LINEA 01

12000 m
120 mm2
ESCENARIO 01 N02
S=5.23 MVA
N01 P=4.54 MW 22.9 kV
CON CONDUCTOR 120 mm2 22.9 kV Q=2.59 Mvar U=21.83 kV
RED U=22.90 kV I=0.13 kA u=95.33 %
P=-9.09 MW u=100.00 % Ploss=0.14 MW
Q=-5.19 Mvar Qloss=0.22 Mvar
Cargabilidad=65.96 %

LINEA 02 CARGA
12000 m S=10.00 MVA
120 mm2 PF=0.880
S=5.23 MVA
P=4.54 MW
Q=2.59 Mvar
I=0.13 kA
Ploss=0.14 MW
Qloss=0.22 Mvar
Cargabilidad=65.96 %

LINEA 01
ESCENARIO 02 12000 m
150 mm2
CON CONDUCTOR 150 mm2 S=5.21 MVA N02
N01 P=4.52 MW 22.9 kV
22.9 kV Q=2.59 Mvar U=21.94 kV
RED U=22.90 kV I=0.13 kA u=95.82 %
P=-9.04 MW u=100.00 % Ploss=0.12 MW
Q=-5.17 Mvar Qloss=0.21 Mvar
Cargabilidad=65.62 %

LINEA 02 CARGA
12000 m S=10.00 MVA
150 mm2 PF=0.880
S=5.21 MVA
P=4.52 MW
Q=2.59 Mvar
I=0.13 kA
Ploss=0.12 MW
Qloss=0.21 Mvar
Cargabilidad=65.62 %
LINEA 01
12000 m
ESCENARIO 03 185 mm2
S=5.18 MVA N02
CON CONDUCTOR 185 mm2 N01 P=4.49 MW 22.9 kV
22.9 kV Q=2.58 Mvar U=22.05 kV
RED U=22.90 kV I=0.13 kA u=96.30 %
P=-8.98 MW u=100.00 % Ploss=0.09 MW
Q=-5.15 Mvar Qloss=0.20 Mvar
Cargabilidad=65.29 %

LINEA 02 CARGA
12000 m S=10.00 MVA
185 mm2 PF=0.880
S=5.18 MVA
P=4.49 MW
Q=2.58 Mvar
I=0.13 kA
Ploss=0.09 MW
Qloss=0.20 Mvar
Cargabilidad=65.29 %

LINEA 01
ESCENARIO 04 12000 m
240 mm2
CON CONDUCTOR 240 mm2 N02
S=5.16 MVA
N01 P=4.47 MW 22.9 kV
22.9 kV Q=2.57 Mvar U=22.14 kV
RED U=22.90 kV I=0.13 kA u=96.68 %
P=-8.95 MW u=100.00 % Ploss=0.07 MW
Q=-5.14 Mvar Qloss=0.19 Mvar
Cargabilidad=65.03 %

LINEA 02 CARGA
12000 m S=10.00 MVA
240 mm2 PF=0.880
S=5.16 MVA
P=4.47 MW
Q=2.57 Mvar
I=0.13 kA
Ploss=0.07 MW
Qloss=0.19 Mvar
Cargabilidad=65.03 %