QUICK ENGINEERING FACTS
TYPICAL SHIPPING
FRAME STD. (BD) BASE ALTER BD’S MAX “BX” CD DIM. WEIGHT IN LBS. STEADY BUSH-
SIZE DIA.INCHES INCHES CPLG BORE CPLG HEIGHT ING KIT
WP-I WP-II
SINGLE PHASE MOTOR PRODUCT ONLY N AVAILABLE.
213P 10 -- 1.001 17.56 162 O
215 P 10 -- 1.001 17.56 186 T
254 P 10 12 1.001 23.38 250 A
256P 10 12 1.001 23.38 275 V
A
THREE PHASE MOTOR PRODUCT ONLY I
213TP 10 -- 1.00 17.56 210 L
A
215TP 10 -- 1.00 17.56 210 B
254TP 10 12/16.5 1.25 23.38 265 L
E
256TP 10 12/16.5 1.25 23.38* 300
LOWER
284TP 10 12/16.5 1.25 24.75 305 BEARING
286TP 10 12/16.5 1.25 24.75 325 IS
324TP 16.5 12 1.501 28.22 635 GREASE
LUBE
326TP 16.5 12 1.501 28.22 675 ON
364TP 16.5 12 1.501 31.16 730 OPEN
MOTORS
365TP 16.5 12 1.501 31.16 800 USE AS
404TP 16.5 20 1.688 36.94 1110 TEFC STD.
405TP 16.5 20 1.688 36.94 1200 PRODUCT THROUGH
WHEN THE
444TP 16.5 20 1.688 44.78 1500 WP-II WP1
445TP 16.5 20 1.688 44.78 1600 IS 447TP
447TP 20/16.5 24.5 2.251 49.78 2200 SPECIFIED FRAME.
5008P 24.5 20/30.5 2.501 57.06 3700 4050
5012P 24.5 20/30.5 2.751 72.30 4850 5300
6808P 30.5 36 3.875 80.06 8000 9150
6810P 30.5 36 3.875 91.06 9000 10350
8005P 42 36 3.875 80.562 9400 10900 NOT
8006P 42 36 3.875 84.562 9800 11700 AVAILABLE
8007P 42 36 3.875 88.562 10600 12500 AS KITS.
THESE
8008P 42 36 3.875 92.562 11400 13300 FRAME
8009P 42 36 3.875 96.562 12200 14100 SIZES
HAVE
8010P 42 36 3.875 100.562 13000 14900 OIL LUBE
8011P 42 36 3.875 104.562 13800 15700 LOWER
GUIDE
8012P 42 36 3.875 108.562 14600 16500 BEARINGS
9601P 42 4.250 85.03 12300 14300 AVAILABLE
AS A
9602P 42 4.250 89.03 13200 15200 MANUFACTURED
9603P 42 4.250 93.03 14100 16100 PRODUCT
9604P 42 4.250 97.03 15000 17000 ONLY
SEE MOD.
9605P 42 SECTION 4.250 101.03 15900 17900
9606P 42 4.250 105.03 16800 18800
9607P 42 4.250 109.03 17700 19700
9608P 42 4.250 113.03 18600 20600
182
July 2007 Brand of Emerson Motor Technologies
www.emersonmotors.com www.usmotors.com
QUICK ENGINEERING FACTS
STD. (BD) ALTER MAX CD-CPLG CD-CRLG TYPICAL TYPICAL TYPICAL STEADY
FRAME
BASE DIA. BD’S CPLG HEIGHT HEIGHT WEIGHT WEIGHT WEIGHT BUSHING
SIZE
INCHES INCHES BORE TEFC X-PROOF TEFC C-DUTY X-PROOF KIT
182 TP 10 -- 1.001 17.56 17.50 150 175 165
184 TP 10 -- 1.001 17.56 17.50 170 190 180
213 TP 10 -- 1.001 17.56 17.50 210 230 220
215 TP 10 -- 1.001 17.56 17.50 220 240 230
254 TP 10 12 1.251 22.94 22.94 265 405 395
256 TP 10 12 1.251 22.94 22.94 300 415 405
284 TP 10 12/16.5 1.251 26.56 26.56 320 515 500
286 TP 10 12/16.5 1.251 26.56 26.56 330 540 520
324 TP 16.5 12 1.501 28.50 28.50 665 760 740
326 TP 16.5 12 1.501 28.50 28.50 690 770 750 AVAILABLE
364 TP 16.5 -- 1.751 30.0 30.0 900 950 925
365 TP 16.5 -- 1.751 30.0 30.0 925 975 940
404 TP 16.5 -- 1.938 39.93 39.94 1350 1455 1430
405 TP 16.5 -- 1.938 39.93 39.94 1500 1750 1725
A444 TP 16.5 20 1.938 43.06 39.94 1400 1475 1435
A445 TP 16.5 20 1.688 39.93 39.94 1750 1800 1775
444 TP 16.5 20 1.937 43.06 42.50 1800 2000 1900
445 TP 16.5 20 1.937 43.06 42.50 1900 2100 2000
447 TP 16.5 20 1.937 46.56 46.00 2200 2400 2300
449 TP 24.5 20 2.501 56.88 56.88 3400 3600 -- NOT
5008 P 24.5 20 2.501 56.50 56.50 3450 3700 3700 AVAILABLE
AS KITS.
5807 P 30.5 24.5 2.750 61.53 61.53 5500 5800 5800
MFG’D
5809 P 30.5 24.5 2.750 68.53 68.53 6500 6800 6800 PRODUCT
5811 P 30.5 24.5 2.750 76.53 76.53 7500 7800 7800 ONLY
183
July 2007 Brand of Emerson Motor Technologies
www.emersonmotors.com www.usmotors.com
DECIMAL
Quick Engineering Facts METRIC
184
July 2007 Brand of Emerson Motor Technologies
www.emersonmotors.com www.usmotors.com
DESIGN
Quick Engineering Facts LETTER
C. DESIGN LETTER
The design letter that is assigned to a polyphase motor is defined by NEMA in Section MG1-16-1. The letter is a func-
tion of torques and locked amps exhibited by the motor. NEMA does not define values for every rating. If a rating is
not contained within the NEMA “envelopes” shown below, it cannot have a design letter on the nameplate. Voltage is
not a factor, only HP and speed. Note that multispeed have no design letter.
60 HZ
SYNCHRONOUS SPEED, RPM
HP
3600 1800 1200 900 720 600 514
1/2 - - -
3/4 - -
1 -
1-1/2
2 DEFINED
3
5 RATINGS
7-1/2
10-125, INCLUSIVE
150 -
200 - -
250 - - -
300-350 - - - -
400-500, INCLUSIVE - - - - -
50 HZ
SYNCHRONOUS SPEED, RPM
HP
3600 1500 1000 750
1/2 - - -
3/4 - -
1 -
1-1/2
2 DEFINED
3
5 RATINGS
7-1/2
10-125, INCLUSIVE
150
200
185
July 2007 Brand of Emerson Motor Technologies
www.emersonmotors.com www.usmotors.com
SUPPLEMENTAL
Quick Engineering Facts INFORMATION
D. FORMULAS
kW = hp x .746
Wk2 referred to motor shaft speed = [driven machine Wk2 (driven machine rpm)2 ] + gear Wk2 at motor speed
motor rpm
Approximate voltage drop (%) = motor kVA in-rush x transformer impedance (normally 5% to 7%)
transformer kVA
Conversion factors: CV = (metric hp) = 735.5 watts = 75 kg-m/sec Wk2 (lb-ft) = 5.93 x GD2 (kg-m2)
Ventilating-air requirements: 100-125 cfm of 400C air at 1/2-in. water pressure for each kW of loss
Degrees F = [(Degrees C) x 9 ] + 32
5
186
July 2007 Brand of Emerson Motor Technologies
www.emersonmotors.com www.usmotors.com
index of
quick engineering facts protection
E. INDEX OF PROTECTION
DEFINITION
012mm
2 Protected against solid 2 Protected against water 2 250 g
Impact energy:
objects over 12mm 15 dripping up to 150 from 15 cm 0.375 J
(e.g. finger) the vertical
02.5 mm
3 Protected against solid 3 60
Protected against rain 3 150 g
Impact energy:
objects over 2.5mm falling at up to 600 from
20 cm 0.500 J
(e.g. tools, wire) the vertical
01 mm
4 Protected against solid 4 Protected against water
4
objects over 1mm
(e.g. thin wire) splashes from all directions
The conditions and severity of the tests must be subject to a specific agreement between the manufac-
turer and the end user.
187
July 2007 Brand of Emerson Motor Technologies
www.emersonmotors.com www.usmotors.com
Quick engineering facts STORAGE
If a motor is not put into immediate service (one month or less), or if it is taken out of service for a prolonged period,
special storage precautions should be taken to prevent environmental damage. The following schedule is recom-
mended as a guide to determine storage needs.
Out of service in storage less than one month -- no special precautions except that space heaters, if supplied, must be
energized any time the motor is not running.
Out of service or in storage for more than one month but less than six months -- store per items 2A, B, C, D, E, F2 and G,
items 3A, B and C, and item 4.
Out of service or in storage for six months or more -- all recommendations.
2. Storage preparation
CAUTION:
DO NOT ATTEMPT TO GREASE BEARINGS WITH DRAIN CLOSED OR WHEN UNIT IS IN OPERATION.
188
July 2007 Brand of Emerson Motor Technologies
www.emersonmotors.com www.usmotors.com
quick engineering facts STORAGE
2) Oil-lubricated motors are shipped without oil and must be filled to the maximum capacity as indicated on the oil
chamber sight gauge window immediately upon receipt. Fill reservoir to maximum level with a properly selected
oil containing rust and corrosion inhibitors such as Texaco Regal Marine #77, Mobil Vaprotec Light, or an
equivalent.
NOTE: Motor must not be moved with oil in reservoir. Drain oil before moving to prevent sloshing and possible damage,
then refill when at new location.
To prevent moisture accumulation, some form of heating must be utilized to prevent condensation. This heating
should maintain the winding temperature at a minimum of 500C above ambient. If space heaters are supplied, they
should be energized. If none are available, single phase or “trickle” heating may be utilized by energizing one phase
of the motor’s winding with a low voltage. Request the required voltage and transformer capacity from Emerson. A
third option is to use an auxiliary heat source and keep the winding warm by either convection or blowing warm air
into the motor.
3. Periodic Maintenance.
Oil should be inspected monthly for evidence of moisture or oxidation. The oil must be replaced whenever contamination
is noted or every twelve months, whichever occurs first.
Grease lubricated bearings must be inspected once a month for moisture and oxidation by purging a small quantity of
grease through the drain. If any contamination is present, the grease must be completely removed and replaced.
All motors must have the shaft rotated once a month to insure the maintenance of a coating lubricant film on the
bearing races and journals.
Insulation History:
The only accurate way to evaluate the condition of the winding insulation is to maintain a history of the insulation
readings. Over a period of months or years these readings will tend to indicate a trend. If a downward trend develops, or
if the resistance drops too low, thoroughly clean and dry the windings, retreating if necessry, by an authorized
electrical apparatus service shop.
1) Using a megohm meter, with winding at ambient temperature, apply DC voltage (noted) for sixty seconds and take
reading
189
July 2007 Brand of Emerson Motor Technologies
www.emersonmotors.com www.usmotors.com
Quick Engineering FACTS STORAGE
F. LONG-TERM STORAGE FOR MOTORS WITH GREASE AND OIL LUBRICATED BEARINGS
R40C = Kt x Rt
Where R40C = insulation resistance (in megohms) corrected to 400C
Rt = measured insulation resistance (in megohms)
Kt = temperature coefficient (from Graph 1)
-10
0
GRAPH 1
10
20
30
40
50
60
WINDING
70
TEMPERATURE (0C)
80
90
100
(Adapted from IEEE 43) 110
0.05 0.1 0.5 1.0 5 10 50 100
INSULATION RESISTANCE
TEMPERATURE COEFFICIENT (kT)
3) Insulation resistance readings must not drop below the value indicated by the following formula:
Rm = Kv + 1
Rm = minimum insulation (in megohms) at 400C
Kv = rated motor voltage in kilovolts
In addition to the individual test reading, a dielectric absorption ratio may be required. The dielectric
absorption ratios is obtained by taking megohm meter readings at a one minute and ten minute interval,
or when hand powered megohm meters are used, at a thirty second and sixty second interval. The voltage
should be the same as outlined in item 3D, part 1.
The ratio is obtained by dividing the second reading by the first reading and is based on a good insulation system in-
creasing its resistance when subjected to a test voltage for a period of time. The ratios are as follows:
190
July 2007 Brand of Emerson Motor Technologies
www.emersonmotors.com www.usmotors.com
STORAGE
QUICK ENGINEERING FACTS TEMPERATURE
CLASSIFICATION
F. LONG-TERM STORAGE FOR MOTORS WITH GREASE AND OIL LUBRICATED BEARINGS
If a lower insulation resistance reading is obtained in either the individual test or dielectric absorption ratio test, thor-
oughly clean and dry the windings. Re-check insulation resistance and dielectic absorption ratio.
NOTE: Slightly lower dielectric absorption ratios may be acceptable when high initial insulation resistance readings are
obtained (1000 + megohms). Refer any questions to the Inquiry Group.
For additional information on insulation testing, refer to IEEE Transaction No. 43.
Motor should be thoroughly inspected and cleaned to restore to an “As Shipped” condition.
Motors which have been subjected to vibration must be disassembled and each bearing inspected for damage.
Oil and/or grease must be completely changed using lubricants and methods recommended on the motor’s
lubrication plate, or in the section titled “LUBRICATION” in the Installation/Maintenance manual.
The winding must be tested to obtain insulation resistance and dielectric absorption ratio as described in
section III, item 3
If storage has exceeded one year, the U.S. MOTORS® Quality Assurance Department must be contacted prior to
equipment startup.
The temperature classification indicates the maximum (hot-spot) temperature at which the insulation system can be operated
for normal expected service life.
191
July 2007 Brand of Emerson Motor Technologies