Está en la página 1de 29

Model: Installers Guide

GATEWAY

Underwriters
Laboratories Listed
READ THIS MANUAL BEFORE INSTALLING OR
OPERATING THIS APPLIANCE. THIS INSTALLERS WARNING: IMPROPER INSTALLA-
GUIDE MUST BE LEFT WITH APPLIANCE FOR TION, ADJUSTMENT, ALTERATION,
FUTURE REFERENCE.
SERVICE OR MAINTENANCE CAN
CAUSE INJURY OR PROPERTY DAM-
WARNING: IF THE INFORMATION AGE. REFER TO THIS MANUAL. FOR
IN THESE INSTRUCTIONS IS NOT ASSISTANCE OR ADDITIONAL INFOR-
FOLLOWED EXACTLY, A FIRE OR MATION CONSULT A QUALIFIED IN-
STALLER, SERVICE AGENCY, OR THE
EXPLOSION MAY RESULT CAUS-
GAS SUPPLIER.
ING PROPERTY DAMAGE, PER-
SONAL INJURY, OR DEATH.

- Do not store or use gasoline or other 1. This appliance may be installed in an af-
flammable vapors and liquids in the vi- termarket, permanently located, manufac-
cinity of this or any other appliance. tured (mobile) home, where not prohibited
- What to do if you smell gas by local codes.
• Do not try to light any appliance.
2. This appliance is only for use with the type
• Do not touch any electrical switch.
of gas indicated on the rating plate. This
• Do not use any phone in your build- appliance is not convertible for use with
ing.
other gases, unless a certified kit is used.
• Immediately call your gas supplier from
a neighbor's phone. Follow the gas
supplier's instructions.
Î
• If you cannot reach your gas supplier, In the Commonwealth of Massachusetts:
call the fire department. • installation must be performed by a licensed
- Installation and service must be plumber or gas fitter;
performed by a qualified installer, service See Table of Contents for location of additional
agency, or the gas supplier. Commonwealth of Massachusetts requirements.

Printed in U.S.A. Copyright 2006 Please contact your Heat & Glo dealer with any
Heat & Glo, a brand of Hearth & Home Technologies Inc. questions or concerns. For the number of your nearest
20802 Kensington Boulevard, Lakeville, MN 55044 Heat & Glo dealer, please call 1-888-427-3973.

This product may be covered by one or more of the following patents: (United States) 4593510, 4686807, 4766876, 4793322, 4811534, 5000162, 5016609, 5076254, 5113843, 5191877, 5218953, 5263471,
5328356, 5341794, 5347983, 5429495, 5452708, 5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485, 5931661, 5941237, 5947112, 5996575, 6006743, 6019099, 6048195, 6053165,
6145502, 6170481, 6237588, 6296474, 6374822, 6413079, 6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2, 6729551, 6736133, 6748940, 6748942, 6769426, 6774802,
6796302, 6840261, 6848441, 6863064, 6866205, 6869278, 6875012, 6880275, 6908039, 6919884, D320652, D445174, D462436; (Canada) 1297749, 2195264, 2225408, 2313972; (Australia) 780250,
780403, 1418504 or other U.S. and foreign patents pending.

Heat & Glo • Gateway • 288-900 Rev. S • 3/06 1


SAFETY AND WARNING INFORMATION

READ and UNDERSTAND all instructions carefully These units MUST use one of the vent systems
! before starting the installation. FAILURE TO ! described in the Installing the Fireplace section of
FOLLOW these installation instructions may result the Installers Guide. NO OTHER vent systems or
in a possible fire hazard and will void the warranty. components MAY BE USED.

Prior to the first firing of the fireplace, READ the This gas fireplace and vent assembly MUST be
! Using Your Fireplace section of the Owners Guide. ! vented directly to the outside and MUST NEVER be
attached to a chimney serving a separate solid fuel
burning appliance. Each gas appliance MUST USE
DO NOT USE this appliance if any part has been a separate vent system. Common vent systems are
! under water. Immediately CALL a qualified service PROHIBITED.
technician to inspect the unit and to replace any part
of the control system and any gas control which has
been under water. INSPECT the external vent cap on a regular basis to
! make sure that no debris is interfering with the air
flow.
! THIS UNIT IS NOT FOR USE WITH SOLID FUEL.

The glass door assembly MUST be in place and


Installation and repair should be PERFORMED by a ! sealed, and the trim door assembly MUST be in
! qualified service person. The appliance and venting place on the fireplace before the unit can be placed
system should be INSPECTED before initial use into safe operation.
and at least annually by a professional service
person. More frequent cleaning may be required
due to excessive lint from carpeting, bedding DO NOT OPERATE this appliance with the glass
material, etc. It is IMPERATIVE that the unit’s ! door removed, cracked, or broken. Replacement of
control compartment, burners, and circulating air the glass door should be performed by a licensed
passageways BE KEPT CLEAN to provide for or qualified service person. DO NOT strike or slam
adequate combustion and ventilation air. the glass door.

Always KEEP the appliance clear and free from The glass door assembly SHALL ONLY be
! combustible materials, gasoline, and other ! replaced as a complete unit, as supplied by the gas
flammable vapors and liquids. fireplace manufacturer. NO SUBSTITUTE material
may be used.
NEVER OBSTRUCT the flow of combustion and
! ventilation air. Keep the front of the appliance DO NOT USE abrasive cleaners on the glass door
CLEAR of all obstacles and materials for servicing ! assembly. DO NOT ATTEMPT to clean the glass
and proper operations. door when it is hot.

Due to the high temperature, the appliance should Turn off the gas before servicing this appliance. It is
! be LOCATED out of traffic areas and away from ! recommended that a qualified service technician
furniture and draperies. Clothing or flammable perform an appliance check-up at the beginning of
material SHOULD NOT BE PLACED on or near the each heating season.
appliance.
Any safety screen or guard removed for servicing
Children and adults should be ALERTED to the ! must be replaced before operating this appliance.
! hazards of high surface temperature and should
STAY AWAY to avoid burns or clothing ignition.
DO NOT place furniture or any other combustible
Young children should be CAREFULLY SUPERVISED ! household objects within 36 inches of the fireplace
when they are in the same room as the appliance.
front.

2 Heat & Glo • Gateway • 288-900 Rev. S • 3/06


Table of Contents
Safety and Warning Information. ..........................................2

Î Service Parts Lists. ...............................................................4

Section 1: Approvals and Codes. .........................................7


Appliance Certification..............................................................7
Installation Codes .....................................................................7
High Altitude Installations ..........................................................7
Î Requirements for the Commonwealth of Massachusetts .......8

Section 2: Getting Started. ...................................................9


Introducing the Heat & Glo Gas Fireplaces ..............................9
Pre-installation Preparation ......................................................9

Section 3: Installing the Fireplace. .................................... 11


Constructing the Fireplace Chase ......................................... 11
Step 1 Locating the Fireplace ............................................. 11
Step 2 Framing the Fireplace .............................................12
Step 3 Negative Pressure ................................................... 13
Step 4 Installing the Vent System ....................................... 14
A. Vent System Approvals ....................................... 14
B. System Components .......................................... 14
C. Vent Termination ................................................. 20
Step 5 Positioning, Leveling, and
Securing the Fireplace ............................................ 22
Step 6 The Gas Control System ......................................... 23
Step 7 The Gas Supply Line ...............................................23
Step 8 Gas Pressure Requirements .................................. 23
Step 9 Wiring the Fireplace ................................................ 24
Step 10 Finishing .................................................................. 25
Step 11 Installing Trim, Logs, and Ember Material ............... 26
Installing the Trim ....................................................26
Shutter Settings .......................................................26
Positioning the Logs ................................................ 26
Placing the Ember Material ..................................... 26
Lava Rock ............................................................... 27
Step 12 Before Lighting the Fireplace ...................................27
Step 13 Lighting the Fireplace .............................................. 27
After the Installation ................................................................27

Section 4: Maintaining and Servicing Your Fireplace. ....28

Î = Contains updated information.


Heat & Glo • Gateway • 288-900 Rev. S • 3/06 3
Service Parts GATEWAY
(NG, LP) Exploded Parts Diagram Beginning Manufacturing Date: 1-02
Ending Manufacturing Date: ______

18

17

14
15
5

19

2 4

16

6 Log Set Assembly

7 12
8
11
10
13 9
Part number list on following page.

4 Heat & Glo • Gateway • 288-900 Rev. S • 3/06


Service Parts List GATEWAY
IMPORTANT: THIS IS DATED INFORMATION. The most current information is located on your dealers VIP site. When ordering,
supply serial and model numbers to ensure correct service parts.

ITEM DESCRIPTION SERIAL # PART NUMBER

1 Burner NG 288-176A

1 Burner LP 288-175A

2 Glass Door Assembly GLA-GATEWAY

3 Louver Assembly, Top 288-252A

4 Louver Assembly, Bottom 288-249A

5 Hood 288-174

6 Log Set Assembly LOGS-GATEWAY

7 Log 1 SRV288-721

8 Log 2 SRV675-722

9 Log 3 SRV288-726

10 Log 4 SRV288-723

11 Log 5 SRV285-720

12 Log 6 SRV278-705

13 Log 7 SRV285-725

14 Side Refractory 288-280

15 Log Grate 288-360A

16 Draft Assist Blower 288-500

17 Surround 288-130

18 Non-combustible Board 288-401

19 Trim Door Mesh MESH-550-C

4" Exhaust Collar Assembly 288-210A

Touch Up Paint TUP-GBK-12

Glass Latch Assembly 386-122A

Outside Air Handle 288-103

Lava Rock Bag 705-420

Mineral Wool 050-721

ACCESSORIES

Fan Kit GFK-160A

Remote Control Kit RC-SMART-HNG

Remote Control Kit SMART-STAT-HNG

Conversion Kit NG NGK-GATEWAY

Conversion Kit LP LPK-GATEWAY

Heat & Glo • Gateway • 288-900 Rev. S • 3/06 5


Service Parts GATEWAY
(NG, LP) Exploded Parts Diagram Beginning Manufacturing Date: 1-02
Ending Manufacturing Date: ______

Intermittent Pilot Ignition 6


Valve Assembly

13 7

5
4
8
1
14 10

11

9
3
12
2
ITEM DESCRIPTION SERIAL # PART NUMBER
1 ON/OFF Rocker Switch 060-521A
2 Valve NG 593-500
2 Valve LP 593-501
3 Flexible Gas Connector 477-301A
4 Module 593-592
5 Wire Assembly 288-593a
6 Pilot Assembly NG 385-510a
6 Pilot Assembly LP 385-511a
7 Pilot Brackete 288-163
8 Valve Bracket 288-145
9 Flex Ball Valve Assembly 302-320A
10 Vacuum Switch 288-521
11 Junction Box 288-250A
12 3V Adaptor Plug 593-593a
13 Burner Orifice (#32A) NG 420-800
13 Burner Orifice (#50A) LP 446-801
14 Vacuum Hose (Teflon Tube) 421-9
Ground Strap 385-512
Pilot Spud (NG) 446-505 Í
Pilot Spud (LP) 446-517 Í
Regulator (NG) NGK-DXF Í
Regulator (LP) LPK-DXF Í

6 Heat & Glo • Gateway • 288-900 Rev. S • 3/06


1 Approvals and Codes

Appliance Certification
The Heat & Glo fireplace model discussed in this Installers edition), and local Building Officials for the options allowed
Guide has been tested to certification standards and listed in obtaining an effective bedroom volume of unconfined
by the applicable laboratories. space.
These models (natural gas and propane) can be installed in
Certification a bedroom (in Canada) if a thermostat (Model WH-STAT) is
installed with the unit. Consult local code authorities.
MODEL: GATEWAY Detailed installation instructions for Model WH-STAT are
LABORATORY: Underwriters Laboratories included with the kit.
TYPE: Vented Gas Fireplace
STANDARD: ANSI Z21.50•CSA2.22 High Altitude Installations
U.L. Listed gas appliances are tested and approved with-
out requiring changes for elevations from 0 to 2,000 feet in
Installation Codes the U. S. A. and in Canada.
The fireplace installation must conform to local codes. Before
installing the fireplace, consult the local building code When installing this appliance at an elevation above 2,000
agency to ensure that you are in compliance with all feet, it may be necessary to decrease the input rating by
applicable codes, including permits and inspections. changing the existing burner orifice to a smaller size. Input
rate should be reduced by 4% for each 1000 feet above a
In the absence of local codes, the fireplace installation must 2000 foot elevation in the U.S.A. or 10% for elevations
conform to the National Fuel Gas Code ANSI Z223.1 (in between 2000 and 4500 feet in Canada. If the heating value
the United States) or the CAN/CGA-B149 Installation Codes of the gas has been reduced, these rules do not apply. To
(in Canada). The appliance must be electrically grounded identify the proper orifice size, check with the local gas
in accordance with local codes or, in the absence of local utility.
codes with the National Electric Code ANSI/NFPA No. 70 If installing this appliance at an elevation above 4,500 feet
(in the United States), or to the CSA C22.1 Canadian Electric (in Canada), check with local authorities.
Code (in Canada).

These models (natural gas and propane) can be installed in


a bedroom (in the United States) which has a total volume
of unconfined space appropriate to the particular installation.
Refer to the National Fuel Gas Code ANSI Z223.1/NFPA54
(current edition). The Uniform Mechanical Code - (current

Heat & Glo Quality Systems


registered by SGS ICS

Heat & Glo • Gateway • 288-900 Rev. S • 3/06 7


Inspection
NOTE: The following requirements reference various
The state or local gas inspector of the side wall horizontally
Massachusetts and national codes not contained in
vented gas fueled equipment shall not approve the installa-
this document.
tion unless, upon inspection, the inspector observes carbon
monoxide detectors and signage installed in accordance with
Requirements for the Commonwealth of the provisions of 248 CMR 5.08(2)(a)1 through 4.
Massachusetts
Exemptions
For all side wall horizontally vented gas fueled equipment The following equipment is exempt from 248 CMR 5.08(2)(a)1
installed in every dwelling, building or structure used in through 4:
whole or in part for residential purposes, including those • The equipment listed in Chapter 10 entitled “Equipment
owned or operated by the Commonwealth and where the Not Required To Be Vented” in the most current edition
side wall exhaust vent termination is less than seven (7) of NFPA 54 as adopted by the Board; and
feet above finished grade in the area of the venting, includ-
ing but not limited to decks and porches, the following re- • Product Approved side wall horizontally vented gas fu-
quirements shall be satisfied: eled equipment installed in a room or structure sepa-
rate from the dwelling, building or structure used in whole
Installation of Carbon Monoxide Detectors or in part for residential purposes.
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gasfitter MANUFACTURER REQUIREMENTS
shall observe that a hard wired carbon monoxide detector
with an alarm and battery back-up is installed on the floor Gas Equipment Venting System Provided
level where the gas equipment is to be installed. In addi-
When the manufacturer of Product Approved side wall hor-
tion, the installing plumber or gasfitter shall observe that a
izontally vented gas equipment provides a venting system
battery operated or hard wired carbon monoxide detector
design or venting system components with the equipment,
with an alarm is installed on each additional level of the
the instructions provided by the manufacturer for installa-
dwelling, building or structure served by the side wall hori-
tion of the equipment and the venting system shall include:
zontal vented gas fueled equipment. It shall be the respon-
sibility of the property owner to secure the services of qual- • Detailed instructions for the installation of the venting
ified licensed professionals for the installation of hard wired system design or the venting system components; and
carbon monoxide detectors.
• A complete parts list for the venting system design or
venting system.
In the event that the side wall horizontally vented gas fu-
eled equipment is installed in a crawl space or an attic, the
hard wired carbon monoxide detector with alarm and bat-
tery back-up may be installed on the next adjacent floor Gas Equipment Venting System NOT Provided
level. When the manufacturer of a Product Approved side wall
In the event that the requirements of this subdivision can horizontally vented gas fueled equipment does not provide
not be met at the time of completion of installation, the the parts for venting the flue gases, but identifies “special
owner shall have a period of thirty (30) days to comply with venting systems”, the following requirements shall be sat-
the above requirements; provided, however, that during said isfied by the manufacturer:
thirty (30) day period, a battery operated carbon monoxide
detector with an alarm shall be installed. • The referenced “special venting system” instructions shall
be included with the appliance or equipment installation
Approved Carbon Monoxide Detectors instructions; and
Each carbon monoxide detector as required in accordance • The “special venting systems” shall be Product Approved
with the above provisions shall comply with NFPA 720 and by the Board, and the instructions for that system shall
be ANSI/UL 2034 listed and IAS certified. include a parts list and detailed installation instructions.

Signage A copy of all installation instructions for all Product Ap-


A metal or plastic identification plate shall be permanently proved side wall horizontally vented gas fueled equipment,
mounted to the exterior of the building at a minimum height all venting instructions, all parts lists for venting instruc-
of eight (8) feet above grade directly in line with the ex- tions, and/or all venting design instructions shall remain
haust vent terminal for the horizontally vented gas fueled with the appliance or equipment at the completion of the
heating appliance or equipment. The sign shall read, in installation.
print size no less than one-half (1/2) inch in size, “GAS See Gas Connection section for additional Common-
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB- wealth of Massachusetts requirements.
STRUCTIONS”.

8 Heat & Glo • Gateway • 288-900 Rev. S • 3/06


2 Getting Started

Introducing the Gateway Fireplace Warranty


The Gateway fireplace is designed to operate with all ex- The Heat & Glo Warranty will be voided by, and Heat & Glo
haust gases expelled to the outside. disclaims any responsibility for, the following actions:
The information contained in this Installers Guide, unless • Installation of any damaged fireplace or vent system com-
noted otherwise, applies to all models and gas control ponent.
systems. Gas fireplace diagrams, including the dimensions,
are shown in this section. • Modification of the fireplace or vent system.
• Installation other than as instructed by Heat & Glo.
Pre-install Preparation
• Improper positioning of the gas logs or the glass door.
This gas fireplace and its components are tested and safe
when installed in accordance with this Installers Guide. • Installation and/or use of any component part not manu-
Report to your dealer any parts damaged in shipment, factured and approved by Heat & Glo, not withstanding
particularly the condition of the glass. Do not install any any independent testing laboratory or other party approval
unit with damaged, incomplete, or substitute parts. of such component part or accessory.
The vent system components are shipped in separate ANY SUCH ACTION MAY POSSIBLY CAUSE A FIRE
packages. The gas logs are shipped in the fireplace and HAZARD.
must be on unwrapped before firing the unit.
Read all of the instructions before starting the
installation. Follow these instructions carefully during
the installation to ensure maximum safety and benefit.
Failure to follow these instructions will void the
owner’s warranty and may present a fire hazard.

When planning a fireplace installation, it’s necessary to


determine:
• Where the unit is to be installed.

• The vent system configuration to be used.

• Gas supply piping.

• Electrical wiring.

• Framing and finishing details.

• Whether optional accessories — devices such as a fan,


wall switch, fresh air kit or remote control — are desired.

If the fireplace is to be installed on carpeting or tile, or on


any combustible material other than wood flooring, the
fireplace must be installed on a metal or wood panel that
extends the full width and depth of the fireplace.

Heat & Glo • Gateway • 288-900 Rev. S • 3/06 9


22 5/8
(575mm)

39 ¼
(997mm)
38 1/8
(968mm)

GAS LINE
ACCESS 39 9/16
(1005mm)
37 5/8
ELECTRICAL (955mm)
ACCESS

2 3 5/8
2 1/8 (51mm) (92mm)
(54mm)

31 ¼ 14 1/16
2 5/8 3 1/8 (794mm) (357mm)
(67mm) (80mm)
5 1/8
(131mm)

TOP STANDOFFS

TOP GRILLE

LOWER
GRILLE

ELECTRICAL
ACCESS

GAS CONTROLS

GAS
ACCESS
RATING PLATE AIR KIT
/LABELS KNOCKOUT

Figure 2.1 Diagram of the GATEWAY

10 Heat & Glo • Gateway • 288-900 Rev. S • 3/06


3 Installing the Fireplace

Constructing the Fireplace Chase


44” (1118mm)

A chase is a vertical box-like structure built to enclose the


gas fireplace and/or its vent system. Vertical vents that run
on the outside of a building may be, but are not required to 44” (1118mm)
be, installed inside a chase.

CAUTION: TREATMENT OF FIRESTOP SPACERS AND


CONSTRUCTION OF THE CHASE MAY VARY WITH THE
TYPE OF BUILDING. THESE INSTRUCTIONS ARE NOT
SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL Figure 3.1 Fireplace Dimensions, Locations,
BUILDING CODES. THEREFORE, YOUR LOCAL BUILD- and Space Requirements
ING CODES MUST BE CHECKED TO DETERMINE THE
REQUIREMENTS FOR THESE STEPS.

Factory-built fireplace chases should be constructed in the The distance from the unit to combustible construction
manner of all outside walls of the home to prevent cold air is to be measured from the unit outer wrap surface to
drafting problems. The chase should not break the outside the combustible construction, NOT from the screw heads
building envelope in any manner. that secure the unit together.

This means that the walls, ceiling, base plate and cantilever
floor of the chase should be insulated. Vapor and air infiltra-
tion barriers should be installed in the chase as per regional Minimum Clearances from the Fireplace to
codes for the rest of the home. Additionally, in regions where Combustible Materials Inches mm
cold air infiltration may be an issue, the inside surfaces Glass Sides or Ends .......... 3 6 ................. 914
may be sheetrocked and taped for maximum air tightness. Floor ....................................... 0 .................... 0
To further prevent drafts, the firestops should be caulked Metal Sides or Ends ........... 1/2 ........... 12.5mm
with high temperature caulk to seal gaps. Gas line holes Edges of Front Face* .......... 0 .................... 0
and other openings should be caulked with high temp caulk Top ....................................... 3 1/2 ............... 8 9
or stuffed with unfaced insulation. If the appliance is being Ceiling** ............................... 3 6 ................. 914
installed on a cement slab, a layer of plywood may be placed * Refer to Diagram of GATEWAY (see Figure 2.1).
underneath to prevent conducting cold up into the room. ** The clearance to the ceiling is measured from the top
of the non-combustible board (see Figure 3.29).
THE CHASE SHOULD BE CONSTRUCTED SO THAT ALL
CLEARANCES TO THE FIREPLACE ARE MAINTAINED
AS SPECIFIED WITHIN THIS INSTALLERS GUIDE.
Minimum Clearances from the Vent Pipe to
Combustible Materials
B-Vent PV-Flex
Inches (mm) Inches (mm)
Step 1. Locating the Fireplace Vertical Sections. ......... 1 (25) ............. 1 (25)
The following diagram shows space and clearance require- Horizontal Sections
ments for locating a fireplace within a room. Top ..................................... 1 (25) ..... 1-1/2 (38)
Bottom .............................. 1 (25) ............. 1 (25)
Clearance Requirements S i d e s ................................. 1 (25) ............. 1 (25)
At Wall Firestops
The top, back, and sides of the fireplace are defined by Top ..................................... 1 (25) ..... 1-1/2 (38)
stand-offs. The minimum clearance to a perpendicular wall Bottom .............................. 1 (25) ............. 1 (25)
extending past the face of the fireplace is one inch (25mm). S i d e s ................................. 1 (25) ............. 1 (25)
The metal ends of the fireplace may NOT be recessed into
combustible construction.
For minimum clearances, see the direct vent termination
clearance diagram in this manual (see Figure 3.22).

Heat & Glo • Gateway • 288-900 Rev. S • 3/06 11


Step 2. Framing the Fireplace
Fireplace framing can be built before or after the fireplace is WARNING: FRAMING DIMENSIONS ASSUME
set in place. Framing should be positioned to accommo- ! USE OF 1/2 INCH THICK WALL COVERING
date wall coverings and fireplace facing material. The dia- MATERIALS ON EXTERIOR OF FRAMING ONLY
gram below shows framing reference dimensions. AND NO SHEETROCK ON INTERIOR OF FRAMING.
CAUTION: MEASURE FIREPLACE DIMENSIONS AND
VERIFY FRAMING METHODS AND WALL COVERING
DETAILS BEFORE FRAMING.

B-Vent
1” (25.4mm)

PV-FLEX
1-1/2” (38mm)

EXHAUST 1”
COLLAR (25.4mm)

NOTE: A 1” clearance (B-Vent) or 1-1/2” clearance


(PV-FLEX) must be maintained between the top of
the pipe in a horizontal configuration and any
combustible materials. Otherwise, 1” clearance
should be maintained between the pipe and any
combustible materials.

Framing should be constructed


of 2 X 4 lumber or heavier.

A= 39 3/4 (1010mm)
B= 21 5/8 (549mm) 1/2 Sheetrock
A
21 3/8 (543mm) 5/8 Sheetrock B
C= 40 1/4 (1022mm) C

Figure 3.2 Framing Dimensions

12 Heat & Glo • Gateway • 288-900 Rev. S • 3/06


Step 3. Negative Pressure • Install the fresh air kit. Install the intake on the side of
the house towards prevailing winds during the heating
WARNING season.
• Ensure adequate outdoor air is supplied for combustion
Asphyxiation Risk.
appliances and exhaust equipment.
• Negative pressure can cause spillage of
combustion fumes and soot. • Ensure furnace and air conditioning return vents are not
• Fireplace needs to draft properly for safety. located in the immediate vicinity of the fireplace.
• Avoid installing the fireplace near doors, walkways or
small isolated spaces.
Draft is the pressure difference needed to vent fireplaces
successfully. Considerations for successful draft include: • Recessed lighting should be of “sealed can” design; at-
• Preventing negative pressure tic hatches weather stripped or sealed; and attic mount-
• Location of fireplace and chimney ed ductwork and air handler joints and seams taped or
sealed.
Negative pressure results from the imbalance of air avail- • Basement installations should be avoided due to stack
able for the fireplace to operate properly. Causes for this effect. Stack effect creates negative pressure in lower
imbalance include: levels. Hearth & Home Technologies recommends the
• Exhaust fans (kitchen, bath, etc.) use of direct vent fireplaces in basements.

• Range hoods Location of the fireplace and chimney will affect performance.
• Combustion air requirements for furnaces, water heat- As shown in Figure 3.3, the chimney should:
ers and other combustion appliances • Be installed through the warm space enclosed by the
• Clothes dryers building envelope. This helps to produce more draft, es-
pecially during lighting and die-down of the fire.
• Location of return-air to furnace or air conditioning
• Penetrate the highest part of the roof. This minimizes
• Imbalances of the HVAC air handling system the effects of wind turbulence.
• Upper level air leaks (recessed lighting, attic hatch open- • Be located away from trees, adjacent structures, un-
ing, duct leaks) even roof lines and other obstructions.
Offsets can restrict draft so their use should be minimized.
To minimize the effects of negative air pressure, the follow- Consider the fireplace location relative to floor and ceiling
ing must be considered: and attic joists.

Recommended Recommended
Location Location

Marginal
Location
Location
Not
Recommended

Location NOT
Recommended

Windward

Leeward

Multi-level Roofs

Figure 3.3

Heat & Glo • Gateway • 288-900 Rev. S • 3/06 13


This unit is equipped to accept outside air. It is recom- Air Damper
mended that an AK-TV air kit be used with this appli-
ance. By using outside make-up air, the amount of room Before lighting the burner, open the damper. Close the
air used for combustion will be reduced. However, in a neg- damper when the burner is off.
ative pressure condition the outside air kit MUST be in- Detailed installation instructions for Model AK-TV Outside
stalled to obtain proper performance and to help prevent Air kit are found in the kit.
spillage of combustion gases.
A 4-inch side collar/damper (found in AK-TV Kit) must be
installed on the fireplace by attaching the side collar to the
outer wrap of the fireplace at the right-hand rear corner using
sheetmetal screws. Attach damper handle (extended handle
found in manual bag) to the damper door prior to attaching
door to outer wrap. Then lift the handle into the notch under
the fireplace. See Figure 3.5. Attach one end of a 4-inch
flexible air duct (not provided in the AK-TV Kit) to the side
collar and the other end of the duct to the make-up air
termination cap. Use plastic tie straps to secure the ends
of the flex duct to each collar.

WARNING
Asphyxiation Risk.
Fire Risk.
Do NOT draw outside combustion air from:
EXHAUST
• Wall, floor or ceiling cavity. COLLAR

• Enclosed space such as an attic or garage. AK-TV


• Close proximity to exhaust vents or chimneys. AIR
DAMPER
Fumes or odor may result. ASSEMBLY

Figure 3.4 Make-up Air


WARNING: WHEN TERMINATING THE VENTING
!
HORIZONTALLY THE MAKE-UP AIR TERMINATION
MUST BE AT A LOWER ELEVATION THAN THE
EXHAUST TERMINATION.

NOTCH

HANDLE

Figure 3.5 Make-up Air Handle

NOTE: Pull handle to open damper. Push handle to close


damper.

14 Heat & Glo • Gateway • 288-900 Rev. S • 3/06


Step 4. Installing the Vent System The following figures are examples of approved venting con-
ditions. Venting downward (3’ maximum) is approved, to
A. Vent System Approvals allow venting below the floor. However, only one downward
Model GATEWAY is approved to use Duravent 4-inch section is allowed for up to, but not exceeding 3’ maximum.
(102mm) diameter B-type vent for installations that terminate
vertically. The PV-Flex Series vent pipe is approved for use NOTE: It is always better to first attach a straight section of
in installations that terminate horizontally. This pipe is tested vent to the unit before attaching an elbow. Avoid using el-
and listed as an approved component of the fireplace. bows in the vent system if possible.
This model may also use single wall rigid or flexible gas Continue to add vent components, until the vent run is com-
vent IF and ONLY IF the vent system is installed within pleted.
non-combustible construction such as a masonry chimney.
The same diameter noted above for B-type vent must be Using the four screws provided in the manual bag, attach
used for single-wall vent (see Figure 3.6). the flue outlet collar. Connect a vent component to the flue
For B-type vent the clearance to combustibles is 1-inch. outlet collar (see Figure 3.6).
Follow vent manufacturers REQUIRED clearances. For PV-
Flex the clearances are 1-1/2” top and 1” sides and bottom
when venting horizontally. For PV-Flex the clearances are
1” all sides when passing vertically through combustible
materials.
High temperature silicone sealant is required at all pipe joints.

NOTE: Due to the positive pressure within the Gateway


venting system, when using PV-FLEX use a 1/2” bead
of silicone caulk on ALL pipe ends and connectors
throughout the vent run to ensure a completely sealed
system. 50 FT.

Vent pipes must be installed within the conditioned house


Î envelope in order to avoid flue gas condensation. Vertical
termination through an unconditioned attic space is
permissible.
The flame and ember appearance may vary based on the
type of fuel burned and the venting configuration used.
B. System Components
Consult Local Building Code Officials and Codes for proper
vent system installations.
Plan and install the vent system using the parameters shown
in this vent system configuration chart.

No. of 90O
Maximum Maximum Maximum
Elbows/
Vertical Run Horizontal Run Total Run
Bends
0 - 40' (12.2m) 40' (12.2m)
1 50' (15.2m) - 50' (15.2m) 40 FT.

1 - 35' (10.7m) 35' (10.7m)


2 - 35' (10.7m) 35' (10.7m)
2 35' (10.7m) 35' (10.7m) 38' (11.6m)
3 30' (9.1m) 35' (10.7m) 35' (10.7m)
Figure 3.6 Vent System Attachment
4 25' (7.6m) 32' (9.8m) 35' (10.7m)
5 25' (7.6m) 30' (9.1m) 33' (10.1m)

MAXIMUM TOTAL RUN: = 50 FT. WARNING: THIS GAS FIREPLACE MUST NEV-
o o
! ER BE VENTED BY CONNECTING TO A CHIM-
MAXIMUM NO. of ELBOWS/BENDS: five - 90 or ten - 45
NEY FLUE SERVING A SEPARATE SOLID FUEL
WARNING: YOU MUST NOT EXCEED THESE BURNING APPLIANCE.
! PARAMETERS.

Heat & Glo • Gateway • 288-900 Rev. S • 3/06 15


H
HORIZONTAL VENTING

H (FT.)
40' MAX. (12.2m)
2’ MIN. (.6m)

TERMINATION
CAP

Figure 3.7 Horizontal Venting and Horizontal Termination

VENTING WITH ONE 90o ELBOW

TERMINATION
V (FT.) CAP
50' MAX. (13.8m)

Figure 3.8 Venting with One 90° Elbow and Vertical Termination

16 Heat & Glo • Gateway • 288-900 Rev. S • 3/06


H
VENTING WITH TWO
90o BENDS
V (FT.) DOWN
3 FT. 3´ MAX. (.91m)
V MAXIMUM
H+ H1 (FT.)
35´ MAX. (10.7m)
V+H+H1 = 38´ MAX.(11.6m)

Note: Only horizontal


venting allowed after
H1
downward venting run.

H1

VENTING WITH TWO


90o BENDS
V (FT.) UP
35´ MAX. (10.7m)
H H+ H1 (FT.)
35´ MAX. (10.7m)
V+H+H1 = 38´ MAX.(11.6m)
Figure 3.9 Venting with Two 90° Bends and Horizontal Termination

VENTING WITH THREE 90o BENDS

V (FT.) (DOWN) H + H1+ H2 (FT.)


3' MAX. (.91m) 35´ MAX. (10.7m)

H V+H+H1+H2 = 35´ MAX.(10.7m)

V 3’
MAXIMUM

Note: Only horizontal


venting allowed after
downward venting run.
H2
H1

Figure 3.10
Venting with Three 90° Elbows and Horizontal Termination

Heat & Glo • Gateway • 288-900 Rev. S • 3/06 17


VENTING WITH FOUR 90o BENDS

V (FT.) (DOWN) H+H1+H2+H3 (FT.)


3' MAX. (.914m) 32' MAX. (9.8m)

H V+H+H1+H2+H3 = 35´ MAX.(10.7m)

3 FT. V
MAXIMUM

H3

H1 H2

Note: Only horizontal


venting allowed after
downward venting run.

Figure 3.11
Venting with Four 90° Bends and Horizontal Termination

VENTING WITH FIVE 90o BENDS

V (FT.) DOWN H+H1+H2+H3+H4 (FT.)


3' MAX. (.914m) 30' MAX. (9.1m)

V+H+H1+H2+H3+H4 = 33´ MAX.(10.1m)

3 FT.
MAXIMUM V

H4
H3

H1
H2

Note: Only horizontal


venting allowed after
downward venting run.

Figure 3.12 Venting with Five 90° Bends and Horizontal Termination

18 Heat & Glo • Gateway • 288-900 Rev. S • 3/06


Install Support Brackets Install Firestops
For Horizontal Runs - Firestops are REQUIRED on both
For Horizontal Runs - The vent system must be sup- sides of a combustible wall through which the vent passes.
ported every five (5) feet of horizontal run by a horizontal
pipe support for B-Vent (see Figure 3.21 for PV-Flex pipe To install firestops for horizontal runs that pass through
support brackets). either interior or exterior walls:
To install support brackets for horizontal runs: • Cut a 7 in. x 8 in. (178mm x 204mm) hole through the wall.

• Place the pipe supports around the vent pipe. • Position the firestops on both sides of the hole previ-
• Nail the pipe supports to the framing members. ously cut and secure the firestops with nails or screws.
• Continue the vent run through the firestops.
For Vertical Runs - The vent system must be supported
every eight (8) feet (2.4m) above the fireplace flue outlet by
wall brackets. NOTE: There must be NO INSULATION or other
combustibles inside the framed firestop opening.
To install support brackets for vertical runs:
• Attach wall brackets to the vent pipe and secure the wall
bracket to the framing members with nails or screws.

WALL STUD
7”

WALL BRACKET

4 INCH PIPE
B-VENT 8”

8 FT.
(2.4mm)

Figure 3.14 Firestop Wall Hole

TRIM HEAT SHIELD IF TOO LONG,


1 INCH ADD TO SHIELD IF TOO SHORT
MIN.
(25.4mm)

4 INCH
ELBOW

INTERIOR
FLUE FIRESTOP
OUTLET

Figure 3.13 Installing Support Brackets

TERMINATION CAP
WITH BUILT-IN
EXTERIOR FIRESTOP

Figure 3.15 Interior & Termination Cap Firestops

Heat & Glo • Gateway • 288-900 Rev. S • 3/06 19


For Vertical Runs - One ceiling firestop is REQUIRED Figure 3.18 shows an attic installation. Keep insulation away
at the hole in each ceiling through which the vent passes. from the vent pipe at least 1 inch (25mm).
To install firestops for vertical runs that pass through ceilings: While it is not mandatory, it is strongly recommended that an
• Position a plumb bob directly over the center of the verti- attic insulation shield be used whenever insulation can come
cal vent component. in contact with the vent pipe. Follow your local building codes.
• Mark the ceiling to establish the centerpoint of the vent.
• Drill a hole or drive a nail through this centerpoint. NAILS (4 REQUIRED)
• Check the floor above for any obstructions, such as wir-
ing or plumbing runs.
• Reposition the fireplace and vent system, if necessary,
to accommodate the ceiling joists and/or obstructions.
• Cut a 6 1/2 in. x 6 1/2 in. (165mm x 165mm) hole through RAFTER

the ceiling, using the centerpoint previously marked.


• Frame the hole with framing lumber the same size as the
ceiling joists.

NOTE: There must be NO INSULATION or other


combustibles inside the framed firestop opening. CEILING

CEILING FIRESTOP
6 1/2" (165mm)
6 1/2" (165mm)
Figure 3.18 Attic Firestop

NOTE: For vertical termination the termination cap must be


CHIMNEY
HOLE listed for the vent pipe used.

EXISTING CEILING
NEW
JOISTS
FRAMING
MEMBERS
CEILING

Figure 3.16 Hole & New Framing Members

If the area above the ceiling is NOT an attic, position and


secure the ceiling firestop on the ceiling side of the previously
cut and framed hole.

JOIST

CEILING

NAILS (4 REQUIRED)
CEILING FIRESTOP

Figure 3.17 Ceiling Firestop (Ceiling Side)

If the area above the ceiling IS an attic, position and secure


the firestop on top of the previously framed hole.

20 Heat & Glo • Gateway • 288-900 Rev. S • 3/06


C. Vent Termination • For vent runs over 25 feet in length, a pipe connector
must be used to connect one pipe section to another
For Horizontal Terminations - To attach and secure (see Figure 3.20).
the termination to the last section of horizontal vent:
• Venting from the fireplace must extend through the inte-
rior firestop to flush with exterior surface. Figure 3.20 PVFLEX-CONNECT
• The termination kit should pass through the wall firestops
from the exterior of the building.
• Adjust the termination cap to its final exterior position on
the building.
• Figure 3.19 shows the approved cap and pipe for hori-
zontal termination. No other components may be used.

NOTE: Due to the positive pressure within the Gateway


venting system, when using PV-FLEX use a 1/2” bead
of silicone caulk on ALL pipe ends and connectors
throughout the vent run to ensure a completely sealed 1/2” bead of Hi temp silicone caulk
system. inside pipe and outside connector

PVFLEX-10
10’ Length of Flex Pipe
Install Support Brackets
The PVFLEX pipe run in a horizontal position must be sup-
ported at least every 4 feet to assure proper clearances to
combustibles is maintained; 1-1/2" on top and 1" on the
sides and bottom. The PVFLEX pipe run in a vertical posi-
tion must be supported every 8 feet to maintain clearances
25’ Length of Flex Pipe to combustibles 1 inch on all sides .
PVFLEX-25

PVFLEX 1-1.2” FLOOR


PVFLEX MIN.
STARTING COLLAR
1” MIN. 1” MIN.

BDA-01TR
Horizontal
Termination Cap
FLOOR
JOISTS
1” MIN.
Figure 3.19

PLUMBERS STRAP
Figure 3.21
WARNING: THE TERMINATION CAP MUST BE PO-
! SITIONED SO THAT THE ARROW IS POINTING UP.

WARNING: THE BOTTOM OF THE VENT


! TERMINATION CAP MUST BE A MINIMUM
OF 12 INCHES (305 MM) ABOVE GROUND LEVEL
(GRADE). THE TOP OF THE CAP MUST BE A MINI-
MUM OF 18 INCHES (457 MM) BELOW COMBUSTI-
BLE MATERIAL, SUCH AS A DECK, AND THE SIDE
OF THE CAP MUST BE A MINIMUM OF 12 INCHES
(305 MM) AWAY FROM A PARALLEL OUTSIDE WALL.
VENTING TERMINALS SHALL NOT BE RECESSED
INTO A WALL OR SIDING. SEE FIGURE 22 FOR VENT
TERMINATION CLEARANCES.

Heat & Glo • Gateway • 288-900 Rev. S • 3/06 21


O
N

P
G R
v
A H
D Q
E (See Note 2)
v

B V
L
B U.S. T
v (3 FT)
v B
v S Electrical S
V V
Service
F v M
v
I D*
v X
A J or K V

V = VENT TERMINAL X = AIR SUPPLY INLET = AREA WHERE TERMINAL IS NOT PERMITTED

A = 12" ....................... clearances above grade, veran- K = 3 ft. (U.S.A.)


(See Note 1) da, porch, deck or balcony 6 ft. (Canada) ......... clearance to a mechanical
B = 12" ....................... clearances to window or door air supply inlet
that may be opened, or to per- L** = 7 ft. ......................... clearance above paved
manently closed window. (See Note 1) sidewalk or a paved driveway
located on public property
D* = 24" ....................... vertical clearance to unventilat-
ed soffit or to ventilated soffit lo- M*** = 18" ......................... clearance under veranda,
cated above the terminal porch, deck or balcony
*60” ...................... for vinyl clad soffits and below N = 12” ......................... non-vinyl sidewalls
12” ......................... vinyl sidewalls
electrical service
O = 24” ......................... non-vinyl soffit and overhang
F = 9" ........................ clearance to outside corner 60” ......................... vinyl soffit and overhang
G = 12" ....................... clearance to inside corner P = 8 ft.
H = 3 ft. (Canada) ...... not to be installed above a gas Q R
MIN MAX
______________________________________________________________________
meter/regulator assembly within
3 feet (90cm) horizontally from the 1 cap 3 feet 2 x Q ACTUAL
______________________________________________________________________
center-line of the regulator 2 caps 6 feet 1 x Q ACTUAL
______________________________________________________________________
I = 3 ft. (U.S.A.) 3 caps 9 feet 2/3 x Q ACTUAL
______________________________________________________________________
6 ft. (Canada) ...... clearance to gas service regu-
4 caps 12 feet 1/2 x Q ACTUAL
lator vent outlet
QMIN = # termination caps x 3 RMAX = (2 / # termination caps) x QACTUAL
J = 9" (U.S.A.)
12" (Canada) ........ clearance to non-mechanical air S = 6" .......................... clearance from sides of elec-
supply inlet to building or the (See Note 5) trical service
combustion air inlet to any other
appliance T = 12" ......................... clearance above electrical
(See Note 5) service

** a vent shall not terminate directly above a sidewalk or paved NOTE 3: Local codes or regulations may require different
driveway which is located between two single family dwellings clearances.
and serves both dwellings. NOTE 4: Termination caps may be hot. Consider their proximity to
*** only permitted if veranda, porch, deck or balcony is fully open on doors or other traffic areas.
a minimum of 2 sides beneath the floor. NOTE 5: Location of the vent termination must not interfere with
access to the electrical service.
NOTE 1: On private property where termination is less than 7 feet
above a sidewalk, driveway, deck, porch, veranda or balcony, use of WARNING: In the U.S: Vent system termination is NOT permitted
a listed cap shield is suggested. in screened porches. You must follow side wall, overhang and
ground clearances as stated in the instructions.
NOTE 2: Termination in an alcove space (spaces open only on one side
and with an overhang) are permitted with the dimensions specified for In Canada: Vent system termination is NOT permitted in screened
vinyl or non-vinyl siding and soffits. 1. There must be 3 feet minimum porches. Vent system termination is permitted in porch areas
between termination caps. 2. All mechanical air intakes within 10 feet with two or more sides open. You must follow all side walls,
overhang and ground clearances as stated in the instructions.
of a termination cap must be a minimum of 3 feet below the termination
cap. 3. All gravity air intakes within 3 feet of a termination cap must be Heat & Glo assumes no responsibility for the improper perfor-
a minimum of 1 foot below the termination cap. mance of the fireplace when the venting system does not meet
these requirements.

Figure 3.22 Vent Termination Minimum Clearances

22 Heat & Glo • Gateway • 288-900 Rev. S • 3/06


For Vertical Terminations - To locate the vent and HORIZONTAL
OVERHANG
install the vent sections:
• Locate and mark the vent centerpoint on the underside
of the roof, and drive a nail through the centerpoint. 2 FT. 2 FT. MIN. VERTICAL
MIN.
WALL
LOWEST
• Make the outline of the roof hole around the centerpoint DISCHARGE
OPENING
nail. TERMINATION
CAP
• The size of the roof hole framing dimensions depend on the
pitch of the roof. There MUST BE a 1-inch (25.4mm) clear- X
12
ance from the vertical vent pipe to combustible materials.
ROOF PITCH
• Mark the roof hole accordingly. IS X/ 12

• Cover the opening of the installed vent pipes. H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING

• Cut and frame the roof hole.


Roof Pitch H (min.) ft.
• Use framing lumber the same size as the roof rafters
and install the frame securely. Flashing anchored to the flat to 6/12 1.0
frame must withstand heavy winds. over 6/12 to 7/12 1.25
over 7/12 to 8/12 1.5
over 8/12 to 9/12 2.0
• Continue to install concentric vent sections up through over 9/12 to 10/12 2.5
the roof hole (for inside vent installations) or up past the over 10/12 to 11/12 3.25
roof line until you reach the appropriate distance above over 11/12 to 12/12 4.0
the roof (for outside terminations). over 12/12 to 14/12 5.0
over 14/12 to 16/12 6.0
over 16/12 to 18/12 7.0
over 18/12 to 20/12 7.5
WARNING: MAJOR U.S. BUILDING CODES over 20/12 to 21/12 8.0
!
SPECIFY MINIMUM CHIMNEY AND/OR Figure 3.23 Minimum Height from Roof to
VENT HEIGHT ABOVE THE ROOF TOP. THESE MIN- Lowest Discharge Opening
IMUM HEIGHTS ARE NECESSARY IN THE INTER-
EST OF SAFETY. SEE THE FOLLOWING DIAGRAM Step 5. Positioning, Leveling, and
FOR MINIMUM HEIGHTS, PROVIDED THE TERMI-
Securing the Fireplace
NATION CAP IS AT LEAST TWO (2) FEET FROM A
The diagram below shows how to properly position, level,
VERTICAL WALL AND 2-FEET BELOW A HORIZON-
and secure the fireplace.
TAL OVERHANG.
• Place the fireplace into position (see Figure 3.24).
• Level the fireplace from side to side and from front to
NOTE: This also pertains to vertical vent systems in- back.
stalled on the outside of the building. • Shim the fireplace with non-combustible material, such
as sheet metal, as necessary.
To seal the roof hole, and to divert rain and snow from the
• Secure the fireplace to the framing using nails or screws
vent system: through the nailing tabs.
• Attach a flashing to the roof using nails, and use a non-
hardening mastic around the edges of the flashing base
where it meets the roof.

• Attach a storm collar over the flashing joint to form a


water-tight seal. Place non-hardening mastic around the
joint, between the storm collar and the vertical pipe.

• Slide the termination cap over the end of the vent pipe
and rotate the pipe clockwise 1/4 turn. NAILING TABS
(BOTH SIDES)

Figure 3.24
Proper Positioning, Leveling,
and Securing of a Fireplace

Heat & Glo • Gateway • 288-900 Rev. S • 3/06 23


Step 6. The Gas Control System WARNING: DO NOT USE AN OPEN FLAME
! TO CHECK FOR GAS LEAKS.
WARNING: THIS UNIT IS NOT FOR USE WITH
! SOLID FUEL. • At the gas line access hole, use insulation to re-pack
the space around the gas pipe.
Intermittent Pilot Ignition (IPI) System
The gas control system used with this model is In- • Insert insulation from the outside of the fireplace and
termittent Pilot Ignition (IPI). This system includes a 3V pack the insulation tightly to totally seal between the
control valve, electronic module, and intermittent pilot. pipe and the outer casing.

FLAME
IPI IGNITION SENSOR
ROD

USE A WRENCH ON
SHUT-OFF VALVE WHEN
TIGHTENING GAS LINE

MANUAL
NOTE: SHUT-OFF VALVE
Flames too close to the ceramic
insulators can cause nuisance lock- GAS VALVE
outs and electrode failure.
FLEX
CONNECTOR

Figure 3.25
Gas Control System

Step 7. The Gas Supply Line


NOTE: Have the gas supply line installed in accordance CONTROL
with local building codes by a qualified installer VALVE GAS LINE
approved and/or licensed as required by the locality. ACCESS

(In the Commonwealth of Massachusetts installation Figure 3.26 Gas Supply Line
must be performed by a licensed plumber or gas
fitter).
NOTE: Before the first firing of the fireplace, the gas Step 8. Gas Pressure Requirements
supply line should be purged of any trapped air.
NOTE: Consult local building codes to properly size
Pressure requirements for Heat & Glo gas fireplaces
the gas supply line leading to the 1/2 inch (13mm) are shown in the table below.
hook-up at the unit.
This gas fireplace is designed to accept a 1/2 inch (13mm) Pressure Natural Gas Propane
gas supply line. To install the gas supply line: Minimum 5.0 inches 11.0 inches
• A listed (and Commonwealth of Massachusetts approved) Inlet Pressure w.c. w.c.
1/2 inch (13mm) tee-handle manual shut-off valve and a
listed flexible gas connector are connected to the 1/2 Maximum Inlet 14.0 inches 14.0 inches
inch (13mm) inlet of the control valve. NOTE: If substi- Gas Pressure w.c. w.c.
tuting for these components, please consult local codes Manifold 3.5 inches 10.0 inches
for compliance. Pressure w.c. w.c.
• Locate the gas line access hole in the outer casing of
the fireplace. A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is
• The gap between the supply piping and gas access hole provided on the inlet and outlet side of the gas control for a
can be plugged with non-combustible insulation to pre- test gauge connection to measure the manifold pressure.
vent cold air infiltration.
The fireplace and its individual shut-off valve must be
• Open the fireplace lower grille, insert the gas supply line
through the gas line hole, and connect it to the shut-off disconnected from the gas supply piping system during
valve. any pressure testing of the system at test pressures in
• When attaching the pipe, support the control so that the excess of one-half (1/2) psig (3.5 kPa).
lines are not bent or torn. The fireplace must be isolated from the gas supply piping
• After the gas line installation is complete, all connec- system by closing its individual shut-off valve during any
tions must be tightened and checked for leaks with a pressure testing of the gas supply piping system at test
commercially-available, non-corrosive leak check solu- pressures equal to or less than one-half (1/2) psig (3.5 kPa).
tion. Be sure to rinse off all leak check solution following
testing.
24 Heat & Glo • Gateway • 288-900 Rev. S • 3/06
SPARK TO
PILOT IGNITOR

HOT NEUTRAL
BLOWER

VACUUM HOSE TO REMOTE,


CONNECTION POINT THERMOSTAT
OR WALL SWITCH IGNITION
MODULE 3V
TRANSFORMER
3V
ORANGE
I (IGNITOR)

ON/OFF
WHITE (SENSOR)
SWITCH BLACK
ASSEMBLY
S

PILOT ASSEMBLY
AND VALVE
ASSEMBLY
OPTIONAL MUST BE
BLOWER BLACK GROUNDED
LEADS
(COMMON GROUND
FAN WITH FIREPLACE
REM CHASSIS)
VACUUM HOSE
120 VAC CONNECTION POINT GROUND TO
JUNCTION BOX FIREPLACE
CHASSIS
VACUUM SWITCH
ORANGE

BROWN

BROWN GREEN

Figure 3.27 Intermittent Pilot Ignition Wiring Diagram

Step 9. Wiring the Fireplace Wall Switch


Position the wall switch in the desired position on a wall.
NOTE: Electrical wiring must be installed by a licensed
Using 14 GA or greater (following local codes) wire the
electrician.
wall switch to the wire harness provided. The ground wire
CAUTION: DISCONNECT REMOTE CONTROLS IF YOU must be securely attached to the ground stud in the junc-
ARE ABSENT FOR EXTENDED TIME PERIODS. THIS tion box. Do not run 110-120 VAC to the valve. This valve
WILL PREVENT ACCIDENTAL FIREPLACE OPERATION. system runs off of the 3 Volt transformer (see Figure 3.25).
For Intermittent Pilot Ignition Wiring System CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC-
TION WHEN SERVICING CONTROLS. WIRING ERRORS
Appliance Requirements
CAN CAUSE IMPROPER AND DANGEROUS OPERA-
• This appliance REQUIRES 110-120 VAC to operate.
TION. VERIFY PROPER OPERATION AFTER SERVICING.
WARNING: DO NOT CONNECT 110-120 VAC
! TO THE GAS CONTROL VALVE OR THE AP- WARNING: CONTINUOUS 110-120 VAC SER-
! VICE MUST BE WIRED TO THE FIREPLACE
PLIANCE WILL MALFUNCTION AND THE VALVE
WILL BE DESTROYED. JUNCTION BOX.

• The gas control system used with this model is (IPI) Inter-
mittent Pilot Ignition. This system includes a 3 Volt control
valve, electronic module, and intermittent pilot.

Optional Accessories
Optional fan and remote control kits require that 110-120
VAC be wired to the factory installed junction box before
the fireplace is permanently installed.

Heat & Glo • Gateway • 288-900 Rev. S • 3/06 25


VARIABLE SPEED CONTROL NOTE: IF ANY OF THE ORIGINAL WIRE
HOT AS SUPPLIED WITH THE APPLIANCE
NEUTRAL
MUST BE REPLACED, IT MUST BE
O
REPLACED WITH TYPE 105 C RATED WIRE.

BLK
BLK

BLK

BLK

BLOWER

REM FAN
TEMPERATURE 120 VAC
SENSOR SWITCH JUNCTION BOX

TEMPERATURE
JUNCTION BOX SENSOR SWITCH

FAN

SPEED CONTROL
(RHEOSTAT)

Figure 3.28
Fan Wiring Diagram

Step 10. Finishing CEILING

Figure 3.29 shows the minimum vertical and corresponding


maximum horizontal dimensions of fireplace mantels or
12”
other combustible projections above the top front edge of
11”
the fireplace. See Figures 1.2 and 3.1 for other fireplace 10”
clearances. 9”
8”
Only non-combustible materials may be used to cover the 7” 36”
black fireplace front. 6” 12”
11”
10”
9”
8”
WARNING: WHEN FINISHING THE FIREPLACE, 7”
! NEVER OBSTRUCT OR MODIFY THE AIR IN-
6”

LET/OUTLET GRILLES IN ANY MANNER.


1-3/4”
NOTE: Sheetrock can be placed on the top edge and sides
of the fireplace (see Figure 3.30).
TOP OF TOP FRONT EDGE
UNIT OF NON-COMBUSTIBLE
BOARD

Figure 3.29
Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles above Fireplace

26 Heat & Glo • Gateway • 288-900 Rev. S • 3/06


CAUTION: IF JOINTS BETWEEN THE FINISHED WALLS Positioning the Logs
AND THE FIREPLACE SURROUND (TOP AND SIDES) Refer to the installation instructions that accompany the
ARE SEALED, A 300° F. MINIMUM SEALANT MATE- logs. Save the Log Instructions with this manual.
RIAL MUST BE USED. THESE JOINTS ARE NOT RE-
QUIRED TO BE SEALED. ONLY NON-COMBUSTIBLE If sooting occurs, the logs might need to be repositioned
MATERIAL (USING 300° F. MINIMUM ADHESIVE, IF slightly to avoid excessive flame impingement.
NEEDED) CAN BE APPLIED AS FACING TO THE FIRE-
PLACE SURROUND. SEE THE DIAGRAM BELOW. Placing the Ember Material
The bag labeled Glowing Ember (050-721) is standard
FINISH WALL MATERIAL MAY BE
COMBUSTIBLE - TOP AND SIDES glowing ember material. To place the ember material:
• Unhook the spring clips around the glass door. Remove
NON-COMBUSTIBLE
BOARD 0” GAP
the glass door.
• Ember material is to be placed on burner with caution. Do
NOT place ember material over burner port holes. Place
only dime size pieces along outer edges of port trails (see
Figure 3.31). The bag is for (4) ember applications. Failure
to apply ember material as directed could result in poor
lighting conditions and sooting problems. Save the remain-
ing ember materials for use during fireplace servicing.

0” GAP 0” GAP

HIGH TEMPERATURE (300OF/149 C


O
MIN.)
TOP & SIDE SEAL JOINT

Figure 3.30 Sealant Material

Hearth Extensions
A hearth extension may be desirable for aesthetic reasons.
However, ANSI or CAN/CGA testing standards do not require
EMBER
hearth extensions for gas fireplace appliances. MATERIAL
FIRST
Step 11. Installing Trim, Logs & Ember Material INCORRECT
GRATE BAR

Installing the Trim EMBER CORRECT


PLACEMENT EMBER
Combustible materials may be brought up to the specified
PLACEMENT
clearances on the side and top front edges of the fireplace,
but MUST NEVER overlap onto the front face. The joints Figure 3.31 Placement of the Ember Material
between the finished wall and the fireplace top and sides
can only be sealed with a 300° F. (149° C) minimum sealant.
• Replace glass door and spring clips.
Install optional marble and brass trim surround kits as
desired. Marble, brass, brick, tile, or other non-combustible • Replace the upper and lower louvers.
materials can be used to cover up the gap between the
sheetrock and the fireplace.
Do not obstruct or modify the air inlet/outlet grilles. When
overlapping on both sides, leave enough space so that the
bottom grille can be lowered and the trim door removed.

Shutter Settings
NG LP
___________________________________________
Burner 1/4” 1/2”

Heat & Glo • Gateway • 288-900 Rev. S • 3/06 27


Lava Rock A small amount of air will be in the gas supply lines. When
If desired, pour the Lava Rock from the plastic bag around first lighting the fireplace, it will take a few minutes for the
the outside of the log grate. DO NOT place any Lava Rock lines to purge themselves of this air. Once the purging is
on top of the burner. complete, the fireplace will light and will operate normally.
Subsequent lightings of the fireplace will not require this
GLASS SPECIFICATIONS: purging of air from the gas supply lines, unless the gas
valve has been turned to the OFF position, in which
MODEL GLASS TYPE case the air would have to be purged.
GATEWAY TEMPERED NOTE: The fireplace should be run 3 to 4 hours on the
initial start-up. Turn it off and let it cool completely. Remove
Heat & Glo fireplaces manufactured with tempered glass and clean the glass. Replace the glass and run the fireplace
may be installed in hazardous locations such as bathtub for an additional 8 hours. This will help to cure the products
enclosures as defined by the CPSC. The tempered glass used in the paint and logs.
has been tested and certified to the requirements of ANSI
Z97.1-1984 and CPSC 16 CFR 1202. (Safety Glazing Certi-
fication Council SGCC # 1595 and 1597. Architectural Test- During this break-in period it is recommended that some
ing, Inc. Reports 02-31919.01 and 02-31917.01.) windows in the house be opened for air circulation. This will
help avoid setting off smoke detectors, and help eliminate
This statement is in compliance with CPSC 16 CFR Sec- any odors associated with the fireplace’s initial burning.
tion 1201.5 “Certification and labeling requirements” which
refers to 15 USC 2063 stating “…Such certificate shall ac-
company the product or shall otherwise be furnished to any
Step 13. Lighting the Fireplace
distributor or retailer to whom the product is delivered.”
Some local building codes require the use of tempered glass You’ve reviewed all safety warnings, you’ve checked the
with permanent marking in such locations. Glass meeting fireplace for gas leaks, you know the vent system is
this requirement is available from the factory. Please con- unobstructed, and you’ve checked for faulty components.
tact your dealer or distributor to order. Now you’re ready to light the fireplace.

WARNING: PLEASE REFER TO THE USER’S


!
Step 12. Before Lighting the Fireplace MANUAL FOR ALL CAUTIONS, SAFETY, AND
WARNING INFORMATION PERTAINING TO THE
Before lighting the fireplace, be sure to do the following: LIGHTING AND OPERATION OF THE FIREPLACE.
Remove all paperwork from underneath the fireplace.
Review safety warnings and cautions After the Installation
• Read the Safety and Warning Information section at
the beginning of this Installers Guide. ! LEAVE THIS INSTALLATION MANUAL WITH
THE APPLIANCE FOR FUTURE REFERENCE.
Double-check for gas leaks
• Before lighting the fireplace, double-check the unit for
possible gas leaks.
Double-check vent terminations and front grilles for
obstructions.
• Before lighting the fireplace, double-check the unit for
possible obstructions that could be blocking the vent ter-
minations or the front grilles.
Double-check for faulty components
• Any component that is found to be faulty MUST BE re-
placed with an approved component. Tampering with the
fireplace components is DANGEROUS and voids all war-
ranties.
• Confirm that 3V transformer is plugged into the junction
box as shown in Figure 3.27.
• Ensure vacuum hose (telfon tube) is firmly connected at
the vacuum hose connection point on both the blower
and the vacuum switch (see Figure 3.27).

28 Heat & Glo • Gateway • 288-900 Rev. S • 3/06


4 Maintaining and Servicing
Your Fireplace

Fireplace Maintenance
Although the frequency of your fireplace servicing and main-
tenance will depend on use and the type of installation, you
should have a qualified service technician perform an appli-
ance check-up at the beginning of each heating season.
See the table below for specific guidelines regarding each
fireplace maintenance task.

IMPORTANT: TURN OFF THE GAS BEFORE SERVICING


YOUR FIREPLACE. Figure 4.1
Burner Flame Patterns
Replacing old ember material
Frequency: Once annually, during the checkup.
Checking Vent System
By: Qualified service technician.
Frequency: Before initial use and at least annually
Task: Brush away loose ember material near the burner.
thereafter, more frequently if possible.
Replace old ember material with new dime-size and shape
pieces of Glowing Ember (050-721). New ember material By: Qualified service technician/Home owner.
should be placed on top of the burner along outer edges of Task: Inspect the external vent cap on a regular basis to
port trails (see Figure 3.29). Save the remaining ember ensure that no debris is interfering with the flow of air. Inspect
material and repeat this procedure at your next servicing. entire vent system for proper function.
For more information, see Placing Ember Material.
Cleaning Glass Door
Cleaning Burner and Controls Frequency: After the first 3 to 4 hours of use. As neces-
Frequency: Once annually. sary after initial cleaning.
By: Home owner.
By: Qualified service technician.
Task: Remove and clean glass after the first 3 to 4 hours of
Task: Brush or vacuum the control compartment, fireplace use. After the initial cleaning, clean as necessary, particu-
logs and burner areas surrounding the logs. larly after adding new ember material. Film deposits on the
inside of the glass door should be cleaned off using a house-
Cleaning Flame Sensor Rod (IPI Systems) hold glass cleaner. NOTE: DO NOT handle or attempt to
Frequency: Annually. clean the door when it is hot and DO NOT use abra-
By: Qualified service technician. sive cleaners.
Task: Make a visual check of the straight flame sensor rod
(see Figure 3.25). Use emery cloth to carefully remove any
existing film or white deposits.

Checking Flame Patterns, Flame Height


Frequency: Periodically.
By: Qualified service technician/Home owner.
Task: Make a visual check of your fireplace’s flame patterns.
Make sure the flames are steady - not lifting or floating.
See Figures 3.25 and 4.1. The sensor tip should be covered
with flame.

Heat & Glo • Gateway • 288-900 Rev. S • 3/06 29

También podría gustarte