positive overshoot. Because of
multiple reflections it is difficult to
troubleshoot circuits that contain
several taps, so test progressively
by moving from tap to tap.
__________________________________________________________________
00901145 – 1 Page 53
T535 Operating Manual Biccolest Limited
___________________________________________________________________
Page 54 00901145 – 1
Biccotest Limited T535 Operating Manual
D= d2 - d1
__________________________________________________________________
00901145 – 1 Page 55
T535 Operating Manual Biccotest Limited
___________________________________________________________________
Page 56 00901145 – 1
Biccotest Limited T535 Operating Manual
6. SPECIFICATION
Displayed Ranges 10 ranges, nominal full scale based on
a velocity factor of 0.667.
30m-15Km
100ft - 50,000 ft
0.3ns -150 μs
__________________________________________________________________
00901145 – 1 Page 57
T535 Operating Manual Biccotest Limited
___________________________________________________________________
Page 58 00901145 – 1
Biccotest Limited T535 Operating Manual
Sensitivity 3mV/cm
Balance Up to 2K ohms.
Line Connections 4mm banana sockets
19mm (3/4 inch) spacing
Input Protection 400 V (d.c. plus peak a.c.)
Filter High Pass cut off frequency 150 kHz
Display Modes
L1 -> L2 Transmit on L1
Receive on L2
__________________________________________________________________
00901145 – 1 Page 59
T535 Operating Manual Biccotest Limited
L1 to M Transfer L1 to Memory.
M Memory trace displayed.
M & L1 Memory and L1 direct displayed.
___________________________________________________________________
Page 60 00901145 – 1
Biccotest Limited T535 Operating Manual